Line current=
√3(Line Voltage)
25 MVA
Line current= = 209.1849A
√3(69kV)
Appatent Power
Line current=
√3(Line Voltage)
25 MVA
Line current= = 1045.9244A
√3(13.8kV)
Step 2:
IEEE Std. C37.20.2-2015 Ratings
Selection of Switchgear Rating and Busbar Rating 5.1 page 8
25 MVA
Busbar load rating=Line current= = 1045.9244A
√3(13.8kV)
The main function of the bus bars is to carry the continuous current and the operating voltage in the
substation.
Description For 13.8 kV
Design of Bus-bar Single Bus Scheme
Type of Bus-bar Copper
Rated continuous current (A, rms) 1000 A
Rated maximum voltage (kV, rms) 15 kV
Power frequency withstand (kV rms) 36 kV
Lightning impulse withstand (BIL) (kV peak) 95 kV
Table 3.2 Ratings of the Bus-bar
Busbar rating
Feeder Load Rating= no. of feeder = 1255.1093A
1255.1093A
Feeder Load Rating= = 313.7773A
4
Conductor Specifications
For feeder lines
The size of conductor (313.7773) (1.25) =392.2217A as indicated that the 80% ampacity of the conductor
shall be the full load current.
Use: ACSR 4/0
Surge arrester providing a low resistance path for the surges the lightning Arrester mainly differs in their
constructional features but same with the operational principle with use of Metal-oxide surge arrester.
Description For 69 kV
Maximum System Voltage L-L (kV, rms) 72.5 kV
Maximum System Voltage L-G (kV, rms) 46.86 kV
Minimum MCOV rating (kV, rms) 42 kV
Duty cycle ratings (kV, rms) 54-72 kV
Table 3.11 Ratings of Surge Arrester
The Table 3.2 shows the ratings of 69 kV surge arrester are indicated in “Guide for the Application of Metal-
Oxide Surge Arrester for Alternating-Current System” IEEE Std. C62.22 -1991.
Description For 69 kV
Rated maximum voltage (kV, rms) 75.5 kV
Rated continuous current (A, rms) 1200 A, 2000A
Rated short-circuit and short-time current (kA, rms) 20 kA
Rated interrupting time (ms) 50 or 83 ms
Maximum permissible tripping time delay (sec.) 2 sec.
Rated closing and latching current (kA, peak) 52 kA
Table 3.4 Ratings of Circuit Breaker
The Table 2.4 shows the ratings of 69 kV circuit breaker are indicated in Table 5 “Standard for AC High-
Voltage Circuit Breaker Rated on a Symmetrical Current Basis-Preferred Ratings and Related Required
Capabilities for Voltages Above 1000 V” IEEE Std. C37.06 -2009.
Surge arrester providing a low resistance path for the surges the lightning Arrester mainly differs in their
constructional features but same with the operational principle with use of Metal-oxide surge arrester.
The Table 3.1 shows the ratings of 13.8 kV surge arrester are indicated in “Guide for the Application of Metal-
Oxide Surge Arrester for Alternating-Current System” IEEE Std. C62.22 -1991.
Circuit breaker is an electrical device that make or break the circuit either manually and automatically under
normal conditions.
The Table 2.3 show the ratings of 13.8 kV circuit breaker are indicated in Table 1 “Standard for AC High-
Voltage Circuit Breaker Rated on a Symmetrical Current Basis-Preferred Ratings and Related Required
Capabilities for Voltages Above 1000 V” IEEE Std. C37.06 -2009.
Surge arrester providing a low resistance path for the surges the lightning Arrester mainly differs in their
constructional features but same with the operational principle with use of Metal-oxide surge arrester.
The Table 3.1 shows the ratings of 13.8 kV surge arrester are indicated in “Guide for the Application of Metal-
Oxide Surge Arrester for Alternating-Current System” IEEE Std. C62.22 -1991.
Circuit breaker is an electrical device that make or break the circuit either manually and automatically under
normal conditions.
Surge arrester providing a low resistance path for the surges the lightning Arrester mainly differs in their
constructional features but same with the operational principle with use of Metal-oxide surge arrester.
The Table 3.1 shows the ratings of 13.8 kV surge arrester are indicated in “Guide for the Application of Metal-
Oxide Surge Arrester for Alternating-Current System” IEEE Std. C62.22 -1991.
Circuit breaker is an electrical device that make or break the circuit either manually and automatically under
normal conditions.
The Table 2.3 show the ratings of 13.8 kV circuit breaker are indicated in Table 1 “Standard for AC High-
Voltage Circuit Breaker Rated on a Symmetrical Current Basis-Preferred Ratings and Related Required
Capabilities for Voltages Above 1000 V” IEEE Std. C37.06 -2009.
