2 12620 65 SISW Backward curved belt driven Terrace- Kitchen 11.11 5.84 72.6 71 968 7.5 6
centrifugal fan. (Bearing outside the Airflow Exhaust
path)
3 24900 65 SISW Backward Curved belt driven Terrace- Loundry- 11.11 11.5 73 73 697 15 6
Centrifugal Fan Exhaust air
4 10000 40 Cabinet type Belt driven Backward curved Basement- Exhaust 9.26 3.33 62.9 69 1156 5.5 4
centrifugal Fan Air
5 13000 35 Cabinet type Belt driven Backward curved Basement- Exhaust 9.59 3.67 66.7 69 993 5.5 6
centrifugal Fan Air
6 3900 35 Cabinet type Belt driven Backward curved Basement- Exhaust 9.01 1.15 62.7 65 1733 1.5 4
centrifugal Fan Air
7 650 30 Circular type Inline Fans Basement- Exhaust Available sp= 24 mmwg 60 2600 0.24 2
Air
7A 650 30 Rectangular type Direct driven Inline Fans Basement- Exhaust Available sp= 34 mmwg 57 1200 0.245 4
Air
8 550 30 Circular type Inline Fans Basement- Exhaust Available sp= 31 mmwg 60 2600 0.24 2
Air
9 1100 32 Cabinet type Belt driven Backward curved Lower Ground- 6.26 0.27 65.4 59 2283 0.37 2
centrifugal Fan Exhaust Air
10 1800 32 Cabinet type Belt driven Backward curved Lower Ground- 8.17 0.48 63.7 61 2275 0.75 2
centrifugal Fan Exhaust Air
11 1650 40 Cabinet type Belt driven Backward curved Lower Ground- 7.49 0.5 67.5 61 2326 0.75 2
centrifugal Fan Exhaust Air
12 1350 35 Cabinet type Belt driven Backward curved Lower Ground- 7.69 0.39 63.3 62 2549 0.55 2
centrifugal Fan Exhaust Air
13 1000 35 Cabinet type Belt driven Backward curved Lower Ground- 7.15 0.29 61.4 61 2810 0.55 2
centrifugal Fan Exhaust Air
14 10500 35 Cabinet type Belt driven Backward curved Lower Ground- 9.72 3.37 58.9 69 1158 5.5 4
centrifugal Fan Exhaust Air
15 4300 35 Cabinet type Belt driven Backward curved Lower Ground- 7.93 1.15 67.2 63 1439 1.5 4
centrifugal Fan Exhaust Air
16 750 35 Cabinet type Belt driven Backward curved Lower Ground- 5.37 0.2 64.2 57 2513 0.37 2
centrifugal Fan Exhaust Air
17 450 32 Circular type Inline Fans Lower Ground- Available sp= 40 mmwg 60 2600 0.24 2
Exhaust Air
18 400 32 Circular type Inline Fans Lower Ground- Available sp= 44 mmwg 60 2600 0.24 2
Exhaust Air
19 2650 35 Cabinet type Belt driven Backward curved Lower Ground- 9.65 0.79 63.8 65 2236 1.1 2
centrifugal Fan Exhaust Air
20 700 32 Cabinet type Belt driven Backward curved Lower Ground- 5.01 0.17 64 56 2386 0.37 2
centrifugal Fan Exhaust Air
21 620 32 Circular type Inline Fans Lower Ground- Available sp= 26 mmwg 60 2600 0.24 2
Exhaust Air
21A 620 32 Rectangular type Direct driven Inline Fans Lower Ground- Available sp= 34 mmwg 57 1200 0.245 4
Exhaust Air
22 4900 40 Cabinet type Belt driven Backward curved Lower Ground- 9.04 1.56 65.6 66 1591 2.2 4
centrifugal Fan Exhaust Air
23 300 25 Circular type Inline Fans Upper Ground- Available sp= 27 mmwg 57 2500 0.141 2
Exhaust Air
24 150 25 Circular type Inline Fans Upper Ground- Available sp= 30 mmwg 59 2650 0.121 2
Exhaust Air
25 250 25 Circular type Inline Fans Upper Ground- Available sp= 33 mmwg 57 2500 0.141 2
Exhaust Air
26 900 25 Cabinet type Belt driven Backward curved Upper Ground- 6.44 0.19 60.3 57 2449 0.37 2
centrifugal Fan Exhaust Air
27 9320 35 Cabinet type Belt driven Backward curved Upper Ground- 8.63 2.71 63 66 1079 3.7 4
