Sie sind auf Seite 1von 1

Login Register

Control Systems Application and Knowledge Store


Ask questions, find answers and share applications Search for questions & tags OK

Home Questions Answers Apps Questions & Tags Users Apps

HOW TO LOCK PARAMETER CHANGE ON ACS 880 DRIVE? Ask a Question Upload New App
Hi,
I need to be able to lock The HIM on the ACS 880 to prevent Parameter change. Popular tags New Users
Can anyone assist with hoe to enable this with a password? 800xA (3171) Uckind
Comments (0) | New Comment KnowledgeArticle Autoel
Drives Tags Configuration ACS880/ACS800 series (1875) Nchunga12
AC 800M (1359) Paco_MR
Answer this question Watch this Question Riccardo Brits Freelance (816) MBiker65
E-mail asked 1 month ago
Report AC500 (761)
Closed

Follow
Recommend 1 Tweet Share Get weekly AKS updates

Partner Exclusive Webinars


Answers
>– Login to the partner portal to register
Hi Riccardo
2
the ACS880 can lock the parameters by setting parameter 96.01 Points Redemption Program
Please read very attention the FW manual about this point, to avoid successives
problems in case you need to modify some others parameters.
- Redeem your points for ABB training, Bluetooth
speakers and mugs. Terms and conditions >
The PW can not be recover simply

Hope this help you Earn points when you refer a


Flavio Mussolin
friend
report AKS Referral Program is "Live" - Learn more
answered 1 month ago

AKS Experts
Comments (4) | New Comment
Dieter Henkel Ask
Rank: 21
2 Hey Riccardo. You can set a master password to prevent eg. the changing of
parameter values and/or loading of firmware or files.
To activate the user lock for the first time, enter the default pass code, 10000000, into Flavio Mussolin Ask
par 96.02 Pass code. This will make parameters 96.100....96.102 visable. Then enter Rank: 4
a new passcode into 96.100 change user pass code, and confirm the code in 96.101 ABB AVP, Senior Electronic and Automation
Engineer with over 30 years of experience in
confirm user passcode. In par 96.102 user lock functionality, you can define the the field of process automation automotive,
actions that you want to prevent. pharmaceutical, hollow glass, steel and rolling.

To close the user lock, enter an invalid pass code into 96.02 pass code, and recycle MMM Ask
control supply. With the lock closed, parameters 96.100...96.102 are hidden. Rank: 5
ABB PA CT Technical Support
To repon, enter your new password into 96.02.

I trust this helps. Govindaraj Ask


Rank: 10
Regards Working in ABB India Operation Center. Have
Project engineering and commissioning
experience in ABB 800xA, Freelance, AC500.
Gavin Nebrigic.

report Zaganeb