Sie sind auf Seite 1von 7

Arc Hazard Assessment for DC Applications in the Transit

Industry

Kenneth S.Y. Cheng Stephen L. Cress Donald J. Minini


Kinectrics Inc. Kinectrics Inc. Excalibur Associates, Inc.
Toronto, Canada Toronto, Canada Connecticut, United States

ITRODUCTIO various industrial and utility work situations related


to AC power systems (e.g. NFPA 70E, IEEE 1584,
During accidental faults on electrical power ArcProTM). There has been, however, a lack of test
systems, workers may be exposed to hazards from data and scientific algorithm development for the
electrical arcs. A prime concern is the exposure of purpose of assessing DC arc hazard analysis. DC arc
workers to the intense radiated component of the arc exposure might occur at locations with sizable battery
energy, which has the potential to cause skin burns. banks and rectifiers such as in power plants or in the
In the United States of America, it has been reported transportation or railway sectors. To-date, there is no
that approximately 80% of electrical injuries are due single set of equations that can be used to evaluate all
to burns from exposure to radiant and convective DC arc hazard situations. Several reviews of possible
energy from electrical arcs [1]. Further studies show methodologies for DC arc hazard computations have
that between 10 and 15 workers are hospitalized been published [8], [9]. In this paper, some of the
everyday due to burns caused by arc flash [2]. Safety most relevant methods are reviewed and of most
programs including arc hazard analysis are dedicated significance, these methods are compared to test data
to protecting workers from burns caused by electric from novel DC arc tests conducted at Kinectrics’
arcs. Arc hazard analysis programs have been High Current Laboratory (e.g. the tests for Bruce
implemented by electric utilities and industries across Power and Coast Mountain Bus Company). In
North America and similar programs have been particular the transit industry should find this
established in some public transportation information relevant to conducting due diligence arc
organizations. These programs are conducted to hazard studies on rail and transit systems involving
select appropriate Personal Protective Equipment DC power at 600V and below.
(PPE) for employees to limit burns to levels that are
considered curable. Safety regulations such as In a transit industry survey conducted for
Occupational Safety and Health Administration Kinectrics Inc., it was apparent that presently, transit
(OSHA) states clearly that it is the employers’ regulators and standard developers such as the
responsibilities to ensure that the employees are Federal Railway Administration (FRA), Federal
adequately protected (OSHA 1910.269 l,6,iii states Transit Administration (FTA) and the American
that the employer shall ensure that each employee Public Transit Association (APTA) have no
who is exposed to the hazards of flames or electric inspection, compliance or standard programs that
arcs does not wear clothing that could increase the deal specifically with arc hazard assessment. For
extent of injury.). In the past few years, several guidance on arc hazard assessment, corporations in
corporations had been heavily penalized for their each State generally default to Federal or State
negligence. One of the more severe penalties OSHA safety regulations (which applies NFPA 70E
charged by OSHA can be found in reference [3]. as the standard for compliance). Ultimately, it is
clear that transit employers are obligated to ensure
Assessment of thermal radiation from arcs is that workers who may be exposed to electric arcs
required for both Alternating Current (AC) and must be clothed to prevent enhanced injury. Rulings
Direct Current (DC) electrical systems. A significant have been awarded against transit companies as
amount of testing and computational method illustrated in reference [4], which describes one of the
development has been conducted related to the highest awards made to an ex-railroad worker.
incident radiated energy that can be produced from
AC faults [5], [6], [7]. This has resulted in a number Survey results indicated that many rail
of useful tools for assessing AC arc hazards in companies in North America are aware of the need
for arc flash safety programs; nevertheless, only a 1500
few have taken the initiative to put these in place and
these are generally at the early stages of program
development. One of the difficulties faced by these 1000
organizations is how to compute arc hazards related
to DC electric systems. 500

