PART 1 – GENERAL
1.01 DESCRIPTION:
C. The fire alarm system shall include conduit, wire, fittings, and accessories required to
provide a complete operating system.
E. All charges and fees required by the local Authority having jurisdiction (AHJ) to inspect
the installation and implement fire alarm notification are to be included by the Contractor
under this section at no additional cost to the Owner.
G. The fire alarm system shall be tied into the local Fire Alarm System via a telephone
transmitted signal.
H. Prior to the installation of the system, the manufacturer of the system and system installer
shall obtain from the local AHJ an Application For Fire Alarm Service, and a copy of all
local requirements.
2. UL 268: Standard for Smoke Detectors for Fire Alarm Signaling Systems
F. Equivalent British/European codes and standards may be used; however, the equivalency
shall be demonstrated and submitted by the Contractor and approved by the CM/CS.
A. Type of System:
1. Fire Alarm System: The fire alarm system shall operate as a low voltage
analog/addressable type system and shall automatically initiate fire alarm signals
whenever any manual or automatic fire detecting devices are placed into an alarm
mode. The system shall indicate areas of alarm and sound local alarms. Initiating
loops and notification loops shall be wired as four-wire class A loops. Initiating
loops and notification loops shall be complete with necessary switches, meters,
relays, pilot lights, surge arresters and addressable modules as required. A
minimum of one thermal cut-out or fuse and surge arrestor for every notification
circuit shall be provided. An annunciator shall indicate the specific location of
the fire.
2. The system shall be capable of operating with a single break or ground fault
condition in the initiating or alarm sounding circuits.
(NTS: Identify type of evacuation alarms that are required. Select one of two paragraphs that
follow.)
3. Evacuation Alarms: Coded evacuation alarm: A fire alarm signal shall be
employed for notifying the occupants to evacuate.
6. The system shall interface to HVAC system and other building systems as shown
on the Contract Drawings and required by applicable codes to provide all required
monitoring and control functions.
B. Sequence of Operation:
a. Automatic programs assigned to the alarm point shall be executed and the
associated indicating devices and relays activated.
b. An exterior strobe at the building in alarm shall energize and the fire alarm
notification devices in only that building shall operate.
c. The system alarm on the Fire Alarm Control Panel and Remote
Annunciator Command Center will indicate condition.
c. The appropriate message will appear on the LCD display at the FACP and
Annunciator Command Center.
A. Shop Drawings: Submit the following in accordance with Section 01300 - Submittals:
1. Copy of this specification section with addenda and all referenced specification
sections with addenda check-mark each paragraph to indicate specification
compliance or indicate deviation and reason for deviation.
2. Installer and system supplier qualifications and list of three similar projects with
name and phone number of contact person.
6. Wiring diagrams from the fire alarm system integrator or supplier differentiating
clearly between factory and field installed wiring. Include diagrams for
equipment and for system with all terminals and interconnections identified.
Identify all diagrams to be specific to this project and distinguish between field
and factory wiring.
1. After approval of the list of shop drawings, and not later than six months prior to
the date of substantial completion, furnish copies of spare parts data for each
different item of materials and equipment specified. The data shall include a
complete list of parts and supplies with current unit prices and source of supply, a
list of supplies that are either normally furnished at no extra cost with the
3. Performance Test Reports: Upon completion of the installed system the submit in
booklet form field tests performed to prove compliance with the specified
performance criteria. Each test report shall indicate the final position of controls.
B. Standard Products: Material and equipment shall be the latest standard products of a
single manufacturer regularly engaged in the manufacture of the product for the 5 years
as a minimum.
3. Certify that the completed system conforms with UL standards upon completion
of the installation.
D. Nameplates: The components of equipment shall have the manufacturer's name, address,
type or style, and catalog number on a plate securely attached to the equipment.
E. Tags: Tags with stamped identification number shall be furnished for keys and locks.
Tags shall be furnished to identify cable and conduit runs, wiring circuits, and all spare
parts furnished for Authority's stock to maintain the system.
G. Verification of Dimensions: Become familiar with details of the work and verify
dimensions in the field.
H. Compliance: The fire detection and internal alarm system shall be configured in
accordance with NFPA 72. The equipment furnished shall be compatible and be UL
listed or FM approved or approved or listed by a nationally recognized testing laboratory
in accordance with the applicable NFPA standards.
I. Accessibility: Enclosures shall be provided with ample gutter space to allow proper
clearance between the enclosure and live parts of the panel equipment. If more than one
modular unit is required to form a control panel, the units shall be installed in a single
cabinet large enough to accommodate all units, and allow ample gutter space for
interconnections of panels and field wires.
J. Verify conduit size and wire quantity, size, and type are suitable for the equipment
supplied. Review the proper installation of each type of device with the equipment
supplier.
