General Model EJA310


Specifications Absolute Pressure Transmitter

GS 01C22D01-00E [Style: S2]

The model EJA310 Absolute Pressure Transmitter can be


used to measure absolute gas, steam, or liquid pressure.
It outputs a 4 to 20 mA DC signal corresponding to the
measured pressure.
The model EJA310 also features remote setup and monitor-
ing through communications with the model BT200/100
BRAIN TERMINAL, CENTUM CS/XL system etc.

■ STANDARD SPECIFICATIONS
Refer to GS 01C22T02-00E for Fieldbus communication
type marked with “.”
Measurement Ranges:

Capsule Measurement Measurement Maximum


Span Range Overpressure
0.67 to 10 kPa 0 to 10 kPa abs 500 kPa abs
L {5 to 75 mmHg} {0 to 75 mmHg abs} {5 kgf/cm2 abs}
3.4 to 130 kPa 0 to 130 kPa abs 500 kPa abs
M
{25 to 960 mmHg} {0 to 960 mmHg abs} {5 kgf/cm2 abs} Process Temperature Limits:
-40 to 120 ⬚C (-40 to 248 ⬚F) (general use type for M and
0.06 to 3 MPa 0 to 3 MPa abs 4.5 MPa abs
A
{0.6 to 30 kgf/cm2} {0 to 30 kgf/cm2 abs} {45 kgf/cm2 abs}
A capsule)
-40 to 100 ⬚C (-40 to 210 ⬚F) (general use type for L
T01E.EPS
capsule)
(See ‘Optional Specifications’ for Explosion-protected
Output Signal “”: types)
4 to 20 mA DC, 2-wire system with digital communication
Ambient Humidity Limits:
Failure Alarm: 5 to 100 % R.H. (at 40 ⬚C)
Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more(standard) Working Pressure Limits:
Down-scale: -5%, 3.2 mA DC 13 Pa abs{0.1 mmHg abs} to maximum working pressure
Note: Applicable for Output signal code D and E For maximum working pressure, see ‘Model and Suffix
Codes.’
Conditions of Communication Line “”: For atmospheric pressure or below, see Figure 2.
Power supply voltage; 16.4 to 42 V DC*
Load resistance; See Figure 1. Power Supply Effect “”:
Note: In case of an intrinsically safe transmitter, external ⫾0.005 %/V (21.6 to 32 V DC, 350 ⍀)
load resistance includes safety barrier resistance. Mounting:
Communication distance; 2-inch pipe mounting.
2 km, when CEV polyethylene-insulated PVC- Mounting Position Effect:
sheathed control cables are used. 390 Pa {40 mmH2O}/90 ⬚.
Note: Communication distance varies depends on kind of No effect for displacement parallel to diaphragm.
cable.
These errors can be corrected by the zero adjustment.
Load capacitance; 0.22 ␮F or less.*
Load inductance; 3.3 mH or less.* Enclosure Classification:
Spacing from power line; 15 cm or more. JIS C0920 immersion proof (equivalent to LEC IP67 and
Input impedance of receiver connected receiving resistance: NEMA 4X)
10 k⍀ or more at 2.4 kHz Explosion-protected Construction:
* for General-use and Flameproof type. See ‘Optional Specification.’
Accuracy: Electrical Connection:
See Table 1 and Figure 3 See ‘Model and Suffix Codes.’
Ambient Temperature Limits: Process Connections:
-40 to 85 ⬚C (-40 to 185 ⬚F)(general-use type) See ‘Model and Suffix Codes.’
-30 to 80 ⬚C (-22 to 176 ⬚F)(with integral indicator)
(See ‘Optional Specifications’ for Explosion-protected Wetted Parts Material:
types) Diaphragm, cover flange, process connector and vent plug;
See ‘Model and Suffix Codes.’
Ambient Temperature Effect: Capsule gaskets; Teflon-coated JIS SUS316L.
See Table 1. Process connector gasket; PTFE (Teflon)

