Sie sind auf Seite 1von 2

Programmable Trip Point Function #1 Disabled

Trigger Condition
Programmable Trip Point Function #1 0 %
Percentage Threshold
Programmable Trip Point Function #1 0 %
Hysteresis Percentage
Programmable Trip Point Function #1 Trip 0 sec
Activation Delay Time
Programmable Trip Point Function #1 Trip 0 sec
Deactivation Delay Time
Programmable Trip Point Function #2 Disabled
Trigger Condition
Programmable Trip Point Function #2 0 %
Percentage Threshold
Programmable Trip Point Function #2 0 %
Hysteresis Percentage
Programmable Trip Point Function #2 Trip 0 sec
Activation Delay Time
Programmable Trip Point Function #2 Trip 0 sec
Deactivation Delay Time
Engine Serial Number Not Programmed
Display Pressure Units Configuration kPa
Display Temperature Units Configuration Degrees Centigrade (Celsius)
Display Volume Units Configuration liters

C15 Genset (FTH12287)


Parameter Value
Equipment ID NOT PROGRAMMED
Engine Serial Number FTH12287
ECM Serial Number 18076876JL
Software Group Part Number 5241151-00
Software Group Release Date MAR17
Software Group Description C15-MEUI-ACERT-A4

Logged Diagnostic Codes [Diagnostic Clock = 0.8772 hours] - C15 Genset (FTH12287)
Code Description Occ. First Last
No Logged
Diagnostic
Codes

Logged Event Codes [Diagnostic Clock = 0.8772 hours] - C15 Genset (FTH12287)
Code Description Occ. First Last
No Logged
Events

Active Diagnostic Codes - C15 Genset (FTH12287)


Code Description
No Active
Codes

Active Event Codes - C15 Genset (FTH12287)


Code Description
No Active
Events

Current Totals - C15 Genset (FTH12287)


Description Value Unit
Total Fuel 11 gal
Total Time 0 hours
Engine Starts 8
Average Fuel Rate Based 43 %
Percent Engine Load Factor

Configuration - C15 Genset (FTH12287)


Description Value Unit
Equipment ID NOT PROGRAMMED
Engine Serial Number FTH12287
ECM Serial Number 18076876JL
Software Group Part Number 5241151-00
Software Group Release Date MAR17
Software Group Description C15-MEUI-ACERT-A4
Rating Number 10
Rated Frequency 50 Hz
Rated Engine Speed 1500 rpm
Rated Real Genset Power Unavailable Parameter
Rated Apparent Genset Power 550 kVA
Rating Configuration Low BSFC
Test Spec 0K71090K7108
Engine Acceleration Rate 500 rpm/s
Low Idle Speed 1100 rpm
Engine Speed Droop 0.0 %
Remote Throttle Control Min Speed 125 rpm
Remote Throttle Control Max Speed 125 rpm
Crank Terminate RPM 400 rpm
Droop Mode Selection Isochronous
Ether Solenoid Configuration Not Installed
Fuel Filter Differential Pressure Switch Unavailable
Config
Engine Oil Temperature Sensor Installation Not Installed
Status
Desired Speed Input Configuration CAN Input
Secondary Desired Speed Input Not Installed
Configuration
Fuel Enable Input Configuration Switch to Ground
Secondary Fuel Enable Input Enable Enabled
Status
Droop/Isochronous Switch Enable Disabled
Emergency Shutdown Override Switch Not Installed
Installation Status
Emergency Shutdown Override Input Switch to Ground
Configuration
Governor Gain Factor #1 13107

Das könnte Ihnen auch gefallen