Electric Arcs 0

An electric arc is the passage of current through 0 0.1 0.2 0.3 0.4
ionized air. The axial temperature of an arc column -500
can reach 15,000 to 25,000°C. In addition to the
radiated thermal energy, tremendous amounts of -1000
noise (150 dB) and pressure (2000 lb/ft2) can also be
released from electric arcs. Accidental arcs can be Figure 2. AC Arc Voltage Waveform
caused by foreign object bridging of phases,
dielectric breakdown and mechanical failure.
16000
The severity of incident energy levels (which 14000
will be the focus of this paper) released from electric 12000
arcs is dependent on the following parameters: 10000
8000
• System voltage
• Available fault current 6000
• Fault duration 4000
• Arc length or gap distance 2000
• Working distance 0
• Electrode materials -2000 0 0.2 0.4 0.6 0.8
• Enclosure around arc
• AC or DC
• Number of phases involved Figure 3. DC Arc Current Waveform
• Arc motion
400
Figure 1 to Figure 4 show sample waveforms of
350
AC and DC arcs. The waveforms were obtained
from controlled laboratory experiments at Kinectrics. 300
250
15000 200
150
10000
100
5000 50
0 0
0 0.2 0.4 0.6 0.8
-5000 0 0.1 0.2 0.3 0.4

-10000
Figure 4. DC Arc Voltage Waveform
-15000
As seen from the figures, there exist considerable
-20000 differences between the AC and DC arcs. Below are
some of the major differences:
Figure 1. AC Arc Current Waveform
• AC arcs encounter zero-crossing, but DC
arcs do not. Therefore, under the
assumption that all other parameters remain
constant, DC arcs generate more energy than • Fault duration: 0.01 to 2 seconds
AC arcs because DC arcs will not have • Working distance: 6”, 12”, 22” and 34”
ignition and re-ignition. • Arcing environment: Open air and enclosed
• The diameter of DC arc’s plasma column • Electrode configurations: Vertical,
remain constant, AC arcs’ plasma column horizontal and series
expands and contracts.
• DC arcs are more difficult to extinguish. With the results obtained from the various tests,
• DC arcs decay characteristics are dependent Kinectrics has examined the relationship between
on the source (ie battery systems have a incident energy and working distances from DC arcs,
finite capacity to sustain the arc). estimated arcing fault current from bolted fault
current, and derived equations to predict the amount
DC ARC TESTIG AT KIECTRICS of incident energy released from DC arcs. Kinectrics
has also compared the measured incident energy and
Kinectrics Inc. has conducted the pioneering DC ArcProTM predictions.
arc hazard tests and modeling at their unique High
Current Laboratory. Kinectrics has recently The following subsections show the sample test
completed DC arc flash test for both Bruce Power results and some of the DC arc hazard developments
(power generation company in Ontario, Canada) and achieved by Kinectrics.
Coast Mountain Bus Company (public transit
company in Vancouver, Canada). Figure 5 shows a 130 V and 260 V DC Test Results
sample open-air arc flash test conducted at
Kinectrics’ High Current Laboratory. Figure 6 shows the measured heat flux from DC
arcs of various lengths and at various available arcing
currents for tests using a 260 V DC source.
Controlled DC arcs were generated between 2
vertical electrodes. At 260 VDC, 1 and 2 inch arc
could easily be sustained at higher arcing faults. The
probability of sustaining arcs is highly dependent on
the electrode configuration, the source voltage and on
the current.

Figure 5. Sample Arc Flash Test

For the DC testing, a special low-impedance


transformer was used to obtain the desired voltage
and current range. The output of the transformer was
connected to one or two high-power three-phase
rectifiers to produce a DC power source. The current
magnitude was controlled by adding resistance or
inductance in the circuit on the output of the rectifier.
Figure 6. 260V DC Heat Flux @ 12” with 1” and 2” Arc Gap
Precise control of arc times was controlled by a test
sequencer and a synchronous make-switch and circuit Extrapolating the heat flux data measured for
breaker. 260V arcs, graphs of incident energy at 12 inches as a
function of time were produced for different fault
DC arc flash testing at Kinectrics has covered the currents levels. The threshold of the hazard/risk
following range of variables: categories set by NFPA 70E were also plotted on
these graphs for 260V DC arcs. Figure 7 shows
• System voltage: 125 V, 250 V and 600V incident energy as a function of time for 260 V DC
DC arcs with 2” gaps. Such curves can serve as a guide
• Bolted fault current: 1 kA to 25 kA for the incident energy from DC arcs for a range of
• Arc gap distance: 0.2” to 6” possible fault conditions.
measured values were averages. Also, the computed
values are intended to be more conservative and more
representative of the maximum hazards.

600 V DC Test Results

600 V DC arc flash tests were performed in both


open-air (electrodes pointing towards one another)
and enclosed (electrodes pointing downwards and
electrodes pointing outwards). It was observed that
with arcs in a box, the two electrode configurations
make very little differences with respect to the
amount of incident energy captured by the
Figure 7. +FPA 70E Categories – 12” Working Distance; 2” calorimeter. Regardless of which direction the
Arc Gap Distance; 260 V DC electrodes point, once the arc is generated, radiated
incident energy will be deflected off the sidewalls of
DC vs. AC Incident Energy the box and captured by the calorimeter at the front
opening. This also explains that radiated incident
Comparisons can be made between the results energy from an enclosed environment is always
from the AC and DC tests with respect to the incident higher than that from an open environment if all other
energy vs. fault current with a fixed arc gap. parameters remain unchanged.
Comparisons were made using data from tests with
1” and 2” gaps and heat flux measured at 24” away The objective of the test was to derive equations
from the arc. Similar fault currents were used for to calculate arcing fault current at 600 V DC and
both AC and DC arcs. ultimately, to predict the amount of incident energy
released from DC arcs at a specified working
The curves in Figure 8 illustrate the results of the distance away from the potential arc. The
measurements at 260 V DC compared to AC with 1” empirically derived equations are as follows:
and 2” arc gap distances. Note that DC arc energy is
consistently higher than AC arc energy for the same ‫ܫ‬௔௥௖ = 0.9063 ∗ ‫ܫ‬௕௙ ଴.଼ଽଶ଻ − 0.1051݁ ଴.ଵ଴ଽଷூ್೑ (‫ ܩ‬− 1)
current (DC vs. AC rms). The average value per unit
‫ܧ‬௜ = (0.9694 ∗ ‫ܫ‬௔௥௖ − 0.0589)
difference in the range from 2,000 A to 10,000 A was
∗ (0.4793 ∗ ln(‫ )ܩ‬+ 1.0027)
estimated to be approximately 1.25.
‫ݐ‬ 6ଶ
∗ ൬ ൰ ∗ ቆ ଶቇ
0.1 ‫ܦ‬
where:

‫ܫ‬௔௥௖ is the arcing fault current in kA


‫ܫ‬௕௙ is the bolted fault current in kA
G is the arc gap distance in inches
t is the fault duration in seconds
D is the working distance in inches

The equations were derived under the following


laboratory testing conditions:

Figure 8. AC vs. DC Heat Flux Comparison at 24” Working • 600 V DC


Distance • Bolted fault current of 2 kA to 25 kA
• Arc gap distance of up to 6” (depending
Figure 8 includes the ArcProTM computation on the configuration of the electrodes
results along with the measured data. It shows that and the available fault current, arcs may
DC average currents produce higher incident energies not be sustainable at an arc gap distance
than numerically equivalent AC rms currents. of 6”)
ArcProTM computations are generally higher than the
AC measured values, mostly due to the fact that the
As with all curve fit approximations, the above For instance, if the working distance is doubled, the
equations should be considered valid within the range incident energy would decrease by a factor of four.
of parameters in the data used to derive the equations. This relationship is true only under the circumstances
that the energy readings captured by the calorimeters
Figure 9 shows the relationship between bolted are 100% radiated thermal energy released by the arc,
fault currents and arcing fault currents with arc gap e.g. This is likely true for the more distant
distances of 1”, 3” and 6”. As obvious from the measurements but calorimeters as close as 6” are
curves, there is an inverse correlation between the likely to be influenced by contact with hot arc
arcing fault currents and the arc gap distances. plasma. In testing this generally leads to a wide
range of incident energy values for calorimeters that
Bolted Fault Current vs. Arcing Fault Current at 600 V DC are very close to the arc.
1" Arc Gap 3" Arc Gap 6" Arc Gap
18

