Project Name

Ajdan Waterfront

Calculation for: Divn/Dept : GDC Job Nr/File No. 357182-MMD-ZZ-XX-CA-H-3300

Validation of Carpark & VRV Condenser Unit Ventilation Calculated by : Debasis Malick Date : 02.08.2016

Checked by : Shiv Kumar Date : 02.08.2016

Ventilation Summary for Carpark & VRV System

Air volume
Air volume
Air-change rate requirement under Supply air quantity
Area Height Volume Air-change rate under requirement under
Parking Zone under fire standard for fan selection
(m2) (m) (m3) standard conditions fire conditions
conditions conditions (m3/s)
3
(m /s)
(m3/s)

Basement 9961 3.8 37851.8 6 10 63.09 105.14 89.37

Makeup air required for VRV condenser


148.50
Unit heat rejection for zone X
Exhaust Air Quantity VRV condenser unit
heat rejection

Total 9961 37851.8 63.09 105.14 237.87

Assumptions/Notes:

1. Carpark zone areas were measured directly from CFD fire simulation analysis on 28/07/2016 237.87
2. The above values only indicate the louver requirements for carpark & VRV condenser ventilation only. Malick, Debasis: 39.6453842593
3. Fan and shaft sizes will be based on air volume under fire conditions As per manufacturer
4. Intake louver area will be based on 2.5.m/s face velocity under standard conditions recommendations 85% 2 fan room
of the exhaust air
5. Exhaust Louver area requirement based on a 2.5m/s face velocity under standard conditions
quantity
6. Air volumes are approximate and to be further validated 4 fan room
7. Basement clear height is 3.8m (SSL to SSl is 4m and promenade level slab thickness is approximately 300mm)
8. Supply air quantity for basement carpark is @ 85% of carpark exhaust air quantity.

Space requirements for basemsnt smoke extraction/ventilation


1. Extraction Car park at 2 locations - Total 2nos. of fan rooms required (2nos. Fan per room@ 26.29m3/s each)
2. Extraction VRV Condenser heat rejactionn at 1 locations - Exhaust fan inside VRV plant room mounted in shaft (3nos.@ 36.37m3/s each)
3. Make up air for car park + VRV condenser unit at 2 locations - Total 2no of fan rooms required (2nos. Fan one room & 2nos. Fan second room @ 22.34 m3/s each)
4. Make up air for VRV condenser unit at 1 locations - Total 2no of fans @ 46.75m3/s each
5. Extraction air slab opening for car park at each location- 2.29m x2.29m assuming a discharge velocity of 10m/s
6. Make-up air slab opening for car park + VRV condenser unit at each location - 3.06m x 3.06m with louver gross area 10.45 sqm assuming a supply velocity of 10m/s
7. Extraction air slab opening for VRV condenser heat rejection unit at one location- 3.32m x3.32m assuming a discharge velocity of 10m/s

Volume per fan intake/exhaust dimensions


(Exhaust) car park shaft area (length and width)

26.29 5.26 2.29

Volume per fan (Supply) intake/exhaust dimensions


car park shaft area (length and width)

22.34 4.47 2.11

Volume per fan


(Exhaust) VRV intake/exhaust dimensions
condenser heat shaft area (length and width)
rejection

49.50 14.85 3.85

Volume per fan (Supply)


intake/exhaust dimensions
VRV condenser heat
shaft area (length and width)
rejection
74.25 14.85 3.85
File No. 357182-MMD-ZZ-XX-CA-H-3300
Sheet No: 1 of 1
2.08.2016

2.08.2016

ry for Carpark & VRV System

Car park+VRV intake


air Sandtrap Louver Exhaust Louver for
Exhaust air Exhaust Louver
free area area requirement
quantity for fan for VRV
requirement based based on standard
selection condenser unit
on standard operation mode
(m3/s) (m2)
operation mode (m2)
(m2)

105.14 80.80 25.2

148.5 47.5

253.64 80.8 25.2 47.5

251.2781513889
Malick, Debasis: 41.8796918981
As per manufacturer Option 1 Option 2
recommendations 85% 61 66
of the exhaust air
quantity
122 132

183 198

6.37m3/s each)
s. Fan second room @ 22.34 m3/s each)
sqm assuming a supply velocity of 10m/s