Sie sind auf Seite 1von 9

Electrical Power and Energy Systems 67 (2015) 501–509

Contents lists available at ScienceDirect

Electrical Power and Energy Systems


journal homepage: www.elsevier.com/locate/ijepes

Evaluation of frequency control application for distributed generation


in Turkey
Levent Kılıç a,⇑, Aysßen Basa Arsoy b
a _
Sßisßecam Group, Energy Efficiency Management, Is Kuleleri Kule 2, 34330 4.Levent, Istanbul, Turkey
b _
Kocaeli University, Department of Electrical Engineering, 41380 Umuttepe, Istanbul, Turkey

a r t i c l e i n f o a b s t r a c t

Article history: Ancillary services are essential for the safe, secure and reliable operation of power systems. They pres-
Received 18 July 2013 ently include both mandatory and competitive services such as voltage control, frequency control and
Received in revised form 6 December 2014 system restart. Since these services were and are still mostly provided by centralized power plants, con-
Accepted 9 December 2014
trols of voltage and frequency in the Turkish power system are also performed by power plants with
Available online 26 December 2014
installed capacity of 50 MW and greater. However, the number of private sector power plants connected
to the national grid at medium voltage has been increasing continuously. The positive impact and the
Keywords:
contribution of such plants should be realized better by further actions.
Frequency control
Power plants
In this paper, frequency control ability in natural gas fired private power plants connected to medium
Distributed generation voltage level is studied. Data taken from a real power plant operation is used for this study. With the
Gas engine growth of such distributed generation units (DGU) on distribution grid and with the deregulation of
Gas turbine the electricity sector, the frequency control may become an applicable scenario for DGU.
Ó 2014 Elsevier Ltd. All rights reserved.

Introduction private plants for effective grid operation [9–11]. For reliability
purpose, reserves have to be taken into consideration as well.
Today’s power systems are undergoing major changes as the Although frequency control is a new subject for Turkey, it has
penetration of generating units at medium voltage grids has been been carried out successfully in practice and is being continued
increasing continuously [1,2]. Such generation units, also called as well. The chronological development of the frequency control
distributed generation, can have a significant impact on some in Turkey is given in Table 1. As can be seen from the table, the con-
parameters such as voltage profile, power quality, reliability, and nection of the Turkish transmission system into the Union for the
frequency [3,4]. This impact cannot be neglected and should be Coordination of Transmission of Electricity (UCTE/ENTSO-E) [12]
taken into consideration in system operation [5]. Although some was initiated in September 2010. Statistical data given in Table 2
studies are available on frequency response of renewable generat- shows that the number of outages in the selected power plant
ing units [6–8], this paper focuses on frequency control of gas which is located at the south side of Turkey, is reduced to zero with
engine type power plants because the major portion of renewable the UCTE connection.
units in Turkey are connected directly to the high voltage transmis- Frequency control has been defined in the Turkish power sys-
sion grid, not to the distribution grid. tem as a mandatory, remunerable ancillary service that is pro-
Combined heat and power (CHP) plants utilizing gas engine or vided by generating units and managed by the system operator
gas turbine are mostly preferred in industrial applications for [13]. Many studies exist on frequency control for mostly conven-
higher energy efficiency. These type of plants rated from 5 MW tional generators having stable characteristics. Not only fre-
to 50 MW can be connected to the distribution grid easily. The quency control [14] but also other issues such as protection
number of CHP plants owned and operated by private sector pro- [15], stability and design have been covered [16–22]. But, there
ducers has been increasing. The requirements and rules set by is not enough contribution in the literature on frequency control
the Turkish Grid Regulating Authority have to be satisfied by the associated with private sector power plants [14]. In the available
literature, the focus is generally given to test procedures. If DG
units are operated with a control mechanism, additional benefits
can be achieved, especially with high penetrated units in distri-
⇑ Corresponding author. bution grid.
E-mail addresses: lkilic@sisecam.com (L. Kılıç), aba@kocaeli.edu.tr (A.B. Arsoy).

http://dx.doi.org/10.1016/j.ijepes.2014.12.040
0142-0615/Ó 2014 Elsevier Ltd. All rights reserved.
502 L. Kılıç, A.B. Arsoy / Electrical Power and Energy Systems 67 (2015) 501–509

Table 1
Official gazette/regulatory authority.