16
The following figure shows similar information
14 as Figure 7, it displays the resulting incident energy
with the arcing fault currents and durations. The
Arcing Fault Current (kA)

12

10 curves can be extrapolated to predict incident energy


8 levels of longer duration. The incident energies were
6 measured at 12” away from the arc with an 1” arc
4 gap.
2

0
Incident Energy at 12" vs. Arc Duration for 1" Gap
0 5 10 15 20 25 30
Arcing Current at 600 VDC
Bolted Fault Current (kA)
2 kA 8.60 kA 13.4 kA Cat 0 Cat 1 Cat 2 Cat 3
30
Figure 9. Arcing Fault Current vs. Bolted Fault Current under
Various Arc Gap distances at 600 V DC 25
Incident Energy (cal/cm2)

20
It can be noted from Figure 9 that at 2 kA or
below, the arcing fault current is approximately equal 15

to the bolted fault current. For the specific lab setup 10


and tests conducted, the arcing fault currents always
remain between 64% and 97% of the bolted fault 5

currents. 0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7

To identify how incident energy from DC arcs Arc Duration (s)

varies with working distances, fault durations were


normalized as seen in Figure 10 below. As a result, Figure 11. Arcing Fault Current and Duration vs. Incident
Energy
incident energy can be plotted as heat flux.

DC Heat Flux Comparison for 1" Arc for Various Distance


0.1 second arc 0.5 second arc COMPARISO OF DC ARC MODELS
100

90
At the time of writing, there is no standardized
80
and verified model to determine incident energy
70
Heat Flux (cal/cm2/s)

released from DC arcs. Another DC arc flash hazard


60

50
equation is proposed in a paper by Doan [8]. This set
40
of equations, as shown below, is applicable for DC
30 systems rated up to 1000 V.

ܸ௦௬௦ ଶ ܶ௔௥௖
20

‫ܧܫ‬୫ୟ୶ ௣௢௪௘௥ = 0.005 ∗ ∗


10

ܴ௦௬௦ ܴଶ
0
0 5 10 15 20 25 30
Distance from Arc (inches)

where:
Figure 10. Heat Flux vs. Working Distances
ܸ௦௬௦ is the system voltage in volts
ܴ௦௬௦ is the system resistance, in ohms
As expected, heat flux or incident energy varies
ܶ௔௥௖ is the arcing time in seconds
inversely with the square of the working distances.
R is the working distance from the arc, in • Bolted fault current of 2 kA to 25 kA
centimeters Arc gap distance of up to 0.5” for 130 V
‫ܧܫ‬୫ୟ୶ ௣௢௪௘௥ is the estimated DC arc flash

DC systems and up to 2” for 260 V DC
incident energy at the maximum power point, in systems
cal/cm2
2. The set of 600 V DC equations Kinectrics
For exposures where the arc is in a box or derived should be used under the following
enclosure, the proposal suggests using a 3-times conditions:
multiplying factor for the resulting incident energy
value. • 600 V DC
• Bolted fault current of 2 kA to 25 kA
Based on laboratory test results, this calculation • Arc gap distance of up to 6” (depending
is shown to be conservative and estimates higher than on the configuration of the electrodes
measured incident energy levels. A comparison of and the available fault current, arcs may
Doan’s equation1, ArcProTM with a modification not be sustainable at an arc gap distance
factor derived from the DC arc flash tests at 120 V of 6”)
and 260 V DC, and the test results at 600 V DC is
shown in the following figure. 3. In situations where the case being assessed
does not fall in 1. or 2. the maximum arc
Heat Flux at 12 inches vs. Arcing Fault Current energy equation proposed by Doan could be
600 VDC
1" Arc Gap 6" Arc Gap Doan Arcpro 1" Arcpro 6"
used as a conservative approach. Further
90 testing and studies are required in order to
80 derive more practical models and formulae.
70
Heat Flux (cal/cm2/s)

60 COCLUSIOS
50

40 Arc hazard analysis is a safety assessment, dedicated


30 to protecting workers who might be exposed to
20
radiated thermal energy from electric arcs. In this
10
paper, the focus is on incident energy released from
0
0 2 4 6 8 10 12 14 16 18
DC arcs, which should be of particular interest to the
Arcing Fault Current (kA) transit industry.