Yokogawa Electric Corporation GS 01C22D01-00E


2-9-32 Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Jan. 1996
Phone: 81-422-52-5690 Fax: 81-422-52-2018 12th Edition Apr. 2001
<<Contents>> <<Index>> 2
Flange Bolts and Nuts Material: External Zero Adjustment “”:
See ‘Model and Suffix Code’. Continuously Adjustable
Amplifier Housing: Resolution; 0.01% of span
Cast aluminum alloy or JIS SCS14A stainless steel Zero Adjustment Limits:
(optional) Zero can be fully elevated or suppressed as long as low and
Painting: high range values are within the measurement range limits
Polyurethane resin baked finish. of the capsule.
Deep sea moss green (Munsell 0.6GY3.1/2.0) Tag Plate:
Integral Indicator: JIS SUS304.
LCD digital indicator (optional) Weight:
Damping Time Constant: 3.9 kg (8.6 lb) without integral indicator, mounting bracket,
(Sum of time constants for amplifier assembly and capsule and process connector.
assembly) Add 1.4 kg (3.1 lb) for JIS SCS14A stainless steel
Amplifier assembly time constant; amplifier housing.
Can be set in 9 increments from 0.2 to 64 sec. EMC Conformity Standards: ,
Capsule assembly time constant; Approx. 0.2 sec.
EN61326, AS/NZS 2064

< Settings When Shipped > “”

Tag Number As specified in order *1 Calibration Range As specified in order


Higher Range Value
Output Mode ‘Linear’
Selected from mmH2O abs, mmHg abs,
Display Mode ‘Linear’ Torr, Pa abs, hPa abs, kPa abs, MPa abs,
Calibration Range
Operation Mode ‘Normal’ unless otherwise specified in order Units mbar abs, bar abs, ftH2O abs, kgf/cm2 abs,
inH2O abs, inHg abs, psia, psi abs or atm.
Damping Time ‘2 sec.’
Constant (Only one unit can be specified)
Calibration Range
Lower Range Value As specified in order T05E.EPS

*1: Up to 16 alphanumeric characters (including - and · ) will be entered in the amplifier memory.

100{750}

M and A capsule

600 L capsule
10{75}
E-10.5
R=
0.0236 Digital
External Communication
2.7{20}
load range Working
resistance BRAIN and HART pressure Applicable range
KPa abs 1{7.5}
250 {mmHg abs}
0.46
R (⍀) {3.45}
0.13{1}
0.1{0.75}

10.5 16.4 24.7 42


Power supply voltage E (V DC)
F02E.EPS 0.013{0.1}
0.01{0.075} -40 0 40 80 120
Figure 1. Relationship Between Power Supply Voltage and
Process temperature (˚C) 85
External Load Resistance
F02E.EPS

Figure 2. Working Pressure and Process Temperature

All Rights Reserved. Copyright © 1996, Yokogawa Electric Corporation GS 01C22D01-00E Apr. 02, 2001-00
<<Contents>> <<Index>> 3
Table 1. Accuracy and Ambient Temperature Effect
(With Linear Output, As Percent of 'x') *1
Capsule L M, A

Pref
Accuracy *2 *3 ±0.25 % For x ≥ Pref ±(0.15+0.1✕ x )% For x < Pref *4

Pref 1
±(0.4 + 1.2✕ x ✕ 4 ) % / 50 ˚C
*5

Zero
shift For x ≥ 1.35 kPa abs {10 mmHg abs} ±(0.3+0.5✕ Pref ) % / 50 ˚C
Pref 1 x
±(1.6✕ x ✕ 4 ) % / 50 ˚C
Ambient For x < 1.35 kPa abs {10 mmHg abs}
temperature
effect
1
±(0.8 + 1.2✕ Pref ✕ ) % / 50 ˚C
Total x 4 ±1.0 % / 50 ˚C For x ≥ Pref
shift *6 For x ≥ 1.35 kPa abs {10 mmHg abs} Pref
±(0.2+0.8✕ x ) % / 50 ˚C
Pref 1
±(0.4 + 1.6✕ x ✕ 4 ) % / 50 ˚C For x < Pref
For x < 1.35 kPa abs {10 mmHg abs}
T06E.EPS
*1: 'x' is the highest value among the absolute values of lower range value (LRV) and higher range value (HRV), and the span value
in a calibration range.
*2: Applicable minimum range ; 130 Pa abs{1 mmHg}
*3: Minimum input pressure on calibration
M and A capsule ; 2.7 kPa abs{20 mmHg abs}
L capsule, M and A capsule with code S1 ; 130 Pa abs{1 mmHg abs}
*4: 1 kPa{7.5 mmHg abs} or below measurement span, 4 seconds or more are required for the Damping time constant.
*5: The specification applies to the range of 0 to 85 ˚C. (below 0 ˚C, values is three times that given in the table)
*6: Combined zero and span shift

