Project:2 X 300 MW Annexure-I Doc. No.

:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000

Sizing of neutral grounding transformer and neutral grounding resistor for STG

1. Calculation for sizing of neutral grounding transformer


Input data:

Capacitance of generator winding C1 := 0.225 micro Farad

Capacitance of busduct C2 := 0.06 micro Farad

Capacitance of generator transformer LV winding C3 := 0.004 micro Farad

Surge capacitor in PT cubicle C4 := 0.25 micro Farad

Calculation :

Total capacitance C := C1 + C2 + C3 + C4

C = 0.539 micro Farad

1
Capacitive reactance Xc :=
2 ⋅ π ⋅ 50 ⋅ C ⋅ 10− 6

Xc = 5.905564 × 103 ohms

Normal voltage of generator (line to line) V1 := 20000 V

V1
Normal phase to neutral voltage Vp1 :=
3

Vp1 = 1.154701 × 104 V

Vp1
Charging current per phase IC1 :=
Xc

IC1 = 1.955276 A

Total charging current IC := 3 ⋅ IC1

IC = 5.865827 A

The primary winding Voltage has been considered same as line to line voltage.

Neutral Grounding Transformer selected Primary Rating = 20000 V.

Total charging current under field forcing conditions ICf := IC ⋅ 1.3

ICf = 7.625575 A

ICf
kVA rating of Neutral Grounding Transformer : kVA := V1 ⋅
1000

kVA = 152.511506
Page 1 of 4
Project:2 X 300 MW Annexure-I Doc. No.:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000
kVA = 152.511506

Since , incase of Earth fault, unit will be tripped with in a Short time , Say 5 minute

Over load factor for 5 minute duty = 2.8

Neutral Grounding Transformer kVA rating( based on 5 min. duty cycle)

kVA
Sa :=
2.8
Sa = 54.468395

Nearest kVA of transformer selected = 55kVA

S := 55

NGT parameters :

kVA capacity of NGT : 55 kVA

Ratio : 20000/230V

Duty cycle : 5 minutes

2. Calculation for sizing of neutral grounding resistor

Primary voltage of NGT Vp := V1 V

Vp = 2 × 104
Secondary voltage of NGT Vs := 230 V

Vp
Transformer turns ratio N :=
Vs

N = 86.956522

For Resonance Grounding,

Ic = IL

3 x Vp/Xc =Vp/XL

Xc
XL :=
3

XL = 1.968521 × 103

Ohomic Value of the reactance w.r.t LV side=R

XL
R :=
2
N

R = 0.260337 ohms

Transformer Percentage impedance = Z

Z := 4%

Zpu := 0.04
Page 2 of 4
Project:2 X 300 MW Annexure-I Doc. No.:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000

Zpu := 0.04

Base Impedance w.r.t LV Side = Zb

Vs ⋅ Vs
Zb :=
S ⋅ 1000

Zb = 0.961818 ohm

Transformer impedance w.r.t LV Side = Zlv

Zlv := Zpu ⋅ Zb

Zlv = 0.038473 ohm

Ohomic value of the Netral grounding resistor = NGR

NGR := R − Zlv

NGR = 0.221864

Current in Secondary of NGT = Is


Is := ICf ⋅ N

Is = 663.093503 A

Current rating is selected as 665 A

NGR parameters :

The resistance value of NGR = 0.222 ohms

Current Rating = 665 A

Duty cycle : 5 minutes

Page 3 of 4
Project:2 X 300 MW Annexure-I Doc. No.:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000

Page 4 of 4