Sie sind auf Seite 1von 184

Main Menu

Quick view
20.12.2011 12:00:05

Metering
S1-1 - Lighting/Level1
Control
Quick view
Open Auto
Alarms Measures

Alarm history
Services
Control
ESC OK
Maintenance Ir 000 A I1 000 A
ESC 1/7

I
I1 310 A I2 315 A
20.12.2011 12:00:05

% % S1-1 - Lighting/Level1
I3 302 A IN 23 A Quick view I U-V PQS E
I Current
Measures

Alarm history
I1 431 A
% % I2 385 A
Control
ESC I3 426 A
Maintenance IN 2 A
ESC 1/10

V 4/7

402 V % 100 120 20.12.2011 12:00:05


U1

398 V % 100 120 S1-1 - Lighting/Level1


U2 Quick view I U-V PQS E
VL-L
VL L
401 V % 100 120 Measures

U3 Alarm history
V12 406 V
V23 415 V
Control
V31 409 V
ESC Maintenance

ESC 1/10

PQS

P 64 kW 20.12.2011 12:00:05

Q 38 kVar
S1-1 - Lighting/Level1
S 51 kVA Quick view I U-V PQS E
PQS
Measures

Alarm history Ptot 127 kW


Qtot 13 kVAr
Control
ESC Stot 129 kVA
Maintenance

ESC 1/12

Ep 14397 kWh 20.12.2011 12:00:05

Eq 8325 kVarh
S1-1 - Lighting/Level1
Es 13035 kVAh Quick view I U-V PQS E
E cumul Reset
Measures

Alarm history
EpIn 165 kWh
EpOut 45 kWh
Control
ESC
Maintenance

ESC 1/3
I
I1 310 A I2 315 A

% %
I3 302 A IN 23 A

% %
ESC

1 2 3 4 5 6

Produit Id Metering
I
Micrologic 5.3A
U-V
Serial number: P07451
PQS
Part number: LU432091
E
Firmware: 1.02
F - PF - cos Φ
ESC ESC OK

NonResettableEnergy 1/3 Load Profile 2/3

EpIN 5111947 kWh 0..49% 610 H

EpOut 12345678 kWh 50...79% 15 H

80..89% 360 H

90..100% 3H

ESC ESC

Modbus-SL Ethernet
External power supply External power supply
24 V DC- +
A 24 V DC
- +
B
D0 = A’ / Rx-, A / Tx-
D1 = B’ / Rx+, B / Tx+

24VDC

ETH1 ETH2

IFM D IFE D

OR

1.3 m E E
F F
C C
Red Black White Blue Red Black White Blue

E1 E2 E3 E4 E5 E6 E1 E2 E3 E4 E5 E6
24 V
0V
A / Tx- D0
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1

24 V
0V
A / Tx- D0
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1

LV434195 LV434196 LV434197

Customer terminal block Customer terminal block


Breaker ULP cord
20.12.2011 12:00:05 20.12.2011 12:00:05

S1-1 - Lighting/Level1 S1-1 - Lighting/Level1

Quick view Product ID Information Reset all Quick view Energy


Counter
Measures
Operation xxx
Measures
Ep 11 318 kWh
Alarm history
Trip SDE xxx
Alarm history
Eq 257 kVArh
Control
Close command xxx
Control
Es 13 815 kVAh
Maintenance Maintenance

ESC 3/3 ESC 6/7

20.12.2011 12:00:05

S1-1 - Lighting/Level1

Quick view Product ID Information Reset all


Load profile
Measures

Alarm history 0 to 49%


50 to 79%
Control
80 to 89%
Maintenance 90 to 100%

ESC 2/3
Ethernet Modbus Modbus
Ethernet

24VDC

C
24VD

ETH 2
2
ETH1 ETH
ETH2
1
ETH 2
ETH 1
ETH
1
ETH

I J J
(factory
set)
I
.YY.ZZ
IFE _XX set)
ACT (factory
0-100/ .YY.ZZ
1 L K/1 IFE_XX
IFE ETH
0-100/
ACT
0-100/
A CT
2 L K/1 t us L K/1
ETH ET H1
Mo d ul e Sta IFE 0-10
0/A CT
t us 2 L K/1 tus
k Sta ETH
Net wor du le Sta
Mo
s-S L tus
Mo dbu orkk Sta
or
L Netw
bu s-S
Mod
11
LV4340
11
LV4340

or
or

I6
C
I5
I4
C
I3
I2

ULP system
C
I1

I6
C
I5
I4
C

ULP system
I3
I2
C
I1
+
DC
24V

A1

O1
I1
O2
I2
O3
I3
APP I4
I5
I6

du le
IO Mo

F H 33
O3
34
T1
A1
T2

O2
24
O1 23
14
13

G
D
C MX1 F
CT
XF CD CE
B E
OF
SD C
MX1 - XF
A SDE D
PF
CH
B
OF
SDE
PF A
CH
General characteristics
DB417466.eps

Environmental characteristics
24VDC
Conforming to standards UL 508, UL 60950, IEC 60950, 60947-6-2
Certi¿cation cUIUs, GOST, FCC, CE
Ambient temperature -20 to +70 °C (-4 to +158 °F)
Relative humidity 5–85 %
ETH1 ETH2 Level of pollution Level 3
Flame resistance ULV0
Mechanical characteristics
Shock resistance 1000 m/s2
Resistance to sinusoidal vibrations 5 Hz < f < 8.4 Hz
A B Electrical characteristics
Resistance to electromagnetic discharge Conforming to IEC/EN 61000-4-3
I J K Immunity to radiated ¿elds 10 V/m
Immunity to surges Conforming to IEC/EN 61000-4-5
ETH1 ETH2
Consumption 120 mA at 24 V input
Physical characteristics
Dimensions 72 x 105 x 71 mm (2.83 x 4.13 x 2.79 in.)
IFE Mounting DIN rail
IFE-XX.YY.ZZ (factory set)
Weight 182.5 g (0.41 lb)
ETH1 LK/10-100/ACT

ETH2 LK/10-100/ACT
C Degree of protection of the installed IO On the front panel (wall mounted enclosure): IP4x
Module Status D Connectors: IP2x
Modbus-SL
Network Status
E Other parts: IP3x
T Connections Screw type terminal blocks
LV434011
F Technical characteristics - 24 V DC power supply
Power supply type Regulated switch type
R
Rated power 72 W
Input voltage 100–120 V AC for single phase
200–500 V AC phase-to-phase
PFC ¿lter With IEC 61000-3-2
H G Output voltage 24 V DC
Power supply out current 3A
Note: it is recommended to use an UL listed/UL listed recognized limited voltage/Limited current
or a class 2 power supply with a 24 V DC, 3 A maximum.

IFE web page description


Monitoring web page
Real time data 67
Device logging
Control web page
Single device control
Diagnostics web page
Statistics
Device information
L
IMU information
A Ethernet 1 and Ethernet 2 communication port. Read device registers
B 24 V DC power supply terminal block. Communication check
C Ethernet communication LEDs: Maitenance web page
yellow: 10 Mb Maintenance log
green: 100 Mb. Maintenance counters
D Module status LED:
Setup web page
steady o : no power
steady green: device operational Device localization/name
steady red: major fault Ethernet con¿guration (dual port)
Àashing green: standby IP con¿guration
Àashing red: minor fault
Àashing green/red: self-test. Modbus TCP/IP ¿ltering
Serial port
E Network status LED:
steady o : not power/no valid IP address Date and time
steady green: connected, valid IP address E-mail server con¿guration
steady orange: default IP address Alarms to be e-mailed
steady red: duplicated IP address
Àashing green/red: Self-test. Device list
F Sealable transparent cover. Device logging
G ULP status LED. Device log export
H Test button (accessible closed cover). SNMP parameters
I Locking pad. Documentation links
J Modbus tra c status LED (LV434011 only). Preferences
K Device name label. Advanced services control
L ULP ports. User accounts
Web page access
A-37
A

6
5

B
4 7
3 8
2 9
1 0
6
5
4 7
3 8
2 9
1 0
C
D

Test E

I H G
4 5 6
3 7
2 8
1 9
General characteristics
DB417467.eps

Environmental characteristics
Conforming to standards UL 508, UL 60950, IED 60950, 60947-6-2
Certi¿cation cUIUs, GOST, FCC, CE
Ambient temperature -20 to +70 °C (-4 to +158 °F)
Relative humidity 5–85 %
Level of pollution Level 3
I1 C I2 I3 C I4 I5 C I6 Flame resistance ULV0
Mechanical characteristics
Shock resistance 1000 m/s2
Resistance to sinusoidal 5 Hz < f < 8.4 Hz
vibrations
Electrical characteristics
A B Resistance to electromagnetic Conforming to IEC/EN 61000-4-3
discharge
Immunity to radiated ¿elds 10 V/m
Immunity to surges Conforming to IEC/EN 61000-4-5
Consumption 165 mA
24VDC I1 C I2 I3 C I4 I5 C I6

Physical characteristics
Dimensions 71.7 x 116 x 70.6 mm (2.83 x 4.56 x 2.78 in.)
C Mounting DIN rail
4 5 6 Weight 229.5 g (0.51 lb)
M 3
2
7
8
I1
AI D Degree of protection of the On the front panel (wall mounted enclosure): IP4x
1 9 I2
APP
I3 O1
installed I/O application module IO parts: IP3x
L I4 O2 E Connectors: IP2x
I5
O3
Connections Screw type terminal blocks
I6 F
K T Technical characteristics - 24 V DC power supply
G
Power supply type Regulated switch type
J IO LV434063
Rated power 72 W
Input voltage 100–120 V AC for single phase
200–500 V AC phase-to-phase
PFC ¿lter With IEC 61000-3-2
O1 O2 O3 A1
13 14 23 24 33 34 T1 T2
Output voltage 24 V DC
Power supply out current 3A
Note: it is recommended to use an UL listed/UL listed recognized limited voltage/Limited current
or a class 2 power supply with a 24 V DC, 3 A maximum.
I H
Digital inputs
Digital input type Self powered digital input with current limitations as per
IEC 61131-2 type 2 standards (7 mA)
Input limit values at state 1 19.8–25.2 V DC, 6.1–8.8 mA
(close)
13 14 23 24 33 34 T1 T2
Input limit values at state 0 0–19.8 V DC, 0 mA
(open)
Maximum cable length 10 m (33 ft)
Note: for a length greater than 10 m (33 ft) and up to 300 m (1,000 ft), it is mandatory to use a
shielded twisted cable. The shield cable is connected to the I/O functional ground of the I/O
1
2
application module.
Digital outputs
Digital output type Bistable relay
Rated load 5 A at 250 V AC

O N Rated carry current 5A


Maximum switching voltage 380 V AC, 125 V DC
Maximum switch current 5A
A 24 V DC power supply terminal block. Maximum switching power 1250 VA, 150 W
B Digital input terminal block: 6 inputs, 3 commons and 1 shield. Minimum permissible load 10 mA at 5 V DC
C 6 input status LEDs.
Contact resistance 30 mΩ
D Analog input status LED.
Maximum operating frequency 18000 operations/hr (Mechanical)
E 3 output status LEDs. 1800 operations/hr (Electrical)
F I/O application module identi¿cation labels. Digital output relay protection External fuse of 5 A or less
G Sealable transparent cover. by an external fuse
H Analog input terminal block. Maximum cable length 10 m (33 ft)
I Digital output terminal blocks. Analog inputs
J ULP status LED. The I/O application module analog input can be connected to a Pt100 temperature sensor
K Test/reset button (accessible with cover closed). Range -30 to 200 °C -22 to 392 °F
L Setting locking pad. Accuracy ±2 °C from -30 to 20 °C ±3.6 °F from -22 to 68 °F
M Application rotary switch: 1 to 9. ±1 °C from 20 to 140 °C ±1.8 °F from 68 to 284 °F
N Switch for I/O addressing (I/O 1 or I/O 2). ±2 °C from 140 to 200 °C ±3.6 °F from 284 to 392 °F
O ULP connectors. Refresh interval 5s 5s

A-41
Ethernet Ethernet

24 Vdc 24 Vdc

I6
C
C C I5
24VD 24VD I4
C
I3
I2
C
I1

ETH 2 ETH2 C
I6
I5
2 2 I4
ETH C
ETH1 ETH
ETH1 I2
I3
1 1 C
ETH ETH I1
+ C
24VD

A1

O1
O2
O3

K
dul e
IO Mo

A1
T2
O3 T1
34
11 33
LV4340
O2

A
24
O1 23
14
13

B B

J
I
H
D

D
E

G
Modbus Modbus

I6
C
I5
I4
C
I3
I2
C
I1

I6
C
I5
I4
C
I3
I2
C
I1
+ C
24VD

A1

O1
I1
O2
O3

K
u le
IO Mod

A1
T2
O3 T1
34
33

A
O2
24
O1 23
14
13

B
B

J
I
H
D

D
E

E
G
Mount ing versions and
c onne t ions

Three types of connection are available: Mounting type


vertical or horizontal rear connection Masterpact circuit breakers are available in two mounting versions :
front connection Fixed Drawout
mixed connection.

PB101578A60_SE_r.eps

PB106363A35.eps
The solutions presented are similar in principle for all
Masterpact NT and NW ¿xed and drawout devices.

The drawout version is prefered in most of the applications due to its following
bene¿ts :
visible separation of the power contacts via racking out
easy and complete access to the device for periodic maintenance
possibility of a quick replacement of the device if necessary.
Rear connection
Horizontal Vertical
PB104354A40.eps

PB104355A40.eps

Simply turn a horizontal rear connector 90° to make it a vertical connector.


For the 6300 A circuit breaker, only vertical connection is available.
Front connection
PB104356A40.eps

Front connection is available for NW ¿xed and drawout versions up to 3200 A.


Mixed connection
PB104357A40.eps

PB104358A40.eps
PB104359A40.eps

Note: Masterpact circuit breakers can be connected indi erently with bare-copper, tinned-copper
and tinned-aluminium conductors, requiring no particular treatment.

A-46
E
i c 6.0
olog
Micr

100

40

menu

alar m

tim e tr 8 12
lo ng
( s) 4 16
Ir .8 .9 2
.7 20
.95
1 24 us
.6 .98 .5 a t 6 Ir an eo
.5 in st ant
1
.4 x In Ii 8 10
6 12
t ime t sd 4 .4 . 3
sh ort
(s) . .2 4 15
Isd 4 5 3 off
3 .3 .1 2
6
8
.2 0 x In
2.5 .1 2
I t test
2 10 on
1.5 delay
x Ir
setting tg .4 .3
(s) .4 .2
E F .3 .1
Ig D G
C H
.2 0
.1 2
I t
o ff
B I on
A
d fa ult
gro un
COM
200 ms
min.
for MX
Interlocking of two Masterpact NT/NW or up to three
PB100842_68_SE.eps

Masterpact NW devices using cables


For cable interlocking, the circuit breakers may be mounted one above the other or
side-by-side.
The interlocked devices may be ¿xed or drawout, three-pole or four-pole, and may
have di erent ratings and sizes.
Interlocking between two Masterpact NT or NW
This function requires:
an adaptation ¿xture on the right side of each device
a set of cables without slip adjustments
the use of a mechanical operation counter CDM is mandatory.
The maximum distance between the ¿xing planes (vertical or horizontal) is 2000 mm.
Interlocking between three Masterpact NW
This function requires:
Interlocking of two Masterpact circuit breakers using cable. a speci¿c adaptation ¿xture installed on the right side of each device
two sets of cables without slip adjustments
the use of a mechanical operation counter CDM is mandatory.
The maximum distance between the ¿xing planes (vertical or horizontal) is 1000 mm.
Installation
The adaptation ¿xtures, sets of cables and circuit breakers or switch-disconnectors
are supplied separately, ready for assembly by the customer.
Installation conditions for cable interlocking systems:
cable length: 2.5 m
radius of curvature: 100 mm
maximum number of curves: 3.
PB113432_R.eps

Possible combinations of “ Normal” and “ Replacement” source circuit breakers

“ Normal N” “ Replacement” R
NT06 to NT16 NW08 to NW40 NW40b to NW63
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A

All combinations of two Masterpact NT and Masterpact NW devices are possible,


whatever the rating or size of the devices.

Possible combinations of three device

NT06 to NT16 NW08 to NW40 NW40b to NW63


NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A

Only Masterpact NW may be used for three-device combinations.


Types of mechanical interlocking and combinations
Interlocking of two Masterpact circuit breakers using cable.
Choice criteria
In the applications where the continuity of service is critical (1) (data centers, airports,
hospitals, marine, oil & gas, process industry, …) the mechanical interlocking by
rods and the drawout version devices are strongly recommended.
Mechanical interlocking by rods is preferred as less energy is consumed by friction,
so it has less e ect on the circuit breaker closing energy.
In terms of breaker mounting type, the drawout version is preferred as :
it provides mechanical isolation of the circuit breaker from possible external stress
on the terminals by having a Àexible connection at the clusters level
it allows simple and total access for periodic maintenance
it allows quick replacement of the device if necessary.
When not possible, cable interlocking or ¿xed versions can be used, but the
installation rules detailed in the 2 sections below must be strictly respected and
mainly :
the busbars or the cables used for the power connections must apply no stress on
(1) for more details please contact your local support. the circuit breakers terminals. Their weight must be supported by the switchboard
Note: for cable length higher than 2,5m please consult us frame.
before ordering the circuit breakers Please refer to the “Switchboard integration - Installation rules – Power connection”
for a customised solution. section in this catalogue as well as to the Data Bulletin “Installation of Fixed
See catalogue “Source changeover systems”, Masterpact NW Circuit Breakers in Electrical Equipment – Class 0613” available on
ref. LVPED211022EN. www.schneider-electric.com for more details.
A-61
H

P P L
L
(m)
2000
Y

61

11.5

2 (1) (2)

15

8
5 17 (1) (2)

F (1) (1)
F (1)
Door (2) Door Door
(2)
F (2)
.

.
.
N
ETH1 ETH2

IFE
IFE-XX.YY.ZZ (factory set)

ETH1 LK/10-100/ACT

92
ETH2 LK/10-100/ACT

Module Status 45
84.8 105
Modbus-SL
Network Status

T LV434011

72 63.6
71
24VDC I1 C I2 I3 C I4 I5 C I6

I1 A1
I2
I3 O1
I4 O2
I5 O3 45 92
I6
84.8 115
IO LV434063

O1 O2 O3 A1
13 14 23 24 33 34 T1 T2

72 63.6

71

45 92
85 105

18 66
73

90 45 85 106

144 63

69
M1M2M3
96
X

96
Y

+ 0.8
X 92 0
X

+ 0.8
10.6 92 0
20.7 23
Y
Z

2 Ø22.5

16.5

X 99.3
+ X
- 0.5
32
19

+
- 0.3
15 37 20 13 2 Ø22.5
+1.5
-
33
Z
17
99.3
Y
129
X

163

1.5...6

100
X

30.6
17.5
39

+0
Ø 22,5 -0,30
100

100 100

100

+0

30 -0,20

Y
A P
E H
A P
E H
Shield Drain
Ethernet
J
24 V DC

Modbus

A A N A
24 V DC
24 V DC B
+24 V
0V

I I I
K Eth 2

C Eth 1

C +24V
0V
D

K +24 V
0V

Eth 1
Eth 2

Eth 2

Eth 1

I
I I
I6
C
I5
I4
C
I3
I2
C
I1

I6
C
I5
I4
C
I3
I2
C
I1
+
DC
24V

A1
K
K O1
O2
O3

K d ule
IO Mo
I6
C

E I1
C
I2
I3
C
I4
I5

A1
T2
O3 T1
34
I6 I6 O2
33
C C 24
I5 23
O1
I3 14
I2 13
C I2
I1 C
I1
+
DC
24V
I6
C
I5

I3
I2
C
I1
+ C
2 4VD

d ule
IO Mo

A1
T2
T1

O2
24
23
O1
14
13
A1
T2
T1

M
O2
24
23
O1
14
13

F
L L L M

F G H H
121
FDM

Color
Red E1 24 V
Black E2 0V
White E5 H
Blue E6 L

Breaker ULP
cord

Red Black White Blue

E1 E2 E3 E4 E5 E6
A / Tx- D0
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
24 V
0V