0.5
L.M.A
Accuracy
% 0.25

0
Value of 'x'
L capsule 0 1.5 {11} 5.4 {40} 10 kPa abs{75 mmHg abs}
M capsule 0 3.1 {22.9} 10.9 {80} 130 kPa abs{960 mmHg abs}
A capsule 0 0.07 {0.71} 0.25 {2.5} 3 MPa abs{30 kgf/cm2 abs}
(Pref)
F03E.EPS

Figure 3. Accuracy

Table 2. Value of 'Pref'


Capsule L M A
5.4 kPa abs 10.9 kPa abs 0.25 MPa abs
Pref {40 mmHg abs} {80 mmHg abs} {2.5 kgf/cm2 abs}
T07E.EPS

All Rights Reserved. Copyright © 1996, Yokogawa Electric Corporation GS 01C22D01-00E Feb. 01, 2000-00
<<Contents>> <<Index>> 4
■ MODEL AND SUFFIX CODES
Model Suffix Codes Description
EJA310 .................................. Absolute pressure transmitter
Output Signal -D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol) *1
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol) *6
Measurement span L............................. 0.67 to 10 kPa {5 to 75 mmHg}
(capsule) M............................. 3.4 to 130 kPa {25 to 960 mmHg}
A............................. 0.06 to 3 MPa {0.6 to 30 kgf/cm2}
Wetted parts material [Body] [Capsule] [Vent plug]
S............................ JIS SCS14A *3 JIS SUS316L *2 JIS SUS316
Process connections 0........................... without process connector (Rc1/4 female on the cover flanges)
1........................... with Rc1/4 female process connector
2........................... with Rc1/2 female process connector
3........................... with 1/4 NPT female process connector
4........................... with 1/2 NPT female process connector
 5........................... without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts material [Maximum working pressure]
(L capsule) (M capsule) (A capsule)
 A........................ SCM435 10 kPa abs 130 kPa abs 3 MPa abs
{75 mmHg abs} {960 mmHg abs} {30 kgf/cm2 abs}
B........................ SUS630 10 kPa abs 130 kPa abs 3 MPa abs
{75 mmHg abs} {960 mmHg abs} {30 kgf/cm2 abs}
Installation -2 . . . . . . . . . . . . . . . . . . . . . . Vertical impulse piping type, right side high pressure, process
connector upside *4
-3 . . . . . . . . . . . . . . . . . . . . . . Vertical impulse piping type, right side high pressure, process
connector downside *4
-6 . . . . . . . . . . . . . . . . . . . . . . Vertical impulse piping type, left side high pressure, process
connector upside *4
-7 . . . . . . . . . . . . . . . . . . . . . . Vertical impulse piping type, left side high pressure, process
connector downside *4
-8 . . . . . . . . . . . . . . . . . . . . . . Horizontal impulse piping type, right side high pressure *5
 -9 . . . . . . . . . . . . . . . . . . . . . . Horizontal impulse piping type, left side high pressure *5
Electrical connection 0.................... G1/2 female, one electrical connection
 2.................... 1/2 NPT female, two electrical connections without blind plug
3.................... Pg 13.5 female, two electrical connections without blind plug
4.................... M20 female, two electrical connections without blind plug
5.................... G1/2 female, two electrical connections and a blind plug
7.................... 1/2 NPT female, two electrical connections and a blind plug
8.................... Pg 13.5 female, two electrical connections and a blind plug
9.................... M20 female, two electrical connections and a blind plug
Integral indicator D................. Digital indicator
E................. Digital indicator with the range setting switch
 N................. (None)
Mounting bracket  A................ JIS SECC 2-inch pipe mounting (flat type)
B................ JIS SUS304 2-inch pipe mounting (flat type)
C................ JIS SECC 2-inch pipe mounting (L type)
D................ JIS SUS304 2-inch pipe mounting (L type)
N................ (None)
Optional codes /■ Optional specification
T08E.EPS
The ‘’ marks indicate the most typical selection for each specification. Example: EJA310-DMS5A-92NN/