Date Official gazette/regulatory Explanation


authority
27.12.2008 27,093 Electricity Market Ancillary Service Regulation was published
01.07.2009 Primary frequency control was initiated
22.03.2010 Synchronous testing with ENTSO-e and dead band was set as 0 (zero)
13.05.2010 27,580 Some modifications on ancillary service
19.08.2010 27,677 Some modifications on ancillary service
18.09.2010 UCTE connection was initiated. Reserve capacity of country was decreased to 300 MW (from 700 MW, almost
halved)
15.10.2010 27,730 Some modifications on ancillary service
10.02.2011 27,842 Penalties seriously increased
15.03.2011 Reserve capacity was decreased to 1%
17.12.2011 28,145 Some modifications on ancillary service
23.12.2011 28,151 Penalties seriously increased
19.01.2012 Test periods were 3 years instead of 1 year

Table 2 Generator power


Statistical data of a power plant in Turkey.
Pmax
Date Events number out of 50.00 ± 0.2 Hz
28.12.2009–31.12.2009 6 b a
Jan’10 8
Feb’10 4 Primary control
Mar’10 0 reserve
Apr’10 1
May’10 6
Jun’10 2
Jul’10 10
Aug’10 9
01.09.2010–18.09.2010 3
18.09.2010–Later 0 fa

Due to common usage of generating units with gas engines, fb


their primary frequency control application is emphasized in this
study. After an overview of frequency control methods and opera-
tional characteristics, the frequency control ability of units with
Frequency
gas engines is evaluated through the test results of a real power
plant. Fig. 1. Power control of two generators having different droops.

Frequency control
f (Hz)
When there is an imbalance between electricity demand and
supply amount, it is important to control frequency, and maintain
it within the desired limits. For this purpose, frequency control by
means of active power can be implemented. The first step is to
describe the power system dynamics by the following power bal- t (s)
ance equation [9,10]:
df s
dW k
¼ Pg  Pc ð1Þ df dyn
dt
where W k ¼ 12 J x2 , is kinetic energy of all rotating machines, Pg is 2
power generation, Pc is power consumption, J is the moment of iner-
tia of all the machines synchronized to the system and x is angular
speed (rad/s).
Eq. (1) describes how the unbalance between generation and 1
consumption (Pg–Pc) will change the rotating energy (dW) in the
system. After differentiating Eq. (1) to calculate small changes, Fig. 2. Frequency drop after power plant trip.
the balance can be expressed in the following form:
dDx
Jx ¼ DP g  DP c ð2Þ By solving Eq. (3), frequency deviation function can be derived
dt as given in Eq. (4).
If we assume that the change in frequency is small, then x = xN
and DPc = KnDf. Thus, J ¼ 2 W k
and Eq. (2) can be expressed as DP g
x2N Df ¼ ð4Þ
follows: K n ð1  ef N K n =ð2W k Þt Þ
W k Df where f2W k
is time constant (T), which is typically 5–10 s and Kn is
2 ¼ DP g  K n Df ð3Þ N Kn
f N dt natural control gain of the network [23,24].
L. Kılıç, A.B. Arsoy / Electrical Power and Energy Systems 67 (2015) 501–509 503

Restore normal
System
Limit deviation
Frequency

Activate Primary Free reserves


Control

Take over Secondary Free reserves


Control

Take over Tertiary


Control

Fig. 3. Tertiary control reserves (UCTE).

