Beruflich Dokumente
Kultur Dokumente
1
Electronic Trivector Meter- ...................................................................................................... 22
DISPLAYPARAMETERS .......................................................................................................... 22
Specifications- ...................................................................................................................... 23
Detailed Study about Transformer ........................................................................................... 24
Principle of operation of Transformer ..................................................................................... 24
Induction law ........................................................................................................................... 25
The Ideal Transformer.............................................................................................................. 26
Leakage flux ............................................................................................................................. 27
Transformer universal emf equation ....................................................................................... 28
Core form and shell form transformers ................................................................................... 28
Equivalent circuit ..................................................................................................................... 29
Cooling ..................................................................................................................................... 30
Insulation drying ...................................................................................................................... 31
Bushings ................................................................................................................................... 32
Classification parameters......................................................................................................... 32
Types ........................................................................................................................................ 32
Applications ............................................................................................................................. 34
Conclusions .............................................................................................................................. 35
Bibliography ............................................................................................................................. 36
2
Tables of Figures
Fig no. 1 Substation its function and types
Fig no.2 Current Transformer
Fig no.3 Potential Transformer
Fig no.4 Transformer at the substation
Fig no.5 Conductors
Fig no.6 Isolator
Fig no.7 Circuit Breaker
Fig no.8 Vacuum Circuit Breaker
Fig no.9 Lightning Arrester
Fig no.10 Electronic Trivector Meter
Fig no.11 A Transformer
Fig no.12 windings in core
Fig no.13 The basic transformer
Fig no.14 Ideal transformer circuit diagram
Fig no.15 Leakage flux of a transformer
Fig no.16 Core form = core type; shell form = shell type
Fig no.17 Basic transformer equivalent circuit
Fig no.18 Cutaway view of liquid-immersed construction transformer
Fig no.19 An electrical substation in Melbourne, Australia showing 3 of 5 220kV/66kV
transformers, each with a capacity of 150 MVA.
3
About UPPCL
UPPCL will be professionally managed utility supplying reliable and cost efficient
electricity to every citizen of the state through highly motivated employees and state of
art technologies, providing an economic return to our owners and maintaining
leadership in the country.
UPPCL Mission
We shall achieve this being a dynamic, forward looking, reliable, safe and trustworthy
organization, sensitive to our customers interests, profitable and sustainable in the long
run, providing uninterrupted supply of quality power, with transparency and integrity in
operation, providing
To the Public
4
We shall measure success on global standards, e.g.
Parameter Measurement
Commercial losses 2%
5
Substation, Its Function And Types
6
Load shedding and prevention of loss of synchronism. Maintaining the system
frequency within targeted limits.
Voltage Control; reducing the reactive power flow by compensation of reactive
power, tap-changing.
Securing the supply by proving adequate line capacity.
Data transmission via power line carrier for the purpose of network monitoring;
control and protection.
Fault analysis and pin-pointing the cause and subsequent improvement in that
area of field.
Determining the energy transfer through transmission lines.
Reliable supply by feeding the network at various points.
Establishment of economic load distribution and several associated functions.
Types of Substation-
The substations can be classified in several ways including the following :
Classification based on voltage levels, e.g. : A.C. Substation : EHV, HV, MV, LV;
HVDC Substation.
Classification based on Outdoor or Indoor : Outdoor substation is under open skv.
Indoor substation is inside a building.
Classification based on configuration, e.g. :
Conventional air insulated outdoor substation or
SF6 Gas Insulated Substation (GIS)
Composite substations having combination of the above two
Classification based on application
Step Up Substation : Associated with generating station as the generating voltage is
low.
Primary Grid Substation : Created at suitable load centre along Primary transmission
lines.
Secondary Substation : Along Secondary Transmission Line.
Distribution Substation : Created where the transmission line voltage is Step Down to
supply voltage.
Bulk supply and industrial substation : Similar to distribution sub-station but created
separately for each consumer.
7
Mining Substation : Needs special design consideration because of extra precaution for
safety needed in the operation of electric supply.
Mobile Substation : Temporary requirement.
NOTE:
Primary Substations receive power from EHV lines at 400KV, 220KV, 132KV and
transform the voltage to 66KV, 33KV or 22KV (22KV is uncommon) to suit the local
requirements in respect of both load and distance of ultimate consumers. These are also
referred to ‘EHV’ Substations.
Secondary Substations receive power at 66/33KV which is stepped down usually to
11KV.
Distribution Substations receive power at 11KV, 6.6 KV and step down to a volt
suitable for LV distribution purposes, normally at 415 volts
8
Main Office Building
Administrative building
Conference room etc.
6/10/11/20/35 KV Switchgear, LV
Indoor Switchgear
Switchgear and Control Panel Building
Low voltage a.c. Switchgear
Control Panels, Protection Panels
Battery Room and D.C. Distribution System
D.C. Battery system and charging equipment
D.C. distribution system
Mechanical, Electrical and Other Auxiliaries
Fire fighting system
D.G. Set
Oil purification system
9
the system more unstable. Disconnecting the faulted component, quickly, tends to
minimize both of these problems.
10
Interconnection:
11
Equipments:
The line in the sub-station operates at high voltages and carry large amount of current.
The measuring instrument and protective devices are designed for low voltages.
Therefore they will not work satisfactorily if mounted directly on the power lines. The
function of instrument transformers is to transfer voltages and currents of power lines to
a value which is convenient for operation of measuring and relays.
It is a step down transfer which steps down the current to a know ratio. The primary of
this transformer consists of one or more thick wires connected in series with the line
and hence is dependent upon the load connected to the system. The secondary consists
of a large number of turns of fine wires and provided for the measuring instruments and
relays, a current which is a constant function of the line current. It also does the work of
sensing abnormalities in current and sent signal the relays to isolate the defective
system.
12
Specification of CT:
Specification of PT:
Ratio - 33 KV / 100 V
Primary Winding - 33 KV
Type - Earthed
Secondary Winding - 100 V
Transformers:
Transformers are the most essential part of a sub-station. In Electricity Urban
Distribution Division, Civil Lines, Allahabad there are two transformers; TR-1, TR-2
both of which are 33/11 KV, 10 MVA. These transformers supplies power over Civil
Lines area within 20 km of range in Allahabad region.
Inside the transformer a high voltage windings are wound over low voltage winding on
a metallic core. There are three such arrangements each for a phase. These three
arrangements are inside the transformer tank, which is filled with transformer oil.
Transformer oil does the primary work of cooling the windings and core which tend to
release heat during operation.
Externally transformers have the appearance of a huge metallic container. We can
observe conservator tank, Bucholtz Relay, Breather, Oil and Winding temperature
13
meter etc. It also has large radiator grills to dissipate the heat from transformer oil and
cool it down. The bushings are present for taking in and out the power lines from the
transformer. Conservator tank helps in maintaining the oil level inside the transformer.
The vaporized oil is condensed to liquid form in that tank. Breather serves the purpose
of absorbing moisture from air that comes in contact with Transformer Oil. Breather
contains silica gel which absorbs moisture. In modern transformers balloon
arrangement is used. The balloon membrane is a porous material which allows dry air
to pass through and absorbs moisture which degrades the Transformer Oil. Transformer
also has a tap changing arrangement which helps in varying the voltage in transformer.
Tap changer is based on the H.V. winding because precision is higher than low voltage
winding and as H.V. winding is wound outside, bringing the tap pointer is easier and
mechanism is easier than tap changer in L.V. winding, which is inside.
Tap changers are of two types:
i) ON Load tap changer
ii) OFF Load tap changer
During yearly maintenance the important tests are Transformer Oil Test and Insulation
Resistance test.
14
In Transformer Oil test:
Limit per IS
Acidity (mg of KOH/gm) 0.5 max
Neutralization Value
Tan Delta (90°, °C) 0.2 max
Dielectric Dissipation Factor
Resistivity (Ω-cm at 90°) 0.1000 X 1012 min
Dielectric Strength 50 KV min
Break Down Voltage (BDV)
Moisture content (PPM) 0.25 max
Insulation Resistance 5000X106 Ω
HV-E, LV-E, HV-LV
Specification of Transformers:
Transformer – 1:
Type: Three Phase
Volts at no load: HV – 33000 V
LV – 11000 V
Amperes: HV – 175 A
LV – 525 A
Frequency: 50 Hz.
Cooling Type: ONAM
Vector group: DYN-11
Max. oil temperature: 45°C
Max. Winding temperature: 50°C
S.C. Current – Duration 2 sec: HV- 2.09 KA
LV- 6.28 KA
Test Voltage (KV (rms)): HV- 70 KV
LV- 28 KV
Impulse Level (KVp): HV-170
15
LV-75
No load loss (max.): 8 KW
Load loss Normally (max.): 50 KW
Core and Winding: 10,670 kg
Tank and Fitting: 6,500 kg
Oil weight: 3,960 kg
Total weight: 21,130 kg
Oil Volume: 4,500 lt
Transformer – 2
Type: Three Phase
Volts at no load: HV – 33000 V
LV – 11000 V
Amperes: HV – 175 A
LV – 525 A
Frequency: 50 Hz.
Cooling Type: ONAM
Vector group: DYN-11
Max. oil temperature: 45°C
Max. Winding temperature: 50°C
S.C. Current – Duration 2 sec: HV- 2.09 KA
LV- 6.28 KA
Test Voltage (KV (rms)): HV- 70 KV
LV- 28 KV
Impulse Level (KVp): HV-170
LV-75
No load loss (max.): 8 KW
Load loss Normally (max.): 50 KW
Core and Winding: 10,670 kg
Tank and Fitting: 6,500 kg
Oil weight: 3,960 kg
Total weight: 21,130 kg
Oil Volume: 4,500 lt
16
Conductors:
Conductors carry electrical power from sending end to receiving end stations. They are
one of the most important as most of capital outlay is invested on them.
The distribution of current throughout the cross-section of a conductor is uniform only
when D.C is passing through it. When A.C flows through a conductor, the current is
non-uniformly distributed over the cross-section in a manner that current density is
higher at the surface compared to the centre of the conductor. This effect becomes more
pronounced with increase in frequency. This phenomenon is called SKIN EFFECT.
This causes large power loss in A.C transmission. To minimize this effect stranded
conductors are used which have added advantage of flexibility. Aluminium conductor
steel reinforced (ACSR) is most commonly used in overhead transmission lines.
Aluminium is used because it is cheaper and lighter than copper but with less
conductivity and tensile strength. To strengthen the conductor, it is steel reinforced.
ACSR conductors have different specifications and are differentiated with names of
animals like deer, dog, panther, zebra etc.
The interconnections within the sub-station are done with ACSR-panther. The
aluminium bus pipes used in 132kv lines are 2.5 inches in diameter while in 33kv and
25kv lines it is 1.5 inches in diameter.
Specifications of Conductors:
17
Isolators:
Isolators are used in breaking a circuit. Isolators can be both mechanically or remotely
operated. Isolators operate on no-load condition. It does not have specified current
breaking or current making capacity. While opening a circuit, the circuit breaker is
opened first, and then isolator and lastly earthing isolator is closed. While closing a
circuit, earthing isolator is opened first, and then isolator is closed followed by circuit
breaker.
Circuit breakers are most important protective devices. With the help of C.T, P.T and
relays they can be made to trip automatically to disconnect any faulty circuit. Circuit
breakers consist of fixed contact, moving contact, extinguishing chamber, roller,
insulation, breather etc. The moving contact with the help of rollers is responsible for
closing and opening of circuit. They are inside the extinguishing chamber and the
whole arrangement is kept inside an oil-filled chamber. Transformer oil is responsible
for cooling.
