SCADAPack 4102

Modbus multivariable transmitter


1

The SCADAPack 4102 Modbus Multivariable Transmitter is


the flagship of our Ethernet transmitter product line, offering
precise measurement of process pressure, differential
pressure and temperature. As a fully digital transmitter,
the product offers a built-in choice of Modbus protocol
over serial and/or Ethernet communications, along with an
optional PID controller and analog output. With this choice,
the 4102 can be used in a wide variety of installations
including low power transmitters in remote locations or as
an addressed device offering control and measurement in an
extended Ethernet network.
2

Product Data Sheet SCADAPack 4102


Specifications

SCADAPack 4102
Features
Optional Analog Output 0 - 20mA, 12 bit, sinking
Optional PID Controller Fully configurable control of analog output relative to any measured variable
LCD Interface1 Two button control, 2-line interface with 13 characters

Communications
Serial Port RS232/485 configurable, 1200 to 38400 baud
Serial Protocol Modbus RTU
Ethernet Port 2 10BaseT, terminal block connection
Ethernet Protocols 2
Modbus/UDP, Modbus RTU in UDP

Accuracy and Stability


Differential & Absolute ±0.05% of span (for spans >= 10% of URL)
Pressure Accuracy ±(0.005)x(URL / Span) % of Span (spans <10% URL)3
Process Temperature Accuracy ±0.28°C (±0.5°F) (not including RTD uncertainties)
Stability <±0.05% of URL per year over 5 years
Static Pressure Effect The zero and span shift for a 0.7MPa (100psi) static pressure change is:
ZERO Shift ±0.004% of URL, SPAN Shift ±0.01% of reading
Ambient Temperature Effect Total effect for a 28°C (55°F) change for absolute and differential pressure is:
Digital Output: ±(0.03%URL + 0.06% Span)

Physical Specifications
Power 9 to 30 VDC. 225mW with LAN (60mW with Serial communications)
Mass 3.5kg (7.8lb) without process connectors
Environmental 5% RH to 95%, non-condensing, – 40°C (– 40°F) to 70°C (158°F)

Certifications
• cCSAus Explosion proof. Class I, Div. 1 Groups B, C and D Hazardous Locations
• cCSAus Class I, Div. 2 Groups A, B, C and D Hazardous Locations
• Temperature code T5 at maximum ambient, 70°C
• Provides non-incendive field circuits for RTD
CSA certified to the following standards:
• CSA Std. C22.2 No. 213-M1987 - Class I, Division 2 Hazardous Locations
• CSA Std. C22.2 - No. 142-M1987 - Process Control Equipment
• UL Std. No. 1604 - Class I and II, Division 2; Class III Hazardous (Classified) Locations
• UL Std No. 916 - Energy Management Equipment
• ATEX: LCIE 07 ATEX 6058 Ex d IIC T6; -50°C ≤ Ta ≤ 70°C per IEC 60079-1, protection type d (Flameproof)
• IECEx: CSA 05.0011 IECEx Ex d IIC T6; -50°C ≤ Ta ≤ 70°C per IEC 60079-1, protection type d (Flameproof)
1 Button control when setup for calibration through a SCADAPack Smart RTU using Realflo software
2 Available without a disabled Ethernet port
3 Accuracy stated includes the effects of Linearity, Hysteresis, and Repeatability

Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
3

Product Data Sheet SCADAPack 4102


Model Code

TBUT4102E2A101U00N represents a sample code for a 4102 with Ethernet

Model Select: Product Description


TBUT4102 Modbus Multivariable Transmitter

Code Select: Output Signal


M Digital - Modbus Protocol, Jumper selectable RS232 or RS485, de-pluggable screw-type terminal block
A Digital - Modbus Protocol, Jumper selectable RS232 or RS485, de-pluggable screw-type terminal block, 1 Analog Output
E Digital - (1) RS485/232 with Modbus Protocol, (1) 10 BaseT Ethernet with Modbus/UDP protocol, 1 Analog Output