Without frequency control, the frequency change is propor-


tional to 1/Kn times the change of power. A frequency control sys-
Table 3 tem should maintain the frequency deviation within ±0.2 Hz.
Maximum step change of power plants.
Primary frequency control
Prime mover Maximum step change Control range (%)
(in 5 s) (%) (in 30 s) (%)
The primary control of frequency is implemented by the fre-
Hydro-(Francis turbine) 20 30 50–100 quency governors in the power plants. The governors change the
Gas engines 10–30 10–30 40–100 output of a power plant in direct proportional to the change in
Gas turbines 10 20 40–100
Steam turbines (coal fired) 2.5 5–10 50–90
the frequency:
DP g 1 Df Df
¼ ¼ K ð5Þ
Pgn sG f n fn
where DPg is change of generator output [MW], Pgn is generator out-
Table 4 put [MW], sG is (%) droop, Df is change in frequency [Hz], and fn is
Maximum ramp rates of power plants. nominal frequency [Hz].
The term sG is called the drop of the generator, and 1/sG equals
Prime mover Max ramp rate (%/min) Range (%)
to proportional gain (K) of the generator governor. In practice, the
Hydro power 40 0–100
gain is measured as regulating power (Rp) which is the ratio of
Gas engines 6 40–100
Aero derivative gas turbines 6 40–100 power change per frequency change [MW/Hz].
Industrial gas turbines 8 40–100 Pgn
Steam turbines – coal fired 2–4 60–90 DP ¼  Df ¼ Rp Df ð6Þ
sG f n

Part Load Efficiency of Power Plant at Regulaon Mode


45%
40%
35%
30%
Efficiency

25%
20%
15%
10%
5%
0%
30% 40% 50% 60% 70% 80% 90% 100%
Output
Gas Engine Gas Turbine

Fig. 4. The net efficiency of power plants outputs at the regulation mode.
504 L. Kılıç, A.B. Arsoy / Electrical Power and Energy Systems 67 (2015) 501–509

Part Load Efficiency at Different Operaon Modes


50%
45%
40%
35%

Efficiency
30%
25%
20%
15%
10%
5%
0%
MW
Efficiency Mode Regulaon Mode

Fig. 5. The net efficiency of an 94 MW gas engine power plant in high efficiency and regulation modes.
Grid Frequency [Hz]
Simulate Frequency [Hz]
Active Power [MW]
Valve Position [%]

Time

Fig. 6. Maximum power reserve test.


L. Kılıç, A.B. Arsoy / Electrical Power and Energy Systems 67 (2015) 501–509 505

Grid Frequency [Hz]


Simulate Frequency [Hz]
Active Power [MW]
Valve Position [%]

Time

Fig. 7. Maximum power sensitivity test.

The primary frequency control is mainly a proportional control control. The final frequency will drop to the level where the load
(P-controller). Frequency fluctuates initially, and a permanent drop corresponds to the output of the lost power plant.
deviation in the frequency takes place. The time constant of the An ideal secondary controller corrects the frequency deviation
primary control lies within the range of few seconds. by using an integral term in the controller.
Fig. 1 shows the power-frequency characteristics of two gener- Z
ators having different droops. In case of a minor frequency drop, 1
DPi ¼ K i ACEi  ACEi dt ð7Þ
generator-a increases its power output more than generator-b. If T ri
the frequency drop is larger than fa, generator-b increases its out-
put until the frequency drops to fb at which point it is also operat- where DPi is power output after the secondary controller in control
ing at the maximum power. The regulating power of a generator is area i, Ki is proportional factor (gain) of the secondary controller in
then the primary control reserve divided by the frequency change area i, ACEi is area control error (ACE) in control area i, Tri is integra-
Df. The regulating power of plant-a is larger than the regulating tion time constant in control area i.
power of plant-b. The controller is then classified as a PI-type (Proportional Inte-
gral). However, in practice it is realized by using ramp loading of
operating power plants.
Secondary frequency control The area control error (ACE) is defined as follows [14]:

Primary frequency control can prevent large frequency varia- ACE ¼ DP þ K Df ð8Þ
tions during a system disturbance; however, it does not bring the
system frequency back to its scheduled value. The main function Here, DP is power control error or deviation in power balance, Df is
of the secondary control system is to correct the deviation dfs deviation of frequency from the set point, K df is frequency control
and to restore the frequency to the scheduled value. The secondary error, K is dependency between deviation of power and system
frequency control systems limit the drop to an acceptable level. frequency.
Fig. 2 shows the frequency behaviors of a system where Line 1 The frequency standard in the UCTE area is 50 Hz. The
has no frequency control while Line 2 has a secondary frequency maximum allowed steady state frequency deviation is ±0.2 Hz.
506 L. Kılıç, A.B. Arsoy / Electrical Power and Energy Systems 67 (2015) 501–509

Grid Frequency [Hz]


Simulate Frequency [Hz]
Active Power [MW]
Valve Position [%]

Time

Fig. 8. Minimum power reserve test.

