CATALOGUE

A complete range for metering,


monitoring & power quality

2017
Contents
The SOCOMEC group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 4 to 11
Why choose SOCOMEC? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 14
Selection guide measurement and monitoring system for electrical installations . . . . . . . p. 16
Selection guide active energy meters and pulse concentrators . . . . . . . . . . . . . . . . . . . . . p. 20
Selection guide multifunction meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 22
Selection guide current transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 24
Selection guide energy monitoring and management software . . . . . . . . . . . . . . . . . . . . . p. 136

Multi-circuit metering & measurement Measurement devices


The DIRIS Digiware range p. 26
Current
new transformers
5 to 5000 A
Current sensors p. 106
DIRIS Digiware TE / TR / TF
p. 28 p. 44
Measurement
Wireless metering & measurement shunts
p. 120
new
Current sensors Other
DIRIS B-30 TE / TR / TF components
p. 38 p. 44 1 to 6000 A
p. 122

Single-circuit metering, measurement & analysis Indicators &


transducers
new new new
Analogue
meters
COUNTIS E DIRIS A DIRIS Q p. 124
p. 52 p. 74 p. 102

Digital
Gateways, dataloggers and interfaces meters
p. 124

new
DIRIS G DATALOG
p. 126 p. 130

Wireless Communication
communication accessories
interfaces
p. 132 p. 134

Software suite
Embedded web server Energy management Cloud energy management
WEBVIEW software HYPERVIEW software N’VIEW

new

p. 137 p. 138 p. 139

Software tools
Management software for
COUNTIS and DIRIS

p. 140

Catalogue 2017 3
An independent manufacturer
The benefit of a specialist

3,500 m2
of test platforms
One of the leading
independent power testing
innovative!
labs in Europe

Since its foundation more than


90 years ago, SOCOMEC continues
to design and manufacture its core
products in Europe. Notably solutions

60,000
for its primary mission: the availability,
control and safety of low voltage
electrical networks.

on-site interventions
per year
Nearly 400 experts in
As an independent manufacturer,
commissioning, technical the Group is committed to constant
audit, consultancy and innovation to improve the energy
maintenance performance of electrical installations in
infrastructures as well as industrial and
commercial sites.

Throughout its history, SOCOMEC


has constantly anticipated market
changes by developing cutting-edge
technologies, providing solutions that
are adapted to customer requirements

10 %
and fully in keeping with international
standards.

“Optimising the performance of your


of turnover invested system throughout its life cycle” - this
is the commitment carried out every
in R&D day by the SOCOMEC teams around
the world, wherever your business
Always at the cutting-edge is located.
of technology for innovative,
SYDIV 181 B

high-quality products

MADE IN
EUROPE

4 Catalogue 2017
Your energy, our expertise
Critical Power and interruptions occurring on the primary
Ensuring the availability and power supply,
storage of high quality power • changeover of static, high availability sources
for transferring the supply to an operational
back-up source,

© Datadock
With its wide range of continuously evolving
• permanent monitoring of the electrical
products, solutions and services, Socomec
facilities to prevent failures and reduce
are recognised experts in the cutting-edge
operating losses,
technologies used for ensuring the highest
availability of the electrical power supply to • energy storage for ensuring the proper
critical facilities and buildings, including: energy mix of buildings and for stabilisation
of the power grid.
• static uninterruptible power supplies (UPS)
for high-quality power free of distortions

Power Control & Safety • isolation and on load breaking for the most
Managing power and demanding applications,
protecting persons and • continuity of the power supply to electrical
facilities facilities via manual or automatic changeover
switching systems,

APPLI 575A
Active in the industrial switching market since
• protection of persons and assets via fuse-
its foundation in 1922, Socomec is today an
based and other specialist solutions.
undisputed leader in the field of low voltage
switchgear, providing expert solutions that
ensure:

Energy Efficiency • measuring energy consumption, identifying


Managing the energy sources of excess consumption and raising
performance of buildings the awareness of occupants about their
impact,
• limiting reactive energy and avoiding the

APPLI 571A
Socomec solutions, from current sensors associated tariff penalties,
through to a wide choice of innovative
• using the best available tariffs, checking utility
scalable software packages are driven by
bills and accurately distributing energy billing
experts in energy performance. They meet the
among consumer entities,
critical requirements of facility managers and
operators of commercial, industrial and local • monitoring and detecting insulation faults.
authority buildings for:

Expert Services • measurement and analysis of a wide


Enabling available, safe range of electrical parameters leading to
and efficient energy recommendations for improving the site’s
power quality,
• optimisation of the total cost of ownership
APPLI 760A

Socomec is committed to delivering a wide and support for a safe transition when
range of value-added services to ensure migrating from an old to a new generation of
the reliability and optimisation of end-users’ equipment.
equipment:
• consultancy, deployment and training from
• prevention and service operations to lower the project engineering stage through to final
the risks and enhance the efficiency of procurement.
operations,

Catalogue 2017 5
Adapted solutions
to meet your energy objectives
HEAVY
Controlling and securing your energy
SMART BUILDINGS
Reducing your energy bills and energy dependency

DELPHYS MX COUNTIS E energy


UPS meter and DIRIS A
multifunction meter
DIRIS Digiware ENERGY ATyS automatic SUNSYS PCS²
(PMD)
multi-circuit MANAGEMENT and remotely energy converter
measurement software operated transfer and energy
system packages switch storage system

NAVAL SHIPS
Energy conversion in environments with harsh restrictions

SHARYS IP rectifier NETYS RT-M UPS and other SIRCO


UPS customised load break
products switches

SHOPPING CENTERS
Assuring your business continuity and visitor safety

COUNTIS E ATyS M automatic EMERGENCY ENERGY


energy meter and remotely CPSS, secure MANAGEMENT
and multi- operated modular power supply software
utility pulse transfer switch for emergency packages
concentrator systems

PUBLIC DISTRIBUTION AND SMART GRID RENEWABLE ENERGY


Helping you to meet the challenge of energy demand and response Guaranteeing the performance, security and
durability of your photovoltaic facilities

SUNSYS PCS² TIPI low-voltage Auxiliary unit SIRCO and SIDER DIRIS Digiware SUNSYS PCS² INOSYS load break PV string
Power Conversion feeder pillar with with ATyS load break switches multi-circuit Power Conversion switches with enclosure
System and DIRIS multi- transfer measurement System and tripping function combiner box
Storage function meter switch system Storage

6 Catalogue 2017
POWER PLANTS
Securing the piloting of your high-security installations
and installations with seismic constraints

INDUSTRY
SHARYS IP UPS and other DIRIS Digiware
rectifier customised multi-circuit
products measurement
system

FUSERBLOC fuse Safety enclosure with


combination switches switch disconnector for
standard and explosive
environment

TRANSPORT
Securing the continuity of your installations

ATyS Bypass MASTERYS IP+ DIRIS A


‘zero outrage’ Rail UPS multifunction
solution meter (PMD)

DATA CENTRES
Meeting the challenge of the availability
and performance of your energy

MODULYS RM GP DELPHYS Xtend GP


Rack-mount modular hot scalable UPS system
UPS

ATYS automatic and DIRIS Digiware multi-


remotely operated circuit measurement
transfer switch system

MEDICAL FACILITIES INDUSTRY


Assuring patient safety and the energy Ensuring the competitiveness of your site
performance of your hospital

MASTERYS IP+ ENERGY Components for DIRIS Digiware SIRCO


UPS  for harsh MANAGEMENT distribution enclosure multi-circuit load break
Green Power 2.0 ATyS automatic and DIRIS Digiware industrial software with FUSERBLOC measurement switches
UPS remotely operated multi-circuit environments packages fuse-combination system
transfer switch measurement switches
system

Catalogue 2017 7
Expert Services your partner
enabling available, safe and efficient energy

SOCOMEC is committed to
deliver a wide range of value-
added services to ensure
the availability of your critical
installation, the safety of your site
operations and the performance
optimisation of your low voltage
equipment during its life cycle.
The expertise and proximity of our
specialists are there to ensure
the reliability and durability of your
equipment.

APPLI 724 A
Key figures
More than 370 Socomec experts supported by 175 engineers and technicians from our distributors, drive the solutions to your specific needs.

Our global presence includes:


• 10 branches in France,
• 12 European subsidiaries,
• 8 Asian subsidiaries,
• representatives in 70+ countries.

Subsidiaries
CARTE 063 H

Distributors

Contact us

On-site service management Technical hotline network Certified expertise


• 60,000 service operations per year (mainly • 20+ languages spoken. • 4,500 hours of technical training deployed
preventive visits). • 3 advanced technical support centres. per year (product, methodology and safety).
• 98% Service Level Agreement compliance • 100,000+ incoming calls handled per year.
rate.
CORPO 269 A
APPLI 571 A

SITE 588 A

8 Catalogue 2017
A cutting-edge laboratory
the backing of an expert

Created in 1965, SOCOMEC’s


laboratory brings its expertise to
guarantee the reliability and the
conformity of our products and
solutions.
Since 2015, the laboratory renamed
Tesla Lab – Power Testing and
Certification in 2015, offers its testing
and certification services to all its
customers.

CORpO 441 A
Proven expertise Vast range of tests International partnership
Tesla Lab is an independant laboratory The laboratory has 100 MVA The laboratory is recognised by the major
specialised in testing of LV switchgears, (Icc 100 kA rms 1 s) short-circuit platform,  certification bodies worldwide: member
components and switchgear assemblies. three 10 kA overload platforms and many of ASEFA and LOVAG, it is accredited
4 M€ has been invested since 2011 in other test facilities covering 2000 m² for: by COFRAC, UL (CTDP), CSA (shared 
this 2000 m² laboratory, where 30 experts • functional tests, certification) and DEKRA (WMT).
guarantee the quality of the performed tests, • mechanical tests: endurance, The partnership with many international
making the Tesla Lab one of the most modern • dielectric tests, certification bodies guarantees the quality
laboratories in Europe. and safety requirements in each country.
• environmental tests: vibrations,
• Ingress Protection (IP),
• temperature rise tests up to 60 °C ambient.

Implementation of standard IEC / EN 61439


Electrical switchgear An original manufacturer Tesla Lab accredited by COFRAC
manufacturers according to IEC / EN 61439 With its world-class testing facilities, the 
IEC / EN 61439 standards define the  standards Tesla Lab can perform all of the tests 
requirements of “Low voltage switchgear Socomec offers a wide range of original required by IEC / EN 61439 standards for 
assemblies” as well as the tests necessary manufacturer solutions complying with switchgear assemblies
to ensure the achievement of the specified IEC 61439 standards.
levels of performance. The compliance • FLEXYS and CADRYS cabinet We can therefore help you to:
with these standards gives a guarantee of systems designed for distribution panel • define a verification program,
safety and performance to the user of the applications. • perform conformity tests,
equipment
• Local switching and equipment cabinets • issue test reports in order to get
covering requirements in power availability certification from third party certification
and safety. bodies (ASEFA, LOVAG, DEKRA, UL, 
• Components for integration. CSA, COFRAC, ASTA…).

Catalogue 2017 9
a high-quality power supply
innovative solutions

Critical equipment requires an


uninterrupted and continuously
available power supply, using
energy of the highest quality. Our
uninterruptible power supplies
(UPS), static transfer systems
(STS), energy storage systems

range 568 B
and rectifiers comprise the most
complete ranges in the world and
cover a very wide variety of
applications for every sector of
activity.

100% availability Continuous innovation Always attentive to customer


High quality energy supply at any moment embedded in the Dna of SOCOMeC, needs
is strategic in many fields such as innovation is a challenge that itself undergoes With our extensive sales and after-sales
telecommunications, data processing or constant reinvention: network, we are always there for you.
certain industrial processes. It is vital to a • First French manufacturer to offer static Our clients are happy with the quality of
number of medical applications. In all these our products and their availability and our
power supplies (1968)
sectors, SOCOMeC has over 45 years of commitment to their needs.
experience at your disposal. • First UPS to use PWM technology (1980)
• First high-performance range of UPS with
Customised solutions IgBT technology (1996)
Underpinned by significant r&D resources, • First modular UPS, with scalable and
our products are constantly evolving to adapt redundant architecture (2001)
to the needs of our customers. • First manufacturer to integrate hybrid
Our products have the approval of some components (2001)
of the most stringently demanding users: • First 200-kVa UPS with IgBT rectifier (2003)
telecom companies, nuclear industry, naval Keeping on track with Socomec
industry, and many more. • new battery charging design (2004)
• Dynamic energy storage system: the SUNSYS PCS2 power converter
Recognised expertise flywheel (2006) storage solution
SOCOMeC UPS solutions (inverters) have • First UPS with 96% efficiency in online
received the most prestigious awards in the double conversion mode (2008)
industry; testimony to the way we listen to the • Most compact STS with 19" hot-swappable
needs of our users: rack design (2009)
• award for excellence in customer service • Most compact 900-kVa UPS (2010)
(2004), • First complete UPS range (10-2400 KW/
• award for product innovation (2006), kVa) with triple-tier technology, 96%
• award for europe's best product range efficiency and an output power factor of 1
strategy (UPS) (2009), (2012)
• award for product innovation (2011), • "Forever Young" design for modular UPS This bidirectional power converter is
• award for excellence in product (2014) the key element of the energy storage
differentiation (2013) system. It ensures that the batteries are
charged and discharged according to the
• award for european company of the year in
required functions.
the UPS sector (2014)
• award for european technological leadership
(UPS) (2015)
VALID FOR FRANCE VALID FOR ITALY

10 Catalogue 2017
Webspace at your service
all our solutions can be adapted to your needs

www.socomec.com
Expertise, customised solutions, products and
services, downloads… All yours in a couple
of clicks! 1 2 3 4

1 Tap into our expertise

2 Discover our customised


solutions

3 Access all our products and


services

4 Download photos,

CORPO 385 A
documentation, software and
CAD files

www.diris-digiware.com
Check out the dedicated site about DIRIS
Digiware, our measuring and monitoring
system. It gives you all the information
you need, including videos, images and
documentation on the most revolutionary
solution on today's market.

CORPO 466 A

Follow us on social media!

Catalogue 2017 11
Alphabetical index

A DIRIS Digiware_____________________________________________26
DIRIS Digiware D and C_____________________________________28
Analogue meters_________________________________________ 124
DIRIS Digiware I____________________________________________34
DIRIS Digiware U___________________________________________32

C DIRIS G_________________________________________________ 126


DIRIS Q800_____________________________________________ 102
Communication accessories_______________________________ 134
COUNTIS and DIRIS management software tools_____________ 140
COUNTIS E0x_____________________________________________52
COUNTIS E1x_____________________________________________54
H
COUNTIS E2x_____________________________________________56 Hour counters___________________________________________ 124

COUNTIS E3x_____________________________________________58 HYPERVIEW____________________________________________ 138


COUNTIS E4x_____________________________________________60
COUNTIS E63_____________________________________________62
COUNTIS ECix_____________________________________________64 M
Current transformers______________________________________ 106 Measurement shunts_____________________________________ 120
Modular transducers______________________________________ 124

D MULTIS L50_______________________________________________70

Datalogger______________________________________________ 130
Digital meters____________________________________________ 124
DIRIS A10_________________________________________________74
N
N’VIEW_________________________________________________ 139
DIRIS A14_________________________________________________78
DIRIS A20_________________________________________________82
DIRIS A40/A41____________________________________________86
DIRIS A60_________________________________________________92
O
DIRIS A80_________________________________________________98 Other electrical measurement devices_______________________ 124
DIRIS B-30________________________________________________38 Other products, measurement devices_______________________ 122

12 Catalogue 2017
P T
PTI: CT automatic short-circuiter____________________________ 122 TE sensors________________________________________________44
TF sensors________________________________________________50

R TR sensors________________________________________________48
Transducers_____________________________________________ 124
RETROFIT Line____________________________________________66
Transformer with integrated converter (CTA-VA)_______________ 122

S V
Selection guide
Voltage transformer BTV 25________________________________ 122
COUNTIS E______________________________________________20
Current transformers______________________________________24
DIRIS A_________________________________________________22
DIRIS Digiware___________________________________________16
W
Energy monitoring and management software_______________ 136 WEBVIEW_______________________________________________ 137

Selector switches________________________________________ 124 Why choose SOCOMEC?___________________________________14


Sensor PT100 - screw type________________________________ 122 Wireless communication interfaces__________________________ 132

Catalogue 2017 13
Why choose SOCOMEC?

Innovative and high performance solutions manufactured by specialists in


Metering, monitoring

electrical energy management


& power quality

A leader in Energy & Power A monitoring device specialist Experts in energy performance
Management • The DIRIS G communication gateways analysis
• With the COUNTIS E, DIRIS A and and DATALOG H dataloggers centralise • Energy management software analyses
associated current sensor ranges, measurement data via hard-wired or multi-utility energy data in order to
SOCOMEC has developed one of radio link. reduce energy consumption.
the most advanced multifunction • Webserver solutions embedded in the • HYPERVIEW offers a wide range of tools
measurement ranges on the market, DIRIS A and DIRIS G products enable for raising user awareness of energy
dedicated to improving your energy the real-time monitoring of electrical consumption, creating reports and for
performance. parameters and alert users in case of dashboard display.
anomaly.

Metering Measurement Power Factor Correction

DIRIS Digiware Multi-circuit DIRIS Digiware Multi-circuit COSYS PFC Power Factor Correction
Power Monitoring Devices Power Monitoring Devices without harmonic protection

COUNTIS E Single-circuit DIRIS A Single-circuit Power Factor Correction with


Energy meters Multifunction meters harmonic protection
COSYS PFC

DIRIS B Wireless
Power Monitoring
Device

14 Catalogue 2017
An independent partner working closely with our customers

Ranges that combine Customised support and partner


performance and quality proximity
The DIRIS A and DIRIS Digiware ranges Our manufacturer’s expertise naturally
are compliant with the latest IEC 61557-12 extends to a complete offer of services.
standard dedicated to multi-measurement From the required preliminary assessment
devices (PMD*). The COUNTIS E range of your installation via in-depth analysis and
complies with the requirements of the latest application of the data, through to software
MID** directive (B+D module). adaptation and training, the experts at
SOCOMEC provide customers with support in
* Performance Measuring and Monitoring Devices.
** MID: Measuring Instruments Directive. improving their energy efficiency and reaching
energy performance targets.