*1: Refer to GS 01C22T01-00E for HART Protocol version.


*2: Diaphragm material is Hastelloy C-276. Indicated is other wetted parts materials.
*3: Indicates cover flange and process connector.
*4: If necessary, specify Mounting bracket code C or D.
*5: If necessary, specify Mounting bracket code A or B.
*6: Refer to GS 01C22T02-00E for Fieldbus communication.

All Rights Reserved. Copyright © 1996, Yokogawa Electric Corporation GS 01C22D01-00E Apr. 02, 2001-00
<<Contents>> <<Index>> 5
■ OPTIONAL SPECIFICATIONS
Item Description Code
Color change Amplifier cover only P
Painting
Coating change Epoxy resin-baked coating X1
Transmitter power supply voltage : 10.5 to 32 V DC ( 10.5 to 28 V DC for JIS intrinsically
Lightning protector safe type, 10.5 to 30 V DC for intrinsically safe type other than JIS, or 9 to 32 V DC for
A
Fieldbus communication type.)
Allowable current : Max. 6000 A ( 1✕40 µs), Repeating 1000 A ( 1✕40 µs ) 100 times
Degrease cleansing treatment K1
Oil-prohibited use Degrease cleansing treatment and with fluorinated oil filled capsule.
Operating temperature -20 to 80°C K2

Oil-prohibited use Degrease cleansing treatment and dehydrating treatment K5


with dehydrating treatment Degrease cleansing treatment and dehydrating treatment with fluorinated oilfilled capsule.
Operating temperature -20 to 80°C K6

P calibration ( psi unit ) D1


Calibration units *1 bar calibration ( bar unit ) ( See Table 3. ) D3
M calibration (kgf/cm2 unit ) D4
Sealing treatment to JIS Sealant(liquid silicone rubber) is coated on JIS SUS630 cover flange mounting nuts against
SUS630 nuts stress corrosion cracking. Y

Total length: 119 mm (standard: 34 mm); Total length when combining with Optional code
Long vent *2 U
K1, K2, K5, and K6: 130 mm. Material: SUS316.
Update time: 0.125 sec or less
Fast response *11 Amplifier assembly damping time constant: 0.1 to 64 sec in 9 increments. F1
Response time (with min. damping time constant): max. 0.3 sec
Output status at CPU failure and hardware error.
Failure alarm down-scale *3 C1
When combining with Optional code F1, output signal is -2.5%, 3.6 mA DC or less.
Stainless steel Amplifier housing material ; JIS SCS14A stainless steel (equivalent to JIS SUS316 cast
E1
amplifier housing *4 stainless steel or ASTM CF-8M)
130 Pa abs {1 mmHg abs}
Minimum input pressure : 130 Pa abs{1 mmHg abs} at range calibrating testing S1
Calibration *5
Gold-plate Surface of isolating diaphragms are gold plated, effective for hydrogen permeation. A1
Cover flange *6 M01
Mill Certificate
Cover flange, Process connector *7 M11
pressure test/ Test Pressure : 50 kPa{0.5 kgf/cm2} *8 Nitrogen(N2) Gas *10 T04
Leak test Certificate Retention time: 10 minutes
Test Pressure : 3 MPa{30 kgf/cm2} *9 T03
T09E.EPS