K. Review selected arrangement with local fire authority for conformance with local
requirements.
3. The technician shall provide the required instruction to the Owner’s personnel in
the system operation, maintenance and programming.
B. Equipment placed into storage shall be protected from the weather, humidity and
temperature variations, dirt, dust, and other contaminants.
B. It shall be the responsibility of the manufacturer and supplier along with the Electrical
Contractor to conform to the seismic design requirements for this project and for the
work of this specification section.
PART 2 - PRODUCTS
2.01 MANUFACTURERS:
A. Notifier
B. Honeywell
C. Simplex - Grinnel
D. Or equal.
(NTS: The system design to include Master Fire Alarm Control Panel at each building.)
B. Communications:
1. The FACP shall have sufficient memory to support its operating system and
databases including:
a. Fire management
b. Alarm management
c. Historical/Trend Data
e. Custom Processes
f. Operator/IO
4. Surge and Transient Protection: Isolation shall be provided at all field point
terminations to suppress induced voltage transients where required. Surge
arrestors shall provide protection from all non-signal electrical surges that could
cause damage to the equipment. Line surge arrestors shall be isolated from the
electrical circuitry that they are protecting.
4. Status Change Report: All alarm or point change reports shall include the point’s
English language description, and the time and date of occurrence.
5. Prioritization: The user shall be able to define the specific system reaction for
each point. Alarms shall be prioritized to minimize nuisance reporting and to
speed operator response to critical alarms. A minimum of three priority levels
shall be provided.
7. Alarm Messages: In addition to the point’s description and the time and date, the
user shall be able to print, display or store a custom alarm message to more fully
describe the alarm condition or direct operator response.
9. History Mode:
a. The system shall be able to store and display at least 900 system events
that have occurred in a non-volatile buffer memory. Display of these
events shall be accomplished on-site through the use of the front control
panel indicators and switches.
2. The analog addressable device interface shall contain its own microprocessor
control.
3. The analog addressable device interface shall communicate and provide power to
all devices on its loop over a single pair of wires. The fire-alarm system shall
4. The analog interface board shall receive analog information from intelligent
detectors and shall process this information to determine normal, alarm, or trouble
conditions. The analog information may also be used for automatic test and
determination of maintenance requirements.
1. The FACP shall provide supervised Class A notification circuits with minimum of
50 percent spare capacity for future devices. The circuit capacity shall be 2.0
amperes maximum per circuit, maximum of 8.0 amperes from the FACP’s power
supply. If a short-circuit trouble occurs on one of the circuits it will not affect the
operation of the remaining circuits.
a. Construction:
(1) Amplifiers shall utilize computer grade solid state components and
shall be provided with output protection devices sufficient to
protect the amplifier against any transient up to 10 times the
highest rated voltage in the system.
b. Inputs:
(1) Each system shall be equipped with separate inputs from the tone
generator, digitalized voice driver and panel mounted microphone.
Microphone inputs shall be of the low impedance, balanced line
type. Both microphone and tone generator input shall be
operational on any amplifier.
(1) The tone generator shall be of the modular, plug-in type with
securely attached labels to identify the component as a tone
generator and to identify the specific tone it produces. The tone
generator shall produce a slow whoop tone, which shall slowly
ascend from low (500 hertz) to high (1200 hertz), and shall be
constantly repeated until interrupted by either the digitalized voice
message, the microphone input, or the alarm silence mode as
specified. Each slow whoop cycle shall last approximately 4
seconds. The tone generator shall be single channel with an
automatic backup generator per channel such that failure of the
primary tone generator cause the backup generator to automatically
take over the functions of the failed unit and also causes transfer of
the common trouble relay.
d. Protection Circuits:
G. Function Relays:
1. The FACP shall provide of Form “C” relay contacts, quantity as required, rated at
1 A at 220 VAC. These relays may be programmed to activate on alarm from any
initiating zone or any combination of initiating zones, analog devices or
addressable modules.
1. The CPU shall communicate with the operator interface, LCD display, LED
display and control other modules in the panel. Removal, disconnection or failure
of any control panel shall be detected and reported by the Central Processing Unit.
2. The CPU shall contain and execute all control-by-event programs for specific
action to be taken if a fire situation is detected in the system. Such control-by-
event programs shall be held in non-volatile programmable memory, and shall not
be lost even if system primary and secondary power failure occurs. The CPU
shall also provide a real time clock for time annotation on the display and remote
optional printer.
1. The operator display shall provide controls and indicators used by the system
operator. The display shall contain, and display as needed, custom alphanumeric
message for all intelligent detectors and addressable modules. Such message
information shall be stored in programmable non-volatile memory.