Data centralisation Monitoring Analysis

DIRIS G communication gateways WEBVIEW web server HYPERVIEW software

HYPERVIEW is hosted
on a local server.
DATALOG H Dataloggers

N’VIEW software

WEBVIEW is embedded N’VIEW is hosted on


in the DIRIS G a Cloud server.
communication gateway.

Catalogue 2017 15
Selection guide
Measurement and monitoring system for electrical installations
DIRIS Digiware
Multi-circuit metering

Build your own system


& measurement

Control and power supply interface Voltage measurement


(24 VDC) module

or +

DIRIS Digiware D DIRIS Digiware C DIRIS


with display without screen Digiware U-x

Current measurement modules Current sensors

+
+

DIRIS DIRIS DIRIS TE TR TF


Digiware I-3x Digiware I-4x Digiware I-6x Solid Split-core Flexible
3 current 4 current 6 current
sensor inputs sensor inputs sensor inputs

Dedicated website

Find the right solution for your needs in just a few clicks
http://www.diris-digiware.com

16 Catalogue 2017
Selection guide
Measurement and monitoring system for electrical installations
DIRIS Digiware

Control and power supply interface

Application Centralisation and display of data Data centralisation Repeater

DIRIS Digiware D-40 D-50 C-31 C-32


p. 28 p. 28 p. 28 p. 28
Function
Centralising measurement points: • • • •
High-resolution LCD display (configuration, selection and visualisation display of circuits) • •
Repeater •
Power supply
24 VDC • • • •
Communication
RS485 Modbus output input •
Digiware Bus • • • •
Ethernet Modbus TCP •

Voltage measurement module

Application Metering Monitoring Analysis

DIRIS Digiware U U-10 U-20 U-30


p. 32 p. 32 p. 32
Multi-measurement
U12, U23, U31, V1, V2, V3, f • • •
U system, V system •
Ph/N unbalance •
Ph/Ph unbalance •
Quality analysis
THDv1, THDv2, THDv3, THDu12, THDu23, THDu31 • •
Individual harmonics U & V (up to rank 63) •
Voltage dips, cutoffs and surges (EN50160) •
Alarms
On threshold •
History of average values
45 days (max) •
Format
Width/number of modules 18 mm / 1 18 mm / 1 18 mm / 1

Catalogue 2017 17
Selection guide
Measurement and monitoring system for electrical installations
DIRIS Digiware

Current measurement modules

Application Metering Monitoring Analysis Monitoring Analysis Metering

DIRIS Digiware I I-30 I-31 I-33 I-35 I-43 I-45 I-60 I-61
p. 34 p. 34 p. 34 p. 34 p. 34 p. 34 p. 34 p. 34
Number of current inputs
3 3 3 3 4 4 6 6
Metering
± kWh, ± kvarh, kVAh • • • • • • • •
Load curves • • • •
Multi-tariff • • • •
Multi-measurement
I1, I2, I3, In, ΣP, ΣQ, ΣS, ΣPF • • • • • • • •
P, Q, S, PF per phase • • • •
Predictive power • •
Current unbalance (Inba, Idir, Iinv, Ihom, Inb) • •
Phi, cos Phi, tan Phi • •
Quality
THDi1, THDi2, THDi3, THDin • • • •
Individual harmonics I (up to level 63) • •
Overcurrents • •
Alarms
On threshold • •
Inputs/outputs 2/2 2/2
History of average values
45 days (max) • •
Format
Width/number of modules 18 mm / 1 18 mm / 1 18 mm / 1 18 mm / 1 27 mm / 1.5 27 mm / 1.5 36 mm / 2 36 mm / 2

18 Catalogue 2017
Selection guide
Measurement and monitoring system for electrical installations
DIRIS Digiware

Current sensors

Solid-core current sensors


new
Suitable for new installations
match the pitch of protective
devices

TE-18 TE-25 TE-35 TE-45 TE-55 TE-90


p. 44 p. 44 p. 44 p. 44 p. 44 p. 44

Nominal current In (A) 5 … 2000 5 … 20 25 … 63 40 … 160 63 … 250 160 … 630 400 … 1000 600 … 2000

Actual coverage range (A) 0.1 … 2400 0.1 … 24 0.5 … 75.6 0.8 … 192 1.26 … 300 3.2 … 756 8 … 1200 12 … 2400

Aperture (mm) Ø 8.4 Ø 8.4 13.5 x 13.5 21 x 21 31 x 31 41 x 41 64 x 64


Dimensions (mm) 28 x 20 x 45 28 x 20 x 45 25 x 32.5 x 65 35 x 32.5 x 71 45 x 32.5 x 86 55 x 32.5 x 100 90 x 126 x 24.6
Connection RJ12 RJ12 RJ12 RJ12 RJ12 RJ12 RJ12
For demands greater than 2000 A, the 5 A / RJ12 adapter guarantees the compatibility of the TCs.

Split-core current sensors

Suitable for existing installations

TR-10 TR-16 TR-24 TR-36


p. 48 p. 48 p. 48 p. 48

Nominal current In (A) 25 … 600 25 … 75 32 … 100 63 … 200 200 … 600

Actual coverage range (A) 0.5 … 720 0.5 … 90 0.64 … 120 1.26 … 240 4 … 720

Aperture (mm) Ø 10 Ø 16 Ø 24 Ø 36
Dimensions (mm) 25 x 39 x 71 30 x 42 x 74 45 x 44 x 95 57 x 42 x 111
Connection RJ12 RJ12 RJ12 RJ12
For demands greater than 600 A, the 5 A / RJ12 adapter guarantees the compatibility of the TCs.

Flexible current sensors


Suitable for existing installations
with space restrictions or with
a high-intensity current

TF-55 TF-120 TF-300


p. 50 p. 50 p. 50

Nominal current In (A) 150 … 6000 150 … 600 500 … 2000 1600 … 6000

Actual coverage range (A) 3 … 7200 3 … 720 10 … 2400 32 … 7200

Aperture (mm) Ø 55 Ø 120 Ø 300


Connection RJ12 RJ12 RJ12

Catalogue 2017 19
Selection guide
Active energy meters and pulse concentrators
COUNTIS E
Single-circuit metering,

Which type Which load


of network? current?
measurement &

Single-phase Single-phase Single-phase Single-phase Three-phase Three-phase


analysis

Network - Input current Direct Direct Direct Direct Direct Direct


up to 32 A up to 40 A up to 63 A up to 80 A up to 63 A up to 80 A
new new new

Active energy meters: COUNTIS E E00 / E02 E03 / E04 E05 / E06 E10 / E11 / E12 E13 / E14 E15 / E16 E17 / E18 E20 / E21/E22 E23 / E24
p. 52 p. 52 p. 52 p. 54 p. 54 p. 54 p. 54 p. 56 p. 56
Main specifications
MID: EN 50470 module B + D certification • (E02) • (E04) • (E06) • (E12) • (E14) • (E16) • (E18) • (E22) • (E24)
RS485 Modbus • • •
M-Bus • •
Ethernet Modbus TCP/RTU •
Width 1 module 1 module 1 module 3 modules 2 modules 2 modules 2 modules 4 modules 4 modules
Input voltage 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 … 400 VAC 230 … 400 VAC
Functions
Total/partial energy kWh •/- •/• •/• •/• (E10, E11) •/• •/• •/• •/• •/•
Active power / Reactive power •/• •/• •/- •/• •/• •/• •/• (E22) •/•
Dual tariff for kWh • • • (E11, E12) • • • • (E21/22) •
Total/partial energy kvarh •/• •/• •/• •/• •/• • (E22) •/•
kVA via COM via COM • • • • (E22) •
Load curve
Measurement (I, V, P, Q, S, F and PF) • • • • • • (E22) •
CT connection indication
Birectional (energy consumption and production) • • • • • • (E22) •
Integrated web server •
Compatibility web server DIRIS G • • •
Accuracy
Active energy (IEC 62053-21) class 1 class 1 class 1 class 1 class 1 class 1 class 1 class 1 class 1
Reactive energy (according to IEC 62053-23) class 2 class 2 class 2 class 2 class 2 class 2 (E22) class 2
Active energy (EN 50470) class B (E02) class B (E04) class B (E06) class B (E12) class B (E14) class B (E16) class B (E18) class B (E22) class B (E24)
Characteristics
Metrological LED • • • • • • • • •
Pulse output 100 Wh 100 Wh 100 Wh 100 Wh 100 Wh 100 Wh 100 Wh 100 Wh
Sealing cover (MID version only) • (E02) • (E04) • (E06) • (E12) • (E14) • (E16) • (E18) • (E22) • (E24)
Phase/neutral inversion protection •

Pulse concentrator COUNTIS ECi2 COUNTIS ECi3


p. 64 p. 64
Case 4 modules 4 modules
Logical inputs 7 7
Analogue inputs 2
ON/OFF output (alarm) 1 1
Partial, total, daily, weekly or monthly kWh or other types of data (liters, m3…) • •
Load curve from 8 to 30 minutes • •
RS485 Modbus • •

20 Catalogue 2017
Selection guide
Active energy meters and pulse concentrators

Which MID Communication View data on


accuracy? certification? or pulse output? the web server?

Three-phase Three-phase 3 x Single-phase


Three-phase
Direct Direct Direct
CT/5 A
up to 80 A up to 100 A up to 100 A
new

E25 / E26 E27/ E28 E30 / E31 / E32 E33 / E34 E35 / E36 E63 E40 / E41 / E42 E43 / E44 E45 / E46
p. 56 p. 56 p. 58 p. 58 p. 58 p. 62 p. 60 p. 60 p. 60

• (E26) • (E28) • (E32) • (E34) • (E36) • (E42) • (E44) • (E44)


• • •
• • •

4 modules 4 modules 7 modules 7 modules 7 modules 7 modules 4 modules 4 modules 4 modules
230 … 400 VAC 230 … 400 VAC 230 … 400 VAC 230 … 400 VAC 230 … 400 VAC 230 … 400 VAC 230 … 400 VAC 230 … 400 VAC 230 … 400 VAC

•/• •/• •/• (E31) •/ via COM (E34) •/ via COM (E36) •/• •/• •/ via COM (E44) •/ via COM (E46)
•/• •/• •/- •/ via COM •/ via COM •/ via COM •/- •/ via COM •/ via COM
• • • (E31 / E32) up to 4 via com up to 4 via com up to 4 via com up to 4 via com up to 4 via com
•/• •/• via COM via COM via COM via COM via COM
• • via COM via COM via COM via COM via COM
via COM via COM via COM via COM via COM
• • via COM via COM via COM via COM via COM
• • •
• • • (E33) • (E35) • (E43) • (E45)

• •

class 1 class 1 class 1 class 1 class 1 class 1 class 0,5s class 0,5s class 0,5s
class 2 class 2 class 2 class 2 class 2
class B (E26) class B (E28) class B (E32) class B (E34) class B (E36) class C (E42) class C (E44) class C (E46)

• • • • • • • • •
100 Wh 100 Wh configurable
• (E26) • (E28) • (E32) • (E34) • (E36) • (E42) • (E44) • (E46)
• • • • • • •

COUNTIS ECi pulse concentrator

Enables pulses from water, gas, L m3 kWh €


compressed air, electricity meters or even
analogue sensors (light, temperature, DIRIS B-30 RF DIRIS B-30 RF

wind etc.) to be registered and stored. All WEBVIEW

data can be centralised and managed by


an energy efficiency software via RS485
communication.
COUNT_344_A_X.AI

CO CO
UN UN
TIS TIS
E Ci3 E Ci3

RS485 Ethernet
COUNTIS ECi DIRIS Digiware DIRIS A COUNTIS E DIRIS B-30 RS DIRIS G-40 / G-60 HYPERVIEW

Catalogue 2017 21
Selection guide
Multifunction meters
DIRIS A
Single-circuit metering,

Which Which
application? functions?
measurement &

Multifunction metering
Application
analysis

(PMD)

new

DIRIS A10 DIRIS A14 DIRIS A20


p. 74 p. 78 p. 82
Multi-measurement
Currents, voltages (ph / ph and ph / n), active / reactive / apparent powers, power factor, frequency • • •
4th CT for neutral current measurement
Voltage/current unbalance
(max. average value (max. average value (max. average value
Currents, voltages, frequency (average values)
for currents) for currents) for currents)
Max. power demand • • •
Temperatures Internal
Tangent phi • cos phi
Hour meter • •
Memorisation of min / max instantaneous values •
Metering
MID: EN 50470 module B + D certification •
kWh (+ /-), kvarh (+ /-) kWh (+), kvarh (+) • kWh (+), kvarh (+)
Logical input(s) for pulse meter(s)
Multi-tariff meters • •
Pulse output(s) 1 as standard with optional module
Active energy accuracy / IEC 62053-21 class 1
Active energy accuracy / IEC 62053-22 class 0.5 s • • •
Active energy accuracy / IEC 62053-22 class 0.2 s
Active energy (EN 50470) Class C
Reactive energy accuracy / IEC 62053-23 class 2 • • •
Compability with IEC 61557-12 • • •
Power management
Load curves (period 5, 8, 10, 15, 20 and 30 minutes) •
Predictive power
Power quality
THD voltages, currents and neutral currents Row 51 Row 63 Row 51
Individual harmonics
EN 50160
Sag, swell and outages, overcurrent
RMS 1/2 period curve backup for events
Management of fault currents
Plug-in modules

• 1 digital input as standard • 1 digital output


• 1 digital output as standard • Modbus RS485
• Modbus as standard communication
for 1 reference • 3 In / 1 out + alarm

22 Catalogue 2017
Selection guide
Multifunction meters

Which
Which Which
communication
dimensions? options?
protocol?

Power monitoring Power monitoring & Power monitoring & residual current
(PMD) events analysis (PMD) monitoring (PMD+RCM)

DIRIS A40 DIRIS A41 DIRIS A60 DIRIS A80


p. 86 p. 86 p. 92 p. 98

• • • •
• •
• •

• • • •

• • • •
by temperature sensor PT100 by temperature sensor PT100 by temperature sensor PT100
• •
• • • •
optional optional • •

• • • •
up to 6 with optional module up to 6 with optional module up to 6 with optional module

up to 6 with optional module up to 6 with optional module up to 6 with optional module

• • • •

• • • •
• • • •

optional optional • •
• • • •

Row 63 Row 63 Row 63 Row 63


Row 63 Row 63 Row 63 Row 63
• •
• •
• •

• 2 pulse outputs • Memory fitted as standard


• Modbus RS485 communication • 2 pulse outputs
• PROFIBUS DP communication • Modbus RS485 communication
• Modbus RS485 communication
• Ethernet communication (available with Modbus gateway) • Ethernet communication
• Ethernet communication
• 2 analogue outputs (available with Modbus gateway)
(available with Modbus gateway)
• 2 inputs / 2 outputs • 2 analogue outputs
• Memory • 2 inputs / 2 outputs
• Temperature inputs • Temperature inputs

Catalogue 2017 23
Selection guide
Current transformers

TCA TCA TCA TCB TCB TCB TCB TCB TCB


Type TRB 60 TRB 70 TRB 135
transformers

14 21 22 17-20 26-30 28-30 26-40 32-40 44-50


Dimensions Primary wound Cable-through Bar or cable-through
Class 0.5 0.5 0.5 1 0.5/1 1 1 0.5/1 0.5/1 1 0.5/1 0.5/1
Current

T2CB T2CB
0.2S version (1) (2)
26-30 32-40
p. 107 p. 109 p. 110
Rating (A)
0.5
5
10 5

15 20 5
20 …
25 40
30
40
50 *
60 25
25
… 40
75 …
150 …
80 150
150
100
125 60
… 60
150 300 … 50
160 400 … 80
100 750 …
200 * 500 100 75
… *
250 600 150 … …
… 150 750 1000 *
300
600 … 200
400 750 150

500 750 …
600 1250
750
800
1000
1200
1250
1500
1600
2000
2500
3000
4000
5000
Dimensions
Height 75.5 85.5 85 65 65 65 65 61 70 75.5 88.5 98.5
Width 61 71 135 45 45 49.5 49.5 75.5 49.9 61 71 86
Depth 35 45 60 30 30 35 50 48 68 48 58 58
Cable (Ø mm) 14 21 22.5 17.5 26 28 26 32 44
Bar 1 20x5 30x10 30x10 32x18 40x10 50x12
Bar 2 20x10 (x2) 40x12 30x5 (x2) 40x10 (x2)
Bar 3
* Class 1.
(1) Please see T2RB 115 for a primary wound 0.2S version. Dimensions are different from TRB 135.
(2) Please see T2CA 225 for a cable-through 0.2S version. Dimensions are different from TCA 22.

24 Catalogue 2017
Selection guide
Current transformers

TCB TCB TCD TCB TBA


TBA 60 TBA 100 TBA 103 TBA 127 TO 23 TO 58 TO 812 TO 816
44-63 55-80 85-100 100-125 80
Bar or cable-through Bar-through Split-core
0.5 0.5 0.5 0.5 0.5/1 0.5 0.5 0.5 0.5 1/3 0.5/1 0.5/1 0.5
T2CB T2BA T2BA T2BA
44-63 100 103 127
p. 111 p. 114 p. 118

100

400

250

200 * 200 1000 250
… 300 … …
1600 … 1600 300 1500
400 … 400
1500 … …
2000 *
2000 2000 1000 400
750 600 …

… … 4000 1200
1000 * 1500 …
3000 … 4000 1200
2000 1000
3000 … …
3000 5000

105.5 123.5 184.8 184.8 129 117 167 150 175 106 158 198 243
96 120 172 172 88 96 129 99 100 93 125 155 195
58 58 52 52 48 68 78 58 55 58 58 58 79
44 55 85 100
63x10 80x10 100x10 123x30 60x30 84x34 100x55 103x41 128x38 33x23 85x55 125x85 165x85
50x10 (x2) 60x30 80x10 (x3) 100x10 (x3)
60x10 (x2)

Catalogue 2017 25
DIRIS Digiware
Measurement and monitoring system for electrical installations
Multi-circuit metering
& measurement

The DIRIS Digiware system


Multiple current acquisition modules connected to the voltage acquisition module and the display.