Circuit breakers are of many types, but in Allahabad sub-station we come across
vacuum circuit breakers and oil circuit breakers.
18
Fig no.7 Circuit Breaker
19
Specifications of VCB:
Voltage- 36 KV,
Current- 1250 Amps,
Frequency- 50 Hz,
Poles- 3,
Breaking Capacity- 25 KA,
Making Capacity- 62.5 KA,
Short circuit Current- 25 KA,
Duration of S.C. Current(Tk)-3s
D.C Component- 50%,
P.F. Withstand Voltage(Vp)-70 KV
Impulse Withstand
Voltage(Vp)- 170 KV
Supply voltage of Trip/close- 24 KV
Auxiliary Supply voltage- 230V , 50 Hz
Weight- 1200(approx.)Kg
In these breakers, some insulating oil is used as an arc-quenching medium. The contacts
are opened under oil and an arc is struck between them. Mineral oil has better insulating
properties than air.
The oil circuit breakers find extensive use in power systems. They are of following
types:-
1) Bulk oil circuit breaker:
a) Plain break oil circuit breakers, and
b) Arc control oil circuit breakers.
2) Low oil circuit breakers.
20
Lightning Arrestor:
Lightning arrestors are composed of insulators with air gaps and non-linear resistances
in between them. Neal gapless arrestors have zinc sulfide which does the work of both
line gaps and non-linear resistance.
D.C. System:
Protection scheme of transformers and circuit breakers are D.C based. It is such that
because this system is completely independent in operation from A.C supply except
charging of battery which are D.C sources. Moreover this system is free from any
voltage fluctuations which might affect the protection system adversely and even cause
failure.
The D.C system consists of power stack VRLA (Valve Regulated Lead Acid) batteries
21
and battery charger.
Battery charger –
Battery charger is charging the battery in various modes and at the same time to supply
load requirements. The system consists of two battery chargers- 1) Float charger, 2)
Float cum boost charger (FCBC) with contactor interlocking circuit and alarm
indication circuit. They work on 415vac, 3-phase, and 50 Hz supply.
DISPLAYPARAMETERS
Meter can be programmed to display maximum 350 parameters that include PF, per
phase RMS voltages and currents, Frequency, Phase sequence, real time clock, kW,
kVA, kVAr, kWH, kVAh, kVArh+, kVArh-, MDs’, Rising demand with elapsed time,
high resolution energies, tamper details, etc.
22
Fig no.10 Electronic Trivector Meter
Specifications-
Phase - 3, 4 wire
Ib- 5A
Imax- 10 A
2 for 600/5
Frequency- 50 Hz
23
Detailed Study about Transformer-
24
Faraday performed the first experiments on induction between coils of wire, including
winding a pair of coils around an iron ring, thus creating the first toroidal closed-core
transformer. However he only applied individual pulses of current to his transformer,
and never discovered the relation between the turn ratio and emf in the windings.
Induction law
The voltage induced across the secondary coil may be calculated from Faraday's law of
induction, which states that:
where Vs is the instantaneous voltage, Ns is the number of turns in the secondary coil
and Φ is the magnetic flux through one turn of the coil. If the turns of the coil are
oriented perpendicularly to the magnetic field lines, the flux is the product of
the magnetic flux density B and the area A through which it cuts. The area is constant,
25
being equal to the cross-sectional area of the transformer core, whereas the magnetic
field varies with time according to the excitation of the primary. Since the same
magnetic flux passes through both the primary and secondary coils in a quasi ideal
transformer, the instantaneous voltage across the primary winding equals
Taking the ratio of these two equations, gives the basic equation,
, where Np/Ns is the turn ratio, usually expressed in round numbers, the
value of this ratio being respectively higher and lower than unity for step-down and
step-up transformers. If a load is connected to the secondary winding, current will flow
in this winding, and electrical energy will be transferred from the primary circuit
through the transformer to the load.
26
If the voltage is increased, then the current is decreased by the same factor.
The impedance in one circuit is transformed by the square of the turn ratio. For
example, if an impedance Zs is attached across the terminals of the secondary coil, it
appears to the primary circuit to have an impedance of n2 * Zs. This relationship is
reciprocal, so that the impedance Zp of the primary circuit appears to the secondary to
be Zp / n2.
When a voltage is applied to the primary winding, a small current flows, driving
magnetic flux around the magnetic circuit of the core.The current required to create the
flux is termed the magnetizing current. Since the ideal core has been assumed to have
near-zero reluctance, the magnetizing current is negligible, although still required, to
create the magnetic field.
The changing magnetic field induces an emf across each winding. Since the ideal
windings have no impedance, they have no associated voltage drop, and so the voltages
VP and VS measured at the terminals of the transformer, are equal to the corresponding
emf sources. The primary emf, acting as it does in opposition to the primary voltage, is
sometimes termed the counter emf. This is in accordance with Lenz's law, which states
that induction of emf always opposes development of any such change in magnetic
field.
Leakage flux
The ideal transformer model assumes that all flux generated by the primary winding
links all the turns of every winding, including itself. In practice, some flux traverses
paths that take it outside the windings. Such flux is termed leakage flux, and results
in leakage inductance in series with the mutually coupled transformer
27
windings. Leakage flux results in energy being alternately stored in and discharged
from the magnetic fields with each cycle of the power supply. It is not directly a power
loss (see Stray losses below), but results in inferior voltage regulation, causing the
secondary voltage to not be directly proportional to the primary voltage, particularly
under heavy load.
If the flux in the core is purely sinusoidal, the relationship for either winding between
its rms voltage Erms of the winding, and the supply frequency f, number of turns N,
core cross-sectional area a in m2 and peak magnetic flux density Bpeak in Wb/m2 or T
(tesla) is given by the universal emf equation:
If the flux does not contain even harmonics the following equation can be used
for half-cycle average voltage Eavg of any wave shape:
Fig no.16 Core form = core type; shell form = shell type
Closed-core transformers are constructed in 'core form' or 'shell form'. When windings
surround the core, the transformer is core form; when windings are surrounded by the
core, the transformer is shell form. Shell form design may be more prevalent than core
form design for distribution transformer applications due to the relative ease in stacking
the core around winding coils. Core form design tends to, as a general rule, be more
economical, and therefore more prevalent, than shell form design for high voltage
28
power transformer applications at the lower end of their voltage and power rating
ranges (less than or equal to, nominally, 230 kV or 75 MVA). At higher voltage and
power ratings, shell form transformers tend to be more prevalent. Shell form design
tends to be preferred for extra high voltage and higher MVA applications because,
though more labor intensive to manufacture, shell form transformers are characterized
as having inherently better kVA-to-weight ratio, better short-circuit strength
characteristics and higher immunity to transit damage.
Equivalent circuit
Winding joule losses and leakage reactances are represented by the following series
loop impedances of the model:
Core loss and reactance is represented by the following shunt leg impedances of the
model:
29
Core losses are caused mostly by hysteresis and eddy current effects in the core and are
proportional to the square of the core flux for operation at a given frequency. The finite
permeability core requires a magnetizing current IM to maintain mutual flux in the core.
Magnetizing current is in phase with the flux, the relationship between the two being
non-linear due to saturation effects. However, all impedances of the equivalent circuit
shown are by definition linear and such non-linearity effects are not typically reflected
in transformer equivalent circuits.[67] With sinusoidal supply, core flux lags the induced
emf by 90°. With open-circuited secondary winding, magnetizing branch
current I0 equals transformer no-load current.Transformer equivalent circuit impedance
and transformer ratio parameters can be derived from the following tests: Open-circuit
test, short-circuit test, winding resistance test, and transformer ratio test.
Cooling
To place the cooling problem in perspective, the accepted rule of thumb is that the life
expectancy of insulation in all electric machines including all transformers is halved for
about every 7° C to 10° C increase in operating temperature, this life expectancy
30
halving rule holding more narrowly when the increase is between about 7° C to 8° C in
the case of transformer winding cellulose insulation.
Insulation drying
31
Bushings
Classification parameters
Types
A wide variety of transformer designs are used for different applications, though they
share several common features. Important common transformer types include:
32
Autotransformer: Transformer in which part of the winding is common to both
primary and secondary circuits.
Capacitor voltage transformer: Transformer in which capacitor divider is used
to reduce high voltage before application to the primary winding.
Distribution transformer, power transformer: International standards make a
distinction in terms of distribution transformers being used to distribute energy from
transmission lines and networks for local consumption and power transformers being
used to transfer electric energy between the generator and distribution primary circuits.
Phase angle regulating transformer: A specialised transformer used to control
the flow of real power on three-phase electricity transmission networks.
Scott-T transformer: Transformer used for phase transformation from
three-phase to two-phase and vice versa.
Polyphase transformer: Any transformer with more than one phase.
Grounding transformer: Transformer used for grounding three-phase circuits to
create a neutral in a three wire system, using a star-delta transformer, or more
commonly, a zigzag grounding winding.
Leakage transformer: Transformer that has loosely coupled windings.
Resonant transformer: Transformer that uses resonance to generate a high
secondary voltage.
Audio transformer: Transformer used in audio equipment.
Output transformer: Transformer used to match the output of a valve amplifier
to its load.
Instrument transformer: Potential or current transformer used to accurately and
safely represent voltage, current or phase position of high voltage or high power
circuits.
33
Applications
Transformers are used to increase voltage before transmitting electrical energy over
long distances through wires. Wires have resistance which loses energy through joule
heating at a rate corresponding to square of the current. By transforming power to a
higher voltage transformers enable economical transmission of power and distribution.
Consequently, transformers have shaped the electricity supply industry, permitting
generation to be located remotely from points of demand. All but a tiny fraction of the
world's electrical power has passed through a series of transformers by the time it
reaches the consumer.
Transformers are also used extensively in electronic products to step-down the supply
voltage to a level suitable for the low voltage circuits they contain. The transformer also
electrically isolates the end user from contact with the supply voltage.
Signal and audio transformers are used to couple stages of amplifiers and to match
devices such as microphones and record players to the input of amplifiers. Audio
transformers allowedtelephone circuits to carry on a two-way conversation over a
single pair of wires. A baluntransformer converts a signal that is referenced to ground
to a signal that has balanced voltages to ground, such as between external cables and
internal circuits.
34
Conclusions
35
Bibliography
http://www.uppcl.org/uppcllink/documents/23022013042217Energy.htm
http://www.uppcl.org/commercial.html
http://www.uppcl.org/govt.html
http://www.powermin.nic.in/ministry_of_power/miscellaneous/pages/Electronic%2
0Trivector%20Meter.htm
http://www.google.co.in/url?sa=t&rct=j&q=what%2Bis%2Belectronic%2Btrivector%
2Bmeter&source=web&cd=3&cad=rja&ved=0CDMQFjAC&url=http%3A%2F%2Fwww
.deedeetechno.com%2Fimages%2Fproducts%2Facb%2Fkrishnaenterprises_trivector
_meter.pdf&ei=ooHWUeiZK8G3rgfKqYHoAQ&usg=AFQjCNF6TJosD3A_P-MluVU4doF
sZjBROA&bvm=bv.48705608,d.bmk
http://t0.gstatic.com/images?q=tbn:ANd9GcQO0l6QgcKqJ84l8EGbZEYmcRyvFVzph
M-ylY3Hx5BI29J9ZbVL
http://www.indiacore.com/image/logos/logo-uppcl-nn.gif
http://www.eon-uk.com/downloads/Civil_Design_and_Construction_Guidance.pdf
36