*1: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by Optional code D1, D3, and D4.
*2: Applicable for vertical impulse piping type (Installation code 2, 3, 6, or 7).
*3: Applicable for Output signal code D and E. The hardware error indicates faulty amplifier or capsule.
*4: Applicable for Electrical connection code 2, 3, 4 and 7. Not applicable for Optional code P and X1.
*5: Applicable for Capsule code M and A and smaller value than 53.3 kPa{400 mmHg abs} of higher range value(HRV).
If Optional code S1 is not specified, minimum input pressure will be 2.7 kPa abs{20 mmHg abs} for calibration testing.
For Capsule code L, the Optional code S1 is covered by standard feature. (Optional code S1 is not required to Capsule code L)
*6: Applicable for Process connections code 0 and 5.
*7: Applicable for Process connections code 1, 2, 3, and 4.
*8: Applicable for Capsule code L and M.
*9: Applicable for Capsule code A.
*10: Pure nitrogen gas is used for oil-prohibited use (Optional code K1, K2, K5, and K6).
*11: Applicable for Output signal code D and E. Consult Yokogawa when combining with Optional code for explosion protected type.
Table 3. Calibration Units
Measurement Optional Code
Span and
Range D1 ( psi Unit ) D3 ( bar Unit ) D4 ( kgf/cm2 Unit )
Span 0.2 to 2.95 inHg 6.7 to 100 mbar 5 to 75 mmHg
L
Range 0 to 2.95 inHg abs 0 to 100 mbar abs 0 to 75 mmHg abs
Span 1 to 38 inHg 34 to 1300 mbar 25 to 960 mmHg
M
Range 0 to 38 inHg abs 0 to 1300 mbar abs 0 to 960 mmHg abs
Span 8.6 to 430 psi 0.6 to 30 bar 0.6 to 30 kgf/cm2
A
Range 0 to 430 psi abs 0 to 30 bar abs 0 to 30 kgf/cm2 abs
T10E.EPS

All Rights Reserved. Copyright © 1996, Yokogawa Electric Corporation GS 01C22D01-00E Jan. 05, 2001-00
<<Contents>> <<Index>> 6
■ OPTIONAL SPECIFICATIONS (For Explosion Protected types “”)
For FOUNDATION Fieldbus explosion protected type , see GS 01C22T02-00E.
Item Description Code
FM Explosion proof Approval *4
Explosion proof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
FF1
Hazardous (classified) locations, indoors and outdoors ( NEMA 4X )
Division 2, 'SEALS NOT REQUIRED', Temp. Class : T6 Amb. Temp. :-40 to 60°C (-40 to 140°F)
Electrical connection : 1/2 NPT female *1
FM Intrinsically safe Approval *4
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1 Hazardous Locations.
Factory Mutual (FM) Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,
Groups E, F & G, and Class III, Division 1 Hazardous Locations.
FS1
Enclosure : "NEMA 4X", Temp. Class : T4, Amb. Temp. : -40 to 60°C (-40 to 140°F)
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 ␮H
[Groups C, D, E, F and G] Vmax=30 V, Imax=225 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 ␮H
Electrical connection : 1/2 NPT female *1
Combined FF1and FS1 *4 FU1
Electrical connection : 1/2 NPT female *1
CENELEC (KEMA) Flameproof Approval *4
EExd IIC T4, T5, T6
Amb. Temp. : T4 and T5 ; -40 to 80°C (-40 to 176°F), T6 ; -40 to 75°C(-40 to 167°F) KF1
Max. process Temp. : T4 ; 120°C(248°F), T5 ; 100°C(212°F), T6 ; 85°C(185°F)
Electrical connection : 1/2 NPT female, Pg 13.5 female and M20 female *2
CENELEC (KEMA) CENELEC (KEMA) Intrinsically safe Approval *4
EEx ia IIC T4, Amb. Temp. : -40 to 60°C(-40 to 140°F)
KS1
Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 ␮H
Electrical connection : 1/2 NPT female, Pg 13.5 female and M20 female *2
Combined KF1, KS1 and Type N Approval *4
Type N Approval Ex nA IIC T4, Amb. Temp. : -40 to 60°C(-40 to 140°F) U=30 V, I=165 mA KU1
Electrical connection : 1/2 NPT female, Pg 13.5 female and M20 female *2
CSA Explosion proof Approval *4
Explosion proof for Class I, Division 1, Groups B, C and D
Dustignitionproof for Class II/III, Division 1, Groups E, F and G
Division2 'SEALS NOT REQUIRED' , Temp. Class : T4, T5, T6 Encl Type 4x CF1
Max. Process Temp. : T4 ; 120°C (248°F), T5 ; 100°C (212°F), T6 ; 85°C (185°F)
Amb. Temp. :-40 to 80°C (-40 to 176°F)
Canadian Standards Electrical connection : 1/2 NPT female *1
Association
(CSA) CSA Intrinsically safe Approval *4
Class I, Groups A, B, C and D Class II and III, Groups E, F and G
Encl Type 4x, Temp. Class : T4, Amb. Temp. : -40 to 60°C (-40 to 140°F) CS1
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 ␮H
Electrical connection : 1/2 NPT female *1
Combined CF1 and CS1 *4
CU1
Electrical connection : 1/2 NPT female *1
SAA Flameproof, Intrinsically safe and Non-sparking Approval *4
Ex d IIC T4/T5/T6, IP67 class I, Zone 1, Amb. Temp. : -40 to 80°C (-40 to 176°F)
Standards Association
Max. Process Temp. : T4 ; 120°C (248°F), T5 ; 100°C (212°F), T6 ; 85°C (185°F)
of Australia SU1
Ex ia IIC T4, IP67 class I, Zone 0 Ex n IIC T4, IP67 class I, Zone 2
(SAA) Ui=30 V DC, Ii=165 mA DC, Wi=0.9 W, Amb. Temp. : -40 to 60°C (-40 to 140°F)
Electrical connection : 1/2 NPT female, Pg 13.5 female and M20 female *2
JIS Flameproof Approval, Ex do IIC T4X *3 *4 *6
JF3
Japanese Industrial Amb. Temp. :-20 to 60°C , Process Temp. : -20 to 120°C
Standards (JIS) JIS Intrinsically safe Approval, Ex ia IIC T4 *5
Amb. Temp. :-20 to 60°C , Process Temp. : -20 to 120°C JS3