• A single centralised • A single voltage • Current measurement • Current sensors


control unit measurement modules (I)
module (U)

A single connection
for communication
DIRIS_DW_011_A_1_CAT

Exclusive to Socomec,
patented

DIRIS Digiware wins a trophy!

The SOCOMEC DIRIS Digiware energy measuring and monitoring solution came first in the 20th edition of the Mesure
magazine's Prize for Technology and was the overall winner in the energy efficiency category.

26 Catalogue 2017
DIRIS Digiware
Measurement and monitoring system for electrical installations

Advantages of the system

Flexible Multi-circuit Plug & Play


Shared functions Ability to monitor several loads via a RJ12 current sensor connection
• Common display. single current measurement module thanks • Fast: automatic detection of ratings and
• A single voltage reference for to independent current inputs. verification of current flow direction.
the entire system. • Reliable: identification of cables by colour-
• Single auxiliary power supply. coding and wiring control by the system.
Installation of components close • Safe: disconnection of the current sensor
to the load secondary under load.
• Modules and sensors can be installed Accurate RJ45 interconnection of modules
at the closest point to the loads to be Accuracy of measurements guaranteed (Digiware Bus)
measured. according to IEC standard 61557-12: • Fast: a single connection, no tool
• Elimination of hazardous voltage • Class 0.5 from 2 % to 120 % of rated required.
on panel doors. current for the global measurement chain • Intelligent: allows communication and
Compact design (associated with TE / TF current sensors). interaction between various modules.
• U and I modules of variable size • Class 0.2 for the meter alone. • Reliable: ensures auxiliary power
(1 to 2 modules). supply to modules without the risk of
• System suited to integration in existing disconnection.
or space-constrained installations. Auto-configuration of parameters
Wide choice of current sensors Cost effective • Network type.
• Solid, split-core or rogowski coil. • Implementation in a quarter of the time vs • Load type.
• Various sizes and formats. existing technologies. • Addressing of modules connected
• Numerous accessories allow the system • Save space in panels. to the Bus.
to be installed in all panels configurations. • Common voltage measurement
functions, display and communication.
• Up to 30% return on investment.

APPLI_636_A

Catalogue 2017 27
DIRIS Digiware D and C
Control and power supply interfaces
Multi-circuit metering

The solution for


& measurement

> Industry
> Building
> Infrastructure
> Data center

diris-dw_005_a_cat
diris-dw_006_a_cat

DIRIS Digiware D-40/D-50 DIRIS Digiware C-31


Centralisation and display of data Centralisation

Strong points
Configuration
with EasyConfig, > Centralising and displaying
see page 140.
measurement data
> A single power supply for the
entire system
Function > A single RS485 or Ethernet
output for the entire system
DIRIS Digiware D-40 and D-50 DIRIS Digiware C-31
DIRIS Digiware D remote screens give you: For applications without a local display
- a local view of the data issued by the DIRIS DIRIS Digiware C-31 interfaces centralise all Conformity to standards
Digiware U and I modules, the system data.
- a power supply to the DIRIS Digiware modules, Through their RS485 Modbus output, they > IEC 61557-12
- access to this data over Ethernet (D-50) or make all this information available to energy
RS485 (D-40) efficiency software (DIRIS G communication
gateways are available to communicate via
Ethernet - Modbus TCP). > ISO 14025
Via an RS485 connection, the
DIRIS Digiware D-50 screen also acts as a DIRIS Digiware C-31 interfaces and C-32
gateway, centralizing all information issued by repeaters are 24 VDC powered.
DIRIS A, DIRIS B and COUNTIS E and making
this information available on Ethernet. > UL
DIRIS Digiware screens are 24 VDC powered.

Advantages
DIRIS Digiware D-40 and D-50 DIRIS Digiware C-31
• High-resolution graphic screen. Compact: Centralise your measurement data
• Made safe by a 24 VDC supply: elimination on 1 module without a local screen, for a
of hazardous voltage on cabinet doors. complete system
• IP65 front panel. - Single 24V power supply (no dangerous
• Ergonomic and easy to use with 10 direct voltage on Digiware modules for an
access buttons for: uninterruptible connection),
- Measurement information - A single RS485 communication.
- Selecting outputs
- Configuration equipment.
• Centralising measurement points:
- Selecting the circuit
- Displaying data.

28 Catalogue 2017
DIRIS Digiware D and C
Control and power supply interfaces

Connections
DIRIS Digiware D-40
Digiware

Digiware
Bus

LIYCY-CY
NC
RS485

RS485
120 Ω 120 Ω
SLAVE
Digiware Bus
SUPPLY
diris-dw_057_a_1_cat

24 VDC 24 VDC
24 V

(20 W max) (20 W max)

*
DIRIS Digiware D-40
(*) 1A / 24 VDC fuse protection is recommended if the 24 VDC power supply is not provided by Socomec.

DIRIS Digiware D-50


RS485 Digiware Ethernet

Ethernet
Ethernet

Digiware
Bus DIRIS Digiware D-50
24 VDC
LIYCY-CY (20 W max)
NC Digiware Bus
diris-dw_056_a_1_cat

*
MASTER
SUPPLY

24 VDC
24 V

(20 W max) RS485


120 Ω
(*) 1A / 24 VDC fuse protection is recommended if the 24 VDC power supply is not provided by Socomec.

DIRIS Digiware C-31


Power supply Digiware Bus Communication
RS485 24VDC
Supply

DIRIS Digiware C
SUPPLY

diris-dw_023_b_1_x_cat
diris-dw_012_a_1_x_cat

DIGIWARE BUS

diris-dw_018_b_1_x_cat
24 V

LIYCY-CY
NC
NC
RS485

RJ45

1 2
ON

DIRIS Digiware C-32


Power supply Digiware Bus
Com Supply
RS485 Modbus 24VDC
SUPPLY

diris-dw_024_b_1_x_cat
diris-dw_013_a_1_x_cat

DIGIWARE BUS

diris-dw_057_a_1_en_cat
24 V

IN
RJ45

OUT

7 mm 7 mm

Catalogue 2017 29
DIRIS Digiware D and C
Control and power supply interfaces

Dimensions
DIRIS Digiware D-40/D-50 DIRIS Digiware C-31

90
diris-dw_037_b_1_x_cat

92

diris-dw_062_a_1_x_cat

C-3x

92 27 18 44 15
18 65

Configuration
Equipment consumption Calculation rules for the max. number of products on the Digiware Bus
Product Power delivered (W) Power consumed (W) The total power consumed by the equipment connected to the Digiware Bus
must not exceed the power from the 24 VDC supply.
Power supply The power supply must not exceed 20 W/70°C or 27 W/40°C.
P15 100-240 VAC / 24 VDC 15 Size with P15 power supply (ref: 4829 0120) delivering 15 W
Cables For example, it is possible to use
• 1 DIRIS Digiware D-50 display (2W)
50 metre package 1.5
• 1 DIRIS Digiware voltage module U-xx (0.72 W)
System interfaces • 50 metres of cable (1.5 W)
DIRIS Digiware D-x0 2 and
DIRIS Digiware C-31 0.8 • 20 DIRIS Digiware current modules I-3x (20 x 0.52 = 10.4 W)
 Total power = 14.62 W
Module voltage or
DIRIS Digiware U-xx 0.72 • 9 DIRIS Digiware current modules I-4x (9 x 1.125 = 10.125 W)
 Total power = 14.345 W.
Current modules Size with a 24 VDC power supply delivering a maximum of 20 W
DIRIS Digiware I-3x 0.52 For example, it is possible to use
DIRIS Digiware I-4x 1.125 • 1 DIRIS Digiware D-50 display (2W)
DIRIS Digiware I-6x 0.7 • 1 DIRIS Digiware voltage module U-xx (0.72 W)
Repeater • 50 metres of cable (1.5 W)
and
DIRIS Digiware C-32 1.5 • 30 DIRIS Digiware current modules I-3x (30 x 0.52 = 15.6 W)
 Total power = 19.82 W
or
• 14 DIRIS Digiware current modules I-4x (14 x 1.125 = 15.72)
 Total power = 19.97 W.
Repeater
Whenever the power consumption is higher than 20 W or the distance is greater than 100 m, a DIRIS Digiware C-32 repeater is required.
In a DIRIS Digiware system, a maximum of 2 repeaters may be used.

100 m max 100 m max


or max. 20 W power consumption or max. 20 W power consumption
diris-dw_039_b_1_gb_cat

DIRIS Digiware U-xx I-3x C-32 I-3x


D-x0
24 VDC I-4x 24 VDC I-4x
power supply power supply

30 Catalogue 2017
DIRIS Digiware D and C
Control and power supply interfaces

Specifications
Electrical characteristics DIRIS Digiware D-40/D-50 features
DIRIS Digiware C-31 Mechanical specifications
Input voltage 24 VDC ± 20 % - 20 W max Type of screen Capacitive touch-screen technology, 10 keys
Connection Removable screw terminal block, 2 positions, Screen resolution 350 x 160 pixels
stranded or solid 0.2-2.5 mm² cable Front panel protection index IP65
P15 power supply Specifications 100-240 VAC/ 24 VDC - 0,63 A - 15 W Communication
Modular format - Dimensions (H x L): 90 x 25 mm
Ethernet RJ45 10/100 Mbs Modbus TCP gateway function (D50)
Communication specifications RJ45 Digiware Control and power supply interface function
Digiware Bus Modbus RTU communication function
RS485 2-3 wires
Function Connection between DIRIS Digiware modules (D50 input / D40 output)
Cable type Specific Socomec cable with RJ45 connections Upgrade and configuration via type B micro
USB
USB connector
RS485
Electrical characteristics
Connection type 2 to 3 half duplex wires
Power supply 24 VDC +10% / -20%
Protocol Modbus RTU
Power consumption 2 VA
Baudrate 1200 … 115 200 bauds
Environmental specifications
Function Data configuration and reading
Storage temperature -20 … +70°C
Location Single-point on DIRIS Digiware C
Operating temperature -10 … +55°C
Mechanical specifications
Humidity 95% at 40°C
Casing type DIN-rail mounting module and base Installation category,
CAT III, 2
Casing protection index IP20 / IK06 degree of pollution
Front panel protection index IP40 on the nose in modular assembly / IK06 Ports D-40 D-50
Environmental specifications Digiware
Inputs Digiware
RS485
Ambient operating temperature -10 … +70°C
Outputs RS485 Ethernet
Storage temperature -25 … +70°C
Operating humidity 55 °C / 97% HR
Operating altitude < 2000 m

References
DIRIS Digiware Reference Digiware connection cables Reference
D-40 Multipoint display, RS485 output 4829 0199 Length 0.10 m 4829 0181
D-50 Multipoint display, Ethernet output 4829 0201 Length  0.20 m 4829 0188
C-31 System interface 4829 0101 Length 0.50 m 4829 0182
C-32 Repeater 4829 0103 RJ45 cables Length 1 m 4829 0183
for Digiware
Power supply Reference Bus Length  2 m 4829 0184
P15 Power supply 100-240 VAC/ 24 VDC 15 W 4829 0120 Length  5 m 4829 0186
Length  10 m 4829 0187
Accessories
Reel 50 m + 100 connectors 4829 0185
To be ordered
Description of accessories Reference Digiware bus terminating resistor (supplied with C and D devices) 4829 0180
in multiples of
Fuse circuit breakers to protect voltage USB configuration cable 4829 0050
4 5601 0017
inputs (type RM) 1 pole + neutral Single-point display Reference
gG 10x38 0.5 A fuses 10 6012 0000
DIRIS D-30(1) Single-point display for DIRIS Digiware I-4x 4829 0200
(1) DIRIS D-30 display characteristics see page 43.

Expert Services

Require integration onto your network?


No problem for our "Expert Services" team. They will fully integrate all your SOCOMEC devices,
audit your system, commission selected equipment and train your staff on its use.
For further information, please contact your nearest SOCOMEC branch.

Catalogue 2017 31
DIRIS Digiware U
Voltage measurement module
Multi-circuit metering

The solution for


& measurement

> Industry
> Building
> Infrastructure
> Data center

diris-dw_005_a_cat

DIRIS Digiware U-10/U-20/ U-30

Strong points
Configuration
with EasyConfig, > 1 single voltage
see page 140.
measurement point for the
entire system
> Plug & Play
Function > Compact
The DIRIS Digiware U module measures voltage for the entire system. This pools together all om
municatio

n
voltage measurements. RJ45 (Digiware Bus) cables
The Digiware RJ45 Bus allows you to pass voltage measurements as well as power supply and are available.
RJ45
communication to all connected products.

Advantages Conformity to standards

• 1 single voltage measurement point for the • No hazardous voltage on cabinet doors. > IEC 61557-12
entire system. • Adapted to all types of network:
• Single point of protection for voltage single-phase, three-phase.
measuring.
• A complete, dedicated solution: > ISO 14025
- metering,
- monitoring voltage,
- quality analysis of the supplied voltage.
> UL

32 Catalogue 2017
DIRIS Digiware U
Voltage measurement module

Voltage measurement module


Application Metering Monitoring Analysis

DIRIS Digiware U U-10 U-20 U-30


Multi-measurement
U12, U23, U31, V1, V2, V3, f • • •
U system, V system •
Ph/N unbalance •
Ph/Ph unbalance •
Quality analysis
THDv1, THDv2, THDv3, THDu12, THDu23, THDu31 • •
Individual harmonics U & V (up to rank 63) •
Voltage dips, cutoffs and surges (EN 50160) •
Alarms
On threshold •
History of average values
45 days (max) •
Format
Width/number of modules 18 mm / 1 18 mm / 1 18 mm / 1

Dimensions Specifications
DIRIS Digiware U Measuring characteristics
Voltage measurement - DIRIS Digiware U
Characteristics of the network
50-300 VAC (Ph/N) - 87-520 VAC (Ph/Ph) - CAT III
measured
Frequency range 45 … 65 Hz
Frequency accuracy Class 0.02
Network type Single-phase/ Two-phase / Two-phase with
neutral / Three-phase / Three-phase with neutral
Measurement by voltage Primary: 400 000 VAC
transformer Secondary: 60, 100, 110, 173, 190 VAC
90

Input consumption ≤ 0.1 VA


Permanent overload 300 VAC Ph/N
diris-dw_059_a_1_x_cat

Accuracy of voltage measurement Class 0.2


Connection Removable screw terminal block, 4 positions,
stranded or solid 0.2 … 2.5 mm² cable
U-xx
Communication specifications
44 15 USB
18 65 Protocol Modbus RTU on USB
Function Configuration of DIRIS Digiware U and I modules
Location On each DIRIS Digiware U and I measurement module
Connection Type B micro USB connector

References
Digiware connection cables Reference DIRIS Digiware Reference
Length 0.10 m 4829 0181 U-10 Metering 4829 0105
Length  0.20 m 4829 0188 U-20 Monitoring 4829 0106
Length 0.50 m 4829 0182 U-30 Analysis 4829 0102
RJ45 cables Length 1 m 4829 0183
for Digiware
Length  2 m 4829 0184 Accessories
Bus
To be ordered
Length  5 m 4829 0186 Description of accessories Reference
in multiples of
Length  10 m 4829 0187 Fuse holder to protect voltage inputs (type
4 5601 0018
Reel 50 m + 100 connectors 4829 0185 RM) 3 pole
Digiware bus terminating resistor (supplied with C and D devices) 4829 0180 gG 10x38 0.5 A fuses 10 6012 0000
USB configuration cable 4829 0050

Catalogue 2017 33
DIRIS Digiware I
Current measurement modules
Multi-circuit metering

The solution for


& measurement

> Industry
> Building
> Infrastructure
> Data center
diris-dw_004_a_cat

diris-dw_007_a_cat

diris-dw_007_a_cat
DIRIS Digiware I-3x DIRIS Digiware I-4x DIRIS Digiware I-6x

Strong points
Configuration
with EasyConfig, > Multi-circuit
see page 140.
> Plug and Play
> Compact
> High-precision measurement
Function chain
DIRIS Digiware I modules measure The RJ45 and RJ12 connections allow you
consumption and monitor the system at the to connect modules very quickly and to
closest point to the loads. The flexibility of automatically configure connected current
Conformity to standards
these modules allows you to allocate the sensors:
> IEC 61557-12
loads to be measured or monitored through - communication address,
independent current inputs. - load type,
For example: - sensor type and ratio,
- 1 three-phase load, - automatic rating and verification of current > ISO 14025
- 3 single-phase loads. travel direction.
Wiring errors are also prevented and
installation is simplified.
> UL

Advantages
• RJ45 and RJ12 rapid connection. • Compliant with standard IEC 61557-12,
• Available with 3, 4 or 6 inputs. guaranteeing the quality and accuracy of
• Single-output or multi-output for maximum the system:
optimisation of the number of products. - class 0.5 for the 2 - 120% rated current
• Compact format: 1 or 2 modules sized for global measurement chain In (with TE/TF
integration at the closest point to the loads. current sensors).
• A complete, dedicated solution:
- metering,
- monitoring,
- quality analysis.

