DESIGN CALCULATION
SHEET
Sheet No. Computed by
of
Checked by Approved by
Subject Soft Water Demand
The Soft Water shall be used for the soul purpose of cleaning the dishes.
Each Kitchen is assumed to have two dishwashers (one standby).
The Terminal handles about 4900 passengers per hour. The dishwasher shall be sized for the
extreme condition of handling 4900 plates per hour.
The ZANUSSU Automatic Dishwasher Catalogue states that the unit handling 4820 plates per hour
(RT 270HD), has the following water consumption rates:
Dishwasher Caracteristiques
Tank Size
Procedure
(liters)
Prewash 107
Washing 114
Prerinse 122
This adds up to 343 liters. The operators is assumed to change the tanks’ water each half an hour.
The water consumption thus needed shall be: 343 x 2 = 686 l/hr
The final Rinse procedure consumes 480 l/hr.
The total water demand needed for this kitchen is, then: 686 + 480 = 1166 l/hr.
The numbers of seats in this area is: 192 seats outside the restaurant, and we assume the same
number of seats inside of it. Which totals 384 seats.
The dishwasher in this kitchen is assumed to handle 2 x 384 = 768 plates per hour.
This Dishwasher (ZANUSSI LS8 – 800 plates/hr) consumes 3.3 liters per cycle.
For the extreme condition of 80 second cycle, 45 cycles shall be accomplished in one hour.
The water consumption would be: 3.3 l/cycle x 45 cycles = 150 l/hr.
of
Checked by Approved by
Subject Soft Water Demand
Assuming that the tank’s water is changed each half an hour, the water consumption rate is:
114 x 2 + 330 = 558 l/hr for each of these two kitchens.
Tanks Sizing
To size the tanks, we shall assume an operating period of 24 hours per day for the
Dishwashers.
kitchen name Qty flow (l/hr) kitchen name Qty flow (l/hr)
Food Court & Bar Ki 1 1166 none 2 1166
Restaurant Kitchen 1 150 none 2 558
Staff Restaurant Kit 1 150 Total = 3448
Total = 1466