3. Factory programmable system indications and keys shall be available for unique
functions. Keys shall be referred to as “Hot Keys”.
4. The Display Interface shall provide a 15-key touch keypad with control capability
to command all system functions, and entry of any numeric information. The
keypad shall include means to enter a minimum of two different passwords to
prevent unauthorized manual control.
5. Ground fault indication shall be displayed on a system and initiating zone basis.
J. Communications Ports:
K. Mechanical Design:
1. The Fire Alarm Control Panel (FACP) shall be housed in a cabinet designed for
mounting recessed or directly to a wall or vertical surface. The back box and door
shall be constructed with provisions for electrical conduit connections. The door
shall provide a key lock and shall include an opening for viewing.
2. The FACP shall be modular in structure for ease of installation and maintenance.
M. Provide addressable monitor modules to interface manual FACP to stations and other
non-addressable detection components as required. The modules shall be capable of
being mounted in a 4 x 4 x 2 1/8-inch junction box.
N. Provide addressable control modules to interface FACP to fire alarm reporting panel,
audible and visual devices and other control components as required. The modules shall
be capable of being mounted in a 4 x 4 x 2 1/8-inch junction box.
a. Provide a test means whereby they will simulate an alarm condition and
report that condition to the FACP. Such a test may initiated at the detector
itself, by activating a magnetic switch, or may be activated remotely on
command from the control panel.
c. Provide dual alarm and power LEDs. Both LEDs shall flash under normal
conditions, indicating that the detector is operational and in regular
communication with the control panel. Both LEDs may be placed into
steady illumination by the control panel, indicating that an alarm condition
has been detected. An output connection shall also be provided in the base
to connect an external remote alarm LED.
2. Addressable pull stations shall, on command from the control panel, send data to
the panel representing the state of the manual switch and the addressable
communication module status. They shall use a key operated test-reset lock, and
shall be designed so that after actual emergency operation, they cannot be restored
to normal use except by the use of a key. Operated stations shall have a positive,
visual indication of operation and utilize a key type reset. Manual stations shall
be constructed of Lexan with clearly visible operating instructions provided on
the cover. The word FIRE shall appear on the front of the stations in raised
letters, 1.75 inches or larger. Mount stations inside a red, weatherproof enclosure
5. Each detector shall be provided with a steel mounting plate, and the entire unit
shall mount on a double gang electrical box.
a. The detectors shall, on command from the control panel, send data to the
panel representing the analog level of smoke intensity.
7. Provide devices suitable for the area classifications (i.e., NEMA 1, NEMA 4,
NEMA 4X, and NEMA 7 (Class I, Division 1 or 2) NEMA 4X, etc).
a. UL 1971 Listed for Emergency Devices for Hearing Impaired in all public
mode installations.
(NTS: Provide either a horn or speaker audible alarm system. Select one of the two following
paragraphs.)
2. Audible Devices: Audible evacuation signals shall be provided meeting the
following requirements:
b. Each electronic signal shall provide four (4) field selectable alarm tones.
The tones shall consist of : slow hoop, continuous, temporal or
interrupted.
d. The device shall have provisions for standard reverse polarity type
supervision and in/out field wiring using terminals that accept 2.5mm2
wiring.
b. Provide speaker mounting plates equipped with mounting holes and other
opening as needed for a complete installation. Fabrication marks and
Q. Alarm Communicator:
1. The control panel shall contain integral facilities for off site digital reporting via
site telephone line when approved by the local authority having jurisdiction in the
system monitoring. Upon sensing an alarm condition within the panel, the
communicator shall capture an operational telephone circuit and automatically
dial. Upon making contact with either the primary or secondary numbers, the
communicator shall establish its system identity and report the alarm condition.
R. Power Supply:
1. The power supply for the FACP and fire alarm peripherals shall be integral to the
FACP. The power supply shall provide FACP and peripheral power needs.
3. Input power shall be 220 VAC 50 Hz. The power supply shall provide internal
batteries and charger. Internal battery capacity shall be sized as required to meet
system requirements.
4. The main power supply shall provide a battery charging circuit consisting of a
fully automatic standby battery charger, rate compensated, capable of maintaining
battery in fully charged state and be capable of recharging batteries to 70% of
alarm capacity within 12 hours. Provide for normal operation of entire system for
24 hours with power remaining to sound alarms for 5 minutes. For remote
stations, provide battery capacity to operate for 60 hours followed by 5 minutes of
alarm in accordance with NFPA 72B.
5. Provide charger with the following supervised functions: circuit protection for
shorts, open, disconnected or reversed polarity battery connection, supervision or
protection of high or low voltage, overcharging and charger failure. Automatic
load shedding or battery disconnect on deep discharge to prevent battery damage.