The performance standard of each grid operator is to control the the network during disturbances. The maximum changes of output
area control error (ACE) to zero on a continuous basis. within a specified time are given in Table 3.
The secondary reserves should be activated within 30 s and
they should be in full output within 15 min. The secondary control Maximum ramp rates
reserves should release the primary reserves for the next distur-
bance in the system. The ramp rate is defined as the change of output within one
minute of time, when the power plant is connected to the network.
Tertiary frequency control Typically five or ten minute ramps are needed in interconnected
power systems. The maximum ramp rates have been given in
The tertiary frequency control is mainly based on manual Table 4 [25,26].
actions initiated by operators. Starting the reserve power plants Hydro plants have the fastest ramp rates, while steam plants
(non spinning reserves) is the action taken manually. Tertiary con- have the lowest ramp rates because of the limitations in tempera-
trol should free the secondary control within a period of time when ture changes in steam turbine. The ramp rates of internal combus-
the system is subjected to a disturbance. UCTE defined this as tion engines and gas turbines are almost the same.
15 min. A schematic flow chart of frequency control for UCTE is
given in Fig. 3. Part of the actions will be taken automatically while Frequency control of MV connected gas turbines and internal
some manually. Automatic actions are typically initiated when the combustion engines
frequency drops below the given limits.
The frequency control is mandatory for power plants with
Operational characteristics installed capacity of 50 MW or greater connected to the Turkish
transmission system at the voltage level of 154–380 kV. The oper-
Maximum step changes ating principles of this control are set by the National Grid Regula-
tion. The similar principles can be applied to the power plants
The maximum step change determines the ability of the power connected to medium voltage systems if the type of the engine uti-
plants to participate in primary control of the output frequency in lized in the plant are the same.
L. Kılıç, A.B. Arsoy / Electrical Power and Energy Systems 67 (2015) 501–509 507

Grid Frequency [Hz]


Simulate Frequency [Hz]
Active Power [MW]
Valve Position [%]

Time

Fig. 9. Minimum power sensitivity test.

The primary frequency control is arranged by using a governor drop in efficiency increases the cost of the regulated power. As
droop control system that measures the frequency and controls the can be seen from Fig. 4, the efficiency of large gas engines at 70%
engine output in proportion to the frequency deviation. The pri- load is approximately 41%. However, the efficiency drops to 34%
mary control of a gas engine power plant can be activated in two for aero-derivative turbines under the same loading conditions.
phases according to the requirement of primary frequency control A gas engine power plant can also be operated at the high effi-
of UCTE system. In the first phase, the power plant can change its ciency mode where the load demand is supplied by the minimum
output by about 30% within 10 s, and in the second phase, by number of units. The studied plant has 6 MW and 8 MW units,
another 30% in 30 s. Thus, a gas engine power plant can typically therefore it can generate stable power from a 4 MW output to an
changes its output by ±30% within 30 s. However, this depends 94 MW output with an efficiency of 40% or higher. This is illus-
on the type of the gas engines. trated in Fig. 5 [25,26].
Secondary control can be made either manually or automatically
by receiving the Automatic Generation Control (AGC) signals from Realized primary control performance tests
the dispatch center. The power plant can increase or decrease its out-
put from the midpoint of 70% by ±30% within five or ten minutes Within the scope of primary frequency control, the amount of
depending on the requirements of the transmission system operator. control reserve in line with the resultant frequency deviations
The efficiency values of internal combustion engines and gas should be continuously supplied for both maximum and minimum
turbine engines can be found in the engine manuals of their ven- output power of the engine. Maximum power corresponds to a set
dors. Values obtained from actual power plants can be given as fol- value which is below the nominal power of the unit by the amount
lows; the efficiency values of large internal combustion engines are of control reserve capacity. Minimum output power of thermal
within a range of 40–45% while those of aero-derivative gas tur- units should not be higher than 65% of the installed capacity of
bines and industrial gas turbines are within the ranges of 35–40% the units. If the system frequency is beyond the limits, units
and 25–35%, respectively. involved with primary frequency control should react immediately
The efficiency of a plant depends on the loading and the operat- and change its output power according to the deviations. Complete
ing mode of the plant. When the plant is operated at the regulation reserve amount that has to be enabled in case of a frequency devi-
mode, the efficiency at the midpoint is very important, because a ation of ±200 mHz should be indicated for each unit. Sensitivity
508 L. Kılıç, A.B. Arsoy / Electrical Power and Energy Systems 67 (2015) 501–509

Grid Frequency [Hz]


Active Power [MW]
Valve Position [%]

Time

Fig. 10. 24 h verification test.

range of primary frequency control system of the units should be Conclusion and suggestions
as narrow as possible, and should not exceed ±10 mHz.
Primary frequency control reserve and sensitivity tests have This paper discusses frequency control ability of generating
been implemented on a real power plant with 94.20 MW installed units focusing on gas engine units. An assessment of frequency
capacity, having 12 gas engines where engines’ nominal powers control methods have been given in terms of the loading variation
are (6  8.73 MW + 6  6.97 MW). Primary control reserve tests and the corresponding power balance equations. The frequency
are achieved in two stages of minimum and maximum levels of control of the power system is performed by primary, secondary
output power. In these stages, the output power is adjusted to a and tertiary control systems operating in sequence. This is realized
value which is below or above the nominal output by the reserve in real power plants by changing the output of medium sized
capacity amount. The test results are shown in Figs. 6 and 7 for power plants automatically or manually at high voltage.
maximum output power level and in Figs. 8 and 9 for minimum The results of primary frequency reserve and sensitivity tests
output power level. Simulation frequency values of f = 49.8 Hz implemented on a real power plant having gas engine units have
and f = 50.2 Hz with the frequency deviations of Df = 200 mHz been evaluated whether or not they satisfy the grid requirements.
and Df = +200 mHz has been applied in the form of a step altera- Since gas engines can change their output dynamically, they do
tions where each step is maintained at least 15 min, as shown in respond to grid frequency deviation not only at the primary but
Figs. 6 and 8. In primary frequency reserve tests, the limits of also at the secondary level if remotely controlled. As well known,
expected reaction of the unit should not exceed maximum 2% distributed generation units having gas engines have been increas-
and minimum 1% of nominal output power of the unit, as stated ing continuously at medium voltage grid. These kind of small sized
in the Grid Regulation. In these reserve tests, the unit is waited power plants’ engines can easily be utilized in controlling fre-
to reach a steady state without changing the adjustments made quency individually or in a group for a secure and reliable opera-
on the unit. In order to start the sensitivity test, frequency devia- tion of distribution grid.
tion amount in increments of 5 mHz is implemented starting from
Df = 5 mHz in plus and minus directions until unit reaction is
observed. If the unit does not react to frequency deviations of
References
±5 mHz, the same processes are repeated for the frequency devia-
tions of ±10 mHz, as seen in Figs. 7 and 9. After the completion of [1] Lise Wietze. Towards a higher share of distributed generation in Turkey.
primary frequency control reserve and sensitivity tests success- Energy Policy 2009;37:4320–8.
fully, recording of actual frequency and normal operation is real- [2] Bayod-Rujula Angel A. Future development of the electricity systems with
distributed generation. Energy 2009;34:377–83.
ized for 24 h, as seen in Fig. 10. The results of these tests [3] Ackermann Thomas, Andersson Göran, Söder Lennart. Distributed generation:
implemented on the units satisfy the grid regulations well. a definition. Electr Pow Syst Res 2001;57:195–204.
L. Kılıç, A.B. Arsoy / Electrical Power and Energy Systems 67 (2015) 501–509 509

