SECTION 16721

FIRE ALARM SYSTEM

PART 1 – GENERAL

1.01 DESCRIPTION:

(NTS: Modify to suit project.)


A. Provide, test, and place into operating condition an electrically operated, microprocessor
based, UL listed, four-wire, analog/addressable, electrically supervised fire detection and
evacuation system as indicated and specified.

(NTS: Verify drawings use same abbreviations.)


B. The System shall include, but not be limited to: Fire Alarm Control Panel (FACP) (or
panels required for each building), remote Annunciator Command Center (ACC), power
supplies and fire alarm initiating and notification devices including addressable monitor
and control modules.

C. The fire alarm system shall include conduit, wire, fittings, and accessories required to
provide a complete operating system.

(NTS: For large facilities, consider a network system.)


D. Connect fire alarm control panels in a local area network via fiber optic cable for data
communication with other areas. Display local information at each network node and the
entire network monitored at the network remote annunciator panel.

E. All charges and fees required by the local Authority having jurisdiction (AHJ) to inspect
the installation and implement fire alarm notification are to be included by the Contractor
under this section at no additional cost to the Owner.

(NTS: Where voice evacuation system is required, include the following:)


F. System shall include a voice evacuation panel in compliance with NFPA 72
requirements.

G. The fire alarm system shall be tied into the local Fire Alarm System via a telephone
transmitted signal.

H. Prior to the installation of the system, the manufacturer of the system and system installer
shall obtain from the local AHJ an Application For Fire Alarm Service, and a copy of all
local requirements.

Libya Infrastructure Master Spec 16721-1 20-Nov-08


1.02 RELATED WORK:

A. Section 15510: Sprinkler Fire Protection

B. Section 15806: Heating, Ventilating and Air Conditioning

C. Section 16050: Electrical Work - General

D. Section 16110: Electrical Raceway Systems

E. Section 16120: Electric Wires and Cables

F. Section 16450: Grounding

1.03 REFERENCES - As specified herein or equivalent IEC or BS Standards:

A. National Fire Protection Association (NFPA):

1. NFPA-70: National Electrical Code (NEC)

2. NFPA-72: National Fire Alarm Code

3. NFPA-101: Life Safety Code

4. NFPA-90A: Standard for the Installation of Air Conditioning and Ventilating


Systems

B. Factory Mutual (FM):

1. FM P7825: Approved Guide

(NTS: Use ASME code for buildings with elevators.)


C. ASME International (ASME):

1. ASME A17.1: Safety Code for Elevators and Escalators

D. Institute of Electrical and Electronics Engineers (IEEE):

1. IEEE C62.41.1: IEEE Guide on the Surges Environment in Low-Voltage (1000


V and Less) AC Power Circuits.

2. IEEE C62.41.2: IEEE Recommended Practice on Characterization of Surges in


Low-Voltage (1000 V and Less) AC Power Circuits.

E. Underwriters' Laboratories (UL)

Libya Infrastructure Master Spec 16721-2 20-Nov-08


1. Fire Protection Equipment Directory

2. UL 268: Standard for Smoke Detectors for Fire Alarm Signaling Systems

3. UL 464: Standard for Audible Signal Appliances

4. UL 1971: Standard for Visual Signaling Appliances

5. UL 864: Control Units for Fire Protective Signaling Systems

6. UL 1971: Signaling Devices for the Hearing Impaired

F. Equivalent British/European codes and standards may be used; however, the equivalency
shall be demonstrated and submitted by the Contractor and approved by the CM/CS.

1.04 SYSTEM DESCRIPTION:

A. Type of System:

1. Fire Alarm System: The fire alarm system shall operate as a low voltage
analog/addressable type system and shall automatically initiate fire alarm signals
whenever any manual or automatic fire detecting devices are placed into an alarm
mode. The system shall indicate areas of alarm and sound local alarms. Initiating
loops and notification loops shall be wired as four-wire class A loops. Initiating
loops and notification loops shall be complete with necessary switches, meters,
relays, pilot lights, surge arresters and addressable modules as required. A
minimum of one thermal cut-out or fuse and surge arrestor for every notification
circuit shall be provided. An annunciator shall indicate the specific location of
the fire.

2. The system shall be capable of operating with a single break or ground fault
condition in the initiating or alarm sounding circuits.

(NTS: Identify type of evacuation alarms that are required. Select one of two paragraphs that
follow.)
3. Evacuation Alarms: Coded evacuation alarm: A fire alarm signal shall be
employed for notifying the occupants to evacuate.

3. Evacuation Alarms: Speaker circuits shall be arranged such that there is a


minimum of one speaker circuit per floor. Loss of any speaker circuit shall not
cause the loss of any other speaker circuit.

4. Trouble Signals: During abnormal conditions such as an open wire or a ground


fault, or where both conditions occur at one point, the system shall be capable of
automatically transmitting clear, intelligible trouble signals.