Code Process Cover Sensor Material Sensor Fill Fluid Bolts


2 316 SS 316 SS Silicone CS-B7

Code Select: Differential & Absolute Pressure Span Limit


Differential Pressure Absolute Pressure (Field Configurable for Gauge)
Standard Sensor (Horizontal process connections with vertical mounting)
A 0.5 to 30 inH2O (0.12 to 7.5 kPa) 1 to 100 psi (0.007 to 0.7 MPa)
B 2 to 200 inH2O (0.50 to 50 kPa) 3 to 300 psi (0.021 to 2.1 MPa)
C 10 to 840 inH2O (2.5 to 210 kPa) 3 to 300 psi (0.021 to 2.1 MPa)
D 2 to 200 inH2O (0.50 to 50 kPa) 30 to 1500 psi (0.21 to 10 MPa)
F 3 to 300 inH2O (0.75 to 75 kPa) 30 to 1500 psi (0.21 to 10 MPa)
E 10 to 840 inH2O (2.5 to 210 kPa) 30 to 1500 psi (0.21 to 10 MPa)
J 2 to 200 inH2O (0.50 to 50 kPa) 30 to 3000 psi (0.21 to 21 MPa)
K 3 to 300 inH2O (0.75 to 75 kPa) 30 to 3000 psi (0.21 to 21 MPa)
L 10 to 840 inH2O (2.5 to 210 kPa) 30 to 3000 psi (0.21 to 21 MPa)
G 2 to 200 inH2O (0.50 to 50 kPa) 30 to 5300 psi (0.21 to 37 MPa)
H 3 to 300 inH2O (0.75 to 75 kPa) 30 to 5300 psi (0.21 to 37 MPa)
N 10 to 840 inH2O (2.5 to 210 kPa) 30 to 5300 psi (0.21 to 37 MPa)
Low Profile Sensor (Vertical process connections with vertical mounting)
U 0.5 to 30 inH2O (0.12 to 7.5 kPa) 1 to 100 psi (0.007 to 0.7 MPa)
V 2 to 200 inH2O (0.50 to 50 kPa) 3 to 300 psi (0.021 to 2.1 MPa)
W 10 to 840 inH2O (2.5 to 210 kPa) 3 to 300 psi (0.021 to 2.1 MPa)
X 2 to 200 inH2O (0.50 to 50 kPa) 30 to 1500 psi (0.21 to 10 MPa)
Z 3 to 300 inH2O (0.75 to 75 kPa) 30 to 1500 psi (0.21 to 10 MPa)
Y 10 to 840 inH2O (2.5 to 210 kPa) 30 to 1500 psi (0.21 to 10 MPa)
M 2 to 200 inH2O (0.50 to 50 kPa) 30 to 3000 psi (0.21 to 21 MPa)
P 3 to 300 inH2O (0.75 to 75 kPa) 30 to 3000 psi (0.21 to 21 MPa)
R 10 to 840 inH2O (2.5 to 210 kPa) 30 to 3000 psi (0.21 to 21 MPa)
Q 2 to 200 inH2O (0.50 to 50 kPa) 30 to 5300 psi (0.21 to 37 MPa)
S 3 to 300 inH2O (0.75 to 75 kPa) 30 to 5300 psi (0.21 to 37 MPa)
T 10 to 840 inH2O (2.5 to 210 kPa) 30 to 5300 psi (0.21 to 37 MPa)

Code Select: Temperature Measurement


1 Terminal Blocks for Connection of External 100 Ohm Platinum RTD (DIN/IEC)

Code Select: Process Connector Type


0 1/4” NPT, Threaded in Process Cover, with red plastic conduit cap
1 1/2” NPT, Flange Adapter c/w CS Grade B7 bolts

Code Select: Transmitter Housing Material Conduit Entry Sizes


1 Epoxy-coated Aluminium (2) 1/2 - 14NPT
3 316 SS (2) 1/2 - 14NPT
Model Codes continue on the next page
4

Product Data Sheet SCADAPack 4102


Model Code

TBUT4102E2A101U00N represents a sample code for a 4102 with Ethernet

Model Select: Approvals


U CSA Class 1 - Div 1 (Groups B,C,D) & Div 2 (Groups A,B,C,D). Approved - Hazardous Locations
X IECEx to Exd IIC T6 and ATEX to EEx d IIC T6

Code Future Option


00 None

Code Select: Options


Select Option group code required:
N None
A Digital Indicator (Black Epoxy)
B Digital Indicator (Black Epoxy), Stainless Steel Process Cover Bolts
E Digital Indicator (Stainless Steel)
F Digital Indicator (Stainless Steel), Stainless Steel Process Cover Bolts
J Stainless Steel Process Cover Bolts
5

Product Data Sheet SCADAPack 4102


Dimensions

mm
84
in 3.3 Process
connection

Conduit
connection,
both sides
(Note 1) Optional
custody
transfer
lock (seal) Blind
both ends flange
97
Process 3.8
connector
(Note 2)

Process
connection

Vent
screw 64 33
Plug 2.5 1.3 No process
112 connection
Note 6 4.4 (this end) 64
2.5
137
Allow 50 mm (2 in) 5.4 124
clearance for cover 4.9 Transmitter with
removal, both
ends. (Note5)
Mounting Options
M1 or M2
External
TERMINALS
FIELD

Extended cover earth


used with optional 208
8.2
(ground)
LCD indicator

For surface mounting


External replace U-Bold with two
L-H Indicator 0.375 in diameter bolts
low-high earth
(ground) of sufficient length to
pressure side L-H
pass through bracket
and surface.

Optional side 99
vent/drain 41.3
3.9
1.626
(Note 3)
Vertical DN 50 or
2 in pipe shown.
Process Rotate U-Bolt 90º
connector Note 4 Optional 4203 for mounting to
(Note 2) 227 mounting horizontal pipe.
5.0 bracket
© 2011 Schneider Electric. All rights reserved - - May 2011

1. Conduit connection 1/2 NPT or PG 13.5, both sides: plug unused connection with metal plug (supplied).
2. Process connectors may be removed and connections made directly to process cover using 1/4 NPT internal thread in
process cover.
3. Process cover can be inverted making optional side vents or side drains.
4. Process connectors can be inverted to give either 51, 54, or 57 mm (2.0, 2.125, or 2.25 in) center-to-center distance
between high and low pressure connections.
5. Topworks can be rotated to any position within one turn counterclockwise of the fully tightened position.
6. Process cover end plugs are substituted for vent screws when optional side vents (Note 3) are specified.

Telemetry & Remote SCADA Solutions | www.schneider-electric.com Document Number TBULM01011-09