Beruflich Dokumente
Kultur Dokumente
1 Introduction
Test parameters and their significance
2
Suitability of different test voltages for on-site testing of XLPE cable systems 2
Introduction
Cable Life
Mistake
Ageing
Damage
Repair
Operation
Manufacturing Transportation Installation
50/60 Hz
Cable life
Testing
Testing
Testing
Power-
freq.
50/60
Hz
Suitability of different test voltages for on-site testing of XLPE cable systems 3
Introduction
Commissioning and Diagnostic Testing
Commissioning test
Quality control after installation of the cable system
Diagnostic test
Check of specific values of the cable system
Condition assessment for remaining life time estimation
Aim
of the cable system
Suitability of different test voltages for on-site testing of XLPE cable systems 4
Content
1 Introduction
Test parameters and their significance
2
Suitability of different test voltages for on-site testing of XLPE cable systems 5
Test parameters and their significance
Characteristics of Test Methods to be Assessed
Suitability of different test voltages for on-site testing of XLPE cable systems 6
Test parameters and their significance
Why test with same Type of Stresses as in Service?
A Cable System
Will be used with constant AC stresses (with occasional
switching and lightning overvoltages)
Quality depends only on performance under these
stresses – A good cable is one that works well a long
time, not one that passed a certain test
Purpose of test
Initiate discharges in defects so that they can be found
Withstand test: Cause sufficient growth in the defects to
lead to breakdown
Suitability of different test voltages for on-site testing of XLPE cable systems 9
Content
1 Introduction
Test parameters and their significance
2
Suitability of different test voltages for on-site testing of XLPE cable systems 10
Differences between AC/DC and MV/HV cables
Field Distribution in Layered Dielectrics
Suitability of different test voltages for on-site testing of XLPE cable systems 12
Differences between AC/DC and MV/HV cables
Differences between MV, HV and EHV Cables
Technical Consequences
Field strength increases with cable voltage
Recommended limit for test field strength (XLPE):
27-30 kV/mm
Allowed ratio between test voltages and operational voltages
for MV 4 times and for HV 2 times higher than for EHV XLPE
cables
Test methods using higher overvoltage's can be applied for
MV cables
Using these methods for HV and EHV cables test voltages
would have to be reduced, in turn reducing sensitivity of test
Suitability of different test voltages for on-site testing of XLPE cable systems 13
Content
1 Introduction
Test parameters and their significance
2
Suitability of different test voltages for on-site testing of XLPE cable systems 14
DC
Suitability of different test voltages for on-site testing of XLPE cable systems 15
Very Low Frequency (VLF)
Suitability of different test voltages for on-site testing of XLPE cable systems 16
Very Low Frequency (VLF)
Suitability of different test voltages for on-site testing of XLPE cable systems 17
OWTS/DAC (Oscillating wave)
(1) Usage of the cable system as test energy storage by charging it with a DC current
(2) The DC charging ramp poses the danger for creating space charges
Might lead to a breakdown of a otherwise healthy insulation
(3) Typical test procedure of 50 „shots“ equals ~ 10 s of continuous AC voltage
(depending on the capacitance of the cable system)
Only faults with a PD inception time of ~ 10 s can be detected
(4) Does not represent stress under service conditions
(5) Test time highly depends on the parameters of the cable and the test system
very bad repeatability and thus not comparable
(6) Due to DC charging different behavior of insulation compared to power frequency AC
test and contiuous AC test not comparable with factory test or other on-site tests
Suitability of different test voltages for on-site testing of XLPE cable systems 18
OWTS/DAC (Oscillating wave)
Suitability of different test voltages for on-site testing of XLPE cable systems 19
Continuous AC 20-300 Hz
(1) Usually resonant circuit with fixed inductance and frequency converter as supply
(2) Test voltage very similar to service voltage. Even at 20 Hz, 1 hour is equivalent with
72.000 oscillations high probability to initiate discharges in faults very good
possibilities to detect faults / e.g. PD
(3) Electric field distribution is very close to that under service voltage represents
very well the stess under service conditions
(4) Very high comparability with tests done at power frequency in the factory
(5) Test can be repeated even on other cables very good repeatability
(6) Test is very well defined in the standards and the existing experience of ~ 20.000
test conducted worldwide with continous AC between 20 - 300 Hz shows similar
performance like the tests done in the factories
Suitability of different test voltages for on-site testing of XLPE cable systems 20
Continuous AC 20-300 Hz
Suitability of different test voltages for on-site testing of XLPE cable systems 21
24 h rated voltage
(2) Only faults which lead to a breakdown withhin 24 h of cable system service voltage
can be found
(3) PD measuring increases the chance to find more defects, but still all the faults with
a PD inception time >24 h remain undetected
Suitability of different test voltages for on-site testing of XLPE cable systems 22
Content
1 Introduction
Test parameters and their significance
2
Suitability of different test voltages for on-site testing of XLPE cable systems 23
IEC Standard
IEC 60502 old version
Suitability of different test voltages for on-site testing of XLPE cable systems 24
IEC Standard
IEC 60502 new version
IEC 60502-2
Suitability of different test voltages for on-site testing of XLPE cable systems 25
IEC Standard
IEC 60502 new version
IEC 60502-2
Suitability of different test voltages for on-site testing of XLPE cable systems 26
IEC Standard
IEC 60840 latest version
IEC 60840
Suitability of different test voltages for on-site testing of XLPE cable systems 27
IEC Standard
IEC 60840 latest version
IEC 60840
Suitability of different test voltages for on-site testing of XLPE cable systems 28
IEC Standard
IEC 62067 latest version
IEC 62067
Suitability of different test voltages for on-site testing of XLPE cable systems 29
IEC Standard
IEC 62067 latest version
IEC 62067
Suitability of different test voltages for on-site testing of XLPE cable systems 30
THANK YOU FOR YOUR
ATTENTION
Michael Hensel
HIGHVOLT Prüftechnik Dresden GmbH
MV cable test van 36 kV / 10 A
Suitability of different test voltages for on-site testing of XLPE cable systems 32
HV cable test system 260/80 kV – 83 A
Suitability of different test voltages for on-site testing of XLPE cable systems 33
Parallel and Series Connections for long HV
Cable Test
L1 + L4 L2 + L5 L3 + L6
6 x WRV 83/260 T
L4 II L5 II L6
Cable type: 400kV XLPE
Cable length: 16km
Cable capacitance: 2360nF
Test voltage: 260kV
Test duration: 1 hour
Suitability of different test voltages for on-site testing of XLPE cable systems 11