[4] Hani Davood, Sadeghi Yazdankhah Ahmad, Madadi Kajabadi Hossein. Impacts [15] Mirsaeidi Sohrab, Said Dalila Mat, Wazir Mustafa Mohd, Hafiz Habibuddin
of distributed generations on power system transient and voltage stability. Mohd, Ghaffari Kimia. An analytical literature review of the available
Electr Pow Energy Syst 2012;43:488–500. techniques for the protection of micro-grids. Int J Electr Pow Energy Syst
[5] Shayeghi H, Shayanfar HA, Jalili A. Load frequency control strategies: a state- (IJEPES) 2014;58(July):300–6.
of-the-art survey for the researchers. Energy Convers Manage [16] Tanweer Syed, Rahman Asadur. Power system analysis by distributed
2009;50:344–53. generation. New Delhi: LAP LAMBERT Academic Publishing; 2013.
[6] El Mokadem M, Courtecuisse V, Saudemont C, Robyns B, Deuse J. Experimental [17] Jurado F, Carpio J. Improving distribution system stability by predictive control
study of variable speed wind generator contribution to primary frequency of gas turbines. Energy Convers Manage 2006;47(May):2961–73.
control. Renew Energy 2009;34:833–44. [18] Shayeghi H, Shayanfar HA, Jalili A. Load frequency control strategies: a state-
[7] Singh Parmar KP, Majhi S, Kothari DP. Load frequency control of a realistic of-art survey for the researcher. Energy Convers Manage 2009;50:344–53.
power system with multi-source power generation. Electr Pow Energy Syst [19] Maslo Karel, Kolcun Michal. Load-frequency control management in Island
2012;42:426–33. operation. Electr Pow Syst Res 2014;114:10–20.
[8] Jones DI, Mansoor SP, Aris FC, Jones GR, Bradley DA, King DJ. A standard [20] Shashi Kant Pandey M, Mohanty Soumya R, Nand Kishor M. A literature survey
methods for specifying the response of hydroelectric plant in frequency- on load-frequency control for conventional and distribution generation power
control mode. Elect Pow Syst Res 2004;68:19–32. systems. Renew Sustain Energy Rev 2013;25:318–34.
[9] Electricity Market Grid Regulation, Official Gazette No. 27418 dated [21] Mirsaeidi Sohrab, Said Dalila Mat, Wazir Mustafa Mohd, Hafiz Habibuddin
26.11.2009. Mohd. Progress and problems in micro-grid protection schemes. Renew
[10] Electricity Market Ancillary Service Regulation, Official Gazette No. 27580 Sustain Energy Rev 2014;37:834–9.
dated 13.05.2010. [22] Dulau Mircea, Bica Dorin. Simulation of speed steam turbine control system.
_
[11] ‘‘Primary Control Service Agreement’’ developed by TürkiyeElektrikIletim A.S
ß. Procedia Technol 2014;12:716–22.
(TEIAS). <www.teias.gov.tr/YanHizmetler.aspx>. [23] Kundur P. Power system stability and control. USA: McGraw-Hill; 1994.
[12] Union for the Co-ordination of Transmission of Electricity UCTE, UCTE [24] Saadat H. Power system analysis. USA: McGraw-Hill; 1999.
operation handbook, 2004 <www.entsoe.eu>. [25] ISO Standard 3046–1:1995. Performance standard of reciprocation internal
[13] Lobato E, Egido I, Rouco L. Monitoring frequency control in the Turkish power combustion engines.
system. Elect Pow Syst Res 2012;84:144–51. [26] ISO 3977–2:1997. Gas turbines – procurement – Part 2: standard reference
[14] Yılmaz O. Yük-Frekans Kontrolü ve Türkiye Elektrik Sistemi Uygulamaları, conditions and ratings.
Genel Değerlendirmeler. ICCI; 2012. p. 145–51.

Das könnte Ihnen auch gefallen