Sie sind auf Seite 1von 6

See

discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/268187673

Dissolved Gas Analysis as a Diagnostic Tools for


Early Detection of Transformer Faults

Article · October 2012

CITATIONS READS

11 996

3 authors, including:

Sherif S. M. Ghoneim Sayed A. Ward


Suez University Benha University
36 PUBLICATIONS 111 CITATIONS 46 PUBLICATIONS 148 CITATIONS

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Mitigation of transient overvoltages due to power system restoration using artificial neural network
as a prediction and detection tool View project

Enhancement of Dielectric and Thermal Properties for Transformer Oil Using Nanoparticles View
project

All content following this page was uploaded by Sayed A. Ward on 30 April 2015.

The user has requested enhancement of the downloaded file.


Advances in Electrical Engineering Systems (AEES) 152
Vol. 1, No. 3, 2012, ISSN 2167-633X
Copyright © World Science Publisher, United States
www.worldsciencepublisher.org

Dissolved Gas Analysis as a Diagnostic Tools for Early


Detection of Transformer Faults
Sherif S. M. Ghoneim1, 2, IEEE Member, Sayed A. Ward3
1
Canal Suez University, Suez, Egypt
2
Taif University-Taif- KSA
3
Benha University- Benha- Egypt
E-mail: ghoneim_sherif2003@yahoo.com

Abstract- Transformers is a device on which cost effective supply of electricity mostly depends. Hence, to manage the
life of transformers, to reduce failures and to extend the life of transformer, some measures are being adopted. Dissolved
gas-in-oil analysis (DGA) is a common practice in transformer fault diagnosis. Some classical methods that depend on
gases concentration in transformers oils are used to interpret transformer faults such as Dornenberg, Rogers, Duval
triangle and key gases methods. These methods in some cases did not give the same results; therefore, an expertise
method is developed to give the fault type according to the dissolved gases concentration in oil. A software code is
designed using logic functions to get the type of the faults in transformers. Comparing the results from this software with
the real laboratory cases as well as some cases in literatures is developed. The results explain the validation of software
to detect the fault in transformer.
Key words: Dissolved gases analysis; Transformer oil; Interpretation of transformer faults.

1. Introduction some cases from previous literatures were used to


compare their results with the proposed method’s results.
The cost of unplanned outages can be reduced by the
early detection of such internal faults in transformer. The 2. Classical methods to diagnose transformer
interpretation of transformer faults using dissolved gases faults
analysis is produced using some techniques that assumed
by Dornenberg, Rogers, Duval triangle and key gases When thermal or electrical stresses, which affect the
methods [1-5]. insulating oil and cellulose material in transformers, are
Dissolved gas analysis is the most important test in higher than the normal permissible value, then certain
determining the condition of a transformer. It is the first combustible gases, referred as fault gases, started to be
indicator of a problem and can identify deteriorating produced inside the transformer. The most significant
insulation and oil, over heating hot spots, partial discharge fault gases produced by oil decomposition are H 2
and arcing. Dissolved gas analysis is made on the basis of
(Hydrogen), C 2 H 6 (Ethane), C 2 H 4 (Ethylene) and C 2 H 2
the standard IEC60599 [6] and IEEEC 57-104TM [7]
(Acetylene) as well as Carbon monoxide (CO) and carbon
standards. A four condition DGA guide to classify risks to
transformers with no previous problems has been published
dioxide (CO 2 ) which produce from decomposition of
in the standard IEEE C57- 104TM. insulated paper (Cellulose). The type of the faults
Several artificial intelligence methods such as Fuzzy [corona, arcing discharge (both electrical faults) and
Logic and Artificial Neural Network (ANN) were overheating (thermal fault)] as well as their severity, play
developed as a technique to interpret the faults in an important role in producing different combustible
transformer [8-15]. gases.
In this paper an expertise method based upon the Based on DGA, many interpretative methods have
dissolved gases analysis (DGA) techniques is developed. been introduced to diagnose the nature of the incipient
Based on the interpretation of the classical techniques to deterioration occurred in transformer.
the cause of transformer faults according to the gases Over the years, several techniques have been
concentration in oil transformer, an expertise system is developed to facilitate the diagnoses of fault gases such as
suggested to give the cause of the transformer fault with Dornenberg method [5], Roger's ratio method [3], Key
the aid of logic functions that is used as in Fuzzy and gases method [5, 16], and Duval Triangle method [4] as
Neural Network. A lot of real cases of analyzing the well as the recently developed techniques such as neural
dissolved gases were collected and used to illustrate the network and fuzzy logic.
validity of the proposed expertise method. In addition,
Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 153

2.1. Key gases method R 4 =C 2 H 6 /C 2 H 2 .


A flow chart that describes step by step procedure to
The key gas method interprets the incipient faults in identify the reason behind transformer faults, is found in
transformer according to some significant gases to assign [5].
four typical fault types. These gases are called “key
gases” [5] which are shown in Fig. 1.
2.3. Roger's ratio method
Overheated Cellulose
100
80
This method was further modified into an IEC standard
60
[3], [18]. The original Rogers ratio method uses four gas
%

40
ratios which are CH 4 /H 2 , C 2 H 6 /CH 4 , C 2 H 4 /C 2 H 6 and
20
C 2 H 2 /C 2 H 4 for diagnosis. The refined Rogers method
0 uses two tables: one defined the code of the ratio, and the
CO H2 CH4 C2H6 C2H2 C2H2 other defined the diagnosis rule. The ratio C 2 H 6 /CH 4
Gases only indicated a limited temperature range of
(a) decomposition, but did not assist in further identification
of fault. Therefore, in IEC standard 599, the further
Overheated Oil
100 development of Roger's ratio method, was deleted.
80 Roger's ratio method and IEC 599 have gained popularity
60 in industrial practices. However, it may give no
%

40 conclusion in some cases. This is the "no decision"


20 problem.
0
CO H2 CH4 C2H6 C2H2 C2H2 2.4. Duval triangle method
Gases

(b) The Duval Triangle was first developed in 1974[19].


Three hydrocarbon gases only (CH 4 , C 2 H 4 and C 2 H 2 ) are
Arcing in Oil
100 only used. These three gases are generated as a result of
80 increasing the level of energy necessary to generate gases
60 in transformers in service. Figure 2 indicates the Triangle
%

40 method. In addition to the 6 zones of individual faults


20 (PD, D1, D2, T1, T2 or T3), an intermediate zone DT has
0 been attributed to mixtures of electrical and thermal faults
CO H2 CH4 C2H6 C2H2 C2H2 in the transformer.
Gases PD
(c) T1
Corona in Oil
100 T2
%
4
H

C2
C

80
H4
%

60
D1 D2 DT
%

40
T3
20

0
CO H2 CH4 C2H6 C2H2 C2H2
Gases
%C2H2
(d)
Fig. 1: Key gas method and four typical faults Fig.2: Duval triangle as a diagnostic tool to detect the incipient faults in
transformer.
(T1 the zone of low thermal fault <300oC, T2 the zone of medium
2.2. Dornenburg ratio method thermal fault 300oC<T<700oC, T3 the zone of high thermal fault
>700oC, D1 discharge of low energy arcing, D2 discharge of high
energy arcing, DT attributes to mixtures of electrical and thermal faults
The Dornenburg method utilizes four calculated gas and PD indicates partial discharge)
ratios to indicate a single fault type from three general
fault types. This procedure requires significant levels of 3. Decision Tree as an Expertise Method
the gases to the present in order for the diagnosis to be
valid. The four ratios and their diagnosis values are given
[17]. Dornenburg method uses five individual gases or When four classical methods of transformer fault
four-key gas ratios, which are:- diagnosis such as Key gas method, Dronenberg method,
R 1 =CH 4 /H 2 , Roger's method and Duval triangle method are applied to
R 2 =C 2 H 2 /C 2 H 4 , interpret the cause of the fault in transformer, conflicts
R 3 =C 2 H 2 /CH 4 , may occur. To overcome this problem a decision fault
Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 154

tree is developed which contains the information between


different faults types. Every fault type takes a number to
help us to get the main cause of the transformer fault.
This is shown in Figure 3.

Fault type

No Fault Fault No Fault Identify


0 1 2

Discharge Thermal
7 3

Partial Arcing <300oC >300 and >700oC Fig. 5: The final report
8 11 4 <700oC 6
5 Figure 6 illustrates the flow chart that used to determine
the main cause of the fault using if statement and logic
functions. It depends on the code from the decision tree
Low High Low High Thermal Cellulose
14 fault.
9 10 12 13
Fig. 3: Decision fault tree

A software code in excel sheet is developed using the


logic function to get transformer fault from the four
classical method that mentioned before, the results
depend on the combustible gases that arise when fault
occurs in transformer. After determining the fault type
from these methods, the program decides the incipient
fault type.
Figure 4 explain the form of the excel sheet that is used to
explain the main fault in transformer and Figure 5
illustrates the final report.

Fig. 6: Flow chart to determine the main cause of the transformer fault

4. Fault Type in Transformers According to


Gas Concentration

Some oil samples are taken from real transformers which


are in operation to carry out the study. In table 1, the
results by the expertise method with that take from the
chemical lab is explained. Figure 7 shows the results of
Fig. 4: The excel sheet that use to give the main cause of transform fault case 1 as in table 1.
Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 155

Table 1: Comparison between the expertise method results and lab Table 2: Comparison between the expertise method results and results
results in literatures
CASE 1 2 3 4 5 CASE Sample 2 in Example 2 Case in [11] Case III in
H2 191 154 36 86 10 [20] in [21] [22]
CH 4 47 11 245 187 24 H2 59 206 769 127
C2H2 0.0001 3 0.0001 0.0001 0.0001 CH 4 93 42 999 24
C2H4 15 8 332 363 24 C2H2 1 221 31 81
C2H6 43 14 144 136 372 C2H4 6 82 1599 32
CO 634 487 538 26 343 C2H6 89 16 234 0.0001
CO 2 6623 3395 2326 198 2583 CO 736 334 - 0.0001
LAB. Therm. Disch. of Therm. Therm. Thermal CO 2 1519 3432 - 2024
RES. 300-700 high >700oC >700oC 300-700 LAB. Therm. Arcing Thermal fault Arcing not
o o
C energy C RES. decomp. Disch. with involve
EXP. Med. High High High Med. temp.>700oC cellulose
METH. thermal arcing thermal thermal thermal EXP. Low therm. High High thermal High
fault discharge fault fault fault METH. fault arcing fault arcing
disch. disch.

Fig. 8: Software results for sample 2 in [3]


Fig. 7: Software results for case 1
6. Conclusions
It is seen from the table that, when the C 2 H 2 is
increased above 2, the expected fault in transformer is The results from different cases under study reveal that
arcing discharge as in case 2. In cases 1 and 3, the the proposed technique (expertise method) is reliable to
dominant gases are CH 4 and C 2 H 6 , hence the expected use as a diagnostic tools to detect the fault in transformer
fault is medium thermal fault. The high thermal fault is in its early stage. The conclusions from the real cases
expected when CH 4 and C 2 H 4 are the dominant gases. explain that the nature of the insulating materials involved
The results explain that the reliability of the expertise in the fault and the nature of the fault itself affect on
method to detect the actual fault in transformer as the distribution of dissolved gases. Based on The results from
laboratory does. the software code and the lab results, we see that the
software code is reliable to diagnosis the transformer fault
5. Comparison between the Expertise based on the gas concentrations. The results from the
Method and other Methods in Literatures software code have a good agreement with the previous
conventional methods for the fault detection in
Table 2 shows that the comparison between the results transformers.
from the software code based on expertise method and the
results from other methods in literatures. References
Figure 8 shows the result from the software code for
sample 2 in [20]. [1] E. Dornenburg, and W. Strittmater, “Monitoring Oil Cooling
Table 2 explains also the reliability and validation of Transformers by Gas Analysis,” Brown Boveri Review, vol. 61, pp.
238-274, 1974.
the proposed expertise method for detecting the inception
[2] IEC Publication 599, Interpretation of the Analysis of Gases in
faults in transformer based on DGA. Transformers and Other Oil-Filled Electrical Equipment in Service, First
Edition, 1978.
Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 156