Attached flameproof Electrical connection : G1/2 female 1 pc. G11


packing adapter *3 Applicable cable : O.D. 8 to 12 mm 2 pcs. G12
T11E.EPS
*1: Applicable for Electrical connection code 2 and 7.
*2: Applicable for Electrical connection code 2, 3, 4, 7, 8, and 9.
*3: If cable wiring is to be used to a JIS flameproof type transmitter, add the YOKOGAWA-assured flameproof packing adapter.
*4: Applicable for Output signal code D and E. For intrinsically safe approval, use the safety barrier certified by the testing laboratories
(BARD-400 is not applicable).
*5: Applicable for output signal code D. See page 8 for JIS-approved safety barrier.
*6: In case that the ambient temperature exceeds 50°C or t-hat the ambient temperature exceeds 45°C with the process temperature of
90°C or above, use heat-resistant cables with maximum allowable temperature of 75°C or above.

All Rights Reserved. Copyright © 1996, Yokogawa Electric Corporation GS 01C22D01-00E Apr. 02, 2001-00
<<Contents>> <<Index>> 7
■ DIMENSIONS
● Vertical Impulse Piping Type
Process connector upside (INSTALLATION CODE '6' )
External indicator Unit : mm (approx.inch)
Process connection conduit connection
259(10.20) (Optional)
197 (7.76)
110 (4.33)
97 146 (5.75) High Low
(3.82) pressure 27 pressure
Process side (Note) (1.06) side
connector
(Optional) Internal
indicator
(2.83)
72

(1.81)
(Optional)
46

(5.83)
(3.07)

148
ø78
234(9.21)

Terminal
(4.02)

side
102

Conduit
Ground connection
terminal
( 2.09)

Vent/Drain plug
12
53

(0.47)
Zero
Mounting bracket adjustment
(L-type, Optional) 2-inch pipe
(O.D. 60.5mm)

Process connector downside (INSTALLATION CODE '7' )


( 2.09)
53

Vent/Drain plug
(4.02)
102
(2.83)
72

High Low
pressure pressure
side (Note) side

Process
connections
F04E.EPS

● Horizontal Impulse Piping Type (INSTALLATION CODE '9' )