Figure 12. Comparison of Existing DC Arc Flash Evaluation OSHA states clearly that it is the employers’
Methods responsibilities to ensure that the employees are
adequately protected with PPE.
As seen from Figure 12, under the specific
scenario, ArcProTM with factor matches well with the Based on the research and testing conducted at
results from the 600 V DC test. It is also important to Kinectrics, the following can be concluded:
note that Doan’s equation is designed for worst case
energy and produced the same results independent of 1. At present, there is no standardized and
the value of the arc gap. verified model to determine incident energy
released from DC arcs.
RECOMMEDATIOS 2. An initial set of DC arc measurements from
Kinectrics laboratories can be used as a
An interim approach for performing arc flash verification tool for proposed DC arc hazard
evaluation at DC equipment could include: analysis tools.
3. The DC arc flash formulas proposed by
1. ArcProTM with factors has been verified for Doan is conservative compared to
the following conditions: measurements. Use of ArcpoTM and the 600
V DC arc hazard equation developed by
• 130 V DC to 260 V DC Kinectrics, is suitable within the range of
parameters for which these models have
1
been verified.
It is assumed that Ibf = 2 Iarc, where Iarc is measured
from the laboratory experiment at Kinectrics
4. There is a need for additional development [6] Doughty, R., Neal, T. and Floyd, L..
of DC arc models. Extrapolation may “Predicting Incident Energy to Better Manage the
produce misleading results. Electric Arc Hazard on 600 V Power distribution
5. It is critical to understand the applications Systems”, United States.
and limitations of the existing models and
equations. [7] ArcProTM Software, Kinectrics Inc..
6. The transit industry with DC systems for 3rd
rail and cantenary applications should find [8] Doan, D.. “Arc Flash Calculations for
the test results and preliminary computation Exposures to DC Systems”, Delaware, United States.
methods mentioned in this paper useful for
initial DC arc hazard assessments. [9] Ammerman, R. et al.. “DC Arc Models and
Incident Energy Calculations”, Colorado, United
ACKOWLEDGEMETS States.

The authors would like to thank the following


individuals and corporate for their contributions
on this paper:

• Carl Keyes, Associate, Kinectrics Inc.


• Claude Maurice, High Current
Laboratory Manager, Kinectrics Inc.
• Coast Mountain Bus Company
• Bruce Power Inc.

REFERECES

[1] IEEE Standards Association: Industry


Backs IEEE/FPA Arc Flash Testing Program with
Initial Donations of $1.25 Million. Retrieved May 8,
2008, from Institute of Electrical and Electronics
Engineers website:
http://standards.ieee.org/esrc/arclfash/pr_arcflash.htm
l

[2] Neitzel, D. (2006). “The Hazards of


Electricity – Do You Know What They Are?”, Texas,
United States.

[3] Harrell, J.. "Pieper Electric to challenge


OSHA citations". Daily Reporter (Milwaukee).
FindArticles.com. March 25, 2011.
http://findarticles.com/p/articles/mi_qn5302/is_20040
402/ai_n24422402/

[4] Stannard, E.. "Injured Ex-Metro-North


Worker Awarded $1.1M". New Haven Register.
April 13, 2010.
http://www.nhregister.com/articles/2010/04/13/news/
aa3ctrailaward041310.txt?viewmode=fullstory

[5] Lee, R. (1982). “The Other Electrical


Hazard: Electric Arc Blast Burns”, United States.

Das könnte Ihnen auch gefallen