34 Catalogue 2017
DIRIS Digiware I
Current measurement modules

Current measurement modules


Application Metering Monitoring Analysis Monitoring Analysis Metering

DIRIS Digiware I I-30 I-31 I-33 I-35 I-43 I-45 I-60 I-61
Number of current inputs
3 3 3 3 4 4 6 6
Metering
± kWh, ± kvarh, kVAh • • • • • • • •
Load curves • • • •
Multi-tariff • • • •
Multi-measurement
I1, I2, I3, In, ΣP, ΣQ, ΣS, ΣPF • • • • • • • •
P, Q, S, PF per phase • • • •
Predictive power • •
Current unbalance (Inba, Idir, Iinv,
• •
Ihom, Inb)
Phi, cos Phi, tan Phi • •
Quality
THDi1, THDi2, THDi3, THDin • • • •
Individual harmonics I (up to level 63) • •
Overcurrents • •
Alarms
On threshold • •
Inputs/outputs 2/2 2/2
History of average values
45 days (max) • •
Format
Width/number of modules 18 mm / 1 18 mm / 1 18 mm / 1 18 mm / 1 27 mm / 1.5 27 mm / 1.5 36 mm / 2 36 mm / 2

Dimensions
DIRIS Digiware I-3x / I-6x DIRIS Digiware I-4x
150

21
45
90

diris-dw_022_b_1_x_cat
diris-dw_060_a_1_x_cat

I-3x I-6x

44 15
18 36 65 27 27
45
58
72

Catalogue 2017 35
DIRIS Digiware I
Current measurement modules

Connections
Associated current sensors
Various types of current sensors are connected to the DIRIS Digiware: closed (TE), split core (TR) or flexible (TF). This range of sensors can be adapted to all types of
new or existing installations.. A rapid RJ12 connection makes wiring easy and reliable and prevents wiring errors. The DIRIS Digiware system automatically recognises
the sensor size and type. This guarantees the overall accuracy of the DIRIS Digiware + current sensor measurement chain.
For more information: voir page 44.

Network and connection examples


I3x
Three-phase Three-phase
3P - 3CT (1 three-phase load) 3P - 1CT (3 balanced, three-phase loads)

L1 L1
L2 L2
L3 L3
diris-dw_032_c_1_x_cat

diris-dw_033_c_1_x_cat

1 1 1 1 1 1
3 3 3
3

V1 V2 V3 VN I01 I02 I03 V1 V2 V3 VN I01 I02 I03


V I V I

I4x
Three phase + neutral Single-phase
3P+N - 4CT (1 three-phase load + Neutral measured) 1P+N-1CT (4 single-phase loads)

L1 L1
L2 N
L3
N

1 1
1 1 1
diris-dw_038_c_1_x_cat

diris-b_061_a_1_x_cat

1 1 1 1
3 +N

V1 V2 V3 VN I01 I02 I03 I04 V1 V2 V3 VN I01 I02 I03 I04


V I V I

1. 0.5 A gG / 0.5 A class CC fuses. 3


CT: Current sensor Load

Accessories
Digiware plug-in connector
With the Digiware plug-in connector you can disconnect a Digiware module form the Bus while ensuring the DIRIS Digiware system continues to
run downstream. This accessory is particularly useful in applications with retractable drawers or critical applications such as in data centres.

36 Catalogue 2017
DIRIS Digiware I
Current measurement modules

Specifications

Measuring characteristics Outputs - DIRIS Digiware I-45


Number of
Current measurement - DIRIS Digiware I 2
outputs
Number of current inputs I-3x: 3 / I-45: 4 / I-6x: 6
Relay type 230 VAC ±15 % - 1 A
Associated current sensors Solid TE, split-core TR, flexible TF current sensors
Function Configurable alarm (current, power, etc.) when threshold is
Accuracy of current 0.2 DIRIS Digiware class only exceeded or remote controlled status
measurement Class 0.5 with TE or TF sensors
Class 1 with TR sensors Connection Removable screw terminal block, stranded or
solid 0.2-2.5 mm² cable
Connection Specific Socomec cable with RJ12 connectors
Inputs - DIRIS Digiware I-45 Communication specifications
Number of inputs 2 USB
Type / Power supply Non-insulated input, internal polarisation 12 VDC max, 1mA Protocol Modbus RTU on USB
Input functions Logic status, pulse meter, multi-tariff Function Configuration of DIRIS Digiware U and I modules
Connection Removable screw terminal block, stranded or Location On each DIRIS Digiware U and I measurement module
solid 0.14-1.5 mm² cable Connection Type B micro USB connector

References
DIRIS Digiware Reference Digiware connection cables Reference
I-30 Metering - 3 current inputs 4829 0110 Length 0.10 m 4829 0181
I-31 Metering + load curve - 3 current inputs 4829 0111 Length  0.20 m 4829 0188
I-33 Monitoring - 3 current inputs 4829 0128 Length 0.50 m 4829 0182
I-35 Analysis - 3 current inputs 4829 0130 RJ45 cables Length 1 m 4829 0183
for Digiware
I-43 Monitoring - 2 inputs/ 2 outputs - 4 current inputs 4829 0129 Bus Length  2 m 4829 0184
I-45 Analysis - 2 inputs/ 2 outputs - 4 current inputs 4829 0131 Length  5 m 4829 0186
I-60 Metering - 6 current inputs 4829 0112 Length  10 m 4829 0187
I-61 Metering + load curve - 6 current inputs 4829 0113 Reel 50 m + 100 connectors 4829 0185
Digiware bus terminating resistor (supplied with C and D devices) 4829 0180
Accessories Reference USB configuration cable 4829 0050
Digiware x 5 plug-in connector 4829 0605 voir page 43.
(1) DIRIS D-30 display characteristics

Expert Services

Require integration onto your network?


No problem for our "Expert Services" team. They will fully integrate all your SOCOMEC devices,
audit your system, commission selected equipment and train your staff on its use.
For further information, please contact your nearest SOCOMEC branch.

Catalogue 2017 37
DIRIS B-30
Wireless power monitoring devices
& wireless metering

The solution for


Measurement

> Industry
> Building
> Infrastructure
> Local authority
diris-b_010_a_1_cat

diris-b_009_a_1_cat
Configuration
with EasyConfig,
see page 140.

DIRIS B-30 DIRIS B-30


Radio frequency (wireless) RS485
Function
Strong points
The DIRIS B-30 is a power monitoring device in The DIRIS B-30 is connected to current
a modular format that communicates wirelessly sensors(1) (RJ12 connection) that are suitable for > Plug & Play
or via RS485. The 4 RJ12 independent current all types of installation: solid TE, split-core TR, > Global accuracy class 0.5
inputs of the device allow it to manage several and flexible TF current sensors. in accordance with
types and number of circuits: for example, (1) See page 44.
IEC 61557-12
4 single-phase loads or 1 three-phase load +
1 single-phase load. > Multi-circuit
> Communication
Advantages
Conformity to standards
Plug & Play Multi-circuit
A rapid RJ12 connection makes wiring easy and • 4 current measurement inputs allow you > IEC 61557-12
reliable and prevents wiring errors. Automatically to configure multiple circuits in order to
> EN 50160
addressing and configuring the product optimise the number of measurement
(communication address, load type, type and devices per installation. > ISO 14025
ratio of current sensor) allow you to simplify > UL(1)
(1) Please contact us.
implementation and to save time. Communication
• The DIRIS B-30 can be connected to:
Selection guide
Class 0.5 in accordance with IEC 61557-12 - a remote DIRIS D-30 screen for displaying DIRIS B-30
• Class 0.2 for the meter alone. measurement and metering data. DIRIS B-30 RS RS485 MODBUS communication
• Class 0.5 from 2% to 120% of nominal - a DIRIS G(1) gateway for centralisation and DIRIS B-30 RF Wireless RF communication
current for the global measurement chain communication of data wirelessly or via Optional modules
(associated with TE/TF current sensors). RS485 and Ethernet. DIRIS O-iod 2 digital inputs / 2 digital outputs
- optional modules to communicate in DIRIS O-ioa 2 analogue inputs /
BACnet IP, BACnet MSTP and PROFIBUS 2 analogue outputs
DP protocol. Digital or analogue input/ DIRIS O-it 3 temperature inputs
output modules can also be connected. DIRIS O-m Additional RS485 communication
(1) See page 39. DIRIS O-p PROFIBUS communication
DIRIS O-b/ip BACnet IP communication
DIRIS O-b/mstp BACnet MSTP communication

Functions
Multi-measurement Quality Load curves and history logs (130 days max.)
• Currents • Voltage Unbalance • Active, reactive and apparent power
- I1, I2, I3, In, Isystem - Vdir, Vinv, Vhom, Udir, Uinv, Unba, Vnba, Vnb, Unb • Currents, voltages and frequency
• Voltages & frequency • Current unbalance Alarms
- V1, V2, V3, VN, Vsystem, U12, U23, U31, - Idir, Iinv, Ihom, Inba, Inb • Alarms for all electrical values, events and input
Usystem, f • Total harmonic distortion status changes, possibility of boolean combination
• Power - Currents THDi1, THDi2, THDi3,THDiN Communication
- P1, P2, P3, ΣP, Q1, Q2, Q3, ΣQ, S1, S2, S3, ΣS - Phase-to-neutral voltage THDv1, THDv2, THDv3 • DIRIS B-30 RF: Radio frequency Communication
- Predictive power ΣP, ΣQ, ΣS - Phase-to-phase voltage THDu12, THDu23, THDu31 (wireless)
• Power factor • Individual harmonics up to rank 63 • DIRIS B-30 RS: RS485 Modbus,
- PF1, PF2, PF3, ΣPF - Currents: I1h, I2h, I3h, INh • Optional modules: RS485, BACnet IP, BACnet MSTP,
• Cos ϕ & tanϕ - Phase-to-neutral voltage: V1h, V2h, V3h PROFIBUS DPV1
- Instantaneous values per phase - Phase-to-phase voltage: U12h, U23h, U31h Inputs
Metering • Active (according to EN 50160) • 2 digital inputs
- Dips, interruptions, swells - Supply by the DIRIS B-30 or external supply
• Active energy: +/- kWh - Function: logic status, circuit breaker status,
• Reactive energy: +/- kvarh pulse meter or synchronisation pulse
• Apparent energy: kVAh
• Multi-tariff (8 max.)

38 Catalogue 2017
DIRIS B-30
Wireless power monitoring devices

DIRIS B-30 display


DIRIS D-30 Dimensions Connection

diris-dw_037_b_1_x_cat

92

diris-d_004_a_1_x_cat
diris-d_001_a_1_cat

RJ9

DIRIS D-30
DIRIS B-30
92 27 18

Optional modules
DIRIS O
Optional modules (4 max.)*
• Digital inputs/outputs
• Analogue inputs/outputs
• Temperature inputs
• Communication protocols
diris-b_031_a

* maximum 4 optional modules with maximum 1 temperature


module and 1 communication module
(Modbus, PROFIBUS, BACnet IP or BACnet MSTP).
Optional module DIRIS B-30

DIRIS O-iod DIRIS O-m


• 2 digital inputs centralises the metering pulses or the input • Provides a second RS485 Modbus communication port to the
diris-o_024_a
diris-o_019_a

status changes of the auxiliary contacts. DIRIS B-30 for simultaneous sending of information via RS485
• 2 digital outputs can be connected to configurable alarms to two supervision stations.
warning of exceeded thresholds (power, current, etc.) or
can be piloted remotely.

DIRIS O-p
• Adds a PROFIBUS DPV1 communication port to the DIRIS B-30.
diris-o_023_a

DIRIS O-ioa
• 2 inputs (4-20 mA) centralise analogue sensors (pressure,
diris-o_018_a

humidity, temperature, etc.)


• 2 outputs (4-20 mA) report the measurements (power,
currents, etc.) to PLCs. DIRIS O-b/ip
• Adds a BACnet IP communication port to the DIRIS B-30.
diris-o_022_a

DIRIS O-it
• 3 temperature inputs to be connected to PT100 or PT1000 DIRIS O-b/mstp
diris-o_020_a

sensors. • Adds a BACnet MSTP communication port to the DIRIS B-30.


diris-o_021_a

• Ambient air temperature:

Accessories
Remote radio antenna DIRIS B-30 sealing cover USB configuration cable (2 m)
• Mounted outside the enclosure of the DIRIS B-30 • Prevents access to the cabling of the monitoring • Advanced configuration of DIRIS B-30 gateways
monitoring device to increase the transmission device. can be achieved using the EASY CONFIG
distance. software via Ethernet or direct USB connection.

Catalogue 2017 39
DIRIS B-30
Wireless power monitoring devices

DIRIS B-30 terminals

Voltage measurement Display Auxiliary power supply


DIRIS D-30

USB
DIRIS O
optional module
diris-d_027_b_1_gb_cat

2 digital
inputs
RS485

Current measurement Self supply Separate power supply


diris-b_020_b_1_x_cat

Easy connection of the power supply from the


RJ12 measurement terminal (specific terminals)
L1 L1
I 01 I 02 I 03 I 04
L2 L2
L3 L3
N N
Voltage measurement and
diris-b_021_a_1_x_cat

110-230VAC
diris-b_025_a_1_x_cat

diris-b_026_a_1_x_cat

auxiliary power supply 1 1 1 1 1 1 1

V1 V2 V3 VN V1 VN V1 V2 V3 VN V1 V2 V3 VN V1 VN
L V1 VN
L
L
N N
N
110-230VAC
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.

2 inputs supplied by the product 2 inputs with external power supply RS485 RJ9 for DIRIS D-30
(self-supply and data)
10-30 VDC
12 VDC
RS485
diris-b_024_b_1_x_cat

Slave
diris-b_022_a_1_x_cat

diris-b_023_a_1_x_cat

diris-b_019_a_1_x_cat
IN
IN

1 1
NC
2
RJ9

2
LIYCY-CY

I 04 I 04 I 01

Terminals of optional DIRIS O modules


Optional module power supply DIRIS O-iod DIRIS O-ioa DIRIS O-it DIRIS O-m RS485
diris-o_014_a_1_x_cat

INPUT INPUT IN3


IN3
SUPPLY
diris-o_010_a_1_x_cat

diris-o_011_a_1_x_cat

diris-o_012_a_1_x_cat

diris-o_013_a_1_x_cat

IN1
IN1 IN2
IN2

OUTPUT OUTPUT

DIRIS O-p DIRIS O-b/ip DIRIS O-b/mstp

SUBD 9 ETH
diris-o_015_a_1_x_cat

diris-o_016_a_1_x_cat

diris-o_017_a_1_x_cat

40 Catalogue 2017
DIRIS B-30
Wireless power monitoring devices

Connections
Associated current sensors
Various types of current sensors can be connected to the DIRIS Digiware: Solid TE , split-core TR , flexible TF current sensors. This range of sensors can be adapted to
all types of new or existing installations. A rapid RJ12 connection makes wiring easy and reliable and prevents wiring errors. The DIRIS B-30 automatically recognises the
sensor size and type. This guarantees the overall accuracy of the DIRIS B-30 + current sensor measurement chain.
For more information: see page 44.

TE solid current sensors


TE / TR / TF current sensors
diris-t_010_a_1_cat

diris-t_003_a_1_cat

TF
DIRIS B-30

TR

TR Split-core current TF Flexible current sensors


sensors
TE

RJ12 Connection
diris-t_014_a_1_cat

diris-t_016_a_1_cat

diris-b_033_a_cat

Network and connection examples


Three phase + neutral Three-phase
3P+N - 4CTs (measurement for 1 three-phase load + Neutral) 3P - 2CTs (2 three-phase loads without neutral)
L1 L1
L2 L2
L3 L3
N

1 1 1 1 1 1 1
diris-b_015_b_1_x_cat

diris-b_016_b_1_x_cat

3 3
3 +N

V1 V2 V3 VN I01 I02 I03 I04 V1 V2 V3 VN I01 I02 I03 I04


V I V I

Three-phase Single-phase
3P+N - 3CTs & 1P+N - 1CT (1 three-phase load & 1 single-phase load) 1P+N-1CT (4 single-phase loads)
L1 L1
L2 N
L3
N

1 1
1 1 1 1
1 1 1 1
diris-b_017_b_1_x_cat

diris-b_018_b_1_x_cat

3 +N 1

V1 V2 V3 VN I01 I02 I03 I04 V1 V2 V3 VN I01 I02 I03 I04


V I V I

1. Fuses 0.5 A gG / 0.5 A class CC.


3
In case of self-supply, a fuse must be added on the neutral. CT: Current sensors Load

Catalogue 2017 41
DIRIS B-30
Wireless power monitoring devices

Dimensions (mm)
DIRIS B-30 DIRIS O optional modules

120

diris-o_001_b_1_x_cat

90
45
diris-b_004_b_1_x_cat

100
90

44 15
15

A 65

DIRIS O optional modules A


54 44 15 36 DIRIS O-iod - DIRIS O-ioa - DIRIS O-it 45 mm
DIRIS O-m - DIRIS O-p - DIRIS O-b/ip - DIRIS O-b/mstp 54 mm
65

Communication architecture
Example of communication architecture with DIRIS G
gateway and WEBVIEW embedded WEB server
For more information about DIRIS G, see page 126.
WEBVIEW
Supervision

Ethernet

DIRIS G-40 / DIRIS G-60


RF - RS485 / Ethernet

RS485
diris-g_003_a_1_x_cat

DIRIS B DIRIS B
RF RF DIRIS B DIRIS B DIRIS A
RS485 RS485 COUNTIS E

References
DIRIS B-30 monitoring devices Reference
DIRIS B-30 RS485 - Modbus - 230VAC 4829 0000
DIRIS B-30 RF - Modbus - 230 VAC 4829 0002