Libya Infrastructure Master Spec 16721-3 20-Nov-08


5. Power Supply for the System: A dedicated branch-circuit for supplying power to
the alarm system shall be provided for the Fire Alarm Control Panel (FACP). The
branch circuits shall be automatically energized from an auxiliary electrical power
system during failures of the normal power supply. Provide battery backup power
consisting of rechargeable, sealed type storage batteries and battery charger.

6. The system shall interface to HVAC system and other building systems as shown
on the Contract Drawings and required by applicable codes to provide all required
monitoring and control functions.

B. Sequence of Operation:

1. When a fire-alarm condition is detected by one of the system initiating devices,


the following functions shall immediately occur:

a. Automatic programs assigned to the alarm point shall be executed and the
associated indicating devices and relays activated.

(NTS: Select one of the two paragraphs below to suit project.)


b. Fire-alarm notification devices in the building shall operate.

b. An exterior strobe at the building in alarm shall energize and the fire alarm
notification devices in only that building shall operate.

c. The system alarm on the Fire Alarm Control Panel and Remote
Annunciator Command Center will indicate condition.

d. The alarm shall be signaled automatically to the local Central Station


Monitoring System

e. Shutdown of HVAC equipment and associated exhaust and pressurization


operations to be initiated.

2. When a trouble condition is detected by one of the system initiating or indicating


circuits, the following functions shall immediately occur:

a. System Trouble will be indicted on FACP and Annunciator Command


Center.

b. A local trouble-sounding device in the FACP and Annunciator Command


Control shall be activated. This sound shall be distinct from the alarm
sound.

c. The appropriate message will appear on the LCD display at the FACP and
Annunciator Command Center.

Libya Infrastructure Master Spec 16721-4 20-Nov-08


1.05 SUBMITTALS:

A. Shop Drawings: Submit the following in accordance with Section 01300 - Submittals:

1. Copy of this specification section with addenda and all referenced specification
sections with addenda check-mark each paragraph to indicate specification
compliance or indicate deviation and reason for deviation.

a. Failure to include a copy of the marked-up specification sections will


result in return of the entire submittal with no further review and
consideration.

2. Installer and system supplier qualifications and list of three similar projects with
name and phone number of contact person.

3. Complete list of equipment and materials, including manufacturer's descriptive


and technical literature, catalog cuts. Shop drawings shall contain complete
conduit riser diagrams, wiring diagrams, and schematic diagrams for the
equipment furnished. Riser diagrams shall identify cable sizes and quantities,
equipment layout, and any other details required to demonstrate that the system
has been coordinated and will properly function as a unit.

4. Manufacturer’s printed installation instructions.

5. Battery capacity calculations to demonstrate that the battery size selected is a


minimum of 125% of the calculated requirement. Calculation to include
supervisory power requirements for all equipment, and alarm power requirements
for all equipment.

(NTS: For a voice evacuation system, include the following:)


a. Calculations to show amplifiers have sufficient capacity to simultaneously
drive fire alarm speakers at their ½ watt tap plus 50 percent spare capacity.

6. Wiring diagrams from the fire alarm system integrator or supplier differentiating
clearly between factory and field installed wiring. Include diagrams for
equipment and for system with all terminals and interconnections identified.
Identify all diagrams to be specific to this project and distinguish between field
and factory wiring.

B. Spare Parts Data:

1. After approval of the list of shop drawings, and not later than six months prior to
the date of substantial completion, furnish copies of spare parts data for each
different item of materials and equipment specified. The data shall include a
complete list of parts and supplies with current unit prices and source of supply, a
list of supplies that are either normally furnished at no extra cost with the

Libya Infrastructure Master Spec 16721-5 20-Nov-08


purchase of the equipment, or specified to be furnished in accordance with
paragraph Special Tools and Spare Parts and a list of additional items
recommended by the manufacturer to assure efficient operation for a period of
120 days.

C. Operating and Maintenance Instruction Manuals:

1. At end of project, submit operating instruction manuals as specified in Section


01730, outlining the step-by-step procedures required for system startup and
operation shall be furnished. The instructions shall include the manufacturer's
name, model number, service manual parts list and brief description of all
equipment and their basic operating features.

2. Maintenance instructions manuals outlining maintenance procedures shall be


furnished. The manual shall include a troubleshooting guide listing possible
breakdown and repairs and a simplified connection wiring diagram for the system
as installed. Provide the names, addresses, and telephone numbers of service
organizations that provide technical assistance and carry stock of repair parts for
the system to be furnished.

3. Performance Test Reports: Upon completion of the installed system the submit in
booklet form field tests performed to prove compliance with the specified
performance criteria. Each test report shall indicate the final position of controls.

D. Submit Certificate of Compliance, signed by manufacturers of fire alarm system


components certifying that their products comply with specified requirements.

E. Submission to Authorities Having Jurisdiction: In addition to routine submission of the


above material, make an identical submission to the authorities having jurisdiction.
Include copies of annotated Contract Drawings as needed to depict component locations
to facilitate review. Upon receipt of comments from the authorities having jurisdiction,
submit them for review. Resubmit if required to make clarifications or revisions to
obtain approval.

1.06 QUALITY ASSURANCE:

A. Provide in accordance with Section 01400 and as specified.

B. Standard Products: Material and equipment shall be the latest standard products of a
single manufacturer regularly engaged in the manufacture of the product for the 5 years
as a minimum.

C. Qualifications of the installer before commencing work: Submit information


demonstrating that the supplier has successfully installed fire alarm systems of the same
scope, type and design as specified.

Libya Infrastructure Master Spec 16721-6 20-Nov-08


1. Submit copies of all required local Licenses and Bonds.

2. Employ on staff a minimum of one full time professional engineer.

3. Certify that the completed system conforms with UL standards upon completion
of the installation.

4. Ongoing maintenance and testing shall be provided to the Owner under a


maintenance contract to maintain the UL listing.

D. Nameplates: The components of equipment shall have the manufacturer's name, address,
type or style, and catalog number on a plate securely attached to the equipment.

E. Tags: Tags with stamped identification number shall be furnished for keys and locks.
Tags shall be furnished to identify cable and conduit runs, wiring circuits, and all spare
parts furnished for Authority's stock to maintain the system.

F. Keys and Locks: All locks shall be keyed alike.

G. Verification of Dimensions: Become familiar with details of the work and verify
dimensions in the field.

H. Compliance: The fire detection and internal alarm system shall be configured in
accordance with NFPA 72. The equipment furnished shall be compatible and be UL
listed or FM approved or approved or listed by a nationally recognized testing laboratory
in accordance with the applicable NFPA standards.

I. Accessibility: Enclosures shall be provided with ample gutter space to allow proper
clearance between the enclosure and live parts of the panel equipment. If more than one
modular unit is required to form a control panel, the units shall be installed in a single
cabinet large enough to accommodate all units, and allow ample gutter space for
interconnections of panels and field wires.

J. Verify conduit size and wire quantity, size, and type are suitable for the equipment
supplied. Review the proper installation of each type of device with the equipment
supplier.

K. Review selected arrangement with local fire authority for conformance with local
requirements.

L. Onsite Technician Services:

1. Provide the services of a representative or technician certified by the


manufacturer of the system, experienced in the installation and operation of the
type of system provided.

Libya Infrastructure Master Spec 16721-7 20-Nov-08


2. The technician shall supervise installation, software documentation, adjustment,
preliminary testing, final testing and certification of the system, and Underwriters
Laboratories listing certification requirements.

3. The technician shall provide the required instruction to the Owner’s personnel in
the system operation, maintenance and programming.

4. Provide services of the manufacturer's service representative during installation,


startup and testing, for a period of three (3) working day(s) plus travel where a
working day is equivalent to 8 hours.

1.07 DELIVERY, STORAGE AND HANDLING:

A. Provide in accordance with Section 01610 and as specified herein.

B. Equipment placed into storage shall be protected from the weather, humidity and
temperature variations, dirt, dust, and other contaminants.

1.08 SEISMIC DESIGN REQUIRMENTS:

A. Conform to the requirements indicated on the structural drawings and as specified in


Section 01900.

B. It shall be the responsibility of the manufacturer and supplier along with the Electrical
Contractor to conform to the seismic design requirements for this project and for the
work of this specification section.

PART 2 - PRODUCTS

2.01 MANUFACTURERS:

A. Notifier

B. Honeywell

C. Simplex - Grinnel

D. Or equal.

2.02 MATERIAL AND EQUIPMENT:

A. General Product Description:

1. Each Fire-Alarm Control Panel (FACP) shall be capable of fire detection,


equipment supervision and control, alarm management, and historical data

Libya Infrastructure Master Spec 16721-8 20-Nov-08


collection and archiving.

(NTS: The system design to include Master Fire Alarm Control Panel at each building.)
B. Communications:

1. The FACP shall have sufficient memory to support its operating system and
databases including:

a. Fire management

b. Alarm management

c. Historical/Trend Data

d. Maintenance Support Applications

e. Custom Processes

f. Operator/IO

2. Communication Ports: Provide data communication ports for simultaneous


operation of devices such as industry standard printers, programming terminal,
PC, transponder and annunciator.

3. Integrated On-Line Diagnostics: The FACP shall continuously perform self-


diagnostics, communication diagnostics and diagnostics on all subsidiary
equipment.

4. Surge and Transient Protection: Isolation shall be provided at all field point
terminations to suppress induced voltage transients where required. Surge
arrestors shall provide protection from all non-signal electrical surges that could
cause damage to the equipment. Line surge arrestors shall be isolated from the
electrical circuitry that they are protecting.

C. System Software Features:

1. Provide software to form a complete operating system as described in this


specification shall be provided.

2. The software programs specified in this section shall be provided as an integral


part of the panel and shall not be dependent upon any higher level computer for
execution.

3. Alarm Management: Alarm management shall be provided to monitor, buffer,


and direct alarm reports to operator devices and memory files. The control unit
shall have capability of performing alarm analysis and signaling. At no time shall

Libya Infrastructure Master Spec 16721-9 20-Nov-08


the panel’s ability to report alarms be affected by operator activity.

4. Status Change Report: All alarm or point change reports shall include the point’s
English language description, and the time and date of occurrence.

5. Prioritization: The user shall be able to define the specific system reaction for
each point. Alarms shall be prioritized to minimize nuisance reporting and to
speed operator response to critical alarms. A minimum of three priority levels
shall be provided.

6. Report Routing: Alarm reports shall be archived for future recall.

7. Alarm Messages: In addition to the point’s description and the time and date, the
user shall be able to print, display or store a custom alarm message to more fully
describe the alarm condition or direct operator response.

8. The FACP shall be capable of storing a library of at least 900 events.

9. History Mode:

a. The system shall be able to store and display at least 900 system events
that have occurred in a non-volatile buffer memory. Display of these
events shall be accomplished on-site through the use of the front control
panel indicators and switches.

10. Field Configurable:

a. The system shall be fully configurable and expandable at the Authority’s


site without the need for EPROM programmers. All configuration shall be
accomplished through downloading of programs from a computer.
Reconfiguration shall not require knowledge of any programming
languages or require any special training. All programs shall be stored in
non-volatile memory. Entry into program mode shall require a special key
and a special password entered into the front panel.

D. Analog Device Interface:

1. The Analog Device Interface will be capable of supporting devices as indicated


on drawings with 25% spare slots for future devices.

2. The analog addressable device interface shall contain its own microprocessor
control.

3. The analog addressable device interface shall communicate and provide power to
all devices on its loop over a single pair of wires. The fire-alarm system shall

Libya Infrastructure Master Spec 16721-10 20-Nov-08


function as a Class A system.

4. The analog interface board shall receive analog information from intelligent
detectors and shall process this information to determine normal, alarm, or trouble
conditions. The analog information may also be used for automatic test and
determination of maintenance requirements.

5. Communication with connected devices shall be performed every 5 seconds or


less. Average time to detect an alarm shall be less than 10 seconds (longer for
alarm verification detectors).

E. Notification Appliance Circuit:

1. The FACP shall provide supervised Class A notification circuits with minimum of
50 percent spare capacity for future devices. The circuit capacity shall be 2.0
amperes maximum per circuit, maximum of 8.0 amperes from the FACP’s power
supply. If a short-circuit trouble occurs on one of the circuits it will not affect the
operation of the remaining circuits.

(NTS: Provide the following for a voice evacuation system.)


F. Amplifiers, Preamplifiers, Tone Generators:

1. Any amplifiers, preamplifiers, tone generators, digitalized voice generators, and


other hardware necessary for a complete, operational, textual audible circuit
conforming to NFPA 72 shall be housed in a fire alarm control unit, terminal
cabinet, or in the fire alarm control panel. The system shall automatically operate
and control all building fire alarm speakers except those installed in the stairs and
within elevator cabs. The speakers in the stairs and elevator cabs shall operate
only when the microphone is used to deliver live messages. Each amplifier shall
have two channels; one to broadcast a message and the other for paging.

a. Construction:

(1) Amplifiers shall utilize computer grade solid state components and
shall be provided with output protection devices sufficient to
protect the amplifier against any transient up to 10 times the
highest rated voltage in the system.

b. Inputs:

(1) Each system shall be equipped with separate inputs from the tone
generator, digitalized voice driver and panel mounted microphone.
Microphone inputs shall be of the low impedance, balanced line
type. Both microphone and tone generator input shall be
operational on any amplifier.

Libya Infrastructure Master Spec 16721-11 20-Nov-08


c. Tone Generator:

(1) The tone generator shall be of the modular, plug-in type with
securely attached labels to identify the component as a tone
generator and to identify the specific tone it produces. The tone
generator shall produce a slow whoop tone, which shall slowly
ascend from low (500 hertz) to high (1200 hertz), and shall be
constantly repeated until interrupted by either the digitalized voice
message, the microphone input, or the alarm silence mode as
specified. Each slow whoop cycle shall last approximately 4
seconds. The tone generator shall be single channel with an
automatic backup generator per channel such that failure of the
primary tone generator cause the backup generator to automatically
take over the functions of the failed unit and also causes transfer of
the common trouble relay.

d. Protection Circuits:

(1) Each amplifier shall be constantly supervised for any condition


which could render the amplifier inoperable at its maximum
output. Failure of any component shall cause automatic transfer to
a designated backup amplifier, illumination of a visual “amplifier
trouble” indicator on the control panel, appropriate logging of the
condition of the system printer, and other actions for trouble
conditions as specified.

G. Function Relays:

1. The FACP shall provide of Form “C” relay contacts, quantity as required, rated at
1 A at 220 VAC. These relays may be programmed to activate on alarm from any
initiating zone or any combination of initiating zones, analog devices or
addressable modules.

H. Central Processing Unit (CPU):

1. The CPU shall communicate with the operator interface, LCD display, LED
display and control other modules in the panel. Removal, disconnection or failure
of any control panel shall be detected and reported by the Central Processing Unit.

2. The CPU shall contain and execute all control-by-event programs for specific
action to be taken if a fire situation is detected in the system. Such control-by-
event programs shall be held in non-volatile programmable memory, and shall not
be lost even if system primary and secondary power failure occurs. The CPU
shall also provide a real time clock for time annotation on the display and remote
optional printer.

Libya Infrastructure Master Spec 16721-12 20-Nov-08


I. Operator Display:

1. The operator display shall provide controls and indicators used by the system
operator. The display shall contain, and display as needed, custom alphanumeric
message for all intelligent detectors and addressable modules. Such message
information shall be stored in programmable non-volatile memory.

2. The display board shall provide an 80-character alphanumeric Liquid Crystal


Display (LCD). It shall also have 24 LEDs for system indication such as AC
POWER; SYSTEM ALARM; SYSTEM TROUBLE; ACKNOWLEDGE;
SIGNAL SILENCE, etc.

3. Factory programmable system indications and keys shall be available for unique
functions. Keys shall be referred to as “Hot Keys”.

4. The Display Interface shall provide a 15-key touch keypad with control capability
to command all system functions, and entry of any numeric information. The
keypad shall include means to enter a minimum of two different passwords to
prevent unauthorized manual control.

5. Ground fault indication shall be displayed on a system and initiating zone basis.

J. Communications Ports:

1. The system shall provide the following interfaces:

a. One port for remote annunciator command center.

b. One port for central station communication.

c. One port for service and field programming.

d. One port for Printer.

K. Mechanical Design:

1. The Fire Alarm Control Panel (FACP) shall be housed in a cabinet designed for
mounting recessed or directly to a wall or vertical surface. The back box and door
shall be constructed with provisions for electrical conduit connections. The door
shall provide a key lock and shall include an opening for viewing.

2. The FACP shall be modular in structure for ease of installation and maintenance.

L. One Person Test Feature:

Libya Infrastructure Master Spec 16721-13 20-Nov-08


1. The control unit shall include a special one person test feature, which will allow a
single person to test all initiating devices and indicating appliance in a system
without returning to the panel to reset the system. A special password shall be
required to enter the test mode. The service-technician shall be able to re-select
the initiating and indicating circuits that are to be included in the one person test
mode. The Walk-Test shall include a special audible indication that a trouble has
been detected on an analog device, for the service-technician to check proper
system wiring.

M. Provide addressable monitor modules to interface manual FACP to stations and other
non-addressable detection components as required. The modules shall be capable of
being mounted in a 4 x 4 x 2 1/8-inch junction box.

N. Provide addressable control modules to interface FACP to fire alarm reporting panel,
audible and visual devices and other control components as required. The modules shall
be capable of being mounted in a 4 x 4 x 2 1/8-inch junction box.

O. Fire-Alarm Initiating Devices:

1. Addressable Devices: All addressable detectors shall:

a. Provide a test means whereby they will simulate an alarm condition and
report that condition to the FACP. Such a test may initiated at the detector
itself, by activating a magnetic switch, or may be activated remotely on
command from the control panel.

b. Provide address-setting means on the detector head using switches. The


detectors shall also store an internal identifying code which the FACP
shall use to identify the type of detector.

c. Provide dual alarm and power LEDs. Both LEDs shall flash under normal
conditions, indicating that the detector is operational and in regular
communication with the control panel. Both LEDs may be placed into
steady illumination by the control panel, indicating that an alarm condition
has been detected. An output connection shall also be provided in the base
to connect an external remote alarm LED.

2. Addressable pull stations shall, on command from the control panel, send data to
the panel representing the state of the manual switch and the addressable
communication module status. They shall use a key operated test-reset lock, and
shall be designed so that after actual emergency operation, they cannot be restored
to normal use except by the use of a key. Operated stations shall have a positive,
visual indication of operation and utilize a key type reset. Manual stations shall
be constructed of Lexan with clearly visible operating instructions provided on
the cover. The word FIRE shall appear on the front of the stations in raised
letters, 1.75 inches or larger. Mount stations inside a red, weatherproof enclosure

Libya Infrastructure Master Spec 16721-14 20-Nov-08


with a clear polycarbonate hinged front cover where station is indicated on the
drawings as NEMA 4, NEMA 4X and hazardous areas including Class I, Division
1 and 2.

3. Analog/Addressable Area Photoelectric Smoke Detectors: Photoelectric Smoke


Detectors shall use the photoelectric principle to measure smoke density and shall,
on command from the control panel send data to the panel representing the analog
level of smoke density. These addressable detectors shall connect with two wires
to one of the control addressable input circuits.

4. Analog/Addressable Thermal Detectors: Thermal detectors shall use an


electronic sensor to respond to temperatures exceeding 60 deg. C or 90 deg. C as
required. Sensing elements shall be replaced without removing the detector base.
The detector shall, on command from the control panel, send data to the panel
representing the analog temperature level. These addressable detectors shall
connect with two wires to one of the control addressable input circuits.

5. Each detector shall be provided with a steel mounting plate, and the entire unit
shall mount on a double gang electrical box.

6. Analog/Addressable Duct Smoke Detectors: Provided under Section 15806.

a. The detectors shall, on command from the control panel, send data to the
panel representing the analog level of smoke intensity.

7. Provide devices suitable for the area classifications (i.e., NEMA 1, NEMA 4,
NEMA 4X, and NEMA 7 (Class I, Division 1 or 2) NEMA 4X, etc).

P. Fire Alarm Indicating Devices:

1. Visual appliances shall be installed as shown on the drawings in accordance with


the requirements of the U.L. 1971 standard and NFPA 72. Where multiple visual
signals are visible from any location, circuitry shall be incorporated for the
synchronization of the flash rate.

a. UL 1971 Listed for Emergency Devices for Hearing Impaired in all public
mode installations.

b. Strobes shall meet UL 1971 flash rate.

c. Visual signals shall incorporate a Xenon flashtube enclosed in a rugged


Lexan lens or equivalent with solid state circuitry.

d. The strobe intensity shall be rated per UL 1971.

Libya Infrastructure Master Spec 16721-15 20-Nov-08


e. The strobes shall be available for semi-flush or surface mounting and in
conjunction with audible signals as required.

(NTS: Provide either a horn or speaker audible alarm system. Select one of the two following
paragraphs.)
2. Audible Devices: Audible evacuation signals shall be provided meeting the
following requirements:

a. Audible Notification appliance shall be electronic and use solid state


components.

b. Each electronic signal shall provide four (4) field selectable alarm tones.
The tones shall consist of : slow hoop, continuous, temporal or
interrupted.

c. The device shall provide UL dBA measurement at 10 feet shall be a


minimum of 85 dBA for separately mounted audible signals.

d. The device shall have provisions for standard reverse polarity type
supervision and in/out field wiring using terminals that accept 2.5mm2
wiring.

e. Combination audiovisual alarm horns shall have a high intensity flashing


light and alarm horn as an integral unit. Both audio and visual
components shall operate from the 24 volt dc polarized indicating circuits.
The horn assembly shall be housed in a rugged, die-cast enclosure, and the
electronic light source shall be sealed in silicone and protected by a Lexan
lens. The word FIRE shall appear on the lens. Audiovisual alarm devices
shall meet the requirements of visual appliances and alarm horns above.
Single and/or dual projectors shall be supplied as shown on the plans.

3. Fire Alarm Speakers:

a. Provide fire alarm speakers conforming to UL 464 having a minimum of


three tap settings and separate terminations for each in and out connection.
Tap settings shall include taps of ¼, ½ and 1 watt. Speakers shall utilize
the ½ watt tap in the system. Speakers shall have an output rating of 84
dBA at 3050 mm (10 feet) as determined by the reverberant room test;
data on peak output as determined in an anechoic chamber is not suitable.
Speakers shall be capable of installation on standard 100 mm (4 inch)
square electrical boxes. Where speakers and strobes are provided in the
same location, they may be combined into a single wall mounted unit.

b. Provide speaker mounting plates equipped with mounting holes and other
opening as needed for a complete installation. Fabrication marks and

Libya Infrastructure Master Spec 16721-16 20-Nov-08


holes shall be ground and finished to provide a smooth and neat
appearance for each plate. Each plate shall be primed and painted.

Q. Alarm Communicator:

1. The control panel shall contain integral facilities for off site digital reporting via
site telephone line when approved by the local authority having jurisdiction in the
system monitoring. Upon sensing an alarm condition within the panel, the
communicator shall capture an operational telephone circuit and automatically
dial. Upon making contact with either the primary or secondary numbers, the
communicator shall establish its system identity and report the alarm condition.

R. Power Supply:

1. The power supply for the FACP and fire alarm peripherals shall be integral to the
FACP. The power supply shall provide FACP and peripheral power needs.

2. Positive-temperature-coefficient thermistors, circuit breakers, or other over-


current protection shall be provided on all power outputs.

3. Input power shall be 220 VAC 50 Hz. The power supply shall provide internal
batteries and charger. Internal battery capacity shall be sized as required to meet
system requirements.

4. The main power supply shall provide a battery charging circuit consisting of a
fully automatic standby battery charger, rate compensated, capable of maintaining
battery in fully charged state and be capable of recharging batteries to 70% of
alarm capacity within 12 hours. Provide for normal operation of entire system for
24 hours with power remaining to sound alarms for 5 minutes. For remote
stations, provide battery capacity to operate for 60 hours followed by 5 minutes of
alarm in accordance with NFPA 72B.

5. Provide charger with the following supervised functions: circuit protection for
shorts, open, disconnected or reversed polarity battery connection, supervision or
protection of high or low voltage, overcharging and charger failure. Automatic
load shedding or battery disconnect on deep discharge to prevent battery damage.

6. Batteries shall be 24 V, rechargeable, gelled electrolyte, totally sealed, fully


charged with al interconnections ready for service, maintenance free, long-life.

S. Wiring within Cabinets, Enclosures, Boxes, Junction Boxes, and Fittings:

1. Provide wiring installed in a neat and workmanlike manner and installed parallel
with or at right angles to the sides and back of any box, enclosure, or cabinet.

Libya Infrastructure Master Spec 16721-17 20-Nov-08


2. Conductors which are terminated, spliced, or otherwise interrupted in any
enclosure, cabinet, mounting, or junction box shall be connected to terminal
blocks.

3. Mark each terminal in accordance with the wiring diagrams of the system.

4. Make connections with approved pressure type terminal blocks, which are
securely mounted.

5. The use of wire nuts or similar devices shall be prohibited.

T. Terminal Cabinets:

1. Provide a terminal cabinet at the base of any circuit riser, and where indicated on
the drawings.

2. Terminal size shall be appropriate for the size of the wiring to be connected.

3. Conductor terminations shall be labeled and a drawing containing conductors,


their labels, their circuits, and their interconnection shall be permanently mounted
in the terminal cabinet.

4. Minimum size is 8 inches high by 8 inches.

U. Alarm Wiring:

1. Signaling line circuits and initiating device circuit field wiring shall be copper, 1
mm2 size conductors at a minimum.

2. Notification appliance circuit conductors, that contain audible alarm devices, shall
be solid copper 2.5mm2 size conductors at a minimum.

3. Where a voice evacuation system is specified, speaker circuits shall be copper


1.5mm2 size conductors at a minimum.

4. Wire size shall be sufficient to prevent voltage drop problems.

5. Power wiring, operating at 220 VAC shall be minimum 4 mm2 solid copper
having similar insulation.

6. Provide all wiring in rigid metal conduit.

V. Conductor Terminations:

Libya Infrastructure Master Spec 16721-18 20-Nov-08


1. Labeling of conductors at terminal blocks in terminal cabinets, FACP, and remote
fire alarm control units shall be provided at each conductor connection.

2. Each conductor or cable shall have a shrink-wrap label to provide a unique and
specific designation.

3. Each terminal cabinet, FACP, and fire alarm control unit shall contain a laminated
drawing which indicates each conductor, its label, circuit, and terminal.

4. The laminated drawing shall be neat, using 12 point lettering minimum size, and
mounted within each cabinet, panel, or unit so that it does not interfere with the
wiring or terminals.

5. Maintain existing color code scheme where connecting to existing equipment.

W. Wiring to Station Fire Alarm Circuit:

1. Wiring from the master fire alarm box to the state telegraphic fire alarm circuit
shall be a two-conductor 6 mm2 in rigid steel conduit.

X. Remote Annunciator Command Center:

1. The remote Annunciator Command Center (ACC) shall be an 80 (4 x 20)


character back-lit LCD type capable of displaying up to 3200 point messages.
The remote annunciator shall have the capability of driving up to 576 LEDs for
future graphic notification. They shall be sixteen switch inputs that can be used
for various system functions; lamp test, trouble silence, general alarm, scroll,
system reset, network reset, etc. All fire-alarm controls shall be operational from
the Annunciator Command Center.

2. The ACC shall have non-volatile memory. Annunciators which rely on the FACP
for memory will not be accepted.

3. The ACC shall be surface mounted with switches located with a locked panel, and
easily visible through a glass or plastic viewing plate. Panel door shall have a
keyed lock identical to the lock on the fire alarm control panel (FACP).

2.03 SPARE PARTS AND SPECIAL TOOLS:

A. Provide one spare FACP mother board and 10 percent or a minimum of 2 devices of the
total devices provided for this Contract as listed below.

1. Pull Stations

2. Manual Pull Stations

Libya Infrastructure Master Spec 16721-19 20-Nov-08


3. Weatherproof Smoke Detectors

4. Photoelectric Smoke Detectors

5. Thermal Detectors.

6. Alarm Audible Devices

7. Alarm Strobes

B. Three sets of special tools necessary for the maintenance of the equipment shall be
furnished. Two spare sets of fuses of each type and size required and five spare lamps for
each type shall be furnished. Spare parts shall be listed on submittal list.

PART 3 - EXECUTION

3.01 INSTALLATION:

A. Install fire alarm system in accordance with the manufacturer's diagrams and printed
instructions, except where otherwise indicated.

1. Wiring: Wiring for systems shall be installed in rigid steel conduit. Provide
conduit as specified in Section 16110: ELECTRICAL RACEWAY SYSTEMS.

2. Station loops shall be arranged to permit disconnecting and bypassing the system
at the base of each riser. External wiring between the control panel and the
stations and horns/lights shall connect to terminal strips in accessible locked
cabinets. Connections to the terminal strips shall be made with terminal spade
lugs or with approved type terminal blocks. Terminal cabinets shall be installed
at each point where a station circuit riser originates or any point along a circuit
where a tap is made. The conductors for the fire alarm system shall not be
installed in conduits, junction boxes, or outlet boxes with conductors of lighting
and power systems. The sum of the cross-sectional areas of individual conductors
shall not exceed 40 percent of the interior cross-sectional area of the conduit.
Gutter space to accommodate all necessary wiring shall be provided.

3. Panels: Panel enclosures shall comply with the requirements of UL 864.


Enclosures having doors over 1220 mm (48 inches) in height shall be provided
with a three-point catch and lock; all other doors shall contain a cabinet type
cylinder lock. Inserts shall be blind fastened so that no screws show on the panel
front.

4. Detectors: Detectors shall be installed in accordance with manufacturer's printed


instructions.

Libya Infrastructure Master Spec 16721-20 20-Nov-08


5. Provide complete wiring and conduit between all equipment. Devices shall be
mounted upon UL listed boxes. Wiring splices and transposing or changing of
colors will not be permitted.

6. Junction boxes shall be painted red and labeled as “Fire Alarm System” with
decal or approved markings.

7. Firm Alarm control systems and equipment shall be connected to separate


dedicated branch circuits, sized as required for proper service. Circuits shall be
labeled “FIRE ALARM.”

8. Review the design drawings and perform a walk-through of all areas with the
AHJ.

3.02 PERMITS AND CERTIFICATIONS:

A. Obtain required local permits.

1. Provide certification of the installation.

3.03 FIELD TESTING:

A. Notify the AHJ, the CM/CS and the Owner 30 days before the performance and
acceptance tests are to be conducted. The tests shall be performed in the presence of the
Owner or his authorized representative. Furnish instruments and personnel required for
the tests. Tests shall be conducted for the following:

1. Verify that the system is free of grounds or open circuits. Wiring runs shall be
tested for continuity, short circuits and grounds before system is energized. The
FACP shall indicate when a ground or open circuit exists.

2. Alarm initiating devices shall be observed and logged for correct zone and
sensitivity. These devices and their bases shall be tagged with adhesive tags
located in an area not visible when installed, showing the initials of the installing
technician and date.

3. Verify that all strobes, audible devices, pull stations, transmitters, automatic
detectors and supervisory devices are functioning as specified.

a. Strobes shall deliver the correct foot-candle. Audible devices shall


delivery the correct sound pressure levels decibels of the specified device.

b. Stations shall close the circuits specified and deliver specified alarm
codes. Verify central station receives alarm.

Libya Infrastructure Master Spec 16721-21 20-Nov-08


c. Automatic detectors shall actuate the specified zones when the appropriate
fire or smoke conditions are generated. The detectors shall be exposed to
actual smoke used to simulate this test on each and every smoke detector
as located in the building; no other test will be accepted.

d. Panels and supervisory devices shall display and control functions as


specified. Loss of AC system power shall also be tested.

(NTS: Add following when the Fire Alarm System annunciates the facility fire protection
system.).
e. Close each sprinkler system valve and verify proper supervisory alarm.

f. Verify activation of all water flow switches.

B. System tests to be performed under the supervision of a qualified representative and the
AHJ.

C. Perform all tests to verify the correction of defects found in the initial testing. If testing
identifies system modifications are required to accomplish the required operation,
perform work at no additional cost to the Owner and retest the system.

D. Furnish training as follows:

1. Training in the receipt, handling and acknowledgment of alarms.

2. Training in the system operation including manual control of output functions


from the system control panel.

3. Training in the testing of the system.

3.04 CONTRACT CLOSEOUT:

A. Provide in accordance with Section 01700.

END OF SECTION