[3] R. R. Rogers, “IEEE and IEC Codes to Interpret Incipient Faults in Different Standards", World Academy of Science, Engineering and
Transformers, Using Gas in Oil Analysis,” IEEE Trans. on Electrical Technology 17 2006.
Insulation, vol. 13, no. 5, pp. 349-354, 1978. [13] J. P. Lee, D. J. Lee, S. S. Kim, P. S. Ji and J.Y. Lim," Dissolved
[4] M. Duval, “Dissolved Gas Analysis: It Can Save Your Transformer,” Gas Analysis of Power Transformer Using Fuzzy Clustering and Radial
IEEE Electrical Insulation Magazine, vol. 5, no. 6, pp. 22-27, 1989. Basis Function Neural Network", Journal of Electrical Engineering &
[5] ANSI/IEEE Std C57.104-1991, IEEE Guide for The Interpretation of Technology, Vol. 2, No. 2, pp. 157~164, 2007.
Gases Generated in Oil-Immersed Transformers, IEEE Power [14] N.A. Muhamad, B.T. Phung, T.R. Blackburn, K.X Lai,"
Engineering Society, 1992. Comparative Study and Analysis of DGA Methods for Transformer
[6] Mukund Hazeeb, S. K. Chand, B. N. De Bhowmick, M. M. Mineral Oil", Journal of Electrical Engineering & Technology, Vol. 2,
Goswami, - “Dissolved Gas Analysis – Some case studies”, Power Grid No. 2, pp. 157~164, 2007.
Corporation of India Limited. [15] Mang-Hui Wang," A Novel Extension Method for Transformer
[7] CIGRE WG A2.18 – “Guide for Life Management Techniques for Fault Diagnosis", IEEE Transactions on Power Delivery, Vol. 18, No. 1,
Power Transformers”, 20th January, 2003. January 2003.
[8] Fábio R. Barbosa, Otacílio M. Almeida, Arthur P. S. Braga, Cícero [16] J.P. Gibeault, On-line monitoring of key fault gases in transformer
M. Tavares, Márcio A. B. Amora, Francisco A. P., “Artificial Neural oil. Operational experience accumulated over the years, SYPROTEC
Network Application In Estimation Of Dissolved Gases In Insulating INC., August 1997.
Mineral Oil From Physical-Chemical Datas For Incipient Fault [17] R.D.Stebbins, J.J.Kelly. S.D.Myers,''Power Hansformer Fault
Diagnosis,” IEEE Trans. Power Del., vol. 6, no. 2, pp. 601-607, Apr. Diagnosis', 1997 IEEE PESWM, Panel Session, New York, Feb.6, 1997.
1991. [18] IEC Publication 60599, Interpretation of the analysis of gases in
[9] CS Chang, CW Lim, Q Su, “Fuzzy-Neural Approach for Dissolved transformer and other oil med electrical equipment in &, Geneva,
Gas Analysis of Power Transformer Incipient Faults", Australasian Switzerland, 1999.
Universities Power Engineering Conference (AUPEC 2004) 26-29 [19] M. Duval, “Fault Gases Formed in Oil-Filled Breathing EHV
September 2004, Brisbane, Australia. Power Transformers- The Interpretation Of Gas Analysis Data”, IEEE
[10] Diego Roberto Morais and Jacqueline Gisèle Rolim,"A Hybrid PAS Conf. Paper No C 74 476-8, 1974.
Tool for Detection of Incipient Faults in Transformers Based on the [20] Sayed A. Ward “Evaluating Transformer Condition Using DGA Oil
Dissolved Gas Analysis of Insulating Oil", IEEE Transactions on Power Analysis”, 2003 Annual Report Conference on Electrical Insulation and
Delivery, Vol. 21, No. 2, April 2006. Dielectric Phenomena.
[11] Rahmat-Allah Hooshmand, Mahdi Banejad, “Fuzzy Logic [21] J. BILBAO, et. al. "Expertise Method to Diagnose Transformer
Application in Fault Diagnosis of Transformers Using Dissolved Gases", Conditions", WSEAS/IASME Conferences, Corfu, Greece, August 17-
Journal of Electrical Engineering & Technology, Vol. 3, No. 3, pp. 19, 2004.
293~299, 2008. [22] Joseph B. DiGiorgio, "Dissolved Gas Analysis of Mineral Oil
[12] Rahmatollah Hooshmand, Mahdi Banejad," Application of Fuzzy Insulating Fluids" , Northern Technology and testing,
Logic in Fault Diagnosis in Transformers using Dissolved Gas based on http://www.nttworldwide.com.

View publication stats

Das könnte Ihnen auch gefallen