Sie sind auf Seite 1von 78

Page 01 of 78

Vendor’s Name : LS-Vina Cable & System.


Company’s Name : Nghi Son Refinery and Petrochemical LLC.
Purchaser : JGCS Consortium
Responsible OC : Chiyoda Corporation
Plant Location : Nghi Son, Vietnam
Project name : NSRP Complex Project
P/ Order No. : PC2182-001-C1
Equipment/Material name : Power and Control Cable
Item Number : Common
Document Title : Cable Specification, data sheet and Cable cross
sectional drawing

NSRP Complex Project (JOB No.: 0-6495-20)

DOCUMENT CLASS: X

ISSUE PURPOSE: AB

RESULT CODE: A, B, R, F ( )
"A"
NEXT STATUS: FA, FR, FI, FC, AB ( )
---
RESUBMISSION DATE: ( )
---
RESPONSIBLE DEPT./ PERSON: ( Nishikubo / K. )Fukuzawa
CGH Electrical - T.
Review Date: (15/Dec/2015 )

A: Approved without Comment; B: Approved with Minor Comment


R: Not Approved; F: Not Subject to Review

Approval or review hereunder shall not be construed to relieve Supplier / Subcontractor of his responsibilities and
liability under the Contract.

Purchaser DOC. No. ORIG. PURCHASE ORDER NO. SERIAL REV.

V C2182-001-C 001 2

Rev Date Page Description Prep’d Chk’d App’d

2 02/12/2015 All As built N.T.Binh P.V.Duong C.T.Tung

D R A
N
I 21-DE UILT15
C - 2 0
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 02 of 78
VC2182-001-C-001

INDEX

1. Minimum bending radius cables…………………………………………………………………………………………Page 03 of 78


2. Cross section drawing for 8261R1…………………………………………………………………………………………Page 04 of 78
3. Cable spec and data sheet for 8261R1…………………………………………………………….......………………Page 05, 06 of 78
4. Cross section drawing for 8261R3…………………………………………………………………………………………Page 07 of 78
5. Cable spec and data sheet for 8261R3………………………………………………………………………..…….......…Page 08 of 78
6. Cross section drawing for 8263R1…………………………………………………………………………………………Page 09 of 78
7. Cable spec and data sheet for 8263R1……………………………………………………………………………...…Pagpe 10, 11 of 78
8. Cross section drawing for 8264R1…………………………………………………………………………………………Page 12 of 78
9. Cable spec and data sheet for 8264R1……………………………………………………………………………….……Page 13 of 78
10. Cross section drawing for 8267R1…………………………………………………………………………………………Page 14 of 78
11. Cable spec and data sheet for 8267R1………………………………………………………………………..…...………Page 15 of 78
12. Cross section drawing for 8261D1…………………………………………………………………………………...……Page 16 of 78
13. Cable spec and data sheet for 8261D1……………………………………………………………………………...…Page 17, 18 of 78
14. Cross section drawing for 8261D2…………………………………………………………………………………...……Page 19 of 78
15. Cable spec and data sheet for 8261D2……………………………………………………………………..……...Page 20, 21, 22 of 78
16. Cross section drawing for 8261D3………………………………………………………………………………….......…Page 23 of 78
17. Cable spec and data sheet for 8261D3……………………………………………………………………..…...…Page 24, 25, 26 of 78
18. Cross section drawing for 8261D4……………………………………………………………………………...…………Page 27 of 78
19. Cable spec and data sheet for 8261D4……………………………………………………………………..……...Page 28, 29, 30 of 78
20. Cross section drawing for 8261D5……………………………………………………………………………...…………Page 31 of 78
21. Cable spec and data sheet for 8261D5………………………………………………………………………..…...………Page 32 of 78
22. Cross section drawing for 8261T2…………………………………………………………………………………………Page 33 of 78
23. Cable spec and data sheet for 8261T2………………………………………………………………………..…...………Page 34 of 78
24. Cross section drawing for 8261T3…………………………………………………………………………………………Page 35 of 78
25. Cable spec and data sheet for 8261T3…………………………………………………………………….....……Page 36, 37, 38 of 78
26. Cross section drawing for 8261T4…………………………………………………………………………………………Page 39 of 78
27. Cable spec and data sheet for 8261T4…………………………………………………………………..….......…Page 40, 41, 42 of 78
28. Cross section drawing for 8263D1………………………………………………………………………………...………Page 43 of 78
29. Cable spec and data sheet for 8263D1……………………………………………….………………..………Page 44, 45, 46, 47 of 78
30. Cross section drawing for 8263D3………………………………………………………………………………...………Page 48 of 78
31. Cable spec and data sheet for 8263D3………………………………………………..……………..………...Page 49, 50, 51, 52 of 78
32. Cross section drawing for 8264D1……………………………………………………………………………...…………Page 53 of 78
33. Cable spec and data sheet for 8264D1………………………………………………..……………..……...…Page 54, 55, 56, 57 of 78
34. Cross section drawing for 8264D3…………………………………………………………………………...........………Page 58 of 78
35. Cable spec and data sheet for 8264D3………………………………………………..……………..……...…Page 59, 60, 61, 62 of 78
36. Cross section drawing for 8267D1………………………………………………………………………….......…………Page 63 of 78
37. Cable spec and data sheet for 8267D1………………………………………………..……………..…...……Page 64, 65, 66, 67 of 78
38. Cross section drawing for 8267D3…………………………………………………………………………….......………Page 68 of 78
39. Cable spec and data sheet for 8267D3………………………………………………..…………………….....………Page 69, 70 of 78
40. Cross section drawing for 826XD..……………………………………………………………………………..............…Page 71 of 78
41. Cable spec and data sheet for 826XD………………………………………………..…………………..…..…..……Page 72, 73 of 78
42. Cross section drawing for 826XD510P, 511P.......……………………………………………………………...…………Page 74 of 78
43. Cable spec and data sheet for 826XD510P, 511P …………………………..………….………………….........…..……Page 75 of 78
44. Cross section drawing for 826XT..…………………………………………………………………………......…….……Page 76 of 78
45. Cable spec and data sheet for 826XT………………………………………………..……………………....…...……Page 77, 78 of 78

D R A
N
I 21-DE UILT15
C - 2 0
AS B
MINIMUM BENDING RADIUS CABLES
Customer: JGC & Consortium
Project: Nghi Son Refinery Plant
Page 03 of 78

NO. CABLE TYPE MINIMUM BENDING RADIUS CABLES

I MEDIUM VOLTAGE CABLES

1 Single core with armour or without armour


Twelve times the overall diameter of the completed cable.
2 Three-core with armour or without armour

II LOW VOLTAGE CABLES

1 Sing core or multi-core with armour Twelve times the overall diameter of the completed cable.

2 Sing core or multi-core without armour Overall diameter of the completed cable.
Thickness of insulation
Example: 25.4 mm and less 25.4 to 50.8 mm 50.8 mm and over
If thickness of insulation less than 3.9mm and overall
diameter of the completed cable less than 25.4mm, 3.9 mm and less 4 5 6
minimum bending radius shall be four times the overall
diameter of the completed cable. 4.0mm to 7.9mm 5 6 7

8.0 mm and over - 7 8

D R A
N
I 21-DECUILT15
- 2 0
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 04 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING

DRAWING NO. : VV2182-001-C-001-01

0.6/1(1.2)kV SINGLE-CORE UNARMOURED XLPE


Conductor Size: 120mm2 to 800mm2
INSULATED Fr-PVC SHEATH CABLES

TAG/PJ SYMBOL: 8261R113-X, 8261R114-X, 8261R115-X, 8261R116-X, 8261R117-X, 8261R118-X, 8261R119-X, 8261R120-X,
8261R121-X

Item Description Material Appling method Remark

1 Conductor Annealed copper wires Circular compacted Class 2 - IEC 60228

2 Insulation XLPE compound Extruding Color: Black

3 Oversheath Fr-PVC compound Extruding Color: Black

- The length in meters shall be printed on oversheath cable.


- Marking method on oversheath: - Printing on oversheath surface with following content
LS-VINA Cable & System * Flame retardant Cu/XLPE/Fr-PVC 500sqmm – 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 05 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV SINGLE-CORE UNARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(CU/XLPE/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
1x120 1x150 1x185 1x240 1x300
1 TAG/PJ SYMBOL 8261R113-X 8261R114-X 8261R115-X 8261R116-X 8261R117-X
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
Cross sectional area mm2 120 150 185 240 300
Number of core No. 1 1 1 1 1
Structure of core Circular compacted
Max. DC resistance at 20oC (R) W/km 0.153 0.124 0.0991 0.0754 0.0601
5 Insulation
Material XLPE
Nominal thickness mm 1.2 1.4 1.6 1.7 1.8
o
Working temperature C 90
o
Short circuit temperature C 250
6 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.00 1.08 1.08 1.16 1.24
7 Reactance of cable (X) flat spaced W/km 0.1418 0.1417 0.1401 0.1388 0.1377
8 Capacitance of the cable (C) mF/km 0.7511 0.7246 0.7126 0.7656 0.8131
9 Current carrying capacity (*) A
In air (Flat Spaced) 475 548 628 742 857
Buried direct in ground (Flat
297 327 363 410 450
Spaced)
10 50Hz testing voltage for 5 minutes kV 3.5
11 Approx. Overall Diameter mm 18 (±2) 20 (±2) 22 (±2) 25 (±2) 28 (±2)
12 Approx. Cable Weight kg/km 1,210 1,490 1,850 2,410 3,000
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 06 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV SINGLE-CORE UNARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(CU/XLPE/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
1x400 1x500 1x630 1x800
1 TAG/PJ SYMBOL 8261R118-X 8261R119-X 8261R120-X 8261R121-X
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)

4 Conductor
Material Annealed copper wires

Cross sectional area mm2 400 500 630 800


Number of core No. 1 1 1 1
Structure of core Circular compacted

Max. DC resistance at 20oC W/km 0.047 0.0366 0.0283 0.0221


5 Insulation
Material XLPE

Nominal thickness mm 2.0 2.2 2.4 2.6


o
Working temperature C 90
o
Short circuit temperature C 250

6 Reactance of cable (X) flat Spaced W/km 0.1364 0.1359 0.1351 0.1342

7 Capacitance of the cable (C) mF/km 0.8347 0.8285 0.8742 0.9159

8 Current carrying capacity (*) A

In air (Flat Spaced) 1031 1190 1381 1481


Buried direct in ground (Flat
480 518 555 572
Spaced)
9 Over sheath

Material Fr-PVC

Color Black

Min. thickness at any point mm 1.32 1.40 1.56 1.64

10 50Hz testing voltage for 5 minutes kV 3.5

11 Approx. Overall Diameter mm 31 (±2.5) 35 (±2.5) 40 (±2.5) 44 (±2.5)

12 Approx. Cable Weight kg/km 3,830 4,890 6,300 8,010


Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 07 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING

DRAWING NO. : VV2182-001-C-001-02

0.6/1(1.2)kV THREE-CORE UNARMOURED XLPE


Conductor Size: 120mm2 to 300mm2
INSULATED Fr-PVC SHEATH CABLES

1 4

3 5

TAG/PJ SYMBOL: 8261R313-X, 8261R314-X, 8261R315-X, 8261R316-X, 8261R317-X

Item Description Material Appling method Remark

1 Conductor Annealed copper wire Circular compacted Class 2 - IEC 60228

2 Insulation XLPE compound Extruding Color: Brown, Black, Grey

3 Filler P. P yarn Stranding Non hygroscopic

4 Binder Foam tape Taping Overlap taping

5 Oversheath Fr-PVC compound Extruding Color: Black

- Core shall be identified by colored XLPE insulation. Color shall be Brown, Black, Grey.
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content
Example: For 3x150mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/Fr-PVC 3x150sqmm – 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev.0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 08 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV THREE-CORE UNARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(CU/XLPE/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
3Cx120 3Cx150 3Cx185 3Cx240 3Cx300
1 TAG/PJ SYMBOL 8261R313-X 8261R314-X 8261R315-X 8261R316-X 8261R317-X
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
Cross sectional area mm2 120 150 185 240 300
Number of core No. 3 3 3 3 3
Structure of core Circular compacted

Max. DC resistance at 20oC (R) W/km 0.153 0.124 0.0991 0.0754 0.0601
5 Insulation
Material XLPE XLPE XLPE XLPE XLPE

Nominal thickness mm 1.2 1.4 1.6 1.7 1.8


o
Working temperature C 90
o
Short circuit temperature C 250

6 Over sheath

Material Fr-PVC

Color Black Black Black Black Black

Min. thickness at any point mm 1.48 1.64 1.72 1.88 1.96

7 Reactance of cable (X) W/km 0.0737 0.0741 0.0735 0.0726 0.0719

8 Capacitance of the cable (C) mF/km 0.7511 0.7246 0.7126 0.7656 0.8131

9 Current carrying capacity (*) A

In air 329 379 433 511 590

Buried direct in ground 306 342 386 446 499

10 50Hz testing voltage for 5 minutes kV 3.5

11 Approx. Overall Diameter mm 38 (±2.5) 42 (±2.5) 46 (±2.5) 52 (±3) 58 (±3)

12 Approx. Cable Weight kg/km 3,860 4,720 5,910 7,700 9,580


Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 09 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-03

3.6/6(7.2)kV SINGLE-CORE UNARMOURED XLPE


Conductor Size: 120mm2 to 630mm2
INSULATED Fr-PVC SHEATH CABLES

1 5

2 6

3 7

4 8

TAG/PJ SYMBOL: 8263R113-X, 8263R114-X, 8263R115-X, 8263R116-X, 8263R117-X, 8263R118-X, 8263R119-X, 8263R120-X

Item Description Material Apply method Remark


1 Conductor Annealed copper wires Circular compacted Class2 - IEC 60228
2 Binder Semi-conducting tape Taping Manufacturer's decision (*)
3 Conductor screen Semi-conducting compound Extruding
4 Insulation XLPE compound Extruding Simultaneously extruded
5 Insulation screen Semi-conducting compound Extruding
6 Metallic screen Copper tape Taping Overlap taping
7 Binder Binder tape Taping Overlap taping
8 Oversheath Fr-PVC compound Extruding Color: Red

Note (*): Semi-conducting tape shall be applied over the conductor for size 500sqmm and over
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :

LS-VINA Cable & System * Flame retardant Cu/XLPE/Fr-PVC 630sqmm – 3.6/6(7.2)kV* (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 10 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


3.6/6(7.2)kV SINGLE-CORE UNARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( CU/XLPE/MS/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx120 1Cx150 1Cx185 1Cx240
1 TAG/PJ SYMBOL 8263R113-X 8263R114-X 8263R115-X 8263R116-X
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 3.6/6(7.2)
4 Conductor
- Material Annealed copper wires
2
- Cross sectional area mm 120 150 185 240
- Number of core No. 1 1 1 1
- Structure of core Circular compacted
0
- DC Max. resistance at 20 C W/km 0.153 0.124 0.0991 0.0754
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3
6 Insulation
- Material XLPE XLPE XLPE XLPE
- Nominal thickness mm 2.5 2.5 2.5 2.6
- Min. thickness mm 2.15 2.15 2.15 2.24
o
- Working temperature C 90
o
- Emergency temperature C 130
o
- Short circuit temperature C 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05
9 Over sheath
- Material Fr-PVC
- Min. thickness mm 1.35 1.43 1.43 1.52
- Color Red
10 Reactance of cable (X) flat spaced W/km 0.1572 0.1548 0.1512 0.1491
11 Capacitance of the cable (C) mF/km 0.4492 0.4884 0.5331 0.5822
12 Current carrying capacity (*) A
In air (Flat Spaced) 475 531 605 707
Buried direct in ground (Flat
309 340 381 437
Spaced)
13 50 Hz testing voltage for 5 minutes kV 12.5
14 Approx. Overall Diameter mm 24 (± 2) 25 (± 2) 27 (± 2) 30 (± 2.5)
15 Approx. Cable Weight kg/km 1,430 1,710 2,070 2,660
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R AThermal resistivity of soil: 1.5K.m/W

N
I 1-DE T15
2
C - 2 0
UIL
Depth of laying: 0.8m

AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 11 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


3.6/6(7.2)kV SINGLE-CORE UNARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( CU/XLPE/MS/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx300 1Cx400 1Cx500 1Cx630
1 TAG/PJ SYMBOL 8263R117-X 8263R118-X 8263R119-X 8263R120-X
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 3.6/6(7.2)
4 Conductor
- Material Annealed copper wires
2
- Cross sectional area mm 300 400 500 630
- Number of core No. 1 1 1 1
- Structure of core Circular compacted
- DC Max. resistance at 200C W/km 0.0601 0.047 0.0366 0.0283
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 2.8 3.0 3.2 3.2
- Min. thickness mm 2.42 2.6 2.78 2.78
o
- Working temperature C 90
o
- Emergency temperature C 130
o
- Short circuit temperature C 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05 0.05 0.05 0.05
9 Over sheath
- Material Fr-PVC
- Min. thickness mm 1.60 1.69 1.77 1.86
- Color Red
10 Reactance of cable (X) flat spaced W/km 0.1475 0.1452 0.1451 0.1424
11 Capacitance of the cable (C) mF/km 0.6025 0.6317 0.6829 0.7678
12 Current carrying capacity (*) A
In air (Flat Spaced) 803 891 1087 1264
Buried direct in ground (Flat
487 532 660 749
Spaced)
13 50 Hz testing voltage for 5 minutes kV 12.5
14 Approx. Overall Diameter mm 33 (± 2.5) 36 (± 2.5) 41 (± 2.5) 45 (± 2.5)
15 Approx. Cable Weight kg/km 3,290 4,150 5,350 6,760
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W
N
I 21-DE UILT15
C - 2 0
Depth of laying: 0.8m

AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 12 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-04

6/10(12)kV SINGLE-CORE UNARMOURED XLPE


Conductor Size: 120mm2 to 630mm2
INSULATED Fr-PVC SHEATH CABLES

1 5

2 6

3 7

4 8

TAG/PJ SYMBOL: 8264R113-X, 8264R117-X, 8264R118-X, 8264R119-X, 8264R120-X

Item Description Material Apply method Remark


1 Conductor Annealed copper wires Circular compacted Class2 - IEC 60228
2 Binder Semi-conducting tape Taping Manufacturer's decision (*)
3 Conductor screen Semi-conducting compound Extruding
4 Insulation XLPE compound Extruding Simultaneously extruded
5 Insulation screen Semi-conducting compound Extruding
6 Metallic screen Copper tape Taping Overlap taping
7 Binder Binder tape Taping Overlap taping
8 Oversheath Fr-PVC compound Extruding Color: Red

Note (*): Semi-conducting tape shall be applied over the conductor for size 500sqmm and over
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :

LS-VINA Cable & System * Flame retardant Cu/XLPE/Fr-PVC 300sqmm – 6/10(12)kV* (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 13 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


6/10(12)kV SINGLE-CORE UNARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( CU/XLPE/MS/Fr-PVC)
Cable size (mm2)
No. Technical characteristics Unit
1Cx120 1Cx300 1Cx400 1Cx500 1Cx630
1 TAG/PJ SYMBOL 8264R113-X 8264R117-X 8264R118-X 8264R119-X 8264R120-X
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 6/10(12)
4 Conductor
- Material Annealed copper wires
2
- Cross sectional area mm 120 300 400 500 630
- Number of core No. 1 1 1 1 1
- Structure of core Circular compacted
0
- DC Max. resistance at 20 C W/km 0.153 0.0601 0.047 0.0366 0.0283
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 3.4 3.4 3.4 3.4 3.4
- Min. thickness mm 2.96 2.96 2.96 2.96 2.96
o
- Working temperature C 90
o
- Emergency temperature C 130
o
- Short circuit temperature C 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05
9 Over sheath
- Material Fr-PVC
- Min. thickness mm 1.43 1.60 1.77 1.77 1.94
- Color Red
10 Reactance of cable (X) flat spaced W/km 0.1623 0.1497 0.1469 0.1457 0.1433
11 Capacitance of the cable (C) mF/km 0.3467 0.5075 0.565 0.6466 0.7265
12 Current carrying capacity (*) A
In air (Flat Spaced) 475 803 891 1087 1264
Buried direct in ground (Flat
308 487 532 660 749
Spaced)
13 50 Hz testing voltage for 5 minutes kV 21
14 Approx. Overall Diameter mm 26 (± 2) 34 (± 2.5) 37 (± 2.5) 41 (± 2.5) 45 (± 2.5)
15 Approx. Cable Weight kg/km 1,510 3,350 4,210 5,370 6,810
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
N C - 2
Thermal resistivity of soil: 1.5K.m/W
I 21-DE UILT15
0
Depth of laying: 0.8m
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 14 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-05

18/30(36)kV SINGLE-CORE UNARMOURED XLPE


Conductor Size: 120mm2 to 630mm2
INSULATED Fr-PVC SHEATH CABLES

1 5

2 6

3 7

4 8

TAG/PJ SYMBOL: 8267R113-X, 8267R117-X, 8267R118-X, 8267R119-X, 8267R120-X

Item Description Material Apply method Remark


1 Conductor Annealed copper wires Circular compacted Class2 - IEC 60228
2 Binder Semi-conducting tape Taping Manufacturer's decision (*)
3 Conductor screen Semi-conducting compound Extruding
4 Insulation XLPE compound Extruding Simultaneously extruded
5 Insulation screen Semi-conducting compound Extruding
6 Metallic screen Copper tape Taping Overlap taping
7 Binder Binder tape Taping Overlap taping
8 Oversheath Fr-PVC compound Extruding Color: Red

Note (*): Semi-conducting tape shall be applied over the conductor for size 500sqmm and over
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :
LS-VINA Cable & System * Flame retardant Cu/XLPE/Fr-PVC 300sqmm – 18/30(36)kV* (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 15 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


18/30(36)kV SINGLE-CORE UNARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( CU/XLPE/MS/Fr-PVC)
Cable size (mm2)
No. Technical characteristics Unit
1Cx120 1Cx300 1Cx400 1Cx500 1Cx630
1 TAG/PJ SYMBOL 8267R113-X 8267R117-X 8267R118-X 8267R119-X 8267R120-X
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 18/30(36)
4 Conductor
- Material Annealed copper wires
- Cross sectional area mm2 120 300 400 500 630
- Number of core No. 1 1 1 1 1
- Structure of core Circular compacted
- DC Max. resistance at 200C W/km 0.153 0.0601 0.047 0.0366 0.0283
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 8.0 8.0 8.0 8.0 8.0
- Min. thickness mm 7.1 7.1 7.1 7.1 7.10
o
- Working temperature C 90
o
- Emergency temperature C 130
o
- Short circuit temperature C 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05 0.05 0.05 0.05 0.05
9 Over sheath
- Material Fr-PVC
- Min. thickness mm 1.69 1.94 2.03 2.11 2.20
- Color Red
10 Reactance of cable (X) flat spaced W/km 0.1835 0.1664 0.1620 0.1594 0.1556
11 Capacitance of the cable (C) mF/km 0.1841 0.2523 0.2772 0.3106 0.345
12 Current carrying capacity (*) A
In air (Flat Spaced) 475 803 891 1087 1264
Buried direct in ground (Flat
308 487 532 660 749
Spaced)
13 50 Hz testing voltage for 5 minutes kV 63
14 Approx. Overall Diameter mm 36 (± 2.5) 44 (± 2.5) 47 (± 2.5) 51 (± 3) 55 (± 3)
15 Approx. Cable Weight kg/km 2,030 4,010 4,900 6,140 7,620
Note(*):
Ambient temperature: 36 0 C

D R A
Ground temperature: 30 0 C

I N C
E - 2 0 15
Thermal resistivity of soil: 1.5K.m/W
21-D BUILDepth
T of laying: 0.8m
AS
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 16 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING

DRAWING NO. : VV2182-001-C-001-07

0.6/1(1.2)kV SINGLE-CORE ARMOURED SHEATH


Conductor Size: 150mm2 to 800mm2
XLPE INSULATED Fr-PVC SHEATH CABLES

1 4

2 5

3 6

TAG/PJ SYMBOL: 8261D114, 8261D115, 8261D116, 8261D117, 8261D118, 8261D119, 8261D120, 8261D121

Item Description Material Appling method Remark

1 Conductor Annealed copper wires Circular compacted Class 2 - IEC 60228

2 Insulation XLPE compound Extruding Color: Black

3 Inner sheath PVC compound Extruding

4 Metallic armour Aluminium wires Stranding

5 Binder Foam tape Taping Overlap taping

6 Oversheath Fr-PVC compound Extruding Color: Black

- The length in meters shall be printed on oversheath cable.


- Marking method on oversheath: - Printing on oversheath surface with following content
Example: For 1Cx500mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/PVC/AWA/Fr-PVC 500sqmm – 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 17 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/AWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
1x150 1x185 1x240 1x300
1 Tag/PJ SYMBOL 8261D114 8261D115 8261D116 8261D117
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 150 185 240 300
Number of core No. 1 1 1 1
Structure of core Circular compacted
Max. DC resistance at 20oC W/km 0.124 0.0991 0.0754 0.0601
5 Insulation
Material XLPE
Nominal thickness mm 1.4 1.6 1.7 1.8
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60
Diameter (Approx.) after inner
6.1 mm 19.2 21.2 23.7 26.2
sheath
7 Armour
Material Aluminium wires
Diameter of wires mm 1.6 (±5%) 1.6 (±5%) 1.6 (±5%) 1.6 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.16 1.24 1.32 1.32
9 Reactance of cable (X) flat spaced W/km 0.1569 0.1546 0.1518 0.1492
10 Capacitance of the cable (C) mF/km 0.7246 0.7126 0.7656 0.8131
11 Current carrying capacity (*) A
In air (trefoil) 422 485 577 668
Buried direct in ground (trefoil) 325 365 420 469
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 26 (±2) 28 (±2) 31 (±2.5) 34(±2.5)
14 Approx. Cable Weight kg/km 1,890 2,280 2,880 3,470
Note(*):
Ambient temperature: 36 0 C

D R A
Ground temperature: 30 0 C

N C -
Thermal resistivity of soil: 1.5K.m/W
I 21-DE UILT15
2 0
Depth of laying: 0.8m
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 18 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/AWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
1x400 1x500 1x630 1x800
1 TAG/PJ SYMBOL 8261D118 8261D119 8261D120 8261D121
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 400 500 630 800
Number of core No. 1 1 1 1
Structure of core Circular compacted
o
Max. DC resistance at 20 C W/km 0.047 0.0366 0.0283 0.0221
5 Insulation
Material XLPE
Nominal thickness mm 2.0 2.2 2.4 2.6
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.76 0.76 0.76 0.92
Diameter (Approx.) after inner
6.1 mm 29.8 33.3 37.6 42.4
sheath
7 Armour
Material Aluminium wires
Diameter of wires mm 2.0 (±5%) 2.0 (±5%) 2.0 (±5%) 2.5 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.48 1.56 1.64 1.80
9 Reactance of cable (X) flat spaced W/km 0.1491 0.1473 0.1450 0.1451
10 Capacitance of the cable (C) mF/km 0.8347 0.8617 0.9066 0.9474
11 Current carrying capacity (*) A
In air (trefoil) 782 899 1034 1139
Buried direct in ground (trefoil) 520 576 633 669
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 38 (±2.5) 42 (±2.5) 47 (±2.5) 53(±3)
14 Approx. Cable Weight kg/km 4,540 5,670 7,160 9,210
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W

D R A
Depth of laying: 0.8m

I N C
E - 2
21-D BUILT
0 15
AS
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 19 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-07

0.6/1(1.2)kV TWO-CORE ARMOURED XLPE


Conductor Size: 2.5mm2 to 240mm2
INSULATED Fr-PVC SHEATH CABLES

1 5

2 6

3 7

4 8

TAG/PJ SYMBOL: 8261D203, 8261D204, 8261D205, 8261D206, 8261D207, 8261D208, 8261D209, 8261D210, 8261D211, 8261D212,
8261D213, 8261D214, 8261D215, 8261D216

Item Description Material Appling method Remark


Circular
1 Conductor Annealed copper wire Class 2 - IEC 60228
stranded/Compacted
2 Insulation XLPE compound Extruding Color: Brown, Blue

3 Filler P. P yarn Stranding Non hygroscopic

4 Binder Foam tape Taping Overlap taping

5 Inner sheath PVC compound Extruding

6 Metallic armour Galvanized steel wires Stranding

7 Binder Foam tape Taping Overlap taping

8 Oversheath Fr-PVC compound Extruding Color: Black

- Core shall be identified by colored XLPE insulation. Color shall be Brown, Blue.
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content
Example: For 2Cx35mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/PVC/SWA/Fr-PVC 2x35sqmm – 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 20 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV TWO-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
2Cx2.5 2Cx4 2Cx6 2Cx10
1 TAG/PJ SYMBOL 8261D203 8261D204 8261D205 8261D206
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 2.5 4 6 10
Number of core No. 2 2 2 2
Structure of core Circular stranded
o
Max. DC resistance at 20 C W/km 7.41 4.61 3.08 1.83
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.7 0.7 0.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60
Diameter (Approx.) after inner
6.1 mm 9.4 10.5 11.6 13.5
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 0.9 (±5%) 0.9 (±5%) 0.9 (±5%) 1.25 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.24
9 Reactance of cable (X) W/km 0.1021 0.0958 0.0911 0.0859
10 Capacitance of the cable (C) mF/km 0.2372 0.2852 0.3355 0.4171
11 Current carrying capacity (*) A
In air 34 47 60 82
Buried direct in ground 42 55 69 92
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 15 (±2) 16 (±2) 17 (±2) 20 (±2)
14 Approx. Cable Weight kg/km 440 510 590 820
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W

D R A
N C -
Depth of laying: 0.8m
I 21-DE UILT15
2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 21 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV TWO-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
2Cx16 2Cx25 2Cx35 2Cx50 2Cx70
1 TAG/PJ SYMBOL 8261D207 8261D208 8261D209 8261D210 8261D211
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 16 25 35 50 70
Number of core No. 2 2 2 2 2
Structure of core Circular compacted
o
Max. DC resistance at 20 C W/km 1.15 0.727 0.524 0.387 0.268
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.9 0.9 1.0 1.1
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60 0.60
Diameter (Approx.) after inner
6.1 mm 14.70 18.00 20.00 22.60 26.40
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 1.25 (±5%) 1.6 (±5%) 1.6 (±5%) 1.6 (±5%) 1.6 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.24 1.40
9 Reactance of cable (X) W/km 0.0835 0.0833 0.0809 0.0802 0.076
10 Capacitance of the cable (C) mF/km 0.4697 0.4757 0.5456 0.5717 0.6282
11 Current carrying capacity (*) A
In air 109 142 176 214 275
Buried direct in ground 119 154 185 218 268
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 21 (±2) 25 (±2) 27 (±2) 30 (±2.5) 34 (±2.5)
14 Approx. Cable Weight kg/km 960 1,430 1,720 2,070 2,710
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W

D R A
Depth of laying: 0.8m
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 22 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV TWO-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
2Cx95 2Cx120 2Cx150 2Cx185 2Cx240
1 TAG/PJ SYMBOL 8261D212 8261D213 8261D214 8261D215 8261D216
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 95 120 150 185 240
Number of core No. 2 2 2 2 2
Structure of core Circular compacted
o
Max. DC resistance at 20 C W/km 0.193 0.153 0.124 0.0991 0.0754
5 Insulation
Material XLPE
Nominal thickness mm 1.1 1.2 1.4 1.6 1.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.76 0.76 0.76 0.92 0.92
Diameter (Approx.) after inner
6.1 mm 30.2 33.4 37.0 41.4 46.4
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 2.0 (±5%) 2.0 (±5%) 2.0 (±5%) 2.5 (±5%) 2.5 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.48 1.56 1.64 1.80 1.96
9 Reactance of cable (X) W/km 0.0741 0.0737 0.0741 0.0735 0.0726
10 Capacitance of the cable (C) mF/km 0.727 0.7511 0.7246 0.7126 0.7656
11 Current carrying capacity (*) A
In air 334 390 449 515 609
Buried direct in ground 321 364 408 461 533
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 39(±2.5) 42 (±2.5) 46 (±2.5) 52 (±3) 57 (±3)
14 Approx. Cable Weight kg/km 3,710 4,410 5,200 6,770 8,300
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W
N
I 21-DE UILT15
C - 2 0
Depth of laying: 0.8m

AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 23 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-08

0.6/1(1.2)kV THREE-CORE ARMOURED XLPE


Conductor Size: 2.5mm2 to 240mm2
INSULATED Fr-PVC SHEATH CABLES

1 5

2 6

3 7

4 8

TAG/PJ SYMBOL: 8261D303, 8261D304, 8261D305, 8261D306, 8261D307, 8261D308, 8261D309, 8261D310, 8261D311, 8261D312,
8261D313, 8261D314, 8261D315, 8261D316

Item Description Material Appling method Remark


Circular
1 Conductor Annealed copper wire Class 2 - IEC 60228
stranded/Compacted
2 Insulation XLPE compound Extruding Color: Brown, Black, Grey

3 Filler P. P yarn Stranding Non hygroscopic

4 Binder Foam tape Taping Overlap taping

5 Inner sheath PVC compound Extruding

6 Metallic armour Galvanized steel wires Stranding

7 Binder Foamtape Taping Overlap taping

8 Oversheath Fr-PVC compound Extruding Color: Black

- Core shall be identified by colored XLPE insulation. Color shall be Brown, Black, Grey.
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content
Example: For 3x35mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/PVC/SWA/Fr-PVC 3x35sqmm – 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 24 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
3Cx2.5 3Cx4 3Cx6 3Cx10
1 TAG/PJ SYMBOL 8261D303 8261D304 8261D305 8261D306
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
Cross sectional area mm2 2.5 4 6 10
Number of core No. 3 3 3 3
Structure of core Circular stranded
o
Max. DC resistance at 20 C W/km 7.41 4.61 3.08 1.83
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.7 0.7 0.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60
Diameter (Approx.) after inner
6.1 mm 10.0 11.2 12.4 14.4
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 0.9 (±5%) 0.9 (±5%) 0.9 (±5%) 1.25 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.24
9 Reactance of cable (X) W/km 0.1021 0.0958 0.0911 0.0859
10 Capacitance of the cable (C) mF/km 0.2372 0.2852 0.3355 0.4171
11 Current carrying capacity (*) A
In air 30 40 51 71
Buried direct in ground 36 46 58 77
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 16 (±2) 17 (±2) 18 (±2) 21 (±2)
14 Approx. Cable Weight kg/km 480 570 660 940
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W

I N C
E - 2
21-D BUILT
Depth of laying: 0.8m
0 15
AS
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 25 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
3Cx16 3Cx25 3Cx35 3Cx50 3Cx70
1 TAG/PJ SYMBOL 8261D307 8261D308 8261D309 8261D310 8261D311
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 16 25 35 50 70
Number of core No. 3 3 3 3 3
Structure of core Circular compacted
Max. DC resistance at 20oC W/km 1.15 0.727 0.524 0.387 0.268
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.9 0.9 1.0 1.1
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60 0.76
Diameter (Approx.) after inner
6.1 mm 15.7 19.2 21.4 24.2 28.7
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 1.25 (±5%) 1.6 (±5%) 1.6 (±5%) 1.6 (±5%) 2.0 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.32 1.40
9 Reactance of cable (X) W/km 0.0835 0.0833 0.0809 0.0802 0.076
10 Capacitance of the cable (C) mF/km 0.4697 0.4757 0.5456 0.5717 0.6282
11 Current carrying capacity (*) A
In air 95 121 150 182 234
Buried direct in ground 100 127 154 182 224
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 22 (±2) 26 (±2) 29 (±2) 32 (±2.5) 37 (±2.5)
14 Approx. Cable Weight kg/km 1,150 1,710 2,090 2,590 3,730
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W

I N C
E - 2
21-D BUILT
Depth of laying: 0.8m
0 15
AS
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 26 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
3Cx95 3Cx120 3Cx150 3Cx185 3Cx240
1 TAG/PJ SYMBOL 8261D312 8261D313 8261D314 8261D315 8261D316
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
Cross sectional area mm2 95 120 150 185 240
Number of core No. 3 3 3 3 3
Structure of core Circular compacted
o
Max. DC resistance at 20 C W/km 0.193 0.153 0.124 0.0991 0.0754
5 Insulation
Material XLPE
Nominal thickness mm 1.1 1.2 1.4 1.6 1.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.76 0.76 0.92 0.92 1.08
Diameter (Approx.) after inner
6.1 mm 32.4 35.8 40.2 44.5 50.3
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 2.0 (±5%) 2.0 (±5%) 2.5 (±5%) 2.5 (±5%) 2.5 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.56 1.64 1.80 1.88 2.04
9 Reactance of cable (X) W/km 0.0741 0.0737 0.0741 0.0735 0.0726
10 Capacitance of the cable (C) mF/km 0.727 0.7511 0.7246 0.7126 0.7656
11 Current carrying capacity (*) A
In air 283 329 379 433 511
Buried direct in ground 269 306 342 386 446
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 41(±2.5) 45 (±2.5) 50 (±3) 55 (±3) 61 (±3)
14 Approx. Cable Weight kg/km 4,680 5,650 7,210 8,640 10,800
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W

N C -
Depth of laying: 0.8m
I 21-DE UILT15
2 0
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 27 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-09

0.6/1(1.2)kV FOUR-CORE ARMOURED XLPE


Conductor Size: 2.5mm2 to 240mm2
INSULATED Fr-PVC SHEATH CABLES

1 5

2 6

3 7

4 8

TAG/PJ SYMBOL: 8261D403, 8261D404, 8261D305, 8261D406, 8261D407, 8261D408, 8261D409, 8261D410, 8261D411, 8261D412,
8261D413, 8261D414, 8261D415, 8261D416

Item Description Material Appling method Remark


Circular
1 Conductor Annealed copper wire Class 2 - IEC 60228
stranded/Compacted
Color: Brown, Black, Grey,
2 Insulation XLPE compound Extruding
Blue
3 Filler P. P yarn Stranding Non hyroscopic

4 Binder Foam tape Taping Overlap taping

5 Inner sheath PVC compound Extruding

6 Metallic armour Galvanized steel wires Stranding

7 Binder Foamtape Taping Overlap taping

8 Oversheath Fr-PVC compound Extruding Color: Black

- Core shall be identified by colored XLPE insulation. Color shall be Brown, Black, Grey, Blue.
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content
Example: For 4x35mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/PVC/SWA/Fr-PVC 4x35sqmm – 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 28 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV FOUR-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
4Cx2.5 4Cx4 4Cx6 4Cx10
1 TAG/PJ SYMBOL 8261D403 8261D404 8261D405 8261D406
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
Cross sectional area mm2 2.5 4 6 10
Number of core No. 4 4 4 4
Structure of core Circular stranded
o
Max. DC resistance at 20 C W/km 7.41 4.61 3.08 1.83
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.7 0.7 0.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60
Diameter (Approx.) after inner
6.1 mm 10.9 12.2 13.6 15.9
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 0.9 (±5%) 0.9 (±5%) 1.25 (±5%) 1.25 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.24
9 Reactance of cable (X) W/km 0.1021 0.0958 0.0911 0.0859
10 Capacitance of the cable (C) mF/km 0.2372 0.2852 0.3355 0.4171
11 Current carrying capacity (*) A
In air 30 40 51 71
Buried direct in ground 36 46 58 77
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 17 (±2) 18 (±2) 20 (±2) 22 (±2)
14 Approx. Cable Weight kg/km 550 650 860 1,110
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W

I N C
E - 2
21-D BUILT
15
Depth of laying: 0.8m
0
AS
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 29 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV FOUR-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
4Cx16 4Cx25 4Cx35 4Cx50 4Cx70
1 TAG/PJ SYMBOL 8261D407 8261D408 8261D409 8261D410 8261D411
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 16 25 35 50 70
Number of core No. 4 4 4 4 4
Structure of core Circular compacted
o
Max. DC resistance at 20 C W/km 1.15 0.727 0.524 0.387 0.268
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.9 0.9 1.0 1.1
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60 0.76
Diameter (Approx.) after inner
6.1 mm 17.3 21.3 23.7 26.9 31.9
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 1.6 (±5%) 1.6 (±5%) 1.6 (±5%) 1.6 (±5%) 2.0 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.32 1.40 1.56
9 Reactance of cable (X) W/km 0.0835 0.0833 0.0809 0.0802 0.076
10 Capacitance of the cable (C) mF/km 0.4697 0.4757 0.5456 0.5717 0.6282
11 Current carrying capacity (*) A
In air 95 121 150 182 234
Buried direct in ground 100 127 154 182 224
9 50Hz testing voltage for 5 minutes kV 3.5
10 Approx. Overall Diameter mm 24 (±2) 28 (±2) 31 (±2.5) 34 (±2.5) 41 (±2.5)
11 Approx. Cable Weight kg/km 1,510 2,050 2,540 3,180 4,560
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W

I N C
E - 2
21-D BUILT
Depth of laying: 0.8m
0 15
AS
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 30 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV FOUR-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
4Cx95 4Cx120 4Cx150 4Cx185 4Cx240
1 TAG/PJ SYMBOL 8261D412 8261D413 8261D414 8261D415 8261D416
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 95 120 150 185 240
Number of core No. 4 4 4 4 4
Structure of core Circular compacted
Max. DC resistance at 20oC W/km 0.193 0.153 0.124 0.0991 0.0754
5 Insulation
Material XLPE
Nominal thickness mm 1.1 1.2 1.4 1.6 1.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.76 0.92 0.92 0.92 1.08
Diameter (Approx.) after inner
6.1 mm 36.0 40.3 44.6 49.5 55.9
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 2.0 (±5%) 2.5 (±5%) 2.5 (±5%) 2.5 (±5%) 2.5 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.64 1.80 1.88 2.04 2.20
9 Reactance of cable (X) W/km 0.0741 0.0737 0.0741 0.0735 0.0726
10 Capacitance of the cable (C) mF/km 0.727 0.7511 0.7246 0.7126 0.7656
11 Current carrying capacity (*) A
In air 283 329 379 433 511
Buried direct in ground 269 306 342 386 446
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 45(±2.5) 51 (±3) 55 (±3) 60 (±3) 67 (±3)
14 Approx. Cable Weight kg/km 5,850 7,450 8,900 10,780 13,560
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W

I N C
E - 2
21-D BUILT
Depth of laying: 0.8m
0 15
AS
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 31 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-10

0.6/1(1.2)kV MULTI-CORE ARMOURED XLPE


Conductor Size: 25mm2 to 70mm2
INSULATED Fr-PVC SHEATH CABLES

1 5

2 6

3 7

4 8

TAG/PJ SYMBOL: 8261D508, 8261D509, 8261D510, 8261D511

Item Description Material Appling method Remark

1 Conductor Annealed copper wire Circular compacted Class 2 - IEC 60228

Color: Brown, Black, Grey,


2 Insulation XLPE compound Extruding
Blue, Green/Yellow
3 Filler P. P yarn Stranding Non hygroscopic

4 Binder Foam tape Taping Overlap taping

5 Inner sheath PVC compound Extruding

6 Metallic armour Galvanized steel wires Stranding

7 Binder Foamtape Taping Overlap taping

8 Oversheath Fr-PVC compound Extruding Color: Black

- Core shall be identified by colored XLPE insulation. Color shall be Brown, Black, Grey, Blue, Green/Yellow
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content
Example: For 5x35mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/PVC/SWA/Fr-PVC 5x35sqmm – 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 32 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV MULTI-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
5Cx25 5Cx35 5Cx50 5Cx70
1 TAG/PJ SYMBOL 8261D508 8261D509 8261D510 8261D511
2 Applied standard IEC 60502-1: 2009, IEC 60332-1
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
Cross sectional area mm2 25 35 50 70
Number of core No. 5 5 5 5
Structure of core Circular compacted
o
Max. DC resistance at 20 C W/km 0.727 0.524 0.387 0.268
5 Insulation
Material XLPE
Nominal thickness mm 0.9 0.9 1.0 1.1
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.76 0.76
Diameter (Approx.) after inner
6.1 mm 23.5 26.2 30.1 35.3
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 1.6 (±5%) 1.6 (±5%) 2.0 (±5%) 2.0 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.32 1.48 1.64
9 Reactance of cable (X) W/km 0.0833 0.0809 0.0802 0.076
10 Capacitance of the cable (C) mF/km 0.4757 0.5456 0.5717 0.6282
11 Current carrying capacity (*) A
In air 121 150 182 234
Buried direct in ground 127 154 182 224
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 31 (±2.5) 34 (±2.5) 39 (±2.5) 44 (±2.5)
14 Approx. Cable Weight kg/km 2,340 2,910 3,980 5,280
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W

I N C
E - 2
21-D BUILT
15
Depth of laying: 0.8m
0
AS
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 33 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-11

0.6/1(1.2)kV TWO-CORE ARMOURED XLPE


Conductor size: 2.5mm2 to 10mm2
INSULATED FR-PVC SHEATH CABLES

1 6

2
7

8
4

5 9

TAG/PJ SYMBOL: 8261T203, 8261T204, 8261T205, 8261T206

Item Description Material Appling method Remark

1 Conductor Annealed copper wire Circular stranded Class 2 - IEC 228

2 Binder Mica tape(s) Taping

3 Insulation XLPE compound Extruding Corlor: Brown, Blue

4 Filler P.P yarn Stranding Non hygroscopic

5 Binder Foam tape Taping Overlap taping

6 Inner sheath PVC compound Extruding

7 Metallic armour Galvanized steel wires Stranding

7 Binder Foam tape Taping Overlap taping

9 Oversheath Fr-PVC compound Extruding Color: Black

- Core shall be identified by colored XLPE insulation. Color shall be Brown, Blue.
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :
Example: For 2Cx6mm2 cable.
LS-VINA Cable & System * Fire resistant Cu/XLPE/PVC/SWA/Fr-PVC 2x6SQMM – 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 34 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV TWO-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(CU/Mica/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
2Cx2.5 2Cx4 2Cx6 2Cx10
1 TAG/PJ SYMBOL 8261T203 8261T204 8261T205 8261T206
2 Applied standard IEC 60502-1: 2009, IEC 60331-21
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 2.5 4 6 10
Number of core No. 2 2 2 2
Structure of core Circular stranded
o
Max. DC resistance at 20 C W/km 7.41 4.61 3.08 1.83
5 Insulation
Material XLPE XLPE XLPE XLPE
Nominal thickness mm 0.7 0.7 0.7 0.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60
Diameter (Approx.) after inner
6.1 mm 10.50 11.60 12.70 14.60
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 0.9 (±5%) 0.9 (±5%) 0.9 (±5%) 1.25 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.24
9 Reactance of cable (X) W/km 0.1114 0.1039 0.0983 0.092
10 Capacitance of the cable (C) mF/km 0.1903 0.2264 0.264 0.3249
11 Current carrying capacity (*) A
In air 34 47 60 82
Buried direct in ground 42 55 69 92
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 16 (±2) 17 (±2) 19 (±2) 21 (±2)
14 Approx. Cable Weight kg/km 470 550 620 860
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W
N
I 21-DE UILT15
C - 2 0
Depth of laying: 0.8m
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 35 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-002-12

0.6/1(1.2)kV THREE-CORE ARMOURED XLPE


Conductor size: 2.5mm2 to 240mm2
INSULATED Fr-PVC SHEATH CABLES

1 6

2
7

8
4

5 9

TAG/PJ SYMBOL: 8261T303, 8261T304, 8261T305, 8261T306, 8261T307, 8261T308, 8261T309, 8261T310, 8261T311,
8261T312, 8261T313, 8261T314, 8261T315, 8261T316

Item Description Material Appling method Remark


Circular compacted/
1 Conductor Annealed copper wire Class 2 - IEC 228
stranded
2 Binder Mica tape(s) Taping
Color: Brown, Black,
3 Insulation XLPE compound Extruding
Grey
4 Filler P.P yarn Stranding Non hygroscopic

5 Binder Foam tape Taping Overlap taping

6 Inner sheath PVC compound Extruding

7 Metallic armour Galvanized steel wires Stranding

8 Binder Foam tape Taping Overlap taping

9 Oversheath Fr-PVC compound Extruding Color: Black

- Core shall be identified by colored XLPE insulation. Color shall be Brown, Black, Grey.
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :
Example: For 3Cx16mm2 cable.
LS-VINA Cable & System * Fire resistant Cu/XLPE/PVC/SWA/Fr-PVC 3x16sqmm – 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev.0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 36 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(CU/Mica/XLPE/PVC/SWA/FR-PVC)

Cable size (mm2)


No Technical characteristics Unit
3Cx2.5 3Cx4 3Cx6 3Cx10
1 TAG/PJ SYMBOL 8261T303 8261T304 8261T305 8261T306
2 Applied standard IEC 60502-1: 2009, IEC 60331-21
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 2.5 4 6 10
Number of core No. 3 3 3 3
Structure of core Circular stranded
o
Max. DC resistance at 20 C W/km 7.41 4.61 3.08 1.83
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.7 0.7 0.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60
Diameter (Approx.) after inner
6.1 mm 11.2 12.4 13.6 15.6
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 0.9 (±5%) 0.9 (±5%) 0.9 (±5%) 1.25 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.24
9 Reactance of cable (X) W/km 0.1114 0.1039 0.0983 0.092
10 Capacitance of the cable (C) mF/km 0.1903 0.2264 0.264 0.3249
11 Current carrying capacity (*) A
In air 30 40 51 71
Buried direct in ground 36 46 58 77
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 17 (±2) 18 (±2) 19 (±2) 22 (±2)
14 Approx. Cable Weight kg/km 530 610 720 1,010
Note(*):
Ambient temperature: 36 0 C

D R A
Ground temperature: 30 0 C

N
I 21-DE UILT15
C -
Thermal resistivity of soil: 1.5K.m/W
2 0
Depth of laying: 0.8m
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 37 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(CU/Mica/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
3Cx16 3Cx25 3Cx35 3Cx50 3Cx70
1 TAG/PJ SYMBOL 8261T307 8261T308 8261T309 8261T310 8261T311
2 Applied standard IEC 60502-1: 2009, IEC 60331-21
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 16 25 35 50 70
Number of core No. 3 3 3 3 3
Structure of core Circular compacted
Max. DC resistance at 20oC W/km 1.15 0.727 0.524 0.387 0.268
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.9 0.9 1.0 1.1
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60 0.76
Diameter (Approx.) after inner
6.1 mm 16.9 20.5 22.6 25.4 29.9
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 1.25 (±5%) 1.6 (±5%) 1.6 (±5%) 1.6 (±5%) 2.0 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.32 1.40
9 Reactance of cable (X) W/km 0.089 0.0877 0.0848 0.0836 0.0789
10 Capacitance of the cable (C) mF/km 0.364 0.3854 0.4401 0.4686 0.5215
11 Current carrying capacity (*) A
In air 95 121 150 182 234
Buried direct in ground 100 127 154 182 224
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 23 (±2) 28 (±2) 30 (±2.5) 33 (±2.5) 38 (±2.5)
14 Approx. Cable Weight kg/km 1,210 1,780 2,160 2,660 3,840
Note(*):
Ambient temperature: 36 0 C

D R A
Ground temperature: 30 0 C

N C -
Thermal resistivity of soil: 1.5K.m/W
I 21-DE UILT15
2 0
Depth of laying: 0.8m
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 38 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(CU/Mica/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
3Cx95 3Cx120 3Cx150 3Cx185 3Cx240
1 TAG/PJ SYMBOL 8261T312 8261T313 8261T314 8261T315 8261T316
2 Applied standard IEC 60502-1: 2009, IEC 60331-21
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 95 120 150 185 240
Number of core No. 3 3 3 3 3
Structure of core Circular compacted
o
Max. DC resistance at 20 C W/km 0.193 0.153 0.124 0.0991 0.0754
5 Insulation
Material XLPE
Nominal thickness mm 1.1 1.2 1.4 1.6 1.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.76 0.76 0.92 0.92 1.08
Diameter (Approx.) after inner
6.1 mm 33.6 37.1 41.4 45.7 51.5
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 2.0 (±5%) 2.0 (±5%) 2.5 (±5%) 2.5 (±5%) 2.5 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.56 1.64 1.80 1.88 2.04
9 Reactance of cable (X) W/km 0.0766 0.076 0.0762 0.0753 0.0743
10 Capacitance of the cable (C) mF/km 0.6017 0.6295 0.6209 0.6210 0.6713
11 Current carrying capacity (*) A
In air 283 329 379 433 511
Buried direct in ground 269 306 342 386 446
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 42(±2.5) 46 (±2.5) 52 (±3) 56 (±43) 62 (±3)
14 Approx. Cable Weight kg/km 4,760 5,740 7,280 8,750 10,870
Note(*):
Ambient temperature: 36 0 C

D R A
Ground temperature: 30 0 C

N
I 21-DE UILT15
C -
Thermal resistivity of soil: 1.5K.m/W
2 0
Depth of laying: 0.8m
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 39 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-13

0.6/1(1.2)kV FOUR-CORE ARMOURED XLPE


Conductor size: 2.5mm2 to 240mm2
INSULATED Fr-PVC SHEATH CABLES

1 6

2
7

8
4

5 9

TAG/PJ SYMBOL: 8261T403, 8261T404, 8261T405, 8261T406, 8261T407, 8261T408, 8261T409, 8261T410, 8261T411,
8261T412, 8261T413, 8261T414, 8261T415, 8261T416

Item Description Material Appling method Remark


Circular compacted/
1 Conductor Annealed copper wire Class 2 - IEC 60228
stranded
2 Binder Mica tape(s) Taping
Color: Brown, Black,
3 Insulation XLPE compound Extruding
Grey, Blue
4 Filler P.P yarn Stranding Non hygroscopic

5 Binder Foam tape Taping Overlap taping

6 Inner sheath PVC compound Extruding

7 Metallic armour Galvanized steel wires Stranding

7 Binder Foam tape Taping Overlap taping

9 Oversheath Fr-PVC compound Extruding Color: Black

- Core shall be identified by colored XLPE insulation. Color shall be Brown, Black, Grey, Blue.
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :
Example: For 4Cx16mm2 cable.
LS-VINA Cable & System * Fire resistant Cu/XLPE/PVC/SWA/Fr-PVC 4x16sqmm – 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 40 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV FOUR-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(CU/Mica/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
4Cx2.5 4Cx4 4Cx6 4Cx10
1 TAG/PJ SYMBOL 8261T403 8261T404 8261T405 8261T406
2 Applied standard IEC 60502-1: 2009, IEC 60331-21
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 2.5 4 6 10
Number of core No. 4 4 4 4
Structure of core Circular stranded
o
Max. DC resistance at 20 C W/km 7.41 4.61 3.08 1.83
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.7 0.7 0.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60
Diameter (Approx.) after inner
6.1 mm 12.30 13.60 14.90 17.20
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 0.9 (±5%) 0.9 (±5%) 1.25 (±5%) 1.25 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.24
9 Reactance of cable (X) W/km 0.1114 0.1039 0.0983 0.092
10 Capacitance of the cable (C) mF/km 0.1903 0.2264 0.264 0.3249
11 Current carrying capacity (*) A
In air 30 40 51 71
Buried direct in ground 36 46 58 77
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 18 (±2) 20 (±2) 21 (±2) 24 (±2)
14 Approx. Cable Weight kg/km 600 710 910 1,170
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W
N
I 21-DE UILT15
C - 2 0
Depth of laying: 0.8m

AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 41 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV FOUR-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(CU/Mica/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
4Cx16 4Cx25 4Cx35 4Cx50 4Cx70
1 TAG/PJ SYMBOL 8261T407 8261T408 8261T409 8261T410 8261T411
2 Applied standard IEC 60502-1: 2009, IEC 60331-21
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
Cross sectional area mm2 16 25 35 50 70
Number of core No. 4 4 4 4 4
Structure of core Circular compacted
o
Max. DC resistance at 20 C W/km 1.15 0.727 0.524 0.387 0.268
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.9 0.9 1.0 1.1
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.60 0.60 0.60 0.60 0.76
Diameter (Approx.) after inner
6.1 mm 18.7 22.7 25.1 28.2 33.2
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 1.6 (±5%) 1.6 (±5%) 1.6 (±5%) 1.6 (±5%) 2.0 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.32 1.40 1.56
9 Reactance of cable (X) W/km 0.089 0.0877 0.0848 0.0836 0.0789
10 Capacitance of the cable (C) mF/km 0.364 0.3854 0.4401 0.4686 0.5215
11 Current carrying capacity (*) A
In air 95 121 150 182 234
Buried direct in ground 100 127 154 182 224
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 26 (±2) 30 (±2.5) 32 (±2.5) 36 (±2.5) 42 (±2.5)
14 Approx. Cable Weight kg/km 1,580 2,150 2,630 3,280 4,660
Note(*):
Ambient temperature: 36 0 C

D R A
Ground temperature: 30 0 C

N
I 21-DE UILT15
C -
Thermal resistivity of soil: 1.5K.m/W
2 0
Depth of laying: 0.8m
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 42 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV FOUR-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
(CU/Mica/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
4Cx95 4Cx120 4Cx150 4Cx185 4Cx240
1 TAG/PJ SYMBOL 8261T412 8261T413 8261T414 8261T415 8261T416
2 Applied standard IEC 60502-1: 2009, IEC 60331-21
3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
Cross sectional area mm2 95 120 150 185 240
Number of core No. 4 4 4 4 4
Structure of core Circular compacted
Max. DC resistance at 20oC W/km 0.193 0.153 0.124 0.0991 0.0754
5 Insulation
Material XLPE XLPE XLPE XLPE XLPE
Nominal thickness mm 1.1 1.2 1.4 1.6 1.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness mm 0.76 0.92 0.92 0.92 1.08
Diameter (Approx.) after inner
6.1 mm 37.3 41.6 46.0 50.8 57.3
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 2.0 (±5%) 2.5 (±5%) 2.5 (±5%) 2.5 (±5%) 2.5 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.64 1.80 1.88 2.04 2.20
9 Reactance of cable (X) W/km 0.0766 0.076 0.0762 0.0753 0.0743
10 Capacitance of the cable (C) mF/km 0.6017 0.6295 0.6209 0.6210 0.6713
11 Current carrying capacity (*) A
In air 283 329 379 433 511
Buried direct in ground 269 306 342 386 446
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 46 (±2.5) 52 (±3) 57 (±3) 62 (±3) 69 (±3)
14 Approx. Cable Weight kg/km 5,940 7,610 9,110 10,880 13,690
Note(*):
Ambient temperature: 36 0 C

D R A
Ground temperature: 30 0 C

N C -
Thermal resistivity of soil: 1.5K.m/W
I 21-DE UILT15
2 0
Depth of laying: 0.8m
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 43 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-14

3.6/6(7.2)kV SINGLE-CORE ARMOURED XLPE


Conductor Size: 240mm2 to 800mm2
INSULATED Fr-PVC SHEATH CABLES

1 6

7
2

8
3
9

4
10

5 11

TAG/PJ SYMBOL: 8263D116, 8263D117, 8263D118, 8263D119, 8263D120, 8263D121

Item Description Material Apply method Remark


1 Conductor Annealed copper wires Circular compacted Class2 - IEC 60228
2 Binder Semi-conducting tape Taping Manufacturer's decision (*)
3 Conductor screen Semi-conducting compound Extruding
4 Insulation XLPE compound Extruding Simultaneously extruded
5 Insulation screen Semi-conducting compound Extruding
6 Metallic screen Copper tape Taping Overlap taping
7 Binder Binder tape Taping Overlap taping
8 Separation sheath PVC compound Extruding
9 Metallic armour Aluminum wires Stranding
10 Binder Binder tape Taping Overlap taping
11 Oversheath Fr-PVC compound Extruding Color: Red

Note (*): Semi-conducting tape shall be applied over the conductor for size 500sqmm and over
- The length in meters shall be printed on the Fr-PVC oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :
Example: For 1Cx630mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/PVC/AWA/Fr-PVC 630sqmm – 3.6/6(7.2)kV* (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 44 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


3.6/6(7.2)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx240 1Cx300 1Cx400
1 TAG/PJ SYMBOL 8263D116 8263D117 8263D118
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 3.6/6(7.2)
4 Conductor
- Material Annealed copper wires
- Cross sectional area mm2 240 300 400
- Number of core No. 1 1 1
- Structure of core Circular compacted
0
- DC Max. resistance at 20 C W/km 0.0754 0.0601 0.047
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 2.6 2.8 3.0
- Min. thickness mm 2.24 2.42 2.60
o
- Working temperature C 90 90 90
o
- Emergency temperature C 130 130 130
o
- Short circuit temperature C 250 250 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05 0.05 0.05
9 Separation sheath
- Material PVC
- Min. thickness mm 0.76 0.76 0.76
Diameter (Approx.) after
9.1 mm 28.2 30.9 34.1
separation sheath
10 Armour
- Material Aluminium wires
- Diameter of wire mm 2.0 (± 5%) 2.0 (± 5%) 2.0 (± 5%)
11 Over sheath
- Material Fr-PVC
- Min. thickness mm 1.69 1.77 1.86
- Color Red

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 45 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


3.6/6(7.2)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx240 1Cx300 1Cx400
12 Reactance of cable (X) flat spaced W/km 0.1624 0.1597 0.1564
13 Capacitance of the cable (C) mF/km 0.5822 0.6025 0.6317
14 Current carrying capacity (*) A
In air (trefoil) 609 698 803
Buried direct in ground (trefoil) 436 489 549
15 50 Hz testing voltage for 5 minutes kV 12.5
16 Approx. Overall Diameter mm 37 (± 2.5) 39(± 2.5) 43 (± 2.5)
17 Approx. Cable Weight kg/km 3,300 3,980 4,910
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 46 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


3.6/6(7.2)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx500 1Cx630 1Cx800
1 TAG/PJ SYMBOL 8263D119 8263D120 8263D121
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 3.6/6(7.2)
4 Conductor
- Material Annealed copper wires
2
- Cross sectional area mm 500 630 800
- Number of core No. 1 1 1
- Structure of core Circular compacted
0
- DC Max. resistance at 20 C W/km 0.0366 0.0283 0.0221
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 3.2 3.2 3.2
- Min. thickness mm 2.78 2.78 2.78
o
- Working temperature C 90 90 90
o
- Emergency temperature C 130 130 130
o
- Short circuit temperature C 250 250 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Min. Thickness mm 0.05 0.05 0.05
9 Separation sheath
- Material PVC
- Min. thickness mm 0.84 0.92 0.92
Diameter (Approx.) after
9.1 mm 38.8 42.9 46.9
separation sheath
10 Armour
- Material Aluminium wires
- Diameter of wire mm 2.5 (± 5%) 2.5 (± 5%) 2.5 (± 5%)
11 Over sheath
- Material Fr-PVC
- Min. thickness mm 2.03 2.11 2.20
- Color Red

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 47 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


3.6/6(7.2)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx500 1Cx630 1Cx800
12 Reactance of cable (X) flat spaced W/km 0.1569 0.1535 0.1504
13 Capacitance of the cable (C) mF/km 0.6829 0.7678 0.8549
14 Current carrying capacity (*) A
In air (trefoil) 910 1045 1191
Buried direct in ground (trefoil) 610 686 762
12 50 Hz testing voltage for 5 minutes kV 12.5
13 Approx. Overall Diameter mm 49 (± 2.5) 53 (± 3) 58 (± 3)
14 Approx. Cable Weight kg/km 6,400 7,940 9,770
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 48 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-15

3.6/6(7.2)kV THREE-CORE ARMOURED XLPE INSULATED


Conductor Size: 16mm2 to 240mm2
Fr-PVC SHEATH CABLES

1 7

2
8

3
9

10
5

6 11

TAG/PJ SYMBOL: 8263D307, 8263D308, 8263D309, 8263D310, 8263D311, 8263D312, 8263D313, 8263D314, 8263D315, 8263D316

Item Description Material Apply method Remark


1 Conductor Annealed copper wires Circular compacted Class2 - IEC 60228

2 Conductor screen Semi-conducting compound Extruding


Simultaneously
3 Insulation XLPE compound Extruding extruded
4 Insulation screen Semi-conducting compound Extruding
5 Metallic screen Copper tape Taping Overlap taping
6 Filler P.P yarn Stranding Non hygroscopic
7 Binder Binder tape Taping Overlap taping
8 Separation sheath PVC compound Extruding
9 Metallic armour Galvanized steel wires Stranding
10 Binder Binder tape Taping Overlap taping
11 Oversheath Fr-PVC compound Extruding Color: Red

- A narrow colour tape shall be longitudinal applied under copper tape layer of each core to identify core. Colour
shall be Brown, Black, Grey.
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :
Example: For 3x185mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/PVC/SWA/Fr-PVC 3x185sqmm – 3.6/6(7.2)kV* (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 49 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


3.6/6(7.2)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
3Cx16 3Cx25 3Cx35 3Cx50 3Cx70
1 TAG/PJ SYMBOL 8263D307 8263D308 8263D309 8263D310 8263D311
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 3.6/6(7.2)
4 Conductor
- Material Annealed copper wires
- Cross sectional area mm2 16 25 35 50 70
- Number of core No. 3 3 3 3 3
- Structure of core Circular compacted
0
- DC Max. resistance at 20 C W/km 1.15 0.727 0.524 0.387 0.268
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 2.5 2.5 2.5 2.5 2.5
- Min. thickness mm 2.15 2.15 2.15 2.15 2.15
o
- Working temperature C 90 90 90 90 90
o
- Emergency temperature C 130 130 130 130 130
o
- Short circuit temperature C 250 250 250 250 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05 0.05 0.05 0.05 0.05
9 Separation sheath
- Material PVC
- Min. thickness mm 0.76 0.76 0.84 0.84 0.92
Diameter (Approx.) after
9.1 mm 28.0 30.7 33.1 35.4 39.3
separation sheath
10 Armour
- Material Galvanized steel wires
- Diameter of wire mm 2.0 (± 5%) 2.5 (± 5%)
11 Over sheath
- Material Fr-PVC
- Min. thickness mm 1.77 1.86 1.94 2.03 2.11
- Color Red

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev.0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 50 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


3.6/6(7.2)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
3Cx16 3Cx25 3Cx35 3Cx50 3Cx70
12 Reactance of cable (X) W/km 0.1241 0.1153 0.11 0.1054 0.0971
13 Capacitance of the cable (C) mF/km 0.2191 0.2548 0.2832 0.3143 0.3622
14 Current carrying capacity (*) A
In air 105 136 163 195 240
Buried direct in ground 94 120 143 168 205
12 50 Hz testing voltage for 5 minutes kV 12.5
13 Approx. Overall Diameter mm 37 (± 2.5) 40 (± 2.5) 43 (± 2.5) 46 (± 2.5) 50 (± 3)
14 Approx. Cable Weight kg/km 2,530 2,990 3,820 4,410 5,350
Note(*):
Ambient temperature: 36 0 C
0
Ground temperature: 30 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 51 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


3.6/6(7.2)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
3Cx95 3Cx120 3Cx150 3Cx185 3Cx240
1 TAG/PJ SYMBOL 8263D312 8263D313 8263D314 8263D315 8263D316
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 3.6/6(7.2)
4 Conductor
- Material Annealed copper wires
2
- Cross sectional area mm 95 120 150 185 240
- Number of core No. 3 3 3 3 3
- Structure of core Circular compacted
- DC Max. resistance at 200C W/km 0.193 0.153 0.124 0.0991 0.0754
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 2.5 2.5 2.5 2.5 2.6
- Min. thickness mm 2.15 2.15 2.15 2.15 2.24
o
- Working temperature C 90 90 90 90 90
o
- Emergency temperature C 130 130 130 130 130
o
- Short circuit temperature C 250 250 250 250 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05 0.05 0.05 0.05 0.05
9 Separation sheath
- Material PVC
- Min. thickness mm 0.92 1.00 1.08 1.08 1.16
Diameter (Approx.) after
9.1 mm 43.0 46.20 49.5 52.9 58.9
separation sheath
10 Armour
- Material Galvanized steel wires
- Diameter of wire mm 2.5 (± 5%)
11 Over sheath
- Material Fr-PVC
- Min. thickness mm 2.20 2.37 2.45 2.54 2.71
- Color Red

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 52 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


3.6/6(7.2)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
3Cx95 3Cx120 3Cx150 3Cx185 3Cx240
12 Reactance of cable (X) W/km 0.0929 0.0902 0.0879 0.0849 0.0833
13 Capacitance of the cable (C) mF/km 0.41 0.4492 0.4884 0.5331 0.5822
14 Current carrying capacity (*) A
In air 292 334 377 430 503
Buried direct in ground 245 277 309 348 401
12 50 Hz testing voltage for 5 minutes kV 12.5
13 Approx. Overall Diameter mm 54 (± 3) 57 (± 3) 61 (± 3) 64 (± 3) 71 (± 4)
14 Approx. Cable Weight kg/km 6,430 7,420 8,560 9,980 12,230
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 53 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-16

6/10(12)kV SINGLE-CORE ARMOURED XLPE


Conductor Size: 240mm2 to 800mm2
INSULATED Fr-PVC SHEATH CABLES
1 6

7
2

8
3
9

4
10

5 11

TAG/PJ SYMBOL: 8264D116, 8264D117, 8264D118, 8264D119, 8264D120, 8264D121

Item Description Material Apply method Remark


1 Conductor Annealed copper wires Circular compacted Class 2 - IEC 60228
2 Binder Semi-conducting tape Taping Manufacturer's decision (*)
3 Conductor screen Semi-conducting compound Extruding
4 Insulation XLPE compound Extruding Simultaneously extruded
5 Insulation screen Semi-conducting compound Extruding
6 Metallic screen Copper tape Taping Overlap taping
7 Binder Binder tape Taping Overlap taping
8 Separation sheath PVC compound Extruding
9 Metallic armour Aluminum wires Stranding
10 Binder Binder tape Taping Overlap taping
11 Over sheath Fr-PVC compound Extruding Color: Red

Note (*): Semi-conducting tape shall be applied over the conductor for size 500sqmm and over
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :
Example: For 1Cx630mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/PVC/AWA/Fr-PVC 630sqmm – 6/10(12)kV* (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 54 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


6/10(12)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx240 1Cx300 1Cx400
1 TAG/PJ SYMBOL 8264D116 8264D117 8264D118
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 6/10(12)
4 Conductor
- Material Annealed copper wires
2
- Cross sectional area mm 240 300 400
- Number of core No. 1 1 1
- Structure of core Circular compacted
0
- DC Max. resistance at 20 C W/km 0.0754 0.0601 0.047
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 3.4 3.4 3.4
- Min. thickness mm 2.96 2.96 2.96
o
- Working temperature C 90 90 90
o
- Emergency temperature C 130 130 130
o
- Short circuit temperature C 250 250 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05 0.05 0.05
9 Separation sheath
- Material PVC
- Min. thickness mm 0.76 0.76 0.84
Diameter (Approx.) after
9.1 mm 29.8 32.1 35.1
separation sheath
10 Armour
- Material Aluminium wires
- Diameter of wire mm 2.0 (± 5%) 2.0 (± 5%) 2.5 (± 5%)
11 Over sheath
- Material Fr-PVC
- Min. thickness mm 1.77 1.86 1.94
- Color Red

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev.0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 55 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


6/10(12)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx240 1Cx300 1Cx400
12 Reactance of cable (X) flat spaced W/km 0.1654 0.1619 0.1595
13 Capacitance of the cable (C) mF/km 0.4602 0.5075 0.5649
14 Current carrying capacity (*) A
In air (trefoil) 609 698 803
Buried direct in ground (trefoil) 436 489 549
15 50 Hz testing voltage for 5 minutes kV 21
16 Approx. Overall Diameter mm 38 (± 2.5) 41 (± 2.5) 45 (± 2.5)
17 Approx. Cable Weight kg/km 3,430 4,090 5,160
Note(*):
Ambient temperature: 36 0 C
0
Ground temperature: 30 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 56 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


6/10(12)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx500 1Cx630 1Cx800
1 TAG/PJ SYMBOL 8264D119 8264D120 8264D121
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 6/10(12)
4 Conductor
- Material Annealed copper wires
2
- Cross sectional area mm 500 630 800
- Number of core No. 1 1 1
- Structure of core Circular compacted
0
- DC Max. resistance at 20 C W/km 0.0366 0.0283 0.0221
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 3.4 3.4 3.4
- Min. thickness mm 2.96 2.96 2.96
o
- Working temperature C 90 90 90
o
- Emergency temperature C 130 130 130
o
- Short circuit temperature C 250 250 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Min. Thickness mm 0.05 0.05 0.05
9 Separation sheath
- Material PVC
- Min. thickness mm 0.84 0.92 0.92
Diameter (Approx.) after
9.1 mm 39.2 43.3 47.3
separation sheath
10 Armour
- Material Aluminium wires
- Diameter of wire mm 2.5 (± 5%) 2.5 (± 5%) 2.5 (± 5%)
11 Over sheath
- Material Fr-PVC
- Min. thickness mm 2.03 2.11 2.28
- Color Red

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 57 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


6/10(12)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx500 1Cx630 1Cx800
12 Reactance of cable (X) flat spaced W/km 0.1574 0.1539 0.1511
13 Capacitance of the cable (C) mF/km 0.6466 0.7265 0.8085
14 Current carrying capacity (*) A
In air (trefoil) 910 1045 1191
Buried direct in ground (trefoil) 610 686 762
15 50 Hz testing voltage for 5 minutes kV 21
16 Approx. Overall Diameter mm 49 (± 2.5) 54 (± 3) 58 (± 3)
17 Approx. Cable Weight kg/km 6,440 7,980 9,830
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 58 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-17

6/10(12)kV THREE-CORE ARMOURED XLPE INSULATED


Conductor Size: 25mm2 to 240mm2
Fr-PVC SHEATH CABLES

1 7

2
8

3
9

10
5

6 11

TAG/PJ SYMBOL: 8264D308, 8264D309, 8264D310, 8264D311, 8264D312, 8264D313, 8264D314, 8264D315, 8264D316

Item Description Material Apply method Remark


1 Conductor Annealed copper wires Circular compacted Class 2 - IEC 60228
2 Conductor screen Semi-conducting compound Extruding
Simultaneously
3 Insulation XLPE compound Extruding
extruded
4 Insulation screen Semi-conducting compound Extruding
5 Metallic screen Copper tape Taping Overlap taping
6 Filler P.P yarn Stranding Non hygroscopic
7 Binder Binder tape Taping Overlap taping
8 Separation sheath PVC compound Extruding
9 Metallic armour Galvanized steel wires Stranding
10 Binder Binder tape Taping Overlap taping
11 Over sheath Fr-PVC compound Extruding Color: Red

- A narrow colour tape shall be longitudinal applied under copper tape layer of each core to identify core. Colour
shall be Brown, Black, Grey.
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :
Example: For 3Cx150mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/PVC/SWA/Fr-PVC 3x150sqmm – 6/10(12)kV* (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 59 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


6/10(12)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
3Cx25 3Cx35 3Cx50 3Cx70
1 TAG/PJ SYMBOL 8264D308 8264D309 8264D310 8264D311
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 6/10(12)
4 Conductor
- Material Annealed copper wires
- Cross sectional area mm2 25 35 50 70
- Number of core No. 3 3 3 3
- Structure of core Circular compacted
0
- DC Max. resistance at 20 C W/km 0.727 0.524 0.387 0.268
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 3.4 3.4 3.4 3.4
- Min. thickness mm 2.96 2.96 2.96 2.96
o
- Working temperature C 90 90 90 90
o
- Emergency temperature C 130 130 130 130
o
- Short circuit temperature C 250 250 250 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05 0.05 0.05 0.05
9 Separation sheath
- Material PVC
- Min. thickness mm 0.84 0.84 0.92 1.00
Diameter (Approx.) after
9.1 mm 34.8 37.0 39.6 43.4
separation sheath
10 Armour
- Material Galvanized steel wires
- Diameter of wire mm 2.5 (± 5%) 2.5 (± 5%) 2.5 (± 5%) 2.5 (± 5%)
11 Over sheath
- Material Fr-PVC
- Min. thickness mm 2.03 2.11 2.20 2.28
- Color Red

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 60 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


6/10(12)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
3Cx25 3Cx35 3Cx50 3Cx70
12 Reactance of cable (X) W/km 0.1236 0.1178 0.1126 0.1036
13 Capacitance of the cable (C) mF/km 0.2025 0.2237 0.2468 0.2823
14 Current carrying capacity (*) A
In air 136 163 195 240
Buried direct in ground 120 143 168 205
15 50 Hz testing voltage for 5 minutes kV 21
16 Approx. Overall Diameter mm 45 (± 2.5) 47 (± 2.5) 50 (± 3) 54 (± 3)
17 Approx. Cable Weight kg/km 3,840 4,300 4,890 5,870
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 61 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


6/10(12)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
3Cx95 3Cx120 3Cx150 3Cx185 3Cx240
1 TAG/PJ SYMBOL 8264D312 8264D313 8264D314 8264D315 8264D316
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 6/10(12)
4 Conductor
- Material Annealed copper wires
2
- Cross sectional area mm 95 120 150 185 240
- Number of core No. 3 3 3 3 3
- Structure of core Circular compacted
- DC Max. resistance at 200C W/km 0.193 0.153 0.124 0.0991 0.0754
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 3.4 3.4 3.4 3.4 3.4
- Min. thickness mm 2.96 2.96 2.96 2.96 2.96
o
- Working temperature C 90 90 90 90 90
o
- Emergency temperature C 130 130 130 130 130
o
- Short circuit temperature C 250 250 250 250 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05 0.05 0.05 0.05 0.05
9 Separation sheath
- Material PVC
- Min. thickness mm 1.00 1.08 1.08 1.16 1.24
Diameter (Approx.) after
9.1 mm 47.10 50.30 53.3 57.0 62.6
separation sheath
10 Armour
- Material Galvanized steel wires
- Diameter of wire mm 2.5 (± 5%) 3.15 (± 5%)
11 Over sheath
- Material Fr-PVC
- Min. thickness mm 2.37 2.45 2.54 2.62 2.79
- Color Red

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 62 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


6/10(12)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
3Cx95 3Cx120 3Cx150 3Cx185 3Cx240
12 Reactance of cable (X) W/km 0.0989 0.0957 0.0931 0.0897 0.0872
13 Capacitance of the cable (C) mF/km 0.3177 0.3467 0.3756 0.4087 0.4602
14 Current carrying capacity (*) A
In air 292 334 377 430 503
Buried direct in ground 245 277 309 348 401
15 50 Hz testing voltage for 5 minutes kV 21
16 Approx. Overall Diameter mm 58 (± 3) 62 (± 3) 65 (± 3) 69 (±3) 76 (± 4)
17 Approx. Cable Weight kg/km 7,010 8,030 9,110 10,600 13,660
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 63 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-18

18/30(36)kV SINGLE-CORE ARMOURED XLPE


Conductor Size: 150mm2 to 800mm2
INSULATED Fr-PVC SHEATH CABLES

1 6

7
2

8
3
9

4
10

5 11

TAG/PJ SYMBOL: 8267D114, 8267D115, 8267D116, 8267D117, 8267D118, 8267D119, 8267D120, 8267D121

Item Description Material Apply method Remark


1 Conductor Annealed copper wires Circular compacted Class 2 - IEC 60228
2 Binder Semi-conducting tape Taping Manufacturer's decision (*)
3 Conductor screen Semi-conducting compound Extruding
4 Insulation XLPE compound Extruding Simultaneously extruded
5 Insulation screen Semi-conducting compound Extruding
6 Metallic screen Copper tape Taping Overlap taping
7 Binder Binder tape Taping Overlap taping
8 Separation sheath PVC compound Extruding
9 Metallic armour Aluminum wires Stranding
10 Binder Binder tape Taping Overlap taping
11 Oversheath Fr-PVC compound Extruding Color: Red

Note (*): Semi-conducting tape shall be applied over the conductor for size 500sqmm and over
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :
Example: For 1Cx630mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/PVC/AWA/Fr-PVC 630sqmm – 18/30(36)kV* (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 64 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


18/30(36)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx150 1Cx185 1Cx240 1Cx300 1Cx400
1 TAG/PJ SYMBOL 8267D114 8267D115 8267D116 8267D117 8267D118
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 18/30(36)
4 Conductor
- Material Annealed copper wires
2
- Cross sectional area mm 150 185 240 300 400
- Number of core No. 1 1 1 1 1
- Structure of core Circular compacted
0
- DC Max. resistance at 20 C W/km 0.124 0.0991 0.0754 0.0601 0.047
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 8.0 8.0 8.0 8.0 8.0
- Min. thickness mm 7.10 7.10 7.10 7.10 7.10
o
- Working temperature C 90 90 90 90 90
o
- Emergency temperature C 130 130 130 130 130
o
- Short circuit temperature C 250 250 250 250 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05 0.05 0.05 0.05 0.05
9 Separation sheath
- Material PVC
- Min. thickness mm 0.84 0.84 0.84 0.92 0.92
Diameter (Approx.) after
9.1 mm 35.5 37.1 39.4 41.9 44.7
separation sheath
10 Armour
- Material Aluminium wires
- Diameter of wire mm 2.5 (± 5%)
11 Over sheath
- Material Fr-PVC
- Min. thickness mm 1.94 2.03 2.11 2.11 2.20
- Color Red

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 65 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


18/30(36)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx150 1Cx185 1Cx240 1Cx300 1Cx400
12 Reactance of cable (X) flat spaced W/km 0.1922 0.1871 0.1818 0.1774 0.1724
13 Capacitance of the cable (C) mF/km 0.1968 0.2111 0.2318 0.2523 0.2772
14 Current carrying capacity (*) A
In air (trefoil) 449 515 609 698 803
Buried direct in ground (trefoil) 335 377 436 489 549
12 50 Hz testing voltage for 5 minutes kV 63
13 Approx. Overall Diameter mm 46 (± 2.5) 47 (± 2.5) 50 (± 3) 52 (± 3) 55 (± 3)
14 Approx. Cable Weight kg/km 3,300 3,750 4,430 5,150 6,100
Note(*):
Ambient temperature: 36 0 C
0
Ground temperature: 30 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 66 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


18/30(36)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx500 1Cx630 1Cx800
1 TAG/PJ SYMBOL 8267D119 8267D120 8267D121
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 18/30(36)
4 Conductor
- Material Annealed copper wires
2
- Cross sectional area mm 500 630 800
- Number of core No. 1 1 1
- Structure of core Circular compacted
0
- DC Max. resistance at 20 C W/km 0.0366 0.0283 0.0221
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 8.0 8.0 8.0
- Min. thickness mm 7.10 7.10 7.10
o
- Working temperature C 90 90 90
o
- Emergency temperature C 130 130 130
o
- Short circuit temperature C 250 250 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Min. Thickness mm 0.05 0.05 0.05
9 Separation sheath
- Material PVC
- Min. thickness mm 1.00 1.08 1.08
Diameter (Approx.) after
9.1 mm 48.8 52.9 56.9
separation sheath
10 Armour
- Material Aluminium wires
- Diameter of wire mm 2.5 (± 5%) 2.5 (± 5%) 2.5 (± 5%)
11 Over sheath
- Material Fr-PVC
- Min. thickness mm 2.28 2.45 2.54
- Color Red

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 67 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


18/30(36)kV SINGLE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/AWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
1Cx500 1Cx630 1Cx800
12 Reactance of cable (X) flat spaced W/km 0.1692 0.1651 0.1612
13 Capacitance of the cable (C) mF/km 0.3106 0.345 0.3802
14 Current carrying capacity (*) A
In air (trefoil) 910 1045 1191
Buried direct in ground (trefoil) 610 686 762
15 50 Hz testing voltage for 5 minutes kV 63
16 Approx. Overall Diameter mm 60 (± 3) 64 (± 3) 68 (± 3)
17 Approx. Cable Weight kg/km 7,450 9,100 10,990
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 68 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-19

18/30(36)kV THREE-CORE ARMOURED XLPE INSULATED


Conductor Size: 95mm2 to 240mm2
Fr-PVC SHEATH CABLES

1 7

2
8

3
9

10
5

6 11

TAG/PJ SYMBOL: 8267D312, 8267D313, 8267D314, 8267D315, 8267D316

Item Description Material Apply method Remark


1 Conductor Annealed copper wires Circular compacted Class 2 - IEC 60228
2 Conductor screen Semi-conducting compound Extruding
3 Insulation XLPE compound Extruding Simultaneously extruded
4 Insulation screen Semi-conducting compound Extruding
5 Metallic screen Copper tape Taping Overlap taping
6 Filler P.P yarn Stranding Non hygroscopic
7 Binder Binder tape Taping Overlap taping
8 Separation sheath PVC compound Extruding
9 Metallic armour Galvanized steel wires Stranding
10 Binder Binder tape Taping Overlap taping
11 Oversheath Fr-PVC compound Extruding Color: Red

- A narrow colour tape shall be longitudinal applied under copper tape layer of each core to identify core. Colour
shall be Brown, Black, Grey.
- The length in meters shall be printed on oversheath cable.
- Marking method on oversheath: - Printing on oversheath surface with following content :
Example: For 3Cx150mm2 cable.
LS-VINA Cable & System * Flame retardant Cu/XLPE/PVC/SWA/Fr-PVC 3x150sqmm – 18/30(36)kV* (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 69 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


18/30(36)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
3Cx95 3Cx120 3Cx150 3Cx185 3Cx240
1 TAG/PJ SYMBOL 8267D312 8267D313 8267D314 8267D315 8267D316
2 Applied standard IEC 60502-2: 2005, IEC 60332-1
3 Rated voltage Uo/U(Um) kV 18/30(36)
4 Conductor
- Material Annealed copper wires
2
- Cross sectional area mm 95 120 150 185 240
- Number of core No. 3 3 3 3 3
- Structure of core Circular compacted
0
- DC Max. resistance at 20 C W/km 0.193 0.153 0.124 0.0991 0.0754
5 Conductor screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
6 Insulation
- Material XLPE
- Nominal thickness mm 8.0 8.0 8.0 8.0 8.0
- Min. thickness mm 7.10 7.10 7.10 7.10 7.10
o
- Working temperature C 90 90 90 90 90
o
- Emergency temperature C 130 130 130 130 130
o
- Short circuit temperature C 250 250 250 250 250
7 Insulation screen
- Material Semi-conducting XLPE
- Min. thickness mm 0.3 0.3 0.3 0.3 0.3
8 Metallic screen
- Material Copper tape
- Thickness mm 0.05 0.05 0.05 0.05 0.05
9 Separation sheath
- Material PVC
- Min. thickness mm 1.32 1.40 1.40 1.48 1.56
Diameter (Approx.) after
9.1 mm 68.6 71.9 74.9 78.5 83.7
separation sheath
10 Armour
- Material Galvanized steel wires
- Diameter of wire mm 3.15 (± 5%)
11 Over sheath
- Material Fr-PVC
- Min. thickness mm 3.05 3.13 3.22 3.30 3.47
- Color Red

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 70 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


18/30(36)kV THREE-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CABLES
( Cu/XLPE/MS/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
3Cx95 3Cx120 3Cx150 3Cx185 3Cx240
12 Reactance of cable (X) W/km 0.1237 0.1192 0.1153 0.1107 0.1062
13 Capacitance of the cable (C) mF/km 0.1713 0.1841 0.1968 0.2112 0.2318
14 Current carrying capacity (*) A
In air 292 334 377 430 503
Buried direct in ground 245 277 309 348 401
12 50 Hz testing voltage for 5 minutes kV 63
13 Approx. Overall Diameter mm 83 (± 4) 86 (± 4) 89 (± 4) 93 (±4) 99 (± 4)
14 Approx. Cable Weight kg/km 11,340 12,540 13,720 15,370 17,780
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C
Thermal resistivity of soil: 1.5K.m/W
Depth of laying: 0.8m

D R A
N
I 21-DE UILT15
C - 2 0
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 71 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-20
Conductor Size: 2Cx1.5mm2, 4Cx1.5mm2 , 6Cx1.5mm2,
0.6/1kV MULTI-CORE ARMOURED XLPE INSULATED 8Cx1.5mm2 , 10Cx1.5mm2, 12Cx1.5mm2, 20Cx1.5mm2,
Fr-PVC OVER SHEATH CONTROL CABLE 2Cx2.5mm2, 4Cx2.5mm2 , 6Cx2.5mm2, 8Cx2.5mm2, 10Cx2.5mm2,
12Cx2.5mm2, 15Cx2.5mm2, 20Cx2.5mm2
1 5

2 6

3 7

4 8

Number of cores, Not scale


TAG/PJ SYMBOL: 826XD409, 826XD410, 826XD411, 826XD411Y, 826XD411X, 826XD412, 826XD414, 826XD509, 826XD510,
826XD511, 826XD511Y, 826XD511X, 826XD512, 826XD513, 826XD514

Item Description Material Applying method Remark


1 Conductor Annealed copper wires Circular stranded Class 2: IEC 60228
2 Insulation XLPE compound Extruding (*)
3 Filler P.P. yarn Stranding Non hygroscopic
4 Binder Foam tape Taping Overlap taping
5 Inner sheath PVC compound Extruding
6 Metallic armour Galvanized steel wires Stranding
7 Binder Foam tape Taping Overlap taping
8 Oversheath Fr-PVC compound Extruding Color: Black
- (*) Core identification:
+ For less than 5 cores: Core shall be identified by colored XLPE insulation, color shall be :
- 2core: Brown, Blue
- 4core: Brown, Black, Grey, Blue
+ For 5 core and more : Core shall be identified by black ink numbering and lettering on White insulation surface of
each core. Distance between groups shall be not more than 100mm. Identifying method shall be ink jet printing.
Example: For first core: " 1-ONE 1-ONE 1-ONE....."
For second core: " 2-TWO 2- TWO 2- TWO....."
………………..
- The length in meters shall be printed on oversheath cable.
- Marking method on over sheath: - Printing on over sheath surface with following content :
Example for: 20x1.5mm2:
LS - VINA Cable & System * Flame retardant Cu/XLPE/PVC/SWA/Fr-PVC 20x1.5sqmm - 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 72 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV MULTI-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CONTROL CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
2Cx1.5 4Cx1.5 6Cx1.5 8Cx1.5 10Cx1.5 12Cx1.5 20Cx1.5
1 TAG/PJ SYMBOL 826XD409 826XD410 826XD411 826XD411Y 826XD411X 826XD412 826XD414

2 Applied standard IEC 60502-1: 2009, IEC 60332-1


3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
Cross sectional area mm2 1.5 1.5 1.5 1.5 1.5 1.5 1.5
Number of core No. 2 4 6 8 10 12 20
Structure of core Circular stranded
o
Max. DC resistance at 20 C W/km 12.1 12.1 12.1 12.1 12.1 12.1 12.1
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.7 0.7 0.7 0.7 0.7 0.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness at any point mm 0.60 0.60 0.60 0.60 0.60 0.60 0.60
Diameter (Approx.) after
6.1 mm 8.5 9.9 11.7 13.1 14.8 15.3 19.0
inner sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 0.9 (±5%) 1.25 (±5%) 1.6 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.24 1.24 1.24 1.24
9 Reactance of cable (X) W/km 0.1098 0.1098 0.1098 0.1098 0.1098 0.1098 0.1098
10 Capacitance of the cable (C) mF/km 0.1968 0.1968 0.1968 0.1968 0.1968 0.1968 0.1968
11 Current carrying capacity (*) A
In air 25 20 18 16 15 14 12
Buried direct in ground 32 26 23 21 20 18 15
50Hz testing voltage for 5
12 kV 3.5
minutes
13 Approx. Overall Diameter mm 14 (±2) 16 (±2) 17 (±2) 20 (±2) 21 (±2) 22 (±2) 26 (±2)
14 Approx. Cable Weight kg/km 350 440 510 710 810 860 1,300
Note(*):
Ambient temperature: 36 0 C
Ground temperature: 30 0 C

