● 0,5% tolerance ●
3 Resistance Winding Measurement Electrical Test Refer to SOP Test MPT-422 ei Ri I I
Perform On all tap
All Clamping Screw must be Approved Drawing and
4 Transformer Manufacture Visual and Mechanical Check Ri I I
tightened properly Manufacturing Checklist
No Leak at pressure 1,1 bar Max OP
5 Final Leakage Test Mechanical Check Refer to SOP QC MPT-409 ei Ri I I
within 20 Hours
6 Testing Electrical characteristic Measuremet Result Fulfill Spec. or within the TEST Report Ri I I
tolerance as specified by standart
design used (IEC 60076)
Outline Drawing Refer to SOP QC
7 Finishing and Delivery Visual Check ; Mechanical & accessories inspection Comply with Standart Reference Ri I I
MPT-411 ei
ROUTINE TEST (Mandatory)
Measurement of the resistance value and
1 Electrical Test According to IEC 60076 Rt
checking polarities Technical Specification / TestReport Wt Wt
● 0,5% tolerance
2 Measurement of the ratio on all taps Electrical Test Rt
● Perform On all tap Technical Specification / TestReport Wt Wt
● + 15% tolerance
3 No Load Losses and excitation current Electrical Test Rt
● + 30% ExcitaƟon Current Technical Specification / TestReport Wt Wt
IEC 60076 and Technical
4 Load Losses and Impedance Electrical Test Rt
Specification Technical Specification / TestReport Wt Wt
Applied Voltage Test (Separate Source
5 Electrical Test As per IEC 60076-1 Rt
Volatge Test) Technical Specification / TestReport Wt Wt
No Breakdown at 2x rated Voltage -
6 Induce Voltage Test Electrical Test Technical Specification / TestReport Rt Wt Wt
200Hz within 30 Seconds
Description : MP Transformer
4x3000kVA ; (2x6.6/0.69/0,69kV ; 2x6,6/0.4kV) Dyn11
INSPECTION AND TEST PLAN 3x60000kVA ; (2x11/150/6.6kV ; 1x11/150kV) YNd11
PO No. O/PO-ZUG-TU/V/14/002
MEDIUM AND POWER TRANSFORMER SO No. : 60189
Document No :
SCHNEIDER ZUG PP
No. Activity Quality Control Operation Acceptance Criteria Verifying Document
Act Sign Act. Sign Act Sign
Manufacturer Procedurs and all
7 Functional Test Electrical Test accessories could operate as Technical Specification / TestReport Rt Wt Wt
specified on catalogue
8 Insulation Resistance Test Electrical Test Rt Wt Wt
9 Dielectric Strenght Of Oil Electrical Test As per IEC 60076-3 Technical Specification / TestReport Rt Wt Wt
Legend
Ri : Routine Inspection
Rt : Routine Test
Tt : Type Test
Wt : Witness Test
R : Review
A : Approve
I : Inform Only
P : Provide
NA : Not Applicable