FLOOR JOIST DESIGN CRITERIA

A PROPOSED 2 STOREY RESIDENTIAL STRUCTURE


DESIGNER:ROZALLIENE C. HOMIGOP
PROJECT: PROPOSED 2 STOREY RESIDENTIAL STRUCTURE
LOCATION:LAS PIÑAS CITY

GENERAL CRITERIA

A. REFERENCE CODE

NATIONAL STRUCTURAL CODE OF THE PHILIPPINES, 7TH EDITION - 2015

B. MATERIAL USED

NARRA, 80% STRESS GRADE


Fb =
C. BENDING STRESS……………………………………………………………………………………………………… 18.00 MPa

Fv =
D. SHEARING STRESS………………………………………………………………………………………………………. 1.91 MPa

E. MODULUS OF ELASTICITY………………………………………………………………………………………… E = MPa

F. UNIT WEIGHT………………………………………………………………………………………………………… = 6.43 KN/cu.m

PROPOSED TWO STOREY RESIDENTIAL STRUCTURE DESIGN CRITERIA TIMBER DESIGN


DESIGN CRITERIA
OREY RESIDENTIAL STRUCTURE

RAL CRITERIA

MPa

MPa

MPa 〖� .𝟗𝟒 ��� 〗 ^�


KN/cu.m

PROPOSED TWO STOREY RESIDENTIAL STRUCTURE DESIGN CRITERIA TIMBER DESIGN


SLAB ANALYSIS
A. DEAD LOAD TRIAL SECTION
FLOOR FINISH
TONGUE AND GROOVE, 16 mm THK 0.12 KPa D. TESTING FOR SHEARING F. TESTING FOR DEF
CEILING FINISH 𝑉𝑚𝑎�= 𝑤𝐿/2=((1.00 𝐾𝑁/𝑚)� (4.275𝑚))/2=2.14 KN
∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=4325/
PLASTERED WOOD LATH 0.38 KPa
ELECTROMECHANICAL 0.10 KPa
B. LIVE LOAD �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)
RESIDENTIAL 1.90 KPa 𝐹�= 3𝑉/2�=1.91=((3)( 〖 2.14�10 〗 ^3))/(2(𝑑/4)(𝑑))
4325 �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 2750) 〗 ^4
1675
4825
d=81.99≈100 𝑚𝑚
3350

b=𝑑/4=81.99/4=20.50≈25 𝑚𝑚 d=235.28≈250 𝑚𝑚
b=𝑑/4=150.05/4=37.51
1780

1575
3150

3250
E. TESTING FOR BENDING

𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.00 𝐾𝑁/𝑚)� 〖 (4.275) 〗 ^2)/8=2.28 KN.m

SPACING OF JOIST 0.40 m


DISTANCE BETWEEN
3350 THE BEAM 3.15 m𝐹�= 6𝑀/ 〖 � 〖� ^2
〗 =18.00 𝑀𝑃𝑎=(6(2.28 〖� 10 〗 ^6) )/ 〖 (𝑑/4)(𝑑) 〗 ^2

C. TRIAL SECTION

P=DL+LL+EM d=144. 66≈150 𝑚𝑚


3062

3050
P= [(0.12 + 0.38 + 0.10) + 1.90] KN/ sq. m

3250
3250

P= 2.50 KN/ sq. m b=𝑑/4=144.66/4=36.165≈50 𝑚𝑚

3900
W=PXS
W= 2.50 KN/sq. m x 0.40 m 3350 s
2000
W= 1.00 KN/m 1675

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST 5 8 0 0 TIMBER DESIGN


SLAB ANALYSIS
H. CHECK FOR BENDING

CHECK FOR ADEQUACY


𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.056 𝐾𝑁/𝑚)� 〖 (4.275) 〗 ^2)/8=2.412 KN.m
USING SECTION 250 mm x 75 mm

Wtotal= (WDL+LL+EM)(S) + (Wwood)(CROSS SECTION)


Wtotal= 2.50(0.40) + (6.43)(0.250 x 0.075) 𝑓�≤𝐹�
Wtotal=1.121 KN/m

USE 250mm
f�= 6𝑀/ 〖�𝑑〗 ^2 =(6(2.412 〖� 10 〗 ^6) )/ 〖 (50)(175) 〗 ^2 =9.45
G. CHECK FOR SHEARING

𝑉𝑚𝑎�= 𝑤𝐿/2=((1.056 𝐾𝑁/𝑚)� (4.275𝑚))/2=2.257 KN 9.45<18.00 ∴𝑆�𝐹𝐸

𝑓�≤𝐹�
I. CHECK FOR DEFLECTION
𝑓�= 3𝑉/2�=((3)( 〖 2.26�10 〗 ^3))/(2(50)(175))=0.387
�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1.056)( 〖 2750) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 175 〗 ^3 ))/12))=5.928

0.387<1.91 ∴𝑆�𝐹𝐸

8.801<12.01 ∴𝑆�𝐹𝐸

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


SLAB ANALYSIS
A. DEAD LOAD TRIAL SECTION
FLOOR FINISH
TONGUE AND GROOVE, 16 mm THK 0.12 KPa D. TESTING FOR SHEARING F. TESTING FOR DEF
CEILING FINISH 𝑉𝑚𝑎�= 𝑤𝐿/2=((1.00 𝐾𝑁/𝑚)� (4.825𝑚))/2=2.41 KN
∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=4825/
PLASTERED WOOD LATH 0.38 KPa
ELECTROMECHANICAL 0.10 KPa
B. LIVE LOAD �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)
RESIDENTIAL 1.90 KPa 𝐹�= 3𝑉/2�=1.91=((3)( 〖 2.14�10 〗 ^3))/(2(𝑑/4)(𝑑))
1675 �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 4825) 〗 ^4
4825
3350 d=87.05≈100 𝑚𝑚

b=𝑑/4=87.05/4=21.76≈25 𝑚𝑚 d=255.40≈275 𝑚𝑚
b=𝑑/4=255.40/4=63.85
1780

1575
3250
E. TESTING FOR BENDING

𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.00 𝐾𝑁/𝑚)� 〖 (4.825) 〗 ^2)/8=2.91 KN.m