Conduit 110 (4.33)


94 72 connection
12 Zero
(3.70) (2.83) (0.47) adjustment
Internal
indicator
(3.07)

(Optional) Terminal
ø78

External indicator
conduit connection side
(7.76)
197

(Optional)
(5.75)
(6.38)

146

Ground
162

terminal

High Low
pressure pressure
side (Note) side
Process
connection
Process Vent plug 27 (1.06)
(4.88)

46 connector
124

(1.81) (Optional) 64 (2.52)


Drain plug
125 (4.92)
(1.85)
47

Mounting bracket
2-inch pipe (O.D. 60.5mm)
(Flat-type, Optional)

F06E.EPS

Note: When Installation code 2, 3, or 8 is selected, high and low pressure side on above figure are reversed.
(i.e. High pressure side is on the right side.)

All Rights Reserved. Copyright © 1996, Yokogawa Electric Corporation GS 01C22D01-00E Aug. 01, 2000-00
<<Contents>> <<Index>> 8
● Terminal Configuration ● Terminal Wiring
+
SUPPLY Power supply and output terminal

CHECK + External indicator(ammeter) terminal*1


Communication Ground terminal


Terminals(BT200 etc.) SUPPLY CHECK CHECK METER
Connection hook*1 *1: When using an external indicator or a check meter,
Connection hook
the internal resistance must be 10 ⍀ or less.
Not available for Fieldbus communication(Output signal
code F).
F05E.EPS

< Ordering Information > “” < Safety Barrier for JIS Intrinsically Safe Type >
Specify the following when ordering
1. Model, suffix codes, and optional codes Supplier Type Model
2. Calibration range and units: MTL3046B
MTL
1) Calibration range can be specified with range value MTL4041B
Isolator
specifications up to 5 digits KFD2-STC3-Ex 1
(excluding any decimal point) for low or high range limits P+F
KFD2-STV3-Ex 1-1, 2, 3
within the range of -32000 to 32000. T001E.EPS
2)Specify only one unit from the table, ‘Settings when
shipped.’ Note: Requirements of capacitance and inductance for cable
3.Select linear or square root for output mode and display wiring.
mode. Cw ≤ Co – 11[nF]
Note: If not specified, the instrument is shipped set for Lw ≤ Lo – 730[µH]
linear mode. (Co: Max. external capacitance)
(Lo: Max. external inductance)
4. Select normal or reverse for operation mode
Note: If not specified, the instrument is shipped in normal < Reference >
operation mode. 1. JIS SUS316L stainless steel; Equivalent to AISI 316L.
5. Display scale and units (for transmitters equipped with 2. JIS SUS316 stainless steel; Equivalent to AISI 316.
integral indicator only) 3. JIS SUS304 stainless steel; Equivalent to AISI 304.
Specify either 0 to 100 % or engineering unit scale and 4. JIS S25C carbon steel; Equivalent to AISI 1025.
‘Range and Unit’ for engineering units scale: 5. JIS SECC Carbon steel.
Scale range can be specified with range limit specifications 6. Teflon; Trademark of E.I. DuPont de Nemours & Co.
up to 5 digits (excluding any decimal point) for low or 7. JIS SCM435 chrome molybdenum steel; Equivalent to
high range limits within the range of -19999 to 19999. AISI 4137.
6. Tag Number (if required) 8. JIS SUS630 stainless steel; Equivalent to ASTM 630.
9. Hastelloy; Trademark of Haynes International Inc.
< Related Instruments > “” 10. JIS SCS14A stainless steel; Equivalent to JIS SUS316
Power Distributor: Refer to GS 1B4T1-E,1B4T2-E. cast stainless steel or ASTM CF-8M.
BRAIN TERMINAL: Refer to GS 1C0A11-E 11. HART; Trademark of the HART Communication
Foundation.
12. FOUNDATION; Trademark of Fieldbus Foundation.

All Rights Reserved. Copyright © 1996, Yokogawa Electric Corporation GS 01C22D01-00E Apr. 02, 2001-00