Beruflich Dokumente
Kultur Dokumente
Two tanks are connected in parallel with a stream line. Heat and Cool the same material and control level of
both tanks. Implement this in PLC using Ladder Diagram programming language.
To detect temperature, RTD PT100 is used. This RTD has a range from -200°C to 650°C.
Let’s say that the temperature of liquid in the tank is to be maintained at 100°C. Calibrate RTD to operate in this
range.
RTD PT100 has a resistance of 100Ω when it is at 0°C and 138.4Ω when at 100°C.
Calibrate 4-20mA output such that when input is 0°C, it gives 4mA output and when it is 100°C, it gives output
20mA.