The Table 3.1 shows the ratings of 13.8 kV surge arrester are indicated in “Guide for the Application of Metal-
Oxide Surge Arrester for Alternating-Current System” IEEE Std. C62.22 -1991.
Circuit breaker is an electrical device that make or break the circuit either manually and automatically under
normal conditions.
The Table 2.3 show the ratings of 13.8 kV circuit breaker are indicated in Table 1 “Standard for AC High-
Voltage Circuit Breaker Rated on a Symmetrical Current Basis-Preferred Ratings and Related Required
Capabilities for Voltages Above 1000 V” IEEE Std. C37.06 -2009.
Surge arrester providing a low resistance path for the surges the lightning Arrester mainly differs in their
constructional features but same with the operational principle with use of Metal-oxide surge arrester.
The Table 3.1 shows the ratings of 13.8 kV surge arrester are indicated in “Guide for the Application of Metal-
Oxide Surge Arrester for Alternating-Current System” IEEE Std. C62.22 -1991.
Circuit breaker is an electrical device that make or break the circuit either manually and automatically under
normal conditions.
The Table 2.3 show the ratings of 13.8 kV circuit breaker are indicated in Table 1 “Standard for AC High-
Voltage Circuit Breaker Rated on a Symmetrical Current Basis-Preferred Ratings and Related Required
Capabilities for Voltages Above 1000 V” IEEE Std. C37.06 -2009.
Step 4
Voltage Transformer
The voltage transformer is an instrument transformer that used for measurement of voltage and to provide
secondary voltage for protection purposes.
IEEE Std. C57.13-2016 Voltage
Transformers 7 Table 15 page 41
Description For 69 kV
Basic Impulse insulation level (kV peak) 350 kV
Rated voltage 69 kV
Maximum system voltage 15.5 kV
Marked ratio 600:1
Frequency (in Hz) 60 Hz
Table 3.9 Ratings of Voltage Transformer
The Table 2.9 shows the ratings of 69 kV current transformer are indicated in “Standard Requirements for
Instrument Transformers” IEEE Std. C57.13 -2016.
Current Transformer
The current transformer is an instrument transformer that used for measurement of current and to provide
secondary current for protection purposes.
IEEE Std. C57.13-2016 Current
Transformers 6.1 page 30
Description For 69 kV
Basic Impulse insulation level in terms of full-wave 350 kV
test voltage
Nominal system voltage 69 kV
Maximum system voltage 72.5 kV
Rated primary current 300 A
Rated secondary current 5A
Frequency (in Hz) 60 Hz
Table 3.7 Ratings of current transformer
The Table 2.7 shows the ratings of 69 kV current transformer are indicated in “Standard Requirements for
Instrument Transformers” IEEE Std. C57.13 -2016.
Voltage Transformer
The voltage transformer is an instrument transformer that used for measurement of voltage and to provide
secondary voltage for protection purposes.
IEEE Std. C57.13-2016 Voltage
Transformers 7 Table 15 page 41
The Table 2.8 shows the ratings of 13.8 kV current transformer are indicated in “Standard Requirements for
Instrument Transformers” IEEE Std. C57.13 -2016.
Current Transformer
The current transformer is an instrument transformer that used for measurement of current and to provide
secondary current for protection purposes.
IEEE Std. C57.13-2016 Current
Transformers 6.1 page 30
The Table 2.6 shows the ratings of 13.8 kV current transformer are indicated in “Standard Requirements for
Instrument Transformers” IEEE Std. C57.13 -2016.
Current Transformer
The current transformer is an instrument transformer that used for measurement of current and to provide
secondary current for protection purposes.
The Table 2.5 shows the ratings of 13.8 kV current transformer are indicated in “Standard Requirements for
Instrument Transformers” IEEE Std. C57.13 -2016.
Current Transformer
The current transformer is an instrument transformer that used for measurement of current and to provide
secondary current for protection purposes.
The Table 2.5 shows the ratings of 13.8 kV current transformer are indicated in “Standard Requirements for
Instrument Transformers” IEEE Std. C57.13 -2016.
Current Transformer
The current transformer is an instrument transformer that used for measurement of current and to provide
secondary current for protection purposes.
The Table 2.5 shows the ratings of 13.8 kV current transformer are indicated in “Standard Requirements for
Instrument Transformers” IEEE Std. C57.13 -2016.
Current Transformer
The current transformer is an instrument transformer that used for measurement of current and to provide
secondary current for protection purposes.
The Table 2.5 shows the ratings of 13.8 kV current transformer are indicated in “Standard Requirements for
Instrument Transformers” IEEE Std. C57.13 -2016.