Alabama Residential Compliance Checklist

2006 International Energy Conservation Code


Climate Zone 2

Date: Name of Evaluator(s):


2
Building Name & Address: Conditioned Floor Area: ft

Building Contact: Name: Phone: Email:

Compliance Approach: Prescriptive (402.1.1 thru 402.1.3) UA Trade-Off (402.1.4) Building Performance (404)

State: Jurisdiction:

Building Type: 1- and 2-Family, Detached: Single Family Modular Townhouse

Multifamily: Apartment Condominium


i
Project Type: New Construction Addition to existing building Existing building renovation

Item Code Verified Complies


1
Number Pre-Inspection/Plan Review Value Value Y N N/A Comments/Notes/Findings
PR1 Construction drawings and
1
[104.1] documentation submitted and
available. Documentation
sufficiently demonstrates energy
code compliance.
PR2 HVAC loads calculations:
2
[403.6] Heating system size(s): kBtu:
Cooling system size(s): kBtu:

Additional Comments:

Item Verified Complies


Number Foundation Inspection Code Value Value Y N N/A Comments/Notes/Findings
FO1 Slab edge insulation R-value. Unheated:
1
[402.2.7, ] Installed per manufacturer’s R-0
instructions. Heated: R-5 R-
FO2 Slab edge insulation Heated: 2 ft. ft.
1
[402.2.8] depth/length.
FO3 Insulation protection.
2
[102.2.1]

Additional Comments:

1
Relevant 2006 IECC code section numbers are included in brackets. Code section numbers followed by an asterisk indicate a Tier 2 checklist item.
1 2
KEY High Impact (Tier 1) Medium Impact (Tier 2) Page 1
General building information only required if different than above

Date: Name of Evaluator(s):


2
Building Name & Address: Conditioned Floor Area: ft

Building Contact: Name: Phone: Email:

Compliance Approach: Prescriptive UA Trade-Off Building Performance

Code Verified Complies


Item Number Framing / Rough-In Inspection Value Value Y N N/A Comments/Notes/Findings
FR1 [402.2.5, Floor insulation R-value R-13 R-
402.2.4, (requirement varies depending on (wood)
1 2
102.1.1] floor type). Installed per (steel)
manufacturer’s instructions.
1
FR2 [402.3] Fenestration U-factor (including Sunrooms:
3
sunrooms) U-
U-0.75
FR3 [402.1.1, Skylight U-factor (including U-0.75 U-
1 3
402.3.5] sunrooms)
1
FR4 [102.1.3] NFRC labels present
3
FR5 [402.1.2, Glazing SHGC value SHGC: 0..4 SHGC:
1
402.3.2]
4
FR6 [402.1.1, Mass wall insulation R-value. R-4 or R-13 R-
1
102.1.1] Installed per manufacturer’s if on interior
instructions.
1
FR7 [403.2.1] Duct insulation R-8 (attic R-
supply)
R-6 (other)
1
FR8 [403.2.3] Duct sealing complies with listed
sealing methods
1
FR9 [403.2.3] Building cavities NOT used for
supply ducts
2
FR10 [403.3] HVAC piping insulation R-2 R-
2
FR11 [403.5] Dampers Installed on all outdoor
Intake and exhaust openings
2
FR12 [403.4] Circulating hot-water piping R-2 R-
insulation
FR13 Recessed lighting fixtures meet
2
[402.4.3] infiltration criteria
2
FR14 Glazed fenestration air leakage: 0.3 cfm/ft
2 2 2
[402.4.4] Swinging door air leakage 0.5 cfm/ft cfm/ ft
2
cfm/ ft

Additional Comments:

2
Steel frame equivalent: R-19 in 2x6 or R-19+R-6 in 2x8 or 2x10
3
Up to 15 ft2 of glazed fenestration, including skylights, may be exempted from U-factor and SHGC requirements under the prescriptive approach.
4
If more than ½ the insulation is on the interior, checklist item #IN1 applies (R-6).
1 2
KEY High Impact (Tier 1) Medium Impact (Tier 2) Page 2
Verified Complies
Item Number Insulation Inspection Code Value Value Y N N/A Comments/Notes/Findings
IN1 Wall insulation R-value. Installed per Wood: R-
[402.1.1 manufacturer’s instructions. R-13
402.2.3-4, Mass:
1 5
102.1.1] R-4

IN2 Basement wall insulation R-value. N/A


1
[402.1.1]
IN3 Basement wall insulation depth N/A
1
[402.2.7]
IN4 Sunroom wall insulation. Installed per R-13 R-
1
[402.2.11] manufacturer’s Instructions.
IN5 Air sealing complies with sealing Visual or optional ACH 50 =
1
[402.4.] requirements checklist
IN6 All installed insulation labeled or installed
2
[102.1.1] R-value provided

Additional Comments:

Final Inspection Code Verified Complied


Item Number Provisions Value Value Y N N/A Comments/Notes/Findings
FI1 Ceiling insulation R-value. R-30 R-
[402.1.1 Installed per manufacturer’s
402.2.1 instructions. Blown
402.2.2, insulation marked every 300
1 2
102.1.1.] ft .
FI2 Sunroom ceiling insulation. R-19 R-
1
[402.2.11] Installed per manufacturer’s
instructions
6
FI3 Door U-factor U-0.65 U-
[402.1.1,
1
402.3.4]
FI4 Heating and cooling
1
[403.2.6] equipment type, make and
model as per plans
FI5 Heat pump thermostat
2
[403.3] installed on heat pumps
FI6 Circulating service hot water
2
[403.4] systems have automatic or
accessible controls
FI7 Certificate posted
2
[401.3]

Additional Comments:

5
Mass equivalent: If more than ½ the insulation is on the exterior, checklist item #FR6 applies (R-4).
6
One side-hinged door up to 24 ft2 can be exempted from the prescriptive door U-factor requirements.