1. Provide wiring installed in a neat and workmanlike manner and installed parallel
with or at right angles to the sides and back of any box, enclosure, or cabinet.
3. Mark each terminal in accordance with the wiring diagrams of the system.
4. Make connections with approved pressure type terminal blocks, which are
securely mounted.
T. Terminal Cabinets:
1. Provide a terminal cabinet at the base of any circuit riser, and where indicated on
the drawings.
2. Terminal size shall be appropriate for the size of the wiring to be connected.
U. Alarm Wiring:
1. Signaling line circuits and initiating device circuit field wiring shall be copper, 1
mm2 size conductors at a minimum.
2. Notification appliance circuit conductors, that contain audible alarm devices, shall
be solid copper 2.5mm2 size conductors at a minimum.
5. Power wiring, operating at 220 VAC shall be minimum 4 mm2 solid copper
having similar insulation.
V. Conductor Terminations:
2. Each conductor or cable shall have a shrink-wrap label to provide a unique and
specific designation.
3. Each terminal cabinet, FACP, and fire alarm control unit shall contain a laminated
drawing which indicates each conductor, its label, circuit, and terminal.
4. The laminated drawing shall be neat, using 12 point lettering minimum size, and
mounted within each cabinet, panel, or unit so that it does not interfere with the
wiring or terminals.
1. Wiring from the master fire alarm box to the state telegraphic fire alarm circuit
shall be a two-conductor 6 mm2 in rigid steel conduit.
2. The ACC shall have non-volatile memory. Annunciators which rely on the FACP
for memory will not be accepted.
3. The ACC shall be surface mounted with switches located with a locked panel, and
easily visible through a glass or plastic viewing plate. Panel door shall have a
keyed lock identical to the lock on the fire alarm control panel (FACP).
A. Provide one spare FACP mother board and 10 percent or a minimum of 2 devices of the
total devices provided for this Contract as listed below.
1. Pull Stations
5. Thermal Detectors.
7. Alarm Strobes
B. Three sets of special tools necessary for the maintenance of the equipment shall be
furnished. Two spare sets of fuses of each type and size required and five spare lamps for
each type shall be furnished. Spare parts shall be listed on submittal list.
PART 3 - EXECUTION
3.01 INSTALLATION:
A. Install fire alarm system in accordance with the manufacturer's diagrams and printed
instructions, except where otherwise indicated.
1. Wiring: Wiring for systems shall be installed in rigid steel conduit. Provide
conduit as specified in Section 16110: ELECTRICAL RACEWAY SYSTEMS.
2. Station loops shall be arranged to permit disconnecting and bypassing the system
at the base of each riser. External wiring between the control panel and the
stations and horns/lights shall connect to terminal strips in accessible locked
cabinets. Connections to the terminal strips shall be made with terminal spade
lugs or with approved type terminal blocks. Terminal cabinets shall be installed
at each point where a station circuit riser originates or any point along a circuit
where a tap is made. The conductors for the fire alarm system shall not be
installed in conduits, junction boxes, or outlet boxes with conductors of lighting
and power systems. The sum of the cross-sectional areas of individual conductors
shall not exceed 40 percent of the interior cross-sectional area of the conduit.
Gutter space to accommodate all necessary wiring shall be provided.
6. Junction boxes shall be painted red and labeled as “Fire Alarm System” with
decal or approved markings.
8. Review the design drawings and perform a walk-through of all areas with the
AHJ.
A. Notify the AHJ, the CM/CS and the Owner 30 days before the performance and
acceptance tests are to be conducted. The tests shall be performed in the presence of the
Owner or his authorized representative. Furnish instruments and personnel required for
the tests. Tests shall be conducted for the following:
1. Verify that the system is free of grounds or open circuits. Wiring runs shall be
tested for continuity, short circuits and grounds before system is energized. The
FACP shall indicate when a ground or open circuit exists.
2. Alarm initiating devices shall be observed and logged for correct zone and
sensitivity. These devices and their bases shall be tagged with adhesive tags
located in an area not visible when installed, showing the initials of the installing
technician and date.
3. Verify that all strobes, audible devices, pull stations, transmitters, automatic
detectors and supervisory devices are functioning as specified.
b. Stations shall close the circuits specified and deliver specified alarm
codes. Verify central station receives alarm.
(NTS: Add following when the Fire Alarm System annunciates the facility fire protection
system.).
e. Close each sprinkler system valve and verify proper supervisory alarm.
B. System tests to be performed under the supervision of a qualified representative and the
AHJ.
C. Perform all tests to verify the correction of defects found in the initial testing. If testing
identifies system modifications are required to accomplish the required operation,
perform work at no additional cost to the Owner and retest the system.
END OF SECTION