centrifugal Fan Exhaust Air
28 750 30 Cabinet type Belt driven Backward curved Upper Ground- 5.37 0.17 64.2 56 2385 0.37 2
centrifugal Fan Exhaust Air
29 1100 40 Cabinet type Belt driven Backward curved First Floor- Exhaust 6.26 0.33 66.1 61 2455 0.55 2
centrifugal Fan Air
30 950 40 Cabinet type Belt driven Backward curved First Floor- Exhaust 6.8 0.3 63.3 61 2851 0.55 2
centrifugal Fan Air
31 2000 32 Cabinet type Belt driven Backward curved Second Floor- 7.29 0.47 70.1 59 1898 0.75 4
centrifugal Fan Exhaust Air
32 400 32 Circular type Inline Fans Second Floor- Available sp= 44 mmwg 60 2600 0.24 2
Exhaust Air
33 400 32 Circular type Inline Fans Third Floor- Exhaust Available sp= 44 mmwg 60 2600 0.24 2
Air
34 600 32 Circular type Inline Fans Third Floor- Exhaust Available sp= 27 mmwg 60 2600 0.24 2
Air
34A 600 32 Rectangular type Direct driven Inline Fans Third Floor- Exhaust Available sp= 35 mmwg 57 1200 0.245 4
Air
35 350 32 Circular type Inline Fans Third Floor- Exhaust Available sp= 49 mmwg 60 2600 0.24 2
Air
36 300 32 Circular type Inline Fans Third Floor- Exhaust Available sp= 34 mmwg 59 2600 0.14 2
Air
37 800 40 Cabinet type Belt driven Backward curved Fourth Floor- Exhaust 5.72 0.25 64.2 59 2684 0.37 2
centrifugal Fan Air
38 600 32 Circular type Inline Fans sixth Floor- Exhaust Available sp= 27 mmwg 60 2600 0.24 2
Air
39 700 40 Cabinet type Belt driven Backward curved sixth Floor- Exhaust 5.01 0.22 62.3 57 2596 0.37 2
centrifugal Fan Air
40 200 25 Circular type Inline Fans sixth Floor- Exhaust Available sp= 26 mmwg 59 2650 0.121 2
Air
41 400 32 Circular type Inline Fans Seventh Floor- Available sp= 44 mmwg 60 2600 0.24 2
Exhaust Air
42 300 32 Circular type Inline Fans Seventh Floor- Available sp= 34 mmwg 59 2600 0.14 2
Exhaust Air
43 200 25 Circular type Inline Fans Seventh Floor- Available sp= 26 mmwg 59 2650 0.121 2
Exhaust Air
44 100 25 Circular type Inline Fans Eighth Floor- Exhaust Available sp= 33 mmwg 59 2650 0.121 2
Air
45 450 25 Circular type Inline Fans Eighth Floor- Exhaust Available sp= 40 mmwg 60 2600 0.24 2
Air
46 950 25 Cabinet type Belt driven Backward curved Eighth Floor- Exhaust 6.8 0.21 59.2 58 2517 0.37 2
centrifugal Fan Air
47 100 25 Circular type Inline Fans Nineth Floor- Available sp= 33 mmwg 59 2650 0.121 2
Exhaust Air
48 500 25 Circular type Inline Fans Tenth Floor- Exhaust Available sp= 36 mmwg 60 2600 0.24 2
Air
49 9100 45 Cabinet type Belt driven Backward curved Basement- Fresh Air 10.56 3.66 59.6 72 1434 5.5 4
centrifugal Fan
50 11250 65 Cabinet type Belt driven Backward curved Basement- Fresh Air 10.41 5.58 67 74 1379 7.5 4
centrifugal Fan
51 11700 40 Cabinet type Belt driven Backward curved Basement- Fresh Air 8.63 3.37 71.7 67 971 5.5 6
centrifugal Fan
52 3500 40 Cabinet type Belt driven Backward curved Basement- Fresh Air 8.09 1.06 67.3 62 1688 1.5 4
centrifugal Fan
53 1650 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 7.49 0.5 67.5 61 2326 0.75 2
centrifugal Fan Air
54 1500 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 6.81 0.44 68.3 60 2248 0.75 2
centrifugal Fan Air
55 1200 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 6.83 0.37 65.6 62 2529 0.55 2
