Measurement of phase

angles of voltage and


current harmonics
Dr. Michael Schwenke, EM DG PRO D PA

© Siemens AG 2016 siemens.com


Measurement of phase angles of voltage and current harmonics

1. Harmonics: cause – impact – measurement - countermeasures


2. Related standards/measurement methods
1. IEC 61000-4-7: General guide on harmonics and interharmonics measurements and
instrumentation
2. IEC 61000-4-30: only PQ measurement methods for harmonic/interharmonic magnitudes are
defined

Harmonic subgroup and


Interharmonic centered subgroup acc.
IEC 61000-4-7/IEC 61000-4-30
3. Goal of measurement and applications
1. Prevailing phase angle, variation factor and prevailing ratio PR
2. Sign of harmonic active power
3. Improved power measurement
4. Implementation in SICAM Q100
5. Example
© Siemens AG 2016
Page 2 04/2016 Dr. Schwenke / EM DG PRO D PA
Power Quality
What to Do? - The ABC Approach

• Ensure that the obtained energy is according to a defined quality.


• Ensure that negative influences to the connected power supply network are within a certain limit.

A Measure B Evaluate C Optimize

• Continuous measurement of relevant • Concentrate, analyze and evaluate • Definition of proper mitigation measures:
parameters at important points in the recorded parameters: • Dedicated energy supply contract with a defined
power supply network: • Assigning data to the point where they are level of Power Quality
• Point of coupling: In-feed from the utility measured • Filters, redundancies etc.
• Transformer feeders • Evaluate data according to necessary limits and • Process optimization
criteria (e.g. EN 50160)
• Point of coupling of specific production units/lines • Use of less sensitive devices and equipment
• Identification of trends, deviations and limit value
• Big loads causing disturbances violations together with the duration and value
• Use of standardized measurement methods • Assigning evaluation results to the related points
(Class A, Class S)
• Identification of possible originator of the
disturbance

© Siemens AG 2016
Page 3 04/2016 Dr. Schwenke / EM DG PRO D PA
Harmonics
What to Do?

• Caused by: power electronic devices, UPS, converter drives, rectifier, fluorescent lamps, power supply for IT equipment,
PV and wind power inverters
• Impact: heating of motors, cables, transformers; malfunction of breakers, relays, PLC communication, resonances

A Measure B Evaluate C Optimize

• (Active) harmonic filter


àreduce impact on neighborhood
equipment
• power factor correction
à Improve energy efficiency

U = 230 V
I = 160 mA
Total Harmonic Distortion

THD U: 2 %

THD I: 190 %
© Siemens AG 2016
Page 4 04/2016 Dr. Schwenke / EM DG PRO D PA
Applications of phase angle information

Goal Analysis of harmonic power flow Analysis of prevailing phase angles

Measurement “relative” phase angle: “absolute” phase angle


· measurement of phase angles · phase angle in relation to the voltage
between harmonic voltages and fundamental
currents (same order number)
Applications · Evaluation of harmonic flows · Assessment of harmonic current
throughout the system measurements in different points in the
· Assignment of responsibilities in system
the system through the · Assessment of summation factors of
identification of harmonic sources harmonic currents from different
and harmonic sinks disturbing loads when they are
· Calculation of active, reactive and connected to the same node
apparent powers · Modeling of disturbing loads and
evaluation of their disturbing effect
· Design of countermeasures for disturbing
loads
© Siemens AG 2016
Page 5 04/2016 Dr. Schwenke / EM DG PRO D PA
Prevailing phase angle, variation factor and prevailing ratio

Prevailing phase angle: aggregation of phase angles over time (e.g. 10 min)

Variation factor VF

Prevailing ratio: PR = 1 - VF

© Siemens AG 2016
Page 6 04/2016 Dr. Schwenke / EM DG PRO D PA
Philips ML 100: High-pressure mercury tube in series with a tungsten filament
Voltage/current of 100 pcs.

© Siemens AG 2016
Page 7 04/2016 Dr. Schwenke / EM DG PRO D PA
Example
voltage/current characteristics and harmonics

© Siemens AG 2016
Page 8 04/2016 Dr. Schwenke / EM DG PRO D PA
Harmonic measurement:
Magnitude, phase angle, Prevailing phase angle, Prevailing angle ratio

Voltage phase A Current phase A

© Siemens AG 2016
Page 9 04/2016 Dr. Schwenke / EM DG PRO D PA
Example
voltage/current charcteristics

Harmonic direction detection: sign of harmonic active power

© Siemens AG 2016
Page 10 04/2016 Dr. Schwenke / EM DG PRO D PA
Improved power calculation

Reactive power for 1 M -1


phase p, quadrature Qp = Qpquad = × å (vpk - N / 4 ´ ipk )
phase shift formula M k=0

Reactive power for hmax


phase p, Budeanu’s Qp = Qpharm = åI i, p × Vi, p × sin(j i, p )
harmonic definition i=1

© Siemens AG 2016
Page 11 04/2016 Dr. Schwenke / EM DG PRO D PA