Sie sind auf Seite 1von 5

CUSTOMER BERG ENGINEERING

ITEM 2500 LITRES DIESEL TANK


SHEET NO. 1 of 3
REV.NO. B
DATE 26/8/2016
CUSTOME BERG ENGINEERING
ITEM 2500 LITRES DIESEL TANK
SHEET NO 2 of 3
REV.NO. B
DATE 26/8/2016

EXTERNAL FIRING CASE

Pressure Drop Calculations in a pipe

Re Reynold No= DVῤ /µ 1642786.66 > 2100.00 hence flow is Turbulant


V Average Fluid Velocity= Q/A 21.2361 m/s
Q Fluid Flow 1424.00 m3/hr
A Pipe area 0.0186 m2
D Pipe diameter 0.15400 m 150 NBx SCH STD (7.11 mm) Pipe Considered
ῤ Density of Fluids 4.32 kg/m^3
µ Viscocity of fluid 0.00860 mm^2/s
µ Viscocity of fluid 0.00001 N-s/m2
∆Pf = Frictional Pressure Drop ῤghL 1339.94 Pascal 0.01 13.40 mbar g = 0.0134 Bar g

ῤ Density of fluid 4.32 kg/m^3


g Acceleration due to gravity 9.81 m/s2
hL Frictional head loss
31.6179 m
hL= f x(L /D )( V2/2g )
ε roughness 0.00015 ft For Wrought Iron
0.00005 m
ε /D Relative roughness 0.00030
Friction Factor
f 0.0000 0.01
64/Re OR 0.316 /(Re)^1/4
L Length of Pipe 24.00 m
Refer attached catalogue
Refer attached catalogue

150NB -FA Pressure drop in a flame arrestor 32.00 mbar g 0.0320 Barg Pin=At the inlet of FM 1.1424 114.24 kPa

1.05 bar a Pout=at the out let of FM 1.0450 104.50 kPa

Total pressure drop through system 45.40 mbar g

0.0454 bar g 1.06 bar a


P Design pressure/MAWP of tank 0.12940 bar g

1.1424 bar a Since Design pressure/MAWP is higher than pressure drop, it is safe. FM= Flame Arrester
CUSTOMER BERG ENGINEERING
ITEM 2500 LITRES DIESEL TANK
SHEET NO. 3 of 3
REV.NO. B
DATE 8/10/2016

Minimum Area Required Venting :-

In Breathing

qth= 782.17 Nm3/hr


Pi= 114.24 kPa
Po= 104.50 kPa
k= 1.02 -
T1= 560 0
K
Z1= 0.96

(i) Considering M = 70 kg/kmol


Amin= 38.814096 cm2

(ii) Considering M = 134 kg/kmol


Amin= 53.702296 cm2

Provided 150 NBx sch STD ( 7.11 mm), vent size having ID, 154.08 mm
The Area of vent is 0.7854 X D^2 186.45904
Safe as Ar < Ap

Das könnte Ihnen auch gefallen