D R A
Thermal resistivity of soil: 1.5K.m/W

N
I 1-DE T15
2
C - 2 0
Depth of laying: 0.8m
UIL
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 73 of 78
VC2182-001-C-002

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV MULTI-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CONTROL CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
2Cx2.5 4Cx2.5 6Cx2.5 8Cx2.5 10Cx2.5 12Cx2.5 15Cx2.5 20Cx2.5
1 TAG/PJ SYMBOL 826XD509 826XD510 826XD511 826XD511Y 826XD511X 826XD512 826XD513 826XD514

2 Applied standard IEC 60502-1: 2009, IEC 60332-1

3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)

4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Number of core No. 2 4 6 8 10 12 15 20
Structure of core Circular stranded
o
Max. DC resistance at 20 C W/km 7.41 7.41 7.41 7.41 7.41 7.41 7.41 7.41
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
o
Working temperature C 90
o
Short circuit temperature C 250

6 Inner sheath
Material PVC
Min. thickness at any point mm 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60
Diameter (Approx.) after
6.1 mm 9.4 10.9 13.0 14.6 16.6 17.2 19.2 21.4
inner sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 0.9 (±5%) 1.25 (±5%) 1.25 (±5%) 1.6 (±5%)

8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.24
9 Reactance of cable (X) W/km 0.1021 0.1021 0.1021 0.1021 0.1021 0.1021 0.1021 0.1021
10 Capacitance of the cable (C) mF/km 0.2372 0.2372 0.2372 0.2372 0.2372 0.2372 0.2372 0.2372
11 Current carrying capacity (*) A
In air 34 30 24 22 21 19 17 16
Buried direct in ground 42 36 30 27 26 24 22 20
50Hz testing voltage for 5
12 kV 3.5
minutes
13 Approx. Overall Diameter mm 15 (±2) 17 (±2) 19 (±2) 21 (±2) 23 (±2) 24 (±2) 26 (±2) 29 (±2)
14 Approx. Cable Weight kg/km 410 510 730 840 970 1,050 1,360 1,600
Note(*):
Ambient temperature: 36 0 C

D R A
Ground temperature: 30 0 C

N
I 21-DE UILT15
Thermal resistivity of soil: 1.5K.m/W
C - 2 0
Depth of laying: 0.8m
AS B
Vendor Doc. No.
NSRP Complex Project Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 74 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-21

0.6/1(1.2)kV MULTI-PAIR ARMOURED XLPE


Conductor Size: 2Px2.5mm2, 3Px2.5mm2
INSULATED Fr-PVC SHEATH CONTROL CABLES

1 5

2 6

3 7

4 8
Number of pairs, Not scale

TAG/PJ SYMBOL: 826XD511P, 826XD510P

Item Description Material Applying method Remark


1 Conductor Annealed copper wires Circular stranded Class 2-IEC 60228

2 Insulation XLPE compound Extruding Colour: Brown, Blue

3 Filler P.P yarn Stranding Non hygroscopic


4 Binder Foam tape Taping Overlap taping

5 Inner sheath PVC compound Extruding

6 Metallic armour Galvanized steel wires Stranding

7 Binder Foam tape Taping Overlap taping

8 Over sheath Fr-PVC compound Extruding Color: Black

* Core identification:
Ink jet printing with white ink on insulation surface of Brown and Blue cores. Distance between groups shall be not
more than 100mm.
Example: For first core: " 1-ONE 1-ONE 1-ONE....."
For second core: " 2-TWO 2-TWO 2-TWO....."
............................
* Pairing: 1 Brown core "1-ONE" and 1 Blue core "1-ONE" shall be paired.
1 Brown core "2-TWO" and 1 Blue core "2-TWO" shall be paired.
..................
* The length in meters shall be printed on oversheath cable.
* Marking method on oversheath: - Printing on over sheath surface with following content :
Example for: 2Px2.5mm2:
LS - VINA Cable & System * Flame retardant Cu/XLPE/PVC/SWA/Fr-PVC 2Px2.5sqmm - 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 75 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV MULTI-PAIR ARMOURED XLPE INSULATED Fr-PVC SHEATH CONTROL CABLES
(Cu/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
2Px2.5 3Px2.5
1 TAG/PJ SYMBOL 826XD510P 826XD511P

2 Applied standard IEC 60502-1: 2009, IEC 60332-1


3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 2.5 2.5
Number of pair No. 2 3
Structure of core Circular stranded
o
Max. DC resistance at 20 C W/km 7.41 7.41
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness at any point mm 0.60 0.60
Diameter (Approx.) after inner
6.1 mm 14.0 15.0
sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 1.25 (±5%) 1.25 (±5%)

8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24
9 Reactance of cable (X) W/km 0.1021 0.1021
10 Capacitance of the cable (C) mF/km 0.2372 0.2372
11 Current carrying capacity (*) A
In air 30 24
Buried direct in ground 36 30
12 50Hz testing voltage for 5 minutes kV 3.5
13 Approx. Overall Diameter mm 20 (±2) 22 (±2)
14 Approx. Cable Weight kg/km 720 850
Note(*):
Ambient temperature: 36 0 C

D R A
Ground temperature: 30 0 C

I N C - 2 15
Thermal resistivity of soil: 1.5K.m/W
0
E ILT of laying: 0.8m
21-D BUDepth
AS
Vendor Doc. No.
NSRP Complex Project Rev.0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 76 of 78
VC2182-001-C-001

CROSS SECTIONAL DRAWING


DRAWING NO. : VV2182-001-C-001-22
Conductor Size: 2Cx1.5mm2, 4Cx1.5mm2 , 6Cx1.5mm2, 8Cx1.5mm2,
0.6/1kV MULTI-CORE ARMOURED PVC
10Cx1.5mm2, 12Cx1.5mm2, 20Cx1.5mm2, 2Cx2.5mm2, 4Cx2.5mm2,
INSULATED Fr-PVC OVER SHEATH CABLE
6Cx2.5mm2, 8Cx2.5mm2, 10Cx2.5mm2, 12Cx2.5mm2, 20Cx2.5mm2

1 6

2
7

8
4

5 9
Number of cores, Not scale
TAG/PJ SYMBOL: 826XTD409, 826XTD410, 826XTD411, 826XTD411Y, 826XTD411X, 826XTD412, 826XTD414, 826XTD509,
826XTD510, 826XTD511, 826XTD511Y, 826XTD511X, 826XTD512, 826XTD514
Item Description Material Applying method Remark
1 Conductor Annealed copper wire Circular stranded Class 2 - IEC 60228

2 Binder Mica tape(s) Taping

3 Insulation XLPE compound Extruding (*)

4 Filler P.P yarn Stranding Non hygroscopic

5 Binder Foam tape Taping Overlap taping

6 Inner sheath PVC compound Extruding

7 Metallic armour Galvanized steel wires Stranding

8 Binder Foam tape Taping Overlap taping

9 Oversheath Fr-PVC compound Extruding Color: Black


- (*) Core identification:
+ For less than 5 cores: Core shall be identified by colored XLPE insulation, color shall be:
- 2core: Brown, Blue
- 4core: Brown, Black, Grey, Blue
+ For 5 core and more : Core shall be identified by black ink numbering and lettering on White insulation surface of
each core. Distance between groups shall be not more than 100mm. Identifying method shall be ink jet printing.
Example: For first core: " 1-ONE 1-ONE 1-ONE....."
For second core: " 2-TWO 2- TWO 2- TWO....."
………………..
- The length in meters shall be printed on oversheath cable.
- Marking method on over sheath: - Printing on over sheath surface with following content :
Example for: 20x2.5mm2:
LS-VINA Cable & System * Fire resistant cable Cu/XLPE/PVC/SWA/Fr-PVC 20x2.5sqmm – 0.6/1kV * (Year)

D R A
N
I 21-DE UILT15
C - 2 0
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 77 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV MULTI-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CONTROL CABLES
(Cu/Mica/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No Technical characteristics Unit
2Cx1.5 4Cx1.5 6Cx1.5 8Cx1.5 10Cx1.5 12Cx1.5 20Cx1.5
1 TAG/PJ SYMBOL 826XTD409 826XTD410 826XTD411 826XTD411Y 826XTD411X 826XTD412 826XTD414

2 Applied standard IEC 60502-1: 2009, IEC 60331-21

3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)

4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 1.5 1.5 1.5 1.5 1.5 1.5 1.5
Number of core No. 2 4 6 8 10 12 20
Structure of core Circular stranded
o
Max. DC resistance at 20 C W/km 12.1 12.1 12.1 12.1 12.1 12.1 12.1
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.7 0.7 0.7 0.7 0.7 0.7
o
Working temperature C 90
o
Short circuit temperature C 250

6 Inner sheath
Material PVC
Min. thickness at any point mm 0.60 0.60 0.60 0.60 0.60 0.60 0.60
Diameter (Approx.) after
6.1 mm 9.6 11.2 13.3 15.0 17.1 17.7 22.0
inner sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 0.9 (±5%) 1.25 (±5%) 1.6 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.24 1.24 1.24 1.24
9 Reactance of cable (X) W/km 0.1203 0.1203 0.1203 0.1203 0.1203 0.1203 0.1203
10 Capacitance of the cable (C) mF/km 0.1598 0.1598 0.1598 0.1598 0.1598 0.1598 0.1598
11 Current carrying capacity (*) A
In air 25 20 18 16 15 14 12
Buried direct in ground 32 26 23 21 20 18 15
50Hz testing voltage for 5
12 kV 3.5
minutes
13 Approx. Overall Diameter mm 15 (±2) 17 (±2) 19 (±2) 21 (±2) 23 (±2) 24 (±2) 29 (±2)
14 Approx. Cable Weight kg/km 400 490 590 810 920 990 1,500
Note(*):
Ambient temperature: 36 0 C

D R A
Ground temperature: 30 0 C

N C
Thermal resistivity of soil: 1.5K.m/W
I 21-DE UILT15
- 2 0
Depth of laying: 0.8m
AS B
NSRP Complex Project Vendor Doc. No. Rev. 0

Purchaser Doc. No.


Title: Specification for Power and Control Cables Page 78 of 78
VC2182-001-C-001

CABLE SPECIFICATION AND DATA SHEET


0.6/1(1.2)kV MULTI-CORE ARMOURED XLPE INSULATED Fr-PVC SHEATH CONTROL CABLES
(Cu/Mica/XLPE/PVC/SWA/Fr-PVC)

Cable size (mm2)


No. Technical characteristics Unit
2Cx2.5 4Cx2.5 6Cx2.5 8Cx2.5 10Cx2.5 12Cx2.5 20Cx2.5
1 TAG/PJ SYMBOL 826XTD509 826XTD510 826XTD511 826XTD511Y 826XTD511X 826XTD512 826XTD514

2 Applied standard IEC 60502-1: 2009, IEC 60331-21


3 Rated voltage (Uo/U(Um)) kV 0.6/1(1.2)
4 Conductor
Material Annealed copper wires
2
Cross sectional area mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Number of core No. 2 4 6 8 10 12 20
Structure of core Circular stranded
o
Max. DC resistance at 20 C W/km 7.41 7.41 7.41 7.41 7.41 7.41 7.41
5 Insulation
Material XLPE
Nominal thickness mm 0.7 0.7 0.7 0.7 0.7 0.7 0.7
o
Working temperature C 90
o
Short circuit temperature C 250
6 Inner sheath
Material PVC
Min. thickness at any point mm 0.60 0.60 0.60 0.60 0.60 0.60 0.60
Diameter (Approx.) after
6.1 mm 10.5 12.3 14.7 16.6 18.9 19.5 24.4
inner sheath
7 Armour
Material Galvanized steel wires
Diameter of wires mm 0.9 (±5%) 1.25 (±5%) 1.6 (±5%)
8 Over sheath
Material Fr-PVC
Color Black
Min. thickness at any point mm 1.24 1.24 1.24 1.24 1.24 1.24 1.24
9 Reactance of cable (X) W/km 0.1114 0.1114 0.1114 0.1114 0.1114 0.1114 0.1114
10 Capacitance of the cable (C) mF/km 0.1903 0.1903 0.1903 0.1903 0.1903 0.1903 0.1903
11 Current carrying capacity (*) A
In air 34 30 24 22 21 19 16
Buried direct in ground 42 36 30 27 26 24 20
50Hz testing voltage for 5
12 kV 3.5
minutes
13 Approx. Overall Diameter mm 16 (±2) 18 (±2) 21 (±2) 23 (±2) 25 (±2) 26 (±2) 32 (±2.5)
14 Approx. Cable Weight kg/km 450 570 800 960 1,090 1,190 1,830
Note(*):
Ambient temperature: 36 0 C

D R A
Ground temperature: 30 0 C

I N C - 2 15
Thermal resistivity of soil: 1.5K.m/W
0
E ILTof laying: 0.8m
21-D BUDepth
AS

Das könnte Ihnen auch gefallen