DIRIS O optional modules Reference


DIRIS O-iod 2 digital inputs / 2 digital outputs 4829 0030
DIRIS O-ioa 2 analogue inputs/2 analogue outputs 4-20 mA 4829 0031
DIRIS O-it 3 temperature inputs PT 100 / PT 1000 4829 0032
DIRIS O-m RS485 Modbus communication 4829 0033
DIRIS O-p PROFIBUS communication 4829 0034
DIRIS O-b/ip BACnet IP communication 4829 0035
DIRIS O-b/mstp BACnet MSTP communication 4829 0036

Accessories Reference
DIRIS D-30 - Single-point display 4829 0200
RJ9 cable for DIRIS D-30 display - 1.5 m 4829 0280
RJ9 cable for DIRIS D-30 display - 3 m 4829 0281
Wireless remote antenna, 868 MHz - 210 mm height 4854 0126
Cable for remote antenna - SMA connector - 3 meter length 4854 0127
DIRIS B-30 sealing cover for I/O terminals 4829 0049
USB configuration cable 4829 0050

42 Catalogue 2017
DIRIS B-30
Wireless power monitoring devices

DIRIS B-30 characteristics DIRIS D-30 display characteristics

Electrical characteristics Mechanical characteristics


Screen type Capacitive touch-screen technology, 10 keys
Auxiliary power supply
Screen resolution 350 x 160 pixels
AC voltage 110-230VAC ±15 % (Ph/N ou Ph/Ph) Cat III
Single product connection
Frequency 50/60 Hz
RJ9 Self-supply and data
Consumption < 2VA without display < 6VA with display
Micro-USB Updating
Connection Removable spring-cage terminal, 2 x 2 positions, 0.5 … 2.5 mm²
solid cable or 0.25 … 1.5 mm² stranded cable with ferrule Degree of protection IP65 (front face)
Environment
Measurement characteristics
Storage temperature (°C) -20 ... +70°C
Energy and power measurement
Operating temperature (°C) -20 ... +70°C
Accuracy Class 0.2 DIRIS B-30 alone
Active energy and active Class 0.5 with TE or TF current sensors Humidity 95 % to 40°C
power Class 1 with TR current sensors Installation category CAT III
Reactive energy accuracy Class 2 with TE, TR or TF current sensors Degree of pollution 2
Power factor measurement
Accuracy Class 0.5 with TE or TF current sensors DIRIS O optional modules characteristics
Class 1 with TR current sensors
Voltage measurement Power supply(1)
Network characteristics measured 50-300VAC (Ph/N) - 87-520VAC (Ph/Ph) - CAT III AC voltage 110-230 VAC ±15 %
Frequency range 45 … 65Hz Frequency 50/60 Hz
Frequency accuracy Class 0.02 (1) No power supply on DIRIS O-it.
Network type Single-phase / Two-phase / Two-phase with DIRIS O-iod - 2 digital inputs/2 digital outputs
neutral / Three-phase / Three-phase with neutral
Number of inputs 2 per optional modules - max. 4 optional modules
Measurement by voltage transformer Primary: 400 000 VAC
Secondary: 60, 100, 110, 173, 190 VAC Optocoupler internal polarisation (12 VDC ± 10 %)
Type
or external polarisation (10-30 VDC ± 10%)
Input consumption ≤ 0.1 VA
Function Logic status or pulse meter
Permanent overload 300VAC Ph/N
Number of outputs 2 per optional modules - max. 4 optional modules
Voltage measurement accuracy Class 0.2
Type Relay / 230VAC ±15 % - 1 A
Connection Removable spring-cage terminal,
2 x 6 positions, 0.5 … 2.5 mm² solid cable Configurable alarm (current, power,…) on threshold overruns
Function
or 0.25 … 1.5 mm² stranded cable with ferrule or remote controlled status
Inputs/Outputs Removable screw terminal, 4 positions,
Current measurement
connection 0.14 to 1.5 mm² stranded or solid cable
Number of current inputs 4
DIRIS O-ioa - 2 analogue inputs/2 analogue outputs
Associated current sensors Solid TE , split-core TR , flexible TF current sensors
Number of inputs 2 per optional modules - max. 4 optional modules
Accuracy Class 0.2 DIRIS B-30 alone
Class 0.5 with TE or TF current sensors Type 4-20 mA
Class 1 with TR current sensors Connection of analogue sensors
Function
Connection RJ12 connectors with specific SOCOMEC cable (pressure, humidity, temperature…)
Number of outputs 2 per optional modules - max. 4 optional modules
Input characteristics
Type 4-20 mA
Number 2 Function Transmission of measurement image (current, power…) to PLCs
Type / Power Optocoupler internal polarisation (12 VDC ± 10 %) DIRIS O-it - 3 temperature inputs
supply or external polarisation (10-30 VDC ± 10%)
Number of inputs 3 external inputs + 1 measurement for ambient temperature
Input function Logic status, pulse meter or synchronisation pulse status (input 1)
Dynamic -20 °C to 150 °C
Communication characteristics Type PT100 or PT1000
DIRIS B-30 RS485 Function inputs 1, 2 and 3 Temperature measurement
Link RS485 DIRIS O-m - RS485 communication
Connection type 2 … 3 half duplex wires Link RS485 2 … 3 half duplex wires
Protocol Modbus RTU Protocol Modbus RTU
Speed 1200 … 115200 bauds Speed 1200 … 115200 bauds
USB DIRIS B-30 RS485 configuration Removable screw terminal, 3 positions,
Connection
DIRIS B-30 RF 0.14 to 1.5 mm² stranded or solid cable
Link Wireless radio frequency DIRIS O-p - PROFIBUS communication
Frequency band 868 MHz (low frequency: 868.1 MHz and high Protocol PROFIBUS DPV1
frequency: 869.5875 MHz) DIRIS O-b/ip - BACnet IP communication
Speed 38400 bauds Protocol BACnet IP
USB DIRIS B-30 RF configuration Speed 10 … 100 Mbit/s
Environment characteristics DIRIS O-b/mstp - BACnet MSTP communication
Operating temperature -10 … +70 °C Protocol BACnet MSTP
Storage temperature -25 … +85 °C Speed 9600 … 76800 bauds
Operating humidity 55 °C / 97% relative humidity
Operating altitude 2000 m
Vibration 1G from 10 Hz to 100Hz

Catalogue 2017 43
TE sensors
Solid current sensors
used with DIRIS Digiware and DIRIS B-30

new
The solution for
Current sensors

> Industry
> Building
> Infrastructure
> Data center

diris-t_003_a_1_cat

diris-t_010_a_1_cat
tore_065_a

TE solid sensors
Strong points
Function
> Plug & Play
TE smart current sensors measure the load currents of an electrical system and send the
data to meters and measurement hubs via an RJ12 plug-and-play output. Thanks to a wide > Accuracy as per standard
measurement range, TE current sensors cover the full current range of 5 to 2000 A, with IEC 61557-12
7 references. TE solid current sensors can be connected to DIRIS Digiware and DIRIS B-30 via a  > Installation
rapid RJ12 connection.
Numerous accessories are available to aid the installation of sensors in any type of cabinet.
Conformity to standards

> IEC 61557-12


Advantages
Plug & Play Installation
• A rapid RJ12 connection makes wiring • The TE solid sensor range is specially > ISO 14025
easy and reliable and prevents wiring errors. designed for new installations, and has the
This also allows automatic detection of the same pitch as the most common protective
sensor type and size/transformation ratio. devices.
> UL
• The sensors can be installed in both
directions.

Accuracy as per standard IEC 61557-12


• Class 0.5 for the global measuring chain
(measurement hub + TE current sensors)
from 2 to 120% of the nominal current In.

44 Catalogue 2017
TE sensors
Solid current sensors
used with DIRIS Digiware and DIRIS B-30

Mounting
Linear assembly with the protective devices Staggered assembly Cable mounting
TE-25 / TE-35 / TE-45 / TE-55 / TE-90 TE-18 / TE-35 / TE-45 / TE-55

diris-t_005_a_1_cat
diris-t_005_a_1_cat

diris-t_035_a_1_cat
DIN rail mounted Back-plate mounting Bar mounting
diris-t_033_a_1_cat

diris-t_034_a_1_cat

diris-t_036_a_1_cat

diris-t_049_a
TE-90 clamps
diris-t_048_a

Connections
TE / TR / TF current sensors

DIRIS B-30 or TF
DIRIS DIGIWARE I

TR

TE

RJ12 Connection
diris-b_033_a_cat

Catalogue 2017 45
TE sensors
Solid current sensors
used with DIRIS Digiware and DIRIS B-30

Mounting accessories
Mounting accessories delivered with TE sensors:
TE-35
TE-45
Switch mounting TE-18 TE-25 TE-55 TE-90

DIN rail and


1 pc 2 pcs
back-plate
diris-t_042_a - 043_a - 044_a - 045_a

DIN rail 2 pcs 2 pcs

Back-plate 4 pcs 4 pcs 6 pcs

Busbar 2 pcs

Compatible accessories
Adapter for CT with 5A secondary Coupling link Sealable cover
• With this adapter you can • Associated with the TE range, this accessory is • Using a sealable cover guarantees the immunity
use a current transformer for inter-connecting the sensors when linear or of the sensor connection on TE/TR/TF current
diris-t_041_a_1_cat

with a 5 A output on the staggered mounted. sensors.


DIRIS Digiware and DIRIS
B-30.
diris-t_046_a_1_cat
diris-t_020_a_1_cat

For use with standard 5


A sensors for measuring
applications of > 2000 A.
The dimensions are the
same as the TE-18.

Dimensions (mm)
TE - Solid current sensors
TE-18 TE-25 / TE-35 / TE-45 / TE-55 TE-90
L 2.2 P

1
=
H

Ø
=
H

= F =
H

= F =
diris-t_023_b_1_fr_cat

diris-t_047_a_1_fr_cat
=

1
=
T

L P
L P 19.7
1. Switch mounting 36

Model Nominal current range (A) Actual coverage range (A) Pitch (mm) H x W x D (mm) F (mm) T (mm)
TE-18 5 … 20 / 25 ... 63 0.1 … 24 / 0.5 … 75 18 45 x 28 x 20 8.6 -
TE-25 40 … 160 0.8 … 192 25 65 x 25 x 32.5 13.5 x 13.5 17.5
TE-35 63 … 250 1.26 … 300 35 71 x 35 x 32.5 21 x 21 17.5
TE-45 160 … 630 3.2 … 756 45 86 x 45 x 32.5 31 x 31 19.5
TE-55 400 … 1000 8 … 1200 55 100 x 55 x 32.5 41 x 41 21.5
TE-90 600 … 2000 12 … 2400 90 126 x 90 x 24.6 64 x 64 -

46 Catalogue 2017
TE sensors
Solid current sensors
used with DIRIS Digiware and DIRIS B-30

Specifications

TE - Solid current sensors


Model TE-18 TE-18 TE-25 TE-35 TE-45 TE-55 TE-90
Nominal current range In (A) 5 … 20 25 … 63 40 … 160 63 … 250 160 … 630 400 … 1000 600 … 2000
Actual coverage range (A) 0.1 … 24 0.5 … 75 0.8 … 192 1.26 … 300 3.2 … 756 8 … 1200 12 … 2400
Max. current (A) 24 75.6 192 300 756 1200 2400
Weight (g) 24 24 69 89 140 187 163
Max. voltage (phase/neutral) 300 V
Rated withstand voltage 3 kV
Frequency 50/60 Hz
Intermittent overload 10 x In over 1 sec
Measurement category CAT III
Protection degree IP30 / IK06
Operating temperature -10 … +70°C
Storage temperature -25 … +85°C
Relative humidity 95% RH non-condensing
Altitude < 2000 m
Connection Socomec RJ12 cable

References
Model Nominal current range (A) Actual coverage range (A) Pitch (mm) Reference
TE-18 5 … 20 0.1 … 24 18 4829 0500
TE-18 25 … 63 0.5 … 75 18 4829 0501
TE-25 40 … 160 0.8 … 192 25 4829 0502
TE-35 63 … 250 1.26 … 300 35 4829 0503
TE-45 160 … 630 3.2 … 756 45 4829 0504
TE-55 400 … 1000 8 … 1200 55 4829 0505
TE-90 600 … 2000 12 … 2400 90 4829 0506

Accessories Reference
Coupling link (20 linear assembly parts and 10 for staggered assembly) 4829 0598
CT/5A adapter (measurements of >2000 A) (max primary current 10000 A/5/A) 4829 0599
Sealable caps (20 pieces) 4829 0600

Cable length (m)


50 m reel + 100
RJ12 connection cables 0.1 0.2 0.3 0.5 1 2 5 10 connectors
Number of cables Reference Reference Reference Reference Reference Reference Reference Reference Reference
1 - - - - - - 4829 0602 4829 0603 4829 0601
3 4829 0580 4829 0581 4829 0582 4829 0595 4829 0583 4829 0584 - - -
4 - - - 4829 0596 4829 0588 4829 0589 - - -
6 4829 0590 4829 0591 4829 0592 4829 0597 4829 0593 4829 0594 - - -

Catalogue 2017 47
TR sensors
Split-core current sensors
used with DIRIS Digiware and DIRIS B-30

The solution for


Current sensors

> Industry
> Building
> Infrastructure
> Data center
diris-t_012_a_1_cat

TR split-core current sensors


Strong points
Function
> Plug & Play
TR smart current sensors measure the load currents of an electrical system and send the
data to meters and measurement hubs via an RJ12 plug-and-play output. Thanks to a wide
> Accuracy as per standard
measurement range, TR current sensors cover the full current range of 25 to 600 A, with
IEC 61557-12
4 references. > Installation
TR split-core current sensors can be connected to DIRIS Digiware and DIRIS B-30 via a rapid
RJ12 connection.
Conformity to standards

> IEC 61557-12


Advantages
Plug & Play Installation
• A rapid RJ12 connection makes wiring • The TR split-core sensor range is specially > ISO 14025
easy and reliable and prevents wiring errors. designed for existing installations and site
This also allows automatic detection of the renovations.
sensor type and size/transformation ratio.
> UL
• The sensors can be installed in both
directions.

Accuracy as per standard IEC 61557-12


• Class 1 for the global measuring chain
(measurement hub + TR current sensors)
from 2 to 120% of the nominal current In.

48 Catalogue 2017
TR sensors
Split-core current sensors
used with DIRIS Digiware and DIRIS B-30

Mounting Dimensions
Cable mounting TR-10 / TR-16 / TR-24 / TR-36
C
L B

Ø
diris-t_037_a_1_cat

diris-t_038_a_1_cat

H
A

diris-t_024_b_1_fr_cat
Accessories P
Sealable cover
• Using a sealable cover Nominal current Actual coverage
guarantees the immunity of Model range (A) range (A) H x W x D (mm) Ø (mm) A (mm) B (mm) C (mm)
the sensor connection on
diris-t_046_a_1_cat

TR-10 25 … 75 0.5 … 90 71 x 25 x 39 10 58 14.5 26


TE/TR/TF current sensors.
TR-16 32 … 100 0.64 … 120 74 x 30 x 42 16 61 19 31
TR-24 63 … 200 1.26 … 200 95 x 45 x 44 24 72 22 34
TR-36 200 … 600 4 … 720 111 x 57 x 42 36 82 34 40.5

Specifications
TR - Split-core sensor
Model TR-10 TR-16 TR-24 TR-36
Nominal current range In (A) 25 … 75 32 … 100 63 … 200 200 … 600
Actual coverage range (A) 0.5 … 90 0.64 … 120 1.26 … 240 4 … 720
Max. current (A) 90 120 240 720
Weight (g) 74 117 211 311
Max. voltage (phase/neutral) 300 V
Rated withstand voltage 3 kV
Frequency 50/60 Hz
Intermittent overload 10 x In for 1s
Measurement category CAT III
Protection degree IP20 / IK06
Operating temperature -10 … +70°C
Storage temperature -25 … +85°C
Relative humidity 95% RH non-condensing
Altitude < 2000 m
Connection Socomec RJ12 cable

References
Nominal current Actual coverage Accessories Reference
Model range (A) range (A) Ø (mm) Reference Sealable caps (20 pieces) 4829 0600
TR-10 25 … 75 0.5 … 90 10 4829 0551
TR-16 32 … 100 0.64 … 120 16 4829 0552
TR-24 63 … 200 1.26 … 200 24 4829 0553
TR-36 200 … 600 4 … 720 36 4829 0554

Cable length (m)


50 m reel +
RJ12 connection cables 0.1 0.2 0.3 0.5 1 2 5 10 100 connectors
Number of cables Reference Reference Reference Reference Reference Reference Reference Reference Reference
1 - - - - - - 4829 0602 4829 0603 4829 0601
3 4829 0580 4829 0581 4829 0582 4829 0595 4829 0583 4829 0584 - - -
4 - - - 4829 0596 4829 0588 4829 0589 - - -
6 4829 0590 4829 0591 4829 0592 4829 0597 4829 0593 4829 0594 - - -

Catalogue 2017 49
TF sensors
Flexible current sensors
used with DIRIS Digiware and DIRIS B-30

The solution for


Current sensors

> Industry
> Building
> Infrastructure
> Data center

diris-t_016_a_1_cat
TF Flexible current sensors
Strong points

Function > Plug & Play


> Accuracy as per standard
TF smart current sensors measure the load currents of an electrical system and send the IEC 61557-12
data to meters and measurement hubs via an RJ12 plug-and-play output. Thanks to a wide
measurement range, TF current sensors cover the full current range of 150 to 6000 A, with > Installation
3 references. TF flexible current sensors can be connected to DIRIS Digiware and DIRIS B-30
via a rapid RJ12 connection.
Conformity to standards

> IEC 61557-12


Advantages
Plug & Play Installation
• A rapid RJ12 connection makes wiring • The TF flexible sensor range is specially > ISO 14025
easy and reliable and prevents wiring errors. designed for existing installations restricted
This also allows automatic detection of the by strict integration constraints or with high-
sensor type and size/transformation ratio. intensity currents. > UL
• The sensors can be installed in both
directions.