centrifugal Fan Air
56 900 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 6.44 0.28 63.9 60 2792 0.55 2
centrifugal Fan Air
57 3900 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 9.01 1.26 64.7 65 1784 1.5 4
centrifugal Fan Air
58 11400 45 Cabinet type Belt driven Backward curved Lower Ground- Fresh 8.41 3.52 73.9 67 990 5.5 6
centrifugal Fan Air
59 2400 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 8.74 0.74 68.5 64 2193 1.1 2
centrifugal Fan Air
60 22400 45 Cabinet type Belt driven Backward curved Lower Ground- Fresh 10.45 7.73 69.4 72 867 11 6
centrifugal Fan Air
61 4410 40 Cabinet type Belt driven Backward curved Lower Ground- Fresh 8.13 1.32 68.2 64 1507 2.2 4
centrifugal Fan Air
62 8388 35 Cabinet type Belt driven Backward curved upper Ground- Fresh 9.73 2.73 58.1 70 1299 5.5 4
centrifugal Fan Air
63 1800 32 Cabinet type Belt driven Backward curved Second Floor- fresh 8.17 0.48 63.7 61 2275 0.75 2
centrifugal Fan Air
64 1000 32 DIDW Backward curved Belt driven Smoke Smoke Evacuation & 5.7 0.24 66 58 2208 0.37 2
spill Centrifugal fan with Cabinet Defumigation
65 23270 32 Vane Axial fans Lift well 17.53 8.02 70.7 81 1450 11 4
pressurization
66 20250 32 Vane Axial fans Lift well 19.23 8.82 59.6 82 1450 11 4
pressurization
67 16500 35 Vane Axial fans Basement- 10.08 4.82 68.4 71 950 5.5 6
Smokespill
70 6480/3240 - Jet fans rated at 300 Deg. C. for 2 Hrs. - 18.2/9.1 1.33/0.1 - 58/43 2850/1 1.50/0.30 2/4
CMH 7 450
70A 4500/2250 - Jet fans rated at 300 Deg. C. for 2 Hrs. - 16.0/8.0 0.74/0.1 - 54/38 2850/1 0.90/0.18 2/4
CMH 0 450
73 450 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 48 1300 0.03 4
& Pantry Area
74 350 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 42 1300 0.022 4
& Pantry Area
75 300 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 42 1300 0.022 4
& Pantry Area
76 250 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 42 1300 0.022 4
& Pantry Area
77 200 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 36 1300 0.016 4
& Pantry Area
78 150 - Wall Mounted Propeller fans Exhaust Air for toilets Free Flow 36 1300 0.016 4
& Pantry Area
79 100 - Slimline axial fan Exhaust Air for toilets Free Flow 47 2200 0.035 2
& Pantry Area
80 16500 35 Vane Axial fans Basement (Normal + 10.08 4.82 68.4 71 950 5.5 6
Fire)
81 42900 35 Vane Axial fans Basement (Normal + 13.32 12.6 74.5 78 950 15 6
Fire)
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP44 I B 2
IP21 I F RO
IP44 I B 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP44 I B 2
IP44 I B 1
IP55 III F 1
IP55 III F 1
IP44 I B 1
IP21 I F RO
IP55 III F 1
IP44 I B 1
IP44 I B 2
IP44 I B 2
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP44 I B 1
IP44 I B 2
IP44 I B 1
IP21 I F RO
IP44 I B 1
IP44 I B 1
IP55 III F 1
IP44 I B 1
IP55 III F 1
IP44 I B 1
IP44 I B 1
IP44 I B 1
IP44 I B 1
IP44 I B 1
IP44 I B 1
IP55 III F 1
IP44 I B 1
IP44 I B 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 1
IP55 III F 12
IP55 III F 10
IP55 III F 2
IP55 III H 2
IP55 III H 2
IP55 III H 2
IP55 III H 9
IP55 III H RO
20
IP44 I B 1
IP44 I B 2
IP44 I B 3
IP44 I B 8
IP44 I B 11
IP44 I B 72
- I - 209
IP55 III H 2
IP55 III H 2
IP55 III H 2