Customer terminal block

External power supply External power supply


24 V DC 24 V DC
- + - +
Ethernet Modbus-SL

D0 = A’ / Rx-, A / Tx-
ULP cable D1 = B’ / Rx+, B / Tx+

24VDC

ETH1 ETH2

IFE IFM

ULP Termination ULP Termination

OR
121
FDM

24VDC

I/O
application
Color module
Red E1 24 V
Black E2 0V
White E5 H
Blue E6 L
Breaker ULP ULP cable
cord
Red Black White Blue

E1 E2 E3 E4 E5 E6
24 V
0V
A / Tx- D0
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
Customer terminal block

Modbus-SL Ethernet

24 V DC 24 V DC

24VDC

ETH1 ETH2

IFM IFE

ULP Termination ULP Termination


OR
110/415 V AC
24/125 V DC
Retro¿t solutions, please contact Schneider
Retro¿t solutions, please contact Schneider
Replacement parts for Micrologic control units
Long-time rating plug (limits setting range for higher accuracy) / 1 part
Standard 0.4 at 1 x Ir 33542
DB404394.eps

Low-setting option 0.4 at 0.8 x Ir 33543


High-setting option 0.8 at 1 x Ir 33544
Without long-time protection o 33545
Battery + cover
Battery (1 part) 33593
DB404395.eps

Cover (1 part) For Micrologic A, E 33592


For Micrologic P and H 47067

menu

Communication option
IFE Ethernet interface LV breaker LV434010
DB417415.eps

Ethernet interface for LV breakers and gateway LV434011

IFM Modbus-SL interface module TRV00210


DB111441.eps

I/O application module LV434063


6 wires terminals drawout (1 part) 33099
6 wires terminals ¿xed (1 part) 47075
User guide IFE DOCA0084EN-00
DB417414.eps

User guide I/O application module DOCA0055EN-00

Accessories
External sensors
External sensor for earth-fault protection (TCE) / 1 part
Sensor rating 400/1600 A 33576
DB404381.eps

Source ground return (SGR) earth-fault protection / 1 part


DB404382.eps

External sensor (SGR) 33579


MDGF summing module 48891

Rectangular sensor for earth-leakage protection + Vigi cable / 1 part


DB404382.eps

280 mm x 115 mm 33573

Vigi cable or external voltage cable / 1 part


Vigi cable or external voltage cable (1 part) 47090
External power supply module (AD) / 1 part
24-30 V DC 54440
DB105360.eps

48-60 V DC 54441
100-125 V DC 54442
110-130 V AC 54443
200-240 V AC 54444
380-415 V AC 54445
Battery module (BAT) / 1 part
1 battery 24 V DC 54446
DB404384.eps

L4
L3 t
Inpu C
24VD

ut
A Outp
AD 220 24VDC G2
G1

Test equipments / 1 part


Hand held test kit (HHTK) 33594
DB404386.eps

Full function test kit (FFTK) 33595


Test report edition come from FFTK 34559
FFTK test cable 2 pin for STR trip unit 34560
FFTK test cable 7 pin for Micrologic trip unit 33590

F-5
menu

L4

L3 Inpu t
24V DC

ut
A Outp C
AD 220 24VD
G2
G1
ART.834783 © 2016 - Schneider Electric - All rights reserved.

Schneider Electric Industries SAS


35, rue Joseph Monier As standards, speci¿cations and designs change from
CS 30323 time to time, please ask for con¿rmation of the
92506 Rueil Malmaison Cedex information given in this publication.
10-31-1247
France
Publication: Schneider Electric Industries SAS
RCS Nanterre 954 503 439 Photos: Schneider Electric This document has been
Capital social 896 313 776 € Publishing: Altavia St Etienne printed on ecological paper.
www.schneider-electric.com

LVPED208008EN 07-2016

Das könnte Ihnen auch gefallen