Accuracy as per standard IEC 61557-12


• Class 0.5 for the global measuring chain
(measurement hub + TF current sensors)
from 2 to 120% of the nominal current In.

50 Catalogue 2017
TF sensors
Flexible current sensors
used with DIRIS Digiware and DIRIS B-30

Mounting Connections
TE / TR / TF current sensors
Cable mounting Bar mounting

DIRIS B-30 TF
or DIRIS DIGIWARE I
diris-t_039_a_1_cat

diris-t_040_a_1_cat

TR

Accessories TE

Sealable cover
RJ12 Connection
• Using a sealable cover
diris-t_046_a_1_cat

guarantees the immunity of


diris-b_033_a_cat

the sensor connection on


TE/TR/TF current sensors.

Dimensions
TF-55 TF-120 / TF-300

1500 1500

Ø6

L Ø 85 Ø 11
85

Ø
diris-t_027_c_1_x_cat

diris-t_028_a_1_x_cat

L
38
18 18 38

Model Nominal current range (A) Actual coverage range (A) Ø loop (mm) L = Loop length (mm)
TF-55 150 … 600 3 … 720 55 182
TF-120 500 … 2000 10 … 2400 120 376
TF-300 1600 … 6000 32 … 7200 300 942

Specifications References
Model TF-55 TF-120 TF-300 Actual
Nominal current range In (A) 150 … 600 500 … 2000 1600 … 6000 Nominal current coverage Ø loop
Actual coverage range (A) 3 … 720 10 … 2400 32 … 7200 Model range (A) range (A) (mm) Reference
Weight (g) 114 142 220 TF-55 150 … 600 3 … 720 55 4829 0570
Max. voltage (phase/neutral) 600 V TF-120 500 … 2000 10 … 2400 120 4829 0571
Rated withstand voltage 3.6 kV TF-300 1600 … 6000 32 … 7200 300 4829 0572
Frequency 50 / 60 Hz
Intermittent overload 10 x In for 1 s Accessories Reference
Measurement category CAT III Sealable caps (20 pieces) 4829 0600
Protection degree IP30 / IK07
Operating temperature -10 … +70°C
Storage temperature -25 … +75°C
Relative humidity 95% RH non-condensing
Altitude < 2000 m
Socomec cable or equivalent RJ12 straight, twisted
Connection
pair, unshielded 300 V cat. III cable. -40 / +85 °C

Cable length (m)


50 m reel + 100
RJ12 connection cables 0.1 0.2 0.3 0.5 1 2 5 10 connectors
Number of cables Reference Reference Reference Reference Reference Reference Reference Reference Reference
1 - - - - - - 4829 0602 4829 0603 4829 0601
3 4829 0580 4829 0581 4829 0582 4829 0595 4829 0583 4829 0584 - - -
4 - - - 4829 0596 4829 0588 4829 0589 - - -
6 4829 0590 4829 0591 4829 0592 4829 0597 4829 0593 4829 0594 - - -

Catalogue 2017 51
COUNTIS E0x
Active energy meters
single-phase - direct 32/40 A
Single-circuit metering,

new
The solution for
measurement &

> Industry
> Marinas
> Shopping centers
analysis

> Data center

count_215_a_1
count_252_a

Strong points

> Compactness
> Output (pulses)
> MID certified B+D module
COUNTIS E04 - MID COUNTIS E02 - MID
> RS485 (MODBUS) and
M-Bus communication

MID certification

Function Functional diagram > COUNTIS E units


comply with the
The COUNTIS E0x is a modular active MID directive to
electrical energy meter displaying the total guarantee accuracy
energy consumed (kWh), allowing direct and reliability when metering,
connection up to 32/40 A. compulsory for energy billing
COUNTIS E02, E04 and E06 are also MID- applications.
certified. > COUNTIS E MID feature
tamper-proof components to
Advantages prevent fraud.

Compactness
Only 1 module wide. Conformity to standards
Output (pulses)
> IEC 62053-21
count_211_a_1_x_cat

The pulse output enables the kWh


class 1
consumption to be reported to a remote
system (PC/BMS) so that it can be analysed COUNTIS E0x COUNTIS E0x > IEC 62053-31
for billing, energy saving or energy cost > IEC 62052-11
management purposes. > EN 50470-1
MID certified B+D module
> EN 50470-3
COUNTIS E units comply with the MID
directive to guarantee accuracy and reliability
when metering, compulsory for energy billing
applications. “Module B+D” certification Common characteristics
guarantees that the design and manufacturing
process of products are approved by an • Compact dimensions.
accredited laboratory. • Measurement accuracy: 1%.
• Displayed on backlit screen.

Models Model-related specifications


E00 Pulse output
E02 Pulse output + MID
E03 Dual tariff + Pulse output + RS485 MODBUS communication
E04 Dual tariff + Pulse output + RS485 MODBUS communication + MID
E05 Dual tariff + Pulse output + M-Bus communication
E06 Dual tariff + Pulse output + M-Bus communication + MID

52 Catalogue 2017
COUNTIS E0x
Active energy meters
single-phase - direct 32/40 A

Front panel
1. Terminal shrouds (COUNTIS E02/E04/E06). 1. Neutral terminal
2. MID marking (COUNTIS E02/E04/E06). 1 2. M-Bus/MODBUS connection
3. Metrological LED (2000 pulses/kWh for 2 3. Metrological LED
1 E00/E02 and 5000 pulses/kWh for 3
4. Navigation button.
E03/E04/E05/E06). 4 5. Backlit LCD display
4. kWh display. 6. Pulse output
2
4 5. Serial number (COUNTIS E02). 7. Current and voltage terminals
5
count_215x_a_2_cat

count_252x_a_1_cat
5

3 7

Case
17.5/18 61/65
47/44
COUNTIS E00/E02 COUNTIS E03 … E06
25
Type modular modular
Number of modules 1 1
Dimensions W x H x D (mm) 17.5 x 85 x 61 18 x 90 x 65
Case degree of protection IP 20 IP 20
Front degree of protection IP 50 IP 50
7 digit LCD with
85/90

Display type 5 +1 digits LCD


45

backlighting
count_212_c_x_cat

Rigid cable cross-section 10 mm2 1.5 … 6 mm²


Flexible cable cross-section 6 mm2 1.5 … 6 mm²
100 g E03/04
Weight 150 g
80 g E05/06

Electrical characteristics
Current measurement (TRMS) COUNTIS E00/E02 COUNTIS E03 … 06 Output (pulses) COUNTIS E00/E02 COUNTIS E03 … 06
Type direct input Number 1
Input consumption < 2 VA < 0.5 VA 27 VDC - 27 mA
Type of optocoupler Max. 15 VDC
Permanent overload 32 A 40 A (IEC 62053-31)
Intermittent overload 30 Imax over 10 ms Fixed pulse weight 100 Wh
Minimum current measured 20 mA Pulse duration 100 ms
Voltage measurements (TRMS) Operating conditions
Range of measurement 196 … 264 VAC 184 … 276 VAC Operating temperature -10 … +55°C -25 … +55°C
Max. 1.5 VA for E03/04 Storage temperature -20 … +70°C -40 … +75°C
Input consumption 8 VA
Max. 1 VA for E05/06 Relative humidity 95% 80%
Permanent overload 264 VAC 280 VAC Communication COUNTIS E03/E04 COUNTIS E05/E06
Energy accuracy Link RS485 Wired
Active (according to IEC 62053-21) Class 1 Type 2 … 3 half duplex wires 2 half duplex
Active (according to EN 50470) Class B Protocol MODBUS in RTU mode M-Bus
Power supply Speed 2400 … 38400 bauds 300, 2400, 9600 bps
Self-powered yes

Terminals and connections


N’ N’ N’
L’ L’ L’
L L L
N N N
+ - NC
count_213_d_1_x_cat

count_239_c_1_x_cat

count_249_a_1_x_cat

N N' L L' 1 3 N N' L L' 1 2 3 4 5 N N' L L' 1 2 3 4


- + RS485 - + M-Bus - +

COUNTIS E00/E02 kWh COUNTIS E03/E04 kWh COUNTIS E05/E06 kWh

N - L: network input. N' - L': network output. 1 - 3: pulse output.

References
COUNTIS E00 COUNTIS E02 COUNTIS E03 COUNTIS E04 COUNTIS E05 COUNTIS E06
Type Reference Reference Reference Reference Reference Reference
Direct 32 A 4850 3019
Direct 32 A - MID 4850 3020
Direct 40 A - Dual tariff + RS485 MODBUS communication 4850 3039
Direct 40 A - Dual tariff + RS485 MODBUS communication + MID 4850 3040
Direct 40 A - Dual tariff + M-Bus communication 4850 3041
Direct 40 A - Dual tariff + M-Bus communication + MID 4850 3042

Catalogue 2017 53
COUNTIS E1x
Active-energy meters
single phase - direct 63/80 A
Single-circuit metering,

new
The solution for
measurement &

> Marinas
> Shopping centers
> Data centers
analysis

count_216_a_1_cat
count_253_a_1_cat

Strong points

> RS485 (MODBUS), M-Bus


COUNTIS E14 - MID COUNTIS E12 - MID
communication, Ethernet or
pulse outputs
> Multi-tariff
> MID certified B+D module
Function Functional diagram
The COUNTIS E1x is a modular active
electrical energy meter displaying the energy MID certification
and power consumed (kWh and kW). It is
designed for single-phase load metering and > COUNTIS E units
is used for direct connections of up to 63 or comply with the
80 A (depending on the model). MID directive to
guarantee accuracy
and reliability when metering,
compulsory for energy billing
applications.
Common characteristics
> COUNTIS E MID feature
• Measurement accuracy: 1%. tamper-proof components to
• Displayed on backlit screen. prevent fraud.

COUNTIS E1x COUNTIS E1x


Conformity to standards
Advantages
> IEC 62053-21
RS485 (MODBUS), M-Bus communication, MID certified B+D module
class 1
Ethernet or pulse outputs COUNTIS E units comply with the MID
To easily centralise your consumption, directive to guarantee accuracy and reliability > IEC 62053-31
COUNTIS E1x devices have either one pulse when metering, compulsory for energy billing > IEC 62052-11
output, one RS485 output (MODBUS), M-Bus applications. “Module B+D” certification > EN 50470-1
or Ethernet Modbus TCP communication. guarantees that the design and manufacturing
> EN 50470-3
With RS485 communication models, you can process of products are approved by an
configure your meters remotely. accredited laboratory.
Multi-tariff
Lets you assign different time slots (every
hour, dip times) or different sources (normal,
back-up) to your energy readings to monitor
your energy consumption in more detail.

Models Model-related specifications


E10 Pulse output
E11 Dual tariff (2 partial indices) + pulse output
E12 Dual tariff + pulse output + MID
E13 Dual tariff + pulse output + MODBUS RS485 communication
E14 Dual tariff + pulse output + MODBUS RS485 communication + MID
E15 Dual tariff + pulse output + M-BUS communication
E16 Dual tariff+ pulse output + M-BUS communication + MID
E17 Dual tariff + Ethernet
E18 Dual tariff + Ethernet + MID

54 Catalogue 2017
COUNTIS E1x
Active-energy meters
single phase - direct 63/80 A

Front panel
1. Terminal shrouds (COUNTIS E12/E14/E16/E18). 1. Backlit LCD display.
1 2. Backlit LCD display. 2. Navigation button.
3. MID marking (COUNTIS E12/E14/E16/E18). 3. Metrological LED (1000 pulses/kWh).
4. Serial number. 4. Voltage, current and neutral terminals.
2 5 5. Navigation button.
count_216x_a_2_cat

6. Metrological LED (1000 pulses/kWh). 1

count_253x_a_2_cat
6
3 2

4
3 4

Case
62.5/64 COUNTIS E10 … E12 COUNTIS E13 … E18
54/36 44/44 Type modular modular
Number of modules 3 2
Dimensions W x H x D 54 x 90 x 62.5 mm 36 x 90 x 64 mm
Case degree of protection IP 20 IP 20
COUNTIS E10

Error Partial Front degree of protection IP 51 IP 51


90/90

45/45
count_190_c_1_x_cat

Display type backlit LCD backlit LCD


RESET Rigid cable cross-section 1.5 … 16 mm2 1.5 … 35 mm2
230VAC 50/60Hz 0.5-10(63)A

Flexible cable cross-section 1 … 16 mm2 1.5 … 35 mm2


C=1Wh/imp
63A

215 g E13/14/17/18
Weight 170 g
205 g E15/16

Electrical characteristics
Measurement of currents COUNTIS E10…E12 COUNTIS E13…E18 Output (pulses) COUNTIS E10 … E12 COUNTIS E13 … E16
Type single phase - direct 63 A single phase - direct 80 A Optocoupler type (IEC 62053-31) Class A (20 … 30 VDC) 27 VDC - 27 mA
Input consumption max. 0.8 VA max. 0.5 VA Number 1 1
Startup current (Ist) 40 mA 20 mA Fixed pulse weight 100 Wh
Minimum current (Imin) 0.5 A(1). 0.25 A 50 ± 2 ms ON time
Pulse duration 100 ms
Transition current (Itr) 1 A(2). 0.5 A 30 ± 2 ms min OFF time
Reference current (Iref) 10 A(3). 5A Operating conditions COUNTIS E10 … E12 COUNTIS E13 … E18
Permanent overload (Imax) 63 A 80 A Operating temperature -10 … 55°C -25 … 55°C
Intermittent overload 1890 A over 10 ms 30 Imax over 10 ms Storage temperature -20 … 70°C -25 … 75°C
Voltage measurement Relative humidity 85% 80%
Range of measurement 230 V ± 20% 230 … 240 V ± 20% Communication COUNTIS E13/14 COUNTIS E15/E16 COUNTIS E17/E18
3.5 VA max E13/14/17/18 Link RS485 Wired RJ45
Consumption (VA) Max. 0.5 VA
7.5 VA max E15/16 2 half duplex
Permanent overload 280 V phase-neutral 290 V phase-neutral Type Full duplex
2-3 half duplex (E13/E14)
Energy accuracy
MODBUS TCP,
Active (according to IEC 62053-21) Class 1 Class 1 Protocol MODBUS® RTU M-BUS
HTTP, NTP, DHCP
Active (according to EN 50470) Class B Class B
Power supply Baudrate 1200 … 57600 bauds 300 … 9600 bauds 10/100 Mbps
Self-powered Yes
Frequency 50/60 Hz
(1) I(min) ≤ 0.5 * Itr (2) Guaranteed precision class of between I(tr) and I(max).
(3) I(ref) = I(b) (base current) = 10 * I(tr) for direct connection COUNTIS devices.

Connection
N
N N N
L L’
L L’ L L’ L L’
count_241_d_1_x_cat
count_181_c_1_x_cat

count_240_c_1_x_cat

count_250_a_1_x_cat

S0 S0 M-BUS
+ - + - COM - + + -
RJ45

1 2 3 4 5 A-V A N
4 6 8 10 1 3 2 A-V A N 1 2 3 4 A-V A N
T1/2* L L’ N RS485
COUNTIS E10/E11/E12 COUNTIS E13/14 COUNTIS E15/16 COUNTIS E17/E18
* Not available on the COUNTIS E10.

References
COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS
E10 E11 E12 E13 E14 E15 E16 E17 E18
Type Reference Reference Reference Reference Reference Reference Reference Reference Reference
Direct 63 A 4850 3000
Direct 63 A - Dual tariff 4850 3001
Direct 63 A - Dual tariff + MID 4850 3002
Direct 80 A - Dual tariff + MODBUS communication via RS485 4850 3043
Direct 80 A - Dual tariff + MODBUS communication via RS485 + MID 4850 3044
Direct 80 A - Dual tariff + M-Bus communication 4850 3045
Direct 80 A - Dual tariff + M-Bus communication + MID 4850 3046
Direct 80 A - Dual tariff + Ethernet Modbus TCP communication 4850 3047
Direct 80 A - Dual tariff + Ethernet Modbus TCP communication + MID 4850 3048

Catalogue 2017 55
COUNTIS E2x
Active-energy meters
three-phase - direct 63/80 A
Single-circuit metering,

new
The solution for
measurement &

> Industry
> Infrastructure
> Data center
analysis

count_254_a_1_cat

count_232_a
COUNTIS E24 - MID COUNTIS E20 Strong points

Function Functional diagram > RS485 (MODBUS), M-BUS,


Ethernet or pulse outputs
The COUNTIS E2x is a modular active > Multi-tariff
electrical energy meter displaying the energy
> Detection of connection errors
and power consumed (kWh and kW). It is
designed for three-phase networks and allows > MID certified B+D module
a direct connection of up to 63/80 A.
Conformity to standards
Common characteristics
• Measurement accuracy: 1% > IEC 62053-21
• Displayed on backlit screen class 1
• Detection of connection errors > IEC 62053-31
COUNTIS E2x
> IEC 62052-11
> EN 50470-1
Advantages > EN 50470-3
RS485 (MODBUS), M-BUS, Ethernet
communication or pulse outputs
To easily centralise your consumption, COUNTIS E2x
COUNTIS E2x devices have either one pulse COUNTIS E2x
output, one RS485 (MODBUS), M-BUS or an
Ethernet Modbus TCP communication output.
With RS485 communication models, you can
configure your meters remotely.
Multi-tariff
Lets you assign different time slots (every MID certified B+D module
hour, dip times) or different sources (normal, COUNTIS E units comply with the MID
back-up) to your energy readings to monitor directive to guarantee accuracy and reliability
your energy consumption in more detail. when metering, compulsory for energy billing
Guaranteed connection (E20/21) applications. “Module B+D” certification
The product is protected against phase/ guarantees that the design and manufacturing
neutral inversion and detects wiring errors. process of products are approved by an
This makes it easier to start up, ensures the accredited laboratory.
device is functioning properly and reduces the
cost of the installation.

