Electronic single phase meter

alpha A220

Electronic single phase meter for residential and


light commercial application
With the deregulation of the energy market, in combination with a changing cost
situation, new flexible tariff structures and a modern energy management are
required. Remote metering and the standardization process become more and
more important. With the adaptation of the alpha meter A220, the conditions to
match these new requirements were created.

The A220 meter is available for direct connection. The meter is in accordance
with the relevant DIN and IEC standards and follows the requirements of VDEW
V2.0 for electronic electricity meters.

Features
 High accuracy and stability  Installation support features
 DIN- or British-Standard version available  Optical interface acc. EN62056-21
 4-Quadrant measurement (+P,-P,+Q,-Q,Q1..Q4)  RS485 or CL0 interface (option)
 4 energy and 4 demand tariffs, independently  Log file for registration of all events with time
controllable and date stamps
 Measurement of active, reactive and apparent  Load profile for billing data (option)
demand o up to 8 channels
 Integrated tariff clock o different modes of storage
 Time back-up with internal battery, exchangeable  Measuring of instantaneous values U, I, f,…,
battery optional (option)
 OBIS identifier system acc. EN62056-61  Instrumentation profile up to 8 channels
 Display largestly according to the VDEW- (option)
specification  1 control input (option, only DIN version)
 Readout of meter data according to the  1 electronic S0 output (option)
EN 62056-21 protocol
 User friendly reading, setting and program-
 Readout of meter data without mains power via ming tool alphaSET
optical interface (option)
 Anti-Tampering features, like
o terminal cover removal detection
o reverse run detection
o absolute value measurement
Technical Data Modifications or deviations are reserved R 1.4

Nominal voltage 2-wire, 1 system 220 .. 240V (-20% .. 15%)


Nominal frequency 50 / 60Hz, +/-5%
Nominal / maximum current Continuous current 5(60)A, 5(80)A, 5(100)A
Short duration 7000A for 2 cycles
Starting current < 16mA
Accuracy Class 2 or 1, EN62053-21
A or B MID app. MI-003
Power supply Nominal voltage 220 … 240V (-20%..+15%)
1 control input (option) Control voltage 230V, only for DIN version available
Threshold Max. 265V AC
„OFF“ at <40V, „ON“ at >60V
1 electronic output BS-Version: S0 Standard Acc. IEC 62053-31
DIN-Version: 230V AC/DC or S0 230V, 100mA (only in DIN version available)
Interfaces Optical interface Acc. IEC 62056-21, max 9600 Baud
Electrical interface (CL0, RS485)
Internal tariff source 4 tariffs Acc. EN 62054-21 (former EN 61038)
4 seasons
weekday dependent tariff scheme
Real Time Clock Accuracy < 5ppm (<0,5s/d)
o
- Time backup for RTC Battery > 8 years continuous operation at 25 C
shelf life of 5 years
Time backup for readout without Supercap 0,5 days
mains power Internal battery 4 years, depending on number of readouts
Additional exchangeable battery 7 years, depending on number of readouts
o o
Temperature conditions Operating temperature -30 ...+70
o o
Storage temperature -40 ...+80
Humidity 0 to 100% rel. humidity, non-condensing
o
Temperature coefficient 0,01% per C (PF=1 and PF=0,5)
EMC compatibility Surge withstand (1,2/50s) 6kV, Rsource = 2Ohm
10kV, Rsource = 40Ohm *)
Dielectric test 4kV, 1min, 50Hz
EMC environmental conditions MID E2
Power consumption < 0,7W, < 8VA
Connections Direct connected meter Terminals: Ø=9,0mm
Auxiliary connections Terminals: Ø=4,0mm
Housing Dimensions DIN 43857 part 1, BS 7856
Protection class Housing: IP54, terminal block: IP31
Material Polycarbonate, non-inflammable, self-
extinguishing synthetic material, recyclable
Mechanical environmental conditions MID M1
Weight <0,4 kg
*) only between main terminals