SPACING OF JOIST 0.40 m


DISTANCE BETWEEN THE BEAM 1.78 m𝐹�= 6𝑀/ 〖��〗 ^2 =18.00 𝑀𝑃𝑎=(6(2.91 〖� 10 〗 ^6) )/ 〖 (𝑑/4)(𝑑) 〗 ^2

C. TRIAL SECTION

P=DL+LL+EM d=157. 14≈175 𝑚𝑚


P= [(0.12 + 0.38 + 0.10) + 1.90] KN/ sq. m
P= 2.50 KN/ sq. m b=𝑑/4=157.14/4=39.284≈50 𝑚𝑚
3062

3050

W=PXS 3250
W= 2.50 KN/sq. m x 0.40 m s
W= 1.00 KN/m

3900
3350
2000
PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR
1 6 7 5 JOIST TIMBER DESIGN
SLAB ANALYSIS
H. CHECK FOR BENDING

CHECK FOR ADEQUACY


𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.133 𝐾𝑁/𝑚)� 〖 (4.825) 〗 ^2)/8=3.296 KN.m
USING SECTION 275 mm x 75 mm

Wtotal= (WDL+LL+EM)(S) + (Wwood)(CROSS SECTION)


Wtotal= 2.50(0.40) + (6.43)(0.275 x 0.075) 𝑓�≤𝐹�
Wtotal=1.133 KN/m

USE 75mm
f�= 6𝑀/ 〖�𝑑〗 ^2 =(6(3.296 〖� 10 〗 ^6) )/ 〖 (75)(275) 〗 ^2 =3.487
G. CHECK FOR SHEARING

𝑉𝑚𝑎�= 𝑤𝐿/2=((1.133 𝐾𝑁/𝑚)� (4.825𝑚))/2=2.732 KN 3.487 <18.00 ∴𝑆�𝐹𝐸

𝑓�≤𝐹�
I. CHECK FOR DEFLECTION
𝑓�= 3𝑉/2�=((3)( 〖 2.73�10 〗 ^3))/(2(75)(250))=0.199

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1.132)( 〖 4825) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((75)( 〖 275 〗 ^3 ))/12))=10.353


0.199<1.91 ∴𝑆�𝐹𝐸

10.353<13.402 ∴𝑆�𝐹𝐸

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


SLAB ANALYSIS
A. DEAD LOAD TRIAL SECTION
FLOOR FINISH
TONGUE AND GROOVE, 16 mm THK 0.12 KPa D. TESTING FOR SHEARING F. TESTING FOR DEF
CEILING FINISH 𝑉𝑚𝑎�= 𝑤𝐿/2=((1.00 𝐾𝑁/𝑚)� (1.675𝑚))/2=0.84 KN
∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=1675/
PLASTERED WOOD LATH 0.38 KPa
ELECTROMECHANICAL 0.10 KPa
B. LIVE LOAD �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)
RESIDENTIAL 1.90 KPa 𝐹�= 3𝑉/2�=1.91=((3)( 〖 0.84�10 〗 ^3))/(2(𝑑/4)(𝑑))
1675 �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 1675) 〗 ^4
4825
3350 d=51.29≈75 𝑚𝑚

b=𝑑/4=51.29/4=12.82≈25 𝑚𝑚 d=115.51≈125 𝑚𝑚

1575
b=𝑑/4=115.51/4=28.88
3250

E. TESTING FOR BENDING

𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.00 𝐾𝑁/𝑚)� 〖 (1.675) 〗 ^2)/8=0.35 KN.m

SPACING OF JOIST 0.40 m


DISTANCE BETWEEN THE BEAM 3.25 m𝐹�= 6𝑀/ 〖��〗 ^2 =18.00 𝑀𝑃𝑎=(6(0.35 〖� 10 〗 ^6) )/ 〖 (𝑑/4)(𝑑) 〗 ^2

C. TRIAL SECTION

P=DL+LL+EM d=77. 62≈100 𝑚𝑚


3062

3050

P= [(0.12 + 0.38 + 0.10) + 1.90] KN/ sq. m


3250

P= 2.50 KN/ sq. m b=𝑑/4=77.62/4=19.404≈25 𝑚𝑚

3900
W=PXS
W= 2.50 KN/sq. m x 0.40 m s
W= 1.00 2000 KN/m
1675

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR


5 8 0 0 JOIST TIMBER DESIGN
SLAB ANALYSIS
H. CHECK FOR BENDING

CHECK FOR ADEQUACY


𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.040 𝐾𝑁/𝑚)� 〖 (1.675) 〗 ^2)/8=0.365 KN.m
USING SECTION 125 mm x 50 mm

Wtotal= (WDL+LL+EM)(S) + (Wwood)(CROSS SECTION)


Wtotal= 2.50(0.40) + (6.43)(0.125 x 0.050) 𝑓�≤𝐹�
Wtotal=1.040 KN/m

USE 50mm
f�= 6𝑀/ 〖�𝑑〗 ^2 =(6(0.365 〖� 10 〗 ^6) )/ 〖 (50)(125) 〗 ^2 =2.80
G. CHECK FOR SHEARING

𝑉𝑚𝑎�= 𝑤𝐿/2=((1.040 𝐾𝑁/𝑚)� (1.675𝑚))/2=0.871 KN 2.80<18.00 ∴𝑆�𝐹𝐸

𝑓�≤𝐹�
I. CHECK FOR DEFLECTION
𝑓�= 3𝑉/2�=((3)( 〖 0.87�10 〗 ^3))/(2(50)(125))=0.209

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1.040)( 〖 1675) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 125 〗 ^3 ))/12))=2.205


0.209<1.91 ∴𝑆�𝐹𝐸

2.21<4.65 ∴𝑆�𝐹𝐸

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


SLAB ANALYSIS
A. DEAD LOAD TRIAL SECTION
FLOOR FINISH
TONGUE AND GROOVE, 16 mm THK 0.12 KPa D. TESTING FOR SHEARING F. TESTING FOR DEF
WATERPROOFING 0.07 KPa 𝑉𝑚𝑎�= 𝑤𝐿/2=((1.03 𝐾𝑁/𝑚)� (3.35𝑚))/2=1.72 KN
∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=3350/
CEILING FINISH
PLASTERED WOOD LATH 0.38 KPa
ELECTROMECHANICAL 0.10 KPa �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)
B. LIVE LOAD 𝐹�= 3𝑉/2�=1.91=((3)( 〖 1.72�10 〗 ^3))/(2(𝑑/4)(𝑑))
RESIDENTIAL 1.90 KPa �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1.03)( 〖 3350) 〗 ^

3350 d=73.55≈75 𝑚𝑚

b=𝑑/4=73.55/4=18.39≈25 𝑚𝑚 d=195.61≈200 𝑚𝑚
1575 b=𝑑/4=195.61/4=48.90
3250

E. TESTING FOR BENDING

𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.03 𝐾𝑁/𝑚)� 〖 (3.350) 〗 ^2)/8=1.44 KN.m

SPACING OF JOIST 0.40 m


DISTANCE BETWEEN THE BEAM 1.58 m𝐹�= 6𝑀/ 〖��〗 ^2 =18.00 𝑀𝑃𝑎=(6(1.44 〖� 10 〗 ^6) )/ 〖 (𝑑/4)(𝑑) 〗 ^2

C. TRIAL SECTION

P=DL+LL+EM d=124. 35≈125 𝑚𝑚


P= [(0.12 + 0.38 + 0.10+0.07) + 1.90] KN/ sq. m
P= 2.57 KN/ sq. m b=𝑑/4=124.35/4=31.087≈50 𝑚𝑚

W=PXS
W= 2.57 KN/sq. m x 0.40 m s
W= 1.028 KN/m
3050

3250

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


SLAB ANALYSIS
H. CHECK FOR BENDING

CHECK FOR ADEQUACY


𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.0923 𝐾𝑁/𝑚)� 〖 (3.35) 〗 ^2)/8=1.532 KN.m
USING SECTION 200 mm x 50 mm

Wtotal= (WDL+LL+EM)(S) + (Wwood)(CROSS SECTION)


Wtotal= 2.57(0.40) + (6.43)(0.200 x 0.050) 𝑓�≤𝐹�
Wtotal=1.0923 KN/m

USE 50mm
f�= 6𝑀/ 〖
��〗^2 =(6(1.532 〖� 10 〗 ^6) )/ 〖 (50)(200) 〗 ^2 =4.60
G. CHECK FOR SHEARING

𝑉𝑚𝑎�= 𝑤𝐿/2=((1.0923 𝐾𝑁/𝑚)� (3.35𝑚))/2=1.83 KN 4.60<18.00 ∴𝑆�𝐹𝐸

𝑓�≤𝐹�
I. CHECK FOR DEFLECTION
𝑓�= 3𝑉/2�=((3)( 〖 1.83�10 〗 ^3))/(2(50)(200))=0.274

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1.0923)( 〖 3550) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 200 〗 ^3 ))/12))=9.047


0.274<1.91 ∴𝑆�𝐹𝐸

9.047<9.31 ∴𝑆�𝐹𝐸

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


4325
1675
4825
SLAB ANALYSIS 3350

A. DEAD LOAD TRIAL SECTION


FLOOR FINISH

1780

1575
3150

3250
TONGUE AND GROOVE, 16 mm THK 0.12 KPa D. TESTING FOR SHEARING F. TESTING FOR DEF
CEILING FINISH 𝑉𝑚𝑎�= 𝑤𝐿/2=((1.00 𝐾𝑁/𝑚)� (3.35𝑚))/2=1.675 KN
∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=3350/
PLASTERED WOOD LATH 0.38 KPa
ELECTROMECHANICAL 0.10 KPa
B. LIVE LOAD �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)
RESIDENTIAL 1.90 KPa 𝐹�= 3𝑉/2�=1.91=((3)( 〖 1.675�10 〗 ^3))/(2(𝑑/4)(𝑑))
3350 �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 3350) 〗 ^4

d=72.54≈75 𝑚𝑚

d=194.26≈200 𝑚𝑚

3062
b=𝑑/4=72.54/4=18.13≈25 𝑚𝑚

3050

3250
3250

b=𝑑/4=194.26/4=48.56

E. TESTING FOR BENDING

3350 𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.00 𝐾𝑁/𝑚)� 〖 (3.35) 〗 ^2)/8=1.40 KN.m


2000
1675
SPACING OF JOIST 0.40 m
DISTANCE BETWEEN THE BEAM 3.25 m𝐹�= 6𝑀/ 〖��〗 ^2 =18.00 𝑀𝑃𝑎=(6(1.40 〖� 10 〗 ^6) )/ 〖 (𝑑/4)(𝑑) 〗 ^2
5800
C. TRIAL SECTION

P=DL+LL+EM d=123. 21≈125 𝑚𝑚


P= [(0.12 + 0.38 + 0.10) + 1.90] KN/ sq. m
P= 2.50 KN/ sq. m b=𝑑/4=123.21/4=30.802≈50 𝑚𝑚

W=PXS
W= 2.50 KN/sq. m x 0.40 m s
W= 1.00 KN/m

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


SLAB ANALYSIS
H. CHECK FOR BENDING

CHECK FOR ADEQUACY


𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.0643 𝐾𝑁/𝑚)� 〖 (3.35) 〗 ^2)/8=1.493 KN.m
USING SECTION 200 mm x 50 mm

Wtotal= (WDL+LL+EM)(S) + (Wwood)(CROSS SECTION)


Wtotal= 2.50(0.40) + (6.43)(0.200 x 0.050) 𝑓�≤𝐹�
Wtotal=1.0643 KN/m

USE 50mm
f�= 6𝑀/ 〖
��〗^2 =(6(1.493 〖� 10 〗 ^6) )/ 〖 (50)(200) 〗 ^2 =4.479
G. CHECK FOR SHEARING

𝑉𝑚𝑎�= 𝑤𝐿/2=((1.0643 𝐾𝑁/𝑚)� (3.35𝑚))/2=1.783 KN 4.479<18.00 ∴𝑆�𝐹𝐸

𝑓�≤𝐹�
I. CHECK FOR DEFLECTION
𝑓�= 3𝑉/2�=((3)( 〖 1.783�10 〗 ^3))/(2(50)(200))=0.267

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1.0643)( 〖 3350) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 200 〗 ^3 ))/12))=8.815


0.267<1.91 ∴𝑆�𝐹𝐸

8.815<9.31 ∴𝑆�𝐹𝐸

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


4325
1675
4825

SLAB A 3 3N
50 A L Y S I S

A. DEAD LOAD TRIAL SECTION

1780

1575
FLOOR FINISH

3250
TONGUE AND GROOVE, 16 mm THK 0.12 KPa D. TESTING FOR SHEARING F. TESTING FOR DEF
CEILING FINISH 𝑉𝑚𝑎�= 𝑤𝐿/2=((1.00 𝐾𝑁/𝑚)� (3.35𝑚))/2=1.675 KN
∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=4275/
PLASTERED WOOD LATH 0.38 KPa
ELECTROMECHANICAL 0.10 KPa
B. LIVE LOAD �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)
RESIDENTIAL 1.90 KPa 𝐹�= 3𝑉/2�=1.91=((3)( 〖 1.675�10 〗 ^3))/(2(𝑑/4)(𝑑))
�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 3350) 〗 ^4

d=72.54≈75 𝑚𝑚
3062
b=𝑑/4=72.54/4=18.13≈25 𝑚𝑚 d=194.26≈200 𝑚𝑚

3050

3250
3250

b=𝑑/4=194.26/4=48.57

3900
E. TESTING FOR BENDING
3350 𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.00 𝐾𝑁/𝑚)� 〖 (3.35) 〗 ^2)/8=1.40 KN.m
2000
1675
SPACING OF JOIST 0.40 m
DISTANCE BETWEEN THE BEAM 3.06 m𝐹�= 6𝑀/ 〖��〗 ^2 =18.00 𝑀𝑃𝑎=(6(1.40 〖� 10 〗 ^6) )/ 〖 (𝑑/4)(𝑑) 〗 ^2
5800
C. TRIAL SECTION

P=DL+LL+EM d=123. 21≈125 𝑚𝑚


P= [(0.12 + 0.38 + 0.10) + 1.90] KN/ sq. m
P= 2.50 KN/ sq. m b=𝑑/4=123.21/4=30.802≈50 𝑚𝑚

W=PXS
W= 2.50 KN/sq. m x 0.40 m s
W= 1.00 KN/m

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


SLAB ANALYSIS
H. CHECK FOR BENDING

CHECK FOR ADEQUACY


𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.0643 𝐾𝑁/𝑚)� 〖 (3.35) 〗 ^2)/8=1.493 KN.m
USING SECTION 200 mm x 50 mm

Wtotal= (WDL+LL+EM)(S) + (Wwood)(CROSS SECTION)


Wtotal= 2.50(0.40) + (6.43)(0.200 x 0.050) 𝑓�≤𝐹�
Wtotal=1.0643 KN/m

USE 50mm
f�= 6𝑀/ 〖
��〗^2 =(6(1.493 〖� 10 〗 ^6) )/ 〖 (50)(200) 〗 ^2 =4.479
G. CHECK FOR SHEARING

𝑉𝑚𝑎�= 𝑤𝐿/2=((1.0643 𝐾𝑁/𝑚)� (3.35𝑚))/2=1.783 KN 4.479<18.00 ∴𝑆�𝐹𝐸

𝑓�≤𝐹�
I. CHECK FOR DEFLECTION
𝑓�= 3𝑉/2�=((3)( 〖 1.783�10 〗 ^3))/(2(50)(200))=0.267

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1.0643)( 〖 3350) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 200 〗 ^3 ))/12))=8.815


0.267<1.91 ∴𝑆�𝐹𝐸

8.815<9.31 ∴𝑆�𝐹𝐸

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


1675
4825
3350
SLAB ANALYSIS
A. DEAD LOAD TRIAL SECTION

1575
3250
FLOOR FINISH
TONGUE AND GROOVE, 16 mm THK 0.12 KPa D. TESTING FOR SHEARING F. TESTING FOR DEF
WATERPROOFING 0.07 KPa 𝑉𝑚𝑎�= 𝑤𝐿/2=((1.028 𝐾𝑁/𝑚)� (2.000𝑚))/2=1.028 KN
∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=4275/
CEILING FINISH
PLASTERED WOOD LATH 0.38 KPa
ELECTROMECHANICAL 0.10 KPa �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)
B. LIVE LOAD 𝐹�= 3𝑉/2�=1.91=((3)( 〖 1.028�10 〗 ^3))/(2(𝑑/4)(𝑑))
RESIDENTIAL 1.90 KPa �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 2000) 〗 ^4

d=56.83≈75 𝑚𝑚
3062

b=𝑑/4=56.83/4=14.21≈25 𝑚𝑚 d=132.85≈150 𝑚𝑚
3050

3250
b=𝑑/4=132.85/4=33.21

3900
E. TESTING FOR BENDING

50 𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.028 𝐾𝑁/𝑚)� 〖 (2.000) 〗 ^2)/8=0.514 KN.m


2000
1675
SPACING OF JOIST 3.05 m
DISTANCE BETWEEN THE BEAM 3.00 m𝐹�= 6𝑀/ 〖��〗 ^2 =18.00 𝑀𝑃𝑎=(6(0.514 〖� 10 〗 ^6) )/ 〖 (𝑑/4)(𝑑) 〗 ^2
5800
C. TRIAL SECTION

P=DL+LL+EM d=88.17≈100 𝑚𝑚
P= [(0.12 + 0.38 + 0.10+0.07) + 1.90] KN/ sq. m
P= 2.57 KN/ sq. m b=𝑑/4=88.17/4=22.04≈25 𝑚𝑚

W=PXS
W= 2.50 KN/sq. m x 0.40 m s
W= 1.028 KN/m

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


SLAB ANALYSIS
H. CHECK FOR BENDING

CHECK FOR ADEQUACY


𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.076 𝐾𝑁/𝑚)� 〖 (2.000) 〗 ^2)/8=0.538 KN.m
USING SECTION 150 mm x 50 mm

Wtotal= (WDL+LL+EM)(S) + (Wwood)(CROSS SECTION)


Wtotal= 2.57(0.40) + (6.43)(0.150 x 0.050) 𝑓�≤𝐹�
Wtotal=1.076225 KN/m

USE 50mm
f�= 6𝑀/ 〖
��〗^2 =(6(0.538 〖� 10 〗 ^6) )/ 〖 (50)(150) 〗 ^2 =2.87
G. CHECK FOR SHEARING

𝑉𝑚𝑎�= 𝑤𝐿/2=((1.076 𝐾𝑁/𝑚)� (2.000𝑚))/2=1.076 KN 2.87<18.00 ∴𝑆�𝐹𝐸

𝑓�≤𝐹�
I. CHECK FOR DEFLECTION
𝑓�= 3𝑉/2�=((3)( 〖 1.076�10 〗 ^3))/(2(50)(150))=0.215

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1.076)( 〖 2000) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 150 〗 ^3 ))/12))=2.684


0.215<1.91 ∴𝑆�𝐹𝐸

2.68<5.56 ∴𝑆�𝐹𝐸

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


3350
SLAB ANALYSIS
TRIAL SECTION

1575
3250

A. DEAD LOAD
FLOOR FINISH
TONGUE AND GROOVE, 16 mm THK 0.12 KPa D. TESTING FOR SHEARING F. TESTING FOR DEF
CEILING FINISH 𝑉𝑚𝑎�= 𝑤𝐿/2=((1.00 𝐾𝑁/𝑚)� (5.80𝑚))/2=2.90 KN ∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=5800/
PLASTERED WOOD LATH 0.38 KPa
ELECTROMECHANICAL 0.10 KPa
B. LIVE LOAD �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)
RESIDENTIAL 1.90 KPa 𝐹�= 3𝑉/2�=1.91=((3)( 〖 2.90�10 〗 ^3))/(2(𝑑/4)(𝑑))
�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 5800) 〗 ^4

d=95.45≈100 𝑚𝑚
3050

3250

d=293.204≈300 𝑚𝑚

3900
b=𝑑/4=95.45/4=23.86≈25 𝑚𝑚
b=𝑑/4=293.04/4=73.30
1675
E. TESTING FOR BENDING

5800 𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.00 𝐾𝑁/𝑚)� 〖 (5.80) 〗 ^2)/8=4.205 KN.m

SPACING OF JOIST 0.40 m


DISTANCE BETWEEN THE BEAM 3.90 m𝐹�= 6𝑀/ 〖��〗 ^2 =18.00 𝑀𝑃𝑎=(6(4.205 〖� 10 〗 ^6) )/ 〖 (𝑑/4)(𝑑) 〗 ^2

C. TRIAL SECTION

P=DL+LL+EM d=177.65≈200 𝑚𝑚
P= [(0.12 + 0.38 + 0.10) + 1.90] KN/ sq. m
P= 2.50 KN/ sq. m b=𝑑/4=177.65/4=44.413≈50 𝑚𝑚

W=PXS
W= 2.50 KN/sq. m x 0.40 m s
W= 1.00 KN/m

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


SLAB ANALYSIS
H. CHECK FOR BENDING

CHECK FOR ADEQUACY


𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.145 𝐾𝑁/𝑚)� 〖 (5.80) 〗 ^2)/8=4.813 KN.m
USING SECTION 300 mm x 75 mm

Wtotal= (WDL+LL+EM)(S) + (Wwood)(CROSS SECTION)


Wtotal= 2.50(0.40) + (6.43)(0.300 x 0.075) 𝑓�≤𝐹�
Wtotal=1.145 KN/m

DON’T USE 75m


f�= 6𝑀/ 〖
��〗^2 =(6(4.813 〖� 10 〗 ^6) )/ 〖 (75)(300) 〗 ^2 =9.45
G. CHECK FOR SHEARING

𝑉𝑚𝑎�= 𝑤𝐿/2=((1.145 𝐾𝑁/𝑚)� (5.80𝑚))/2=3.32 KN 4.28<18.00 ∴𝑆�𝐹𝐸

𝑓�≤𝐹�
I. CHECK FOR DEFLECTION
𝑓�= 3𝑉/2�=((3)( 〖 3.32�10 〗 ^3))/(2(75)(300))=0.22

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1.145)( 〖 5800) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((75)( 〖 300 〗 ^3 ))/12))=16.827


0.22<1.91 ∴𝑆�𝐹𝐸

16.827<16.11 ∴𝑁𝑂𝑇 𝑆�𝐹𝐸

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


1675
825
3350
SLAB ANALYSIS
A. DEAD LOAD TRIAL SECTION

1575
3250
FLOOR FINISH
TONGUE AND GROOVE, 16 mm THK 0.12 KPa D. TESTING FOR SHEARING F. TESTING FOR DEF
CEILING FINISH 𝑉𝑚𝑎�= 𝑤𝐿/2=((1.00 𝐾𝑁/𝑚)� (1.675𝑚))/2=0.84 KN ∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=1675/
PLASTERED WOOD LATH 0.38 KPa
ELECTROMECHANICAL 0.10 KPa
B. LIVE LOAD �_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)
RESIDENTIAL 1.90 KPa 𝐹�= 3𝑉/2�=1.91=((3)( 〖 0.84�10 〗 ^3))/(2(𝑑/4)(𝑑))
�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 1675) 〗 ^4

d=51.29≈75 𝑚𝑚
3050

3250

b=𝑑/4=51.29/4=12.82≈25 𝑚𝑚 d=115.51≈125 𝑚𝑚
b=𝑑/4=115.51/4=28.5≈

3900
E. TESTING FOR BENDING
2000
1675 𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.00 𝐾𝑁/𝑚)� 〖 (1.675) 〗 ^2)/8=0.35 KN.m

SPACING OF JOIST 0.40 m


5800
DISTANCE BETWEEN THE BEAM 3.25 m𝐹�= 6𝑀/ 〖��〗 ^2 =18.00 𝑀𝑃𝑎=(6(0.35 〖� 10 〗 ^6) )/ 〖 (𝑑/4)(𝑑) 〗 ^2

C. TRIAL SECTION

P=DL+LL+EM d=77. 62≈100 𝑚𝑚


P= [(0.12 + 0.38 + 0.10) + 1.90] KN/ sq. m
P= 2.50 KN/ sq. m b=𝑑/4=77.62/4=19.404≈25 𝑚𝑚

W=PXS
W= 2.50 KN/sq. m x 0.40 m s
W= 1.00 KN/m

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


SLAB ANALYSIS
H. CHECK FOR BENDING

CHECK FOR ADEQUACY


𝑀𝑚𝑎�= (𝑤𝐿^2)/8=((1.04 𝐾𝑁/𝑚)� 〖 (1.675) 〗 ^2)/8=0.365 KN.m
USING SECTION 125 mm x 50 mm

Wtotal= (WDL+LL+EM)(S) + (Wwood)(CROSS SECTION)


Wtotal= 2.50(0.40) + (6.43)(0.125 x 0.050) 𝑓�≤𝐹�
Wtotal=1.04 KN/m

USE 50mm
f�= 6𝑀/ 〖
��〗^2 =(6(0.365 〖� 10 〗 ^6) )/ 〖 (50)(125) 〗 ^2 =2.802
G. CHECK FOR SHEARING

𝑉𝑚𝑎�= 𝑤𝐿/2=((1.04 𝐾𝑁/𝑚)� (1.675𝑚))/2=0.87 KN 2.802<18.00 ∴𝑆�𝐹𝐸

𝑓�≤𝐹�
I. CHECK FOR DEFLECTION
𝑓�= 3𝑉/2�=((3)( 〖 0.87�10 〗 ^3))/(2(50)(125))=0.209

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1.04)( 〖 1675) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 125 〗 ^3 ))/12))=2.205


0.209<1.91 ∴𝑆�𝐹𝐸

2.205<4.65 ∴𝑆�𝐹𝐸

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

F. TESTING FOR DEFLECTION


∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=4325/360=12.01 𝑚𝑚

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 2750) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)((𝑑/4)(𝑑^3 )/12))

d=235.28≈250 𝑚𝑚
b=𝑑/4=150.05/4=37.512≈50 𝑚𝑚

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

USE 250mm x 75 mm

56)( 〖 2750) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 175 〗 ^3 ))/12))=5.928

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

F. TESTING FOR DEFLECTION


∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=4825/360=13.403 𝑚𝑚

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 4825) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)((𝑑/4)(𝑑^3 )/12))

d=255.40≈275 𝑚𝑚
b=𝑑/4=255.40/4=63.85≈75 𝑚𝑚

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

USE 75mm x 275 mm

)( 〖 4825) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((75)( 〖 275 〗 ^3 ))/12))=10.353

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

F. TESTING FOR DEFLECTION


∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=1675/360=4.65 𝑚𝑚

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 1675) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)((𝑑/4)(𝑑^3 )/12))

d=115.51≈125 𝑚𝑚
b=𝑑/4=115.51/4=28.88≈50 𝑚𝑚

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

USE 50mm x 125 mm

0)( 〖 1675) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 125 〗 ^3 ))/12))=2.205

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

F. TESTING FOR DEFLECTION


∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=3350/360=9.31 𝑚𝑚

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1.03)( 〖 3350) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)((𝑑/4)(𝑑^3 )/12))

d=195.61≈200 𝑚𝑚
b=𝑑/4=195.61/4=48.901≈50 𝑚𝑚

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

USE 50mm x 200 mm

3)( 〖 3550) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 200 〗 ^3 ))/12))=9.047

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

F. TESTING FOR DEFLECTION


∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=3350/360=9.31 𝑚𝑚

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 3350) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)((𝑑/4)(𝑑^3 )/12))

d=194.26≈200 𝑚𝑚
b=𝑑/4=194.26/4=48.56≈50 𝑚𝑚

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

USE 50mm x 200 mm

3)( 〖 3350) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 200 〗 ^3 ))/12))=8.815

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

F. TESTING FOR DEFLECTION


∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=4275/360=9.31 𝑚𝑚

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 3350) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)((𝑑/4)(𝑑^3 )/12))

d=194.26≈200 𝑚𝑚
b=𝑑/4=194.26/4=48.57≈50 𝑚𝑚

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

USE 50mm x 200 mm

3)( 〖 3350) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 200 〗 ^3 ))/12))=8.815

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

F. TESTING FOR DEFLECTION


∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=4275/360=5.56 𝑚𝑚

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 2000) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)((𝑑/4)(𝑑^3 )/12))

d=132.85≈150 𝑚𝑚
b=𝑑/4=132.85/4=33.21≈50 𝑚𝑚

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

USE 50mm x 150 mm

6)( 〖 2000) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 150 〗 ^3 ))/12))=2.684

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

F. TESTING FOR DEFLECTION


∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=5800/360=16.11 𝑚𝑚

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 5800) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)((𝑑/4)(𝑑^3 )/12))

d=293.204≈300 𝑚𝑚
b=𝑑/4=293.04/4=73.301≈75 𝑚𝑚

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

DON’T USE 75mm x 300 mm

5)( 〖 5800) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((75)( 〖 300 〗 ^3 ))/12))=16.827

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

F. TESTING FOR DEFLECTION


∆_(�𝐿𝐿𝑂𝑊 )=𝐿/360=1675/360=4.65 𝑚𝑚

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)

�_�𝐶𝑇= 〖 5𝑤𝐿 〗 ^4/(384 𝐸𝐼)=(5(1)( 〖 1675) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)((𝑑/4)(𝑑^3 )/12))

d=115.51≈125 𝑚𝑚
b=𝑑/4=115.51/4=28.5≈50 𝑚𝑚

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


NALYSIS

USE 50mm x 125 mm

)( 〖 1675) 〗 ^4)/(384(5.94 𝑋 〖 10 〗 ^3)(((50)( 〖 125 〗 ^3 ))/12))=2.205

PROPOSED 2 STOREY RESIDENTIAL STRUCTURE FLOOR JOIST TIMBER DESIGN


w l vmax
V 1 4.325 2.1625
fv v d b
fv 1.91 2162.5 82.42083303 20.60520826 100 25

mmax w l mmax
1 4.325 2.338203125
f m d b
f 18 2338203.125 3117604.167 146.0854595 36.521364887 150

allow. Displac l allow displacement


4325 12.01388889

act. Deflectionw l e d b
12.01388889 1 4325 5940 3064463187 235.28194524 58.82048631

for checking
w= 1+ 1.1205625
shearing
w l vmax
V 1.1205625 4.325 2.423216406
fv 0.1938573 SAFE

bending
mmax w l mmax
1.1205625 4.325 2.620102739
f 3.353731506 SAFE

for deflection
act. Deflectionw l e i act. Deflection
12.01388889 1.1205625 4325 5940 1.96043E+15 97656250 8.801016261
max d max b
250 75
250 75
0.25 0.075

50

250 75

. Deflection
SAFE
w l vmax
V 1 4.825 2.4125
fv v d b
fv 1.91 2412.5 87.05477604 21.76369401 100 25

mmax w l mmax
1 4.825 2.910078125
f m d b
f 18 2910078.125 3880104.167 157.1379664 39.284491591 175

allow. Displac l allow displacement


4825 13.40277778

act. Deflectionw l e d b
13.40277778 1 4825 5940 4254886955 255.4006549 63.85016372

for checking
w= 1+ 1.13261875
shearing
w l vmax
V 1.13261875 4.825 2.732442734
fv 0.1987231 SAFE

bending
mmax w l mmax
1.13261875 4.825 3.296009048
f 3.486687258 SAFE

for deflection
act. Deflectionw l e i act. Deflection
13.40277778 1.13261875 4825 5940 3.06933E+15 129980468.75 10.35254802
max d max b
275 75
275 75
0.275 0.075

50

275 75

. Deflection
SAFE
w l vmax
V 1 1.675 0.8375
fv v d b
fv 1.91 837.5 51.29220265 12.82305066 75 25

mmax w l mmax
1 1.675 0.350703125
f m d b
f 18 350703.125 467604.1667 77.61746553 19.404366382 100

allow. Displac l allow displacement


1675 4.652777778

act. Deflectionw l e d b
4.652777778 1 1675 5940 178008404 115.50748472 28.87687118

for checking
w= 1+ 1.0401875
shearing
w l vmax
V 1.0401875 1.675 0.871157031
fv 0.2090777 SAFE

bending
mmax w l mmax
1.0401875 1.675 0.364797007
f 2.801641013 SAFE

for deflection
act. Deflectionw l e i act. Deflection
4.652777778 1.0401875 1675 5940 4.09393E+13 8138020.8333 2.20548655
max d max b
125 50
125 50
0.125 0.05

25

125 50

. Deflection
SAFE
w l vmax
V 1.028 3.35 1.7219
fv v d b
fv 1.91 1721.9 73.54665151 18.38666288 75 25

mmax w l mmax
1.028 3.35 1.44209125
f m d b
f 18 1442091.25 1922788.333 124.3494378 31.087359451 125

allow. Displac l allow displacement


3350 9.305555556

act. Deflectionw l e d b
9.305555556 1.028 3350 5940 1463941117 195.60542802 48.90135701

for checking
w= 1.028 + 1.0923
shearing
w l vmax
V 1.0923 3.35 1.8296025
fv 0.2744404 SAFE

bending
mmax w l mmax
1.0923 3.35 1.532292094
f 4.596876281 SAFE

for deflection
act. Deflectionw l e i act. Deflection
9.305555556 1.0923 3350 5940 6.87846E+14 33333333.333 9.046795045
max d max b
200 50
200 50
0.2 0.05

50

200 50

. Deflection
SAFE
w l vmax
V 1 3.35 1.675
fv v d b
fv 1.91 1675 72.53812863 18.13453216 75 25

mmax w l mmax
1 3.35 1.4028125
f m d b
f 18 1402812.5 1870416.667 123.2100464 30.802511607 125

allow. Displac l allow displacement


3350 9.305555556

act. Deflectionw l e d b
9.305555556 1 3350 5940 1424067235 194.25965968 48.56491492

for checking
w= 1+ 1.0643
shearing
w l vmax
V 1.0643 3.35 1.7827025
fv 0.2674054 SAFE

bending
mmax w l mmax
1.0643 3.35 1.493013344
f 4.479040031 SAFE

for deflection
act. Deflectionw l e i act. Deflection
9.305555556 1.0643 3350 5940 6.70214E+14 33333333.333 8.814889652
max d max b
200 50
200 50
0.2 0.05

50

200 50

. Deflection
SAFE
w l vmax
V 1 3.35 1.675
fv v d b
fv 1.91 1675 72.53812863 18.13453216 75 25

mmax w l mmax
1 3.35 1.4028125
f m d b
f 18 1402812.5 1870416.667 123.2100464 30.802511607 125

allow. Displac l allow displacement


3350 9.305555556

act. Deflectionw l e d b
9.305555556 1 3350 5940 1424067235 194.25965968 48.56491492

for checking
w= 1+ 1.0643
shearing
w l vmax
V 1.0643 3.35 1.7827025
fv 0.2674054 SAFE

bending
mmax w l mmax
1.0643 3.35 1.493013344
f 4.479040031 SAFE

for deflection
act. Deflectionw l e i act. Deflection
9.305555556 1.0643 3350 5940 6.70214E+14 33333333.333 8.814889652
max d max b
200 50
200 50
0.2 0.05

50

200 50

. Deflection
SAFE
w l vmax
V 1.028 2 1.028
fv v d b
fv 1.91 1028 56.82710068 14.20677517 75 25

mmax w l mmax
1.028 2 0.514
f m d b
f 18 514000 685333.3333 88.16589459 22.041473649 100

allow. Displac l allow displacement


2000 5.555555556

act. Deflectionw l e d b
5.555555556 1.028 2000 5940 311515152 132.85251908 33.21312977

for checking
w= 1.028 + 1.076225
shearing
w l vmax
V 1.076225 2 1.076225
fv 0.215245 SAFE

bending
mmax w l mmax
1.076225 2 0.5381125
f 2.869933333 SAFE

for deflection
act. Deflectionw l e i act. Deflection
5.555555556 1.076225 2000 5940 8.6098E+13 14062500 2.684187555
max d max b
150 50
150 50
0.15 0.05

25

150 50

. Deflection
SAFE
w l vmax
V 1 5.8 2.9
fv v d b
fv 1.91 2900 95.44604572 23.86151143 100 25

mmax w l mmax
1 5.8 4.205
f m d b
f 18 4205000 5606666.667 177.651241 44.412810244 200

allow. Displac l allow displacement


5800 16.11111111

act. Deflectionw l e d b
16.11111111 1 5800 5940 7390606061 293.20408279 73.3010207

for checking
w= 1+ 1.144675
shearing
w l vmax
V 1.144675 5.8 3.3195575
fv 0.2213038 SAFE

bending
mmax w l mmax
1.144675 5.8 4.813358375
f 4.278540778 SAFE

for deflection
act. Deflectionw l e i act. Deflection
16.11111111 1.144675 5800 5940 6.47686E+15 168750000 16.82684621
max d max b
300 75
300 75
0.3 0.075

50

300 75

. Deflection
FAIL
w l vmax
V 1 1.675 0.8375
fv v d b
fv 1.91 837.5 51.29220265 12.82305066 75 25

mmax w l mmax
1 1.675 0.350703125
f m d b
f 18 350703.125 467604.1667 77.61746553 19.404366382 100

allow. Displac l allow displacement


1675 4.652777778

act. Deflectionw l e d b
4.652777778 1 1675 5940 178008404 115.50748472 28.87687118

for checking
w= 1+ 1.0401875
shearing
w l vmax
V 1.0401875 1.675 0.871157031
fv 0.2090777 SAFE

bending
mmax w l mmax
1.0401875 1.675 0.364797007
f 2.801641013 SAFE

for deflection
act. Deflectionw l e i act. Deflection
4.652777778 1.0401875 1675 5940 4.09393E+13 8138020.8333 2.20548655
max d max b
125 50
125 50
0.125 0.05

25

125 50

. Deflection
SAFE