Models Model-related specifications


E20 Pulse output
E21 Dual tariff (2 partial indices) + pulse output
E22 Dual tariff + pulse output + MID
E23 Dual tariff + pulse output + MODBUS RS485 communication
E24 Dual tariff + pulse output + MODBUS RS485 communication + MID
E25 Dual tariff + pulse output + M-BUS communication
E26 Dual tariff+ pulse output + M-BUS communication + MID
E27 Dual tariff + pulse output + Ethernet
E28 Dual tariff + pulse output + Ethernet + MID

56 Catalogue 2017
COUNTIS E2x
Active-energy meters
three-phase - direct 63/80 A

Front panel
1. Backlit LCD display. 1. Neutral terminal
2. Navigation button.
1 2. Backlit LCD display
3. Reset button. 3. Navigation button.
4. Metrological LED 4. ENTER key
(1000 pulses/kWh). 3 5. Metrological LED
count_232x_a_1_cat

count_254x_a_1_cat
2 4
2 6. Current and voltage terminals
3 5
4
6
1

Case Electrical characteristics


62.5/64 Measurement of currents COUNTIS E20 … E21 COUNTIS E22 … E28
72 45/44 Type three-phase - direct 63 A three-phase - direct 80 A
Input consumption 0.8 VA max. per phase 0.5 VA max. per phase
Startup current (Ist) 40 mA 20 mA
(1)
Minimum current (Imin) 0.5 A . 0.25 A
COUNTIS E20
Transition current (Itr) 1 A(2). 0.5 A
count_191_c_1_x_cat

(3)
Error Partial Reference current (Iref) 10 A . 5A
Permanent overload (Imax) 63 A 80 A
90

45

RESET
Intermittent overload 1890 A over 10 ms 30 Imax over 10 ms
63A
3X230(400)VAC 50/60Hz 0.5-10(63)A
C=1Wh / imp Voltage measurement
Range of measurement 230 ... 400 V ±20% 230 ... 240 V ±20%
7.5 VA max (0,5 W) per phase
Consumption (VA) Max. 2 VA E22/25/26 / 3.5 VA max (1 W)
per phase E23/24/27/28
COUNTIS E20 … E21 COUNTIS E23 …E28 280 V phase-neutral / 480 V phase-phase E20/21
Permanent overload
Type modular modular 290 V phase-neutral / 500 V phase-phase E22 ... E28
Number of modules 4 4 Energy accuracy
Dimensions W x H x D 72 x 90 x 62.5 mm 72 x 90 x 64 mm Active (according to IEC 62053-21) Class 1 Class 1
Case degree of protection IP 20 IP 20 Active (according to EN 50470) Class B Class B
Power supply
Front degree of protection IP 51 IP 51
Self-powered Yes
Display type Backlit LCD 8-digit backlit LCD
Frequency 50/60 Hz
Rigid cable cross-section 1.5 … 16 mm2 1.5 … 35 mm2 Output (pulses) COUNTIS E20 … E21 COUNTIS E22 … E28
Flexible cable cross-section 1 … 16 mm2 1.5 … 35 mm2 250 VAC/DC - 100 mA
Weight 170 g 440 g Optocoupler type (IEC 62053-31) Class A (20 ... 30 VDC) (E22) 27 VDC - 27 mA
(E23 ... E28)
2 (E22)
Number 1
1 (E23 ... E28)
Fixed pulse weight 100 Wh
50 ± 2 ms ON time
Connection Pulse duration 100 ms 30 ± 2 ms min OFF
time
Operating conditions COUNTIS E20-E21 COUNTIS E22-E28
count_182_b_1_x_cat

N
L1
L2
L1’
L2’ Operating temperature -10 … 55°C -25 … 55°C
L3 L3’ Storage temperature -20 … 70°C -25 … 75°C
+ -
Relative humidity 85% 80%
2
N
4 6 1
L1 L1’ L2
3 5 7
L2’ L3 L3’
9 11 Communication COUNTIS E23/24 COUNTIS E25/E26 COUNTIS E27/E28
COUNTIS E20 Link RS485 Wired RJ45
2 half duplex
Type Full duplex
2 to 3 half duplex (E23/24)
count_183_a_1_x_cat

N
L1 L1’ ® MODBUS TCP,
L2 L2’ Protocol MODBUS RTU M-BUS
L3 L3’ HTTP, NTP, DHCP
+ - Baudrate 1200 … 115200 bauds 300 … 9600 bauds 10/100 Mbps
2 4 6 8 10 1 3 5 7 9 11 (1) I(min) ≤ 0.5 * Itr (2) Guaranteed precision class of between I(tr) and I(max).
N T1/2 L1 L1’ L2 L2’ L3 L3’
COUNTIS E21
(3) I(ref) = I(b) (base current) = 10 * I(tr) for direct connection COUNTIS devices.
count_242_b_1_x_cat
count_323_a_1_x_cat

count_243_c_1_x_cat

count_251_a_1_x_cat

N N N N
L1 L1’ L1 L1’ L1 L1’ L1 L1’
L2 L2’ L2 L2’ L2 L2’ L2 L2’
L3 L3’ L3 L3’ L3 L3’ L3 L3’
COM - + - + M-Bus - + - +
RJ45
N 1 2 3 4 5 6 A-V A A-V A A-V A N 1 2 3 4 5 6 7 A-V A A-V A A-V A N 1 2 3 4 5 6 A-V A A-V A A-V A N 1 2 A-V A A-V A A-V A
T1/2 S0 S0 RS485 S0 T1/2 T1/2 S0 S0
COUNTIS E22 COUNTIS E22/E23/E24 COUNTIS E25/E26 COUNTIS E27/E28

References
COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS
E20 E21 E22 E23 E24 E25 E26 E27 E28
Type Reference Reference Reference Reference Reference Reference Reference Reference Reference
Direct 63 A 4850 3003
Direct 63 A - Dual tariff 4850 3004
Direct 80 A - Dual tariff + MID 4850 3049
Direct 80 A - Dual tariff + MODBUS communication via RS485 4850 3050
Direct 80 A - Dual tariff + MODBUS communication via RS485 + MID 4850 3051
Direct 80 A - Dual tariff + M-Bus communication 4850 3052
Direct 80 A - Dual tariff + M-Bus communication + MID 4850 3053
Direct 80 A - Dual tariff + Ethernet Modbus TCP communication 4850 3054
Direct 80 A - Dual tariff + Ethernet Modbus TCP + MID 4850 3055

Catalogue 2017 57
COUNTIS E3x
Active energy meters
three-phase - direct 100 A
Single-circuit metering,

The solution for


measurement &

> Industry
> Infrastructure
> Data centre
analysis

count_219_a

Strong points
COUNTIS E32 - MID

> RS485 communication


(MODBUS or M-BUS)
Function Principle diagram or pulse output
The COUNTIS E3x is a modular active > Detection of connection errors
electrical energy meter displaying the energy > MID certified B+D module
and power consumed (kWh and kW) directly > Bi-directional metering
on its backlit LCD display. It is designed for
three-phase load metering and is used for > Multi-measurement
direct connections of up to 100 A. and load curve
COUNTIS E32, E34 and E36 are MID
certified.
MID certification
Common characteristics COUNTIS E3x
> COUNTIS E
• Measurement accuracy: 1 % comply with the
• Backlit LCD display. MID directive,
• Detects connection errors. guaranteeing
count_225_a_1_x_cat

accuracy and reliability when


COUNTIS E3x metering, an indispensable
function for energy billing
COUNTIS E3x
Advantages applications.
RS485 communication (MODBUS or M-BUS) MID certified B+D module > COUNTIS E MID feature
or pulse output COUNTIS E products with MID certification tamper-proof components to
To enable the remote reporting of energy provide the guaranteed accuracy required prevent fraud.
consumption, COUNTIS E3x are provided for applications in which sub-billing of the
with either a pulse output or an RS485 electrical energy consumed is necessary.
communication output, with MODBUS or “Module B+D” certification guarantees that Conformity to standards
M-BUS protocol. the design and manufacturing process of
products are approved by an accredited > IEC 62053-21
In addition to their reporting functions,
laboratory. class 1
COUNTIS E3x with RS485 can be configured
remotely and enable access to multi- Bi-directional metering > IEC 62053-31
measurement values. (available only on the E33 and E35) > IEC 62053-11
Detection of connection errors This function is for metering energy production > EN 50470-1
The product is protected against phase/ or energy consumption.
> EN 50470-3
neutral inversion and detects wiring errors. This Multi-measurement and load curve
simplifies the installation and commissioning, Display of electrical values
thereby reducing associated costs, and (I, U, V, P, Q, S, PF) and load curve over a
ensures that the device operates correctly. 7 day period via communication.

Models Key characteristics


E30 Pulse output
E31 Dual tariff (2 partial counters) + Pulse output
E32 Dual tariff + MID + Pulse output
E33 Dual tariff + RS485 MODBUS communication
E34 Dual tariff + RS485 MODBUS communication + MID
E35 Dual tariff + M-BUS communication
E36 Dual tariff + M-BUS communication + MID

58 Catalogue 2017
COUNTIS E3x
Active energy meters
three-phase - direct 100 A

Front panel Electrical characteristics


1. Terminal shrouds Current measurement
(COUNTIS E32, E34
1 Type three-phase - direct 100 A
and E36).
Input consumption 0.5 VA max. per phase
2. Backlit LCD display.
Startup current (Ist) 80 mA
3. MID marking
Minimum current (Imin) 0.5 A(1)
(COUNTIS E32, E34
and E36). Transition current (Itr) 2 A(2)
2
5 4. Serial number Reference current (Iref) 20 A(3)
count_179x_b_1_cat

6 (COUNTIS E32, E34 Permanent overload (Imax) 100 A


7 and E36). Intermittent overload 3000 A max for 10 ms
5. Navigation key. Voltage measurement
6. Reset key. Range of measurement 230 ... 400 V ± 20 %
3 4 7. Metrological LED. Consumption (VA) 2
Permanent overload 280 V phase-neutral / 480 V phase-phase
Energy accuracy
Active (according to IEC 62053-21) Class 1
Case Active (according to EN 50470) Class B
Power supply
62.5 Self-supplied yes
126 45 Frequency 50 / 60 Hz
Output (pulsed) (COUNTIS E30/E31/E32)
Number 1
Type of optocoupler IEC 62053-31 class A (20 ... 30 VDC)
Fixed pulse weight 100 Wh
COUNTIS E30

Error Partial
count_192_b_1_x_cat

Pulse duration 100 ms


90

45

Operating conditions
RESET

100A
3X230(400)VAC 50/60Hz 0.5-20(100)A
C=2Wh / imp Operating temperature -10 … 55 °C
Storage temperature -20 … 70 °C
Relative humidity 85 %
Communication COUNTIS E33/34 COUNTIS E35/E36
Link RS485 Connection
Type 2 half duplex wires 2 half duplex wires
Type modular Protocol MODBUS RTU M-BUS
Number of modules 7 Speed 4800 … 38 400 bauds 300 … 9600 bauds
Dimensions W x H x D 126 x 90 x 62.5 mm (1) I(min) ≤ 0.5 * Itr
(2) The accuracy class is guaranteed between Itr and Imax.
Case degree of protection IP20
(3) I(ref) = I(b) (base current) = 10 * I(tr) for direct connection COUNTIS.
Front degree of protection IP51
Display type backlit LCD display
Rigid cable cross-section 2.5 … 35 mm2
Flexible cable cross-section 2.5 … 35 mm2
Weight 490 g

Connection
N N N
1 1 1
L1 L1’ L1 L1’ L1 L1’
1 1 1
L2 L2’ L2 L2’ L2 L2’
1 1 1
L3 L3’ L3 L3’ L3 L3’
count_184_c_1_x_cat

count_188_e_1_x_cat

count_185_c_1_x_cat

+ - + - + -

2 4 6 1 3 5 7 9 11 2 15 17 13 1 3 5 7 9 11 2 4 6 8 10 1 3 5 7 9 11
N L1 L1’ L2 L2’ L3 L3’ N RS485 L1 L1’ L2 L2’ L3 L3’ N T1/2 L1 L1’ L2 L2’ L3 L3’
COUNTIS E30 COUNTIS E33/E34/E35/E36 COUNTIS E31/E32
1. 100 A gG / Am fuses max.

References
COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS
E30 E31 E32 E33 E34 E35 E36
Type Reference Reference Reference Reference Reference Reference Reference
100 A direct 4850 3005
100 A direct - Dual tariff 4850 3006
100 A direct - Dual tariff - MID 4850 3007
100 A direct - Dual tariff with RS485 MODBUS com. (1) 4850 3012
100 A direct - Dual tariff with RS485 MODBUS com. - MID(1) 4850 3013
100 A direct - Dual tariff with M-BUS communication (1) 4850 3025
100 A direct - Dual tariff with M-BUS communication - MID(1) 4850 3026
Management software for COUNTIS See page 140
(1) 4 tariffs through RS485 communication.

Catalogue 2017 59
COUNTIS E4x
Active energy meters
three-phase - via CT up to 6000 A
Single-circuit metering,

The solution for


measurement &

> Industry
> Infrastructure
> Data centre
analysis

Strong points

> RS485 communication


(MODBUS or M-BUS) or
pulse output
COUNTIS E44 - MID - (3000 A MID - 6000 A not MID)
> Detection of connection errors
Function Principle diagram > MID certified B+D module
The COUNTIS E4x is a modular active and > Bi-directional metering
reactive electrical energy meter displaying > Multi-measurement
the energies and active power consumed and load curve
(kWh, kVArh and kW) directly on its backlit
LCD display. It is designed for three-phase
load metering with connection via CT and MID certification
is suitable for applications of up to 6000 A
(3000 A for MID). > COUNTIS E
COUNTIS E42, E44 and E46 are MID certified. comply with the
COUNTIS E4x MID directive,
guaranteeing
Common characteristics accuracy and reliability when
• Measurement accuracy: 1 % / 0,5%(MID). metering, an indispensable
• Backlit LCD display. function for energy billing
• Detects connection errors. applications.
COUNTIS E4x > COUNTIS E MID feature
tamper-proof components to
COUNTIS E4x
prevent fraud.
Advantages
RS485 communication (MODBUS or M-BUS) MID certified B+D module
or pulse output COUNTIS E products with MID certification Conformity to standards
To enable the remote reporting of energy provide the guaranteed accuracy required for
> IEC 62053-21
consumption, COUNTIS E4x are provided applications in which sub-billing of the electrical
class 1
with either a pulse output or an RS485 energy consumed is necessary. “Module B+D”
communication output, with MODBUS or certification guarantees that the design and > IEC 62053-23
M-BUS protocol. manufacturing process of products are class 2
In addition to their reporting functions, approved by an accredited laboratory. > IEC 62053-31
COUNTIS E4x with RS485 can be configured Bi-directional metering > IEC 62053-11
remotely and enable access to multi- (available on E43 and E45) > EN 50470-1
measurement values. This function is for metering energy production > EN 50470-3
Detection of connection errors or energy consumption.
The product is protected against phase/ Multi-measurement and load curve
neutral inversion and detects wiring errors. This Display of electrical values
simplifies the installation and commissioning, (I, U, V, P, Q, S, PF) and load curve over a
thereby reducing associated costs, and 7 day period via communication.
ensures that the device operates correctly.

Models Key functions


E40 Pulse output
E41 Dual tariff (2 partial counters) + Pulse output
E42 Dual tariff + MID + Pulse output
E43 Dual tariff + RS485 MODBUS communication
E44 Dual tariff + RS485 MODBUS communication + MID
E45 Dual tariff + M-BUS communication
E46 Dual tariff + M-BUS communication + MID

60 Catalogue 2017
COUNTIS E4x
Active energy meters
three-phase - via CT up to 6000 A

Front panel Electrical characteristics


1. Terminal shrouds (COUNTIS E42, E44 and E46). Current measurement
1 2. Backlit LCD display. three-phase on CT/5A up to 6000 A
3. MID marking (COUNTIS E42, E44 and E46). Type
(3000 A for MID products)
4. Serial number (COUNTIS E42, E44 and E46). Input consumption 0.2 VA per phase
2 5 5. Navigation key. Startup current (Ist) 10 mA
count_218x_a_2_cat

6
7 6. Reset key. Minimum current (Imin) 50 mA(1)
8
7. Metrological LED. Transition current (Itr) 250 mA(2)
8. Programming key. Reference current (Iref) 5 A(3)
3 4 Permanent overload (Imax) 6A
Intermittent overload 120 A for 0.5 s
Voltage measurement
Range of measurement 230 … 400 V ± 20 %
Case Consumption (VA) 2 VA
Permanent overload 280 V phase-neutral / 480 V phase-phase
62.5 Energy accuracy
72 45 Active (according to IEC 62053-21) Class 0,5s
Active (according to EN 50470) Class C (COUNTIS E42/44/E46)
Power supply
Self-supplied yes
COUNTIS E40

Error Partial
Frequency 50 / 60 Hz
count_193_b_1_x_cat

Output (pulsed) (COUNTIS E40/E41/E42)


90

45

PROG

RESET
Number 1
3X230(400)VAC 50/60Hz 0.05-5(6)A
C=0.1Wh/imp Type of optocoupler IEC 62053-31 Class A (20 ... 30 VDC)
Pulse weight 100 Wh, 1 kWh, 10 kWh, 100 kWh
50 ms, 100 ms, 200 ms, 400 ms, 800 ms,
Pulse duration
1000 ms, 1500 ms
Operating conditions
Type modular Operating temperature -10 … 55 °C
Number of modules 4 Storage temperature -20 … 70 °C
Dimensions W x H x D 73 x 90 x 62.5 mm Relative humidity 85 %
Case degree of protection IP20 Communication COUNTIS E43/E44 COUNTIS E45/E46
Front degree of protection IP51 Link RS485 Connection
Display type backlit LCD display Type 2 half duplex wires 2 half duplex wires
Rigid cable cross-section 1.5 … 10 mm2 Protocol MODBUS RTU M-BUS
Flexible cable cross-section 1 … 6 mm2 Speed 4800 … 38400 bauds 300 … 9600 bauds
Weight 230 g (1) I(min) ≤ 0.5 * Itr
(2) The accuracy class is guaranteed between Itr and Imax.
(3) I(ref) = I(b) (base current) = 10 * I(tr) for direct connection COUNTIS.

Connection
Recommendation:
- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.
- When disconnecting the COUNTIS, the secondary of each current transformer must be short-circuited. This operation can be carried out automatically by a
SOCOMEC PTI, an accessory which is included in this catalogue. Please consult us.
N N N
L1 L1 L1
L2 L2 L2
L3 L3 L3
count_189_f_1_x_cat

count_187_d_1_x_cat
count_186_c_1_x_cat

1 1 1 1 1 1 1 1 1

+ - + - + -

4 6 12 14 16 2 1 3 5 7 9 11 RS485 12 14 16 2 1 3 5 7 9 11 4 6 8 10 12 14 16 2 1 3 5 7 9 11
U1 U2 U3 N S1 S2 S1 S2 S1 S2 U1 U2 U3 N S1 S2 S1 S2 S1 S2 T1/2 U1 U2 U3 N S1 S2 S1 S2 S1 S2
L1 L2 L3 L1 L2 L3 L1 L2 L3
COUNTIS E40 COUNTIS E43/E44/E45/E46 COUNTIS E41/E42
1. Fuses 0.5 A gG / 0.5 A class CC.

References
COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS
E40 E41 E42 E43 E44 E45 E46
Type Reference Reference Reference Reference Reference Reference Reference
Via CT 4850 3008
Via CT - Dual tariff 4850 3009
Via CT - Dual tariff - MID 4850 3015
Via CT - Dual tariff with RS485 MODBUS com.(1) 4850 3017
Via CT - Dual tariff with RS485 MODBUS com. - MID(1) 4850 3014
Via CT - Dual tariff with M-BUS com.(1) 4850 3027
Via CT - Dual tariff with M-BUS com. - MID(1) 4850 3028
Management software for COUNTIS See page 140
(1) 4 tariffs through RS485 communication.

Catalogue 2017 61
COUNTIS E63
Active energy meters
3 x single-phase - direct 100 A
Single-circuit metering,

The solution for


measurement &

> Data centres


> Infrastructure
analysis

Strong points
COUNTIS E63
> Compact
> Advanced multi-
measurement functions
Function Principle diagram > Detection of connection errors
The COUNTIS E63 is a modular active
electrical energy meter which provides
Conformity to standards
metering for three single-phase loads, with
direct connection of up to 100 A. It directly
> IEC 62053-21
displays the total and partial energy and
class 1
power (kWh and kW) consumed by each
single-phase load. > IEC 62053-31
> IEC 62053-11

Management software
count_205_a_1_x_cat

CO
UN
TIS
E 63
COUNTIS E63 > To get the most effective
use from your Socomec
measurement and metering
devices, we offer a range of
dedicated software tools.
See page 140.

Advantages
Compact Detection of connection errors
Due to the integration of three single-phase The product is protected against
meters in the same case (7 modules wide), phase/neutral inversion and detects wiring
the COUNTIS E63 provides significant errors. This simplifies the installation and
space-saving. commissioning, thereby reducing associated
costs, and ensures that the device operates
Advanced multi-measurement functions correctly.
Advanced multi-measurement functions are
available via RS485 MODBUS communication:
• Instantaneous currents: I1, I2, I3
• Instantaneous voltages: V1, V2, V3
• Instantaneous power: 3P, 3S
• Instantaneous power factors: 3PF
• Load curves for each of the 3 phases:
Viewing of average positive active power
consumption over a programmable period.

62 Catalogue 2017
COUNTIS E63
Active energy meters
3 x single-phase - direct 100 A

Front panel
1. Backlit LCD display
2. Navigation key
3. Reset key
4. Metrological LED
count_201x_a_1_cat

2
3
4

Case
62.5 Type modular
126 45 Number of modules 7
Dimensions W x H x D 126 x 90 x 62.5 mm
Case degree of protection IP20
Front degree of protection IP51
count_203_a_1_x_cat

COUNTIS E60

Error Partial
Display type backlit LCD display
90

45

Rigid cable cross-section 2.5 … 35 mm2


3X230(400)VAC 50/60Hz 0.5-20(100)A
RESET / PROG

C=2Wh / imp
Flexible cable cross-section 2.5 … 35 mm2
Weight 490 g
3 x phases 100A

Electrical characteristics
Current measurement Power supply
Type 3 x single-phase - direct 100 A Self-supplied yes
Input consumption 0.5 VA max. per phase Frequency 50 / 60 Hz
Startup current (Ist) 80 mA Operating conditions
Minimum current (Imin) 0.5 A Operating temperature -10 … 55 °C
Transition current (Itr) 2A Storage temperature -20 … 70 °C
Reference current (Iref) 20 A Relative humidity 95 %
Permanent overload (Imax) 100 A Communication
Intermittent overload 3000 A max for 10 ms Link RS485
Voltage measurement Type 2 … 3 half duplex wires
Range of measurement 230 ... 400 V ± 20 % Protocol MODBUS RTU
Consumption on inrush (VA) 2 MODBUS® speed 4800 … 38400 bauds
Permanent overload 280 V phase-neutral / 480 V phase-phase
Energy accuracy
Active (according to IEC 62053-21) Class 1

Connection
N
L1 L1’
L2 L2’
L3 L3’
count_206_b_1_GB_cat

+ - 0

2 15 17 13 1 3 5 7 9 11
N RS485 L - 1 - L’ L - 2 - L’ L - 3 - L’
COUNTIS E63

References
COUNTIS E63
Type Reference
3 x single phase - 100 A direct with RS485 MODBUS communication 4850 3016

Catalogue 2017 63
COUNTIS ECix
Multi-utility pulse concentrator
Single-circuit metering,

The solution for


measurement &

> Data centres


> Industry
> Infrastructure
analysis

Strong points

> Up to 7 multi-utility meters


COUNTIS ECi3 and 2 analogue sensors
> Load curves
> RS485 MODBUS
communication
> Improved customisation
Function Principle diagram
The COUNTIS ECix is a multi-utility pulse Management software
concentrator which communicates via an
RS485 link using MODBUS protocol. > To get the most effective
It enables pulses from water, gas, use from your Socomec
CO
UN
TIS
E Ci3

compressed air, electricity meters and, for measurement and metering


COUNTIS ECi
the COUNTIS ECi3, the output of analogue devices, we offer a range of
sensors (light, temperature, wind etc.) to be CO
UN
TIS
E 63
dedicated software tools.
registered and stored. All data, ie. total and 485
See page 140.
partial meters and load curves (available COUNTIS E 232
count_210_c_1_gb_cat

for all logical and analogue inputs) can


be centralised via RS485 communication L
using MODBUS protocol.
m3

kWh


PC

Energy efficiency software

Advantages
Up to 7 multi-utility meters and RS485 MODBUS communication
2 analogue sensors • Centralisation and transmission of pulse and
• 7 digital inputs + 2 analogue inputs. analogue data to a supervision station.
• Total, partial and programmable metering • Remote configuration of COUNTIS ECi
(day, week, month, year). device.
Load curves Improved customisation
Load curves are available for each of the • Selection of the measuring unit:
7 logical inputs. kWh, m3, liters.
A history of average values are available for • Selection of the currency unit: €, K€, £, $.
the 2 analogue inputs (ECi3). Values can be displayed in the unit of your
choice and energy costs can be directly
calculated.

Models Key characteristics


ECi2 7 insulated inputs
ECi3 7 insulated inputs + 2 analogue inputs.

64 Catalogue 2017
COUNTIS ECix
Multi-utility pulse concentrator

Front panel Characteristics


1. Backlit LCD display. Auxiliary power supply
2. Navigation keys. Self-supplied no
3. Validation pushbutton in programming mode. Alternating voltage 110 / 400 VAC
4. Communication status indicator (COM). Direct voltage 120 / 300 VDC
Tolerance ± 10 %
count_207x_b_2_cat

Frequency 45 / 65 Hz
2 Consumption 5 VA
Insulation voltage 3.5 kV
3 Communication
Link RS485
Type 2 … 3 half duplex wires
Protocol MODBUS RTU
1 4
MODBUS® speed 9600 … 38400 bauds
Inputs
Number 7
Case Control voltage (integrated) 10…30 VDC
Minimum signal width 10 ms
73 67 Maximum signal width 2s
44 Minimum duration between 2 pulses 30 ms
Edge triggering rising
Analogue inputs (ECi3)
Number 2
Current 25 mA
Accuracy 0.5 %
count_208_a_1_x_cat

Response time 500 ms


Input resistance 200 Ω
90

45

Consumption 0.1 VA
Operating conditions
Operating temperature -10 … +55 °C
Storage temperature -20 … +70 °C
Relative humidity 95 %

Type modular
Number of modules 4
Dimensions W x H x D 73 x 90 x 67 mm
Case degree of protection IP20
Front degree of protection IP51
Display type backlit LCD display
Terminal blocks type fixed
Rigid cable cross-section 1 … 10 mm2
Flexible cable cross-section 0.5 … 6 mm2
Weight 215 g

Connection
Us 31 : logical input n°1. 13-15-17 : RS485 link.
32 : logical input n°2.
1 2 3 4 5 6 7 33 : logical input n°3. 5-6 : Analogue input n°1.
1 1 34 : logical input n°4. 7-8 : Analogue input n°2.
R = 120 Ω 35 : logical input n°5. 9-10 : output.
36 : logical input n°6. 20-22 : power supply
count_209_a_1_x_cat

31 32 33 34 35 36 51 50 13 15 17 37 5 6 7 8 9 10 20 22 37 : logical input n°7. U=110...400 VAC ± 10 %.


+ 0V + - + - + - OUT PUT AUX
RS485 0/4...20 mA SUPPLY 51-50 : Inputs internal/
external power supply.
COUNTIS ECi
1. 0.5 A gG fuses.

References
COUNTIS ECi2 COUNTIS ECi3
Auxiliary power supply Us Reference Reference
230 / 400 VAC 4853 0000
230 / 400 VAC + 2 analogue inputs 4853 0001

Description of accessories Reference Reference


Panel mounting kit 192J 8015 192J 8015
Management software for COUNTIS See page 140

Catalogue 2017 65
RETROFIT Line
MID active energy meter dedicated to existing installations
Single-circuit metering,

The solution for


measurement &

> Light Industry


> Infrastructure
> Data centers
analysis

refit_002_a_1_cat

refit_010_a_1_cat
COUNTIS E44R TC0 36
400 A

Function Strong points


Existing sites, having been built before The RETROFIT Line consists of COUNTIS
optimised energy consumption was a meters combined with TCO split-core current > High overall accuracy
consideration, are especially in need of a transformers. Together they allow measuring > Easy installation
dedicated energy efficient solution. and metering single and three phase networks > Proven products
COUNTIS products with MID certification up to 600 A, even inside the most confined
cabinet spaces. > Communication to a
provide the guaranteed accuracy required
Monitoring system
for applications in which sub-billing of the
electrical energy consumed is necessary. > Guaranteed connections
To meet this requirement, the RETROFIT Line
allows you to easily add metering points in
electrical enclosures which are very restricted
Conformity to standards
in terms of integration.
COUNTIS:
> IEC 62053-21
Advantages > IEC 62053-22
High overall accuracy Communication to Monitoring > IEC 62053-23
A global system measuring accuracy of The data from RETROFIT products can be > IEC 62053-31
better than 1% in energy from 10 to 120% of transferred to a central monitoring system.
nominal current. > EN 50470-3
Guaranteed connections > EN 50470-1
Easy installation The product is protected against phase/
TCO split-core transformers mean the power neutral inversion and detects wiring errors.
cables do not need to be disconnected. Commissioning has been simplified to ensure
Operations are quicker and minimise the the device operates correctly: installation costs
electrical disconnection time. are therefore reduced.

Proven products
The COUNTIS products are based on
standard SOCOMEC ranges.

66 Catalogue 2017
RETROFIT Line
MID active energy meter dedicated to existing installations

Meters
Function
The COUNTIS E4xR is an active electrical energy meter designed for The COUNTIS E44R pack offers MODBUS RTU communication via
three-phase networks. It is used for connection via TCO up to 600 A. RS485 and includes 4 tariffs.
The COUNTIS E42R is a totalising meter allowing direct reading of the COUNTIS E42R and E44R are MID-certified (B + D module).
power consumed, using a pulse output. It is a dual tariff meter for dual
tariff invoicing.

Technical characteristics(1)

COUNTIS E42R COUNTIS E44R


Current measurement
Type TC/1 up to 600 A TC/1 up to 600 A
Input consumption 0.2 VA per phase 0.2 VA per phase
Overload 24 A / 0.5 s 24 A / 0.5 s
Permanent overload 1.2 A 1.2 A
Minimum current measured 10 mA 10 mA
Voltage measurement
Range of measurement 230 … 400 V ± 15 % 230 … 400 V ± 15 %
Input consumption 2 VA 2 VA
Permanent overload 280 V 280 V
Energy accuracy
Active (according to EN 50470) Class C Class C
(1) Features not mentioned are identical to those of COUNTIS E4x standard products.

Front panel, terminals, case, connection


See the standard COUNTIS E range catalogue pages.

References
Meters Reference Current transformers Reference
COUNTIS E42R 4850 3021 TCO 24 100/1 182T 4910
COUNTIS E44R 4850 3022 TCO 24 250/1 182T 4925
TCO 36 400/1 182T 4940
TCO 36 600/1 182T 4960

What are the advantages of a MID meter?


It allows to resell electricity
The MID directive guarantees safe and reliable metering. The meter is tamper-proof and its accuracy is guaranteed
thanks to calibration on a metrology bench.
COUNTIS E42R and E44R are MID-certified (B + D module). It is mandatory and this means SOCOMEC is required
to supply products which meet the design and manufacturing requirements imposed by this standard.
The specificity of MID product
- Standardised accuracy A, B or C: Socomec MID meters have a guaranteed accuracy class C ± 0.5%.
- Tamper-proof devices: protection cover and seals are provided.
- Mandatory markings: CE + MID front and side marking confirms the compliance to modules B + D.
- Related Certificate: provided by Socomec, it formalizes the accuracy verification of the energy meter at four different current levels.

Catalogue 2017 67
RETROFIT Line
MID active energy meter dedicated to existing installations

TCO - split-core current transformers


Function
The TCO small split-core current transformers must be only combined The RETROFIT pack guarantees overall accuracy to within less
with COUNTIS RETROFIT energy meters. than 1%.

Technical characteristics

TCO 24 TCO 36
Internal diameter (mm) 24 36
Overall accuracy class(1) 1 1
Ø Dimensions H x W x D (mm) 74.5 x 45 x 34 91 x 57 x 40.5
(1) Overall accuracy of the COUNTIS RETROFIT + TCO combination: (1) Global accuracy guaranteed when associating COUNTIS Retrofit + split-
H core CT with load between 10 % to 120 % of In.
refit_017_a_1_gb_cat

D
W

The advantages of TCO split-core current transformers


Wide current range
The TCOs accept a primary current between 100 and 600 A making it possible to connect at different points in the installation.
A guaranteed overall accuracy
Combined with the COUNTIS RETROFIT products, the TCO guarantees overall accuracy is better than 1%.
Compact
With their compact and open design, the TCOs are easily positioned on existing installations without the need to disconnect/reconnect the
cables or modify the installation. Measurement points can therefore be placed in the most confined panels.

68 Catalogue 2017
RETROFIT Line
MID active energy meter dedicated to existing installations

Services
Take advantage of the advice offered by an energy specialist
Socomec offers a full range of customised • Implementation
services for your energy efficiency requirements • Training

sydiv_069_a_1_gb_cat
and can help you find the best solution: • Electrical facility audit
• Project engineering.

For more details download our Service brochure available on our web site :
www.socomec.com or contact your SOCOMEC office.

Zoom

Think about it
COUNTIS Eci
count_207_a_1_cat

Communicate consumption information whatever the


energy (electricity, water, gas...) to a PC or PLC. Please
see the COUNTIS Eci catalogue pages.

Catalogue 2017 69
MULTIS L50
Digital panel meter
three phases - via CT up to 6000 A dimensions 96 x 96 mm
Single-circuit metering,

new
The solution for
measurement &

> Industry
> Infrastructure
analysis

multi_076_a_1_cat.eps
Strong points
MULTIS L50
> Large backlit LCD display
> Direct display of
Function Principle diagram multimeasurement and
metering values
The MULTIS L50 is a panel mounted digital
> RS485 MODBUS
meter displaying multi-measurement and
communication
energy values directly on its large backlit
LCD display. It is designed for utilisation > Inputs/Output for control/
on three-phase or single-phase networks command ou pulses
with connection via CT and is suitable for
applications of up to 6000 A. The product can
Conformity to standards
MUL
TIS
L5
0

be configured by the user via the keypad and


the display.
MULTIS L50
> IEC 62053-21
class 1
Advantages > IEC 62053-23
Easy to use class 2
MUL
multi_063_a_1_x_cat

Thanks to its large backlit LCD display and


TIS
L5
0

its multiple viewing screens with direct MUL


TIS
L5
0

pushbutton access, MULTIS L50 provide MULTIS L50


clear readings and are easy to use.
MULTIS L50
They directly display a number of multi-
measurement and metering values.

Advanced functionalities
The MULTIS L50 offers input/output functions
as standard and has a pulse output or RS485
MODBUS communication output.

Functions

Multi-measurement Metering Communications(1)


• Currents • Active energy: ± kWh RS485 with MODBUS protocol
- instantaneous: I1, I2, I3, In • Reactive energy: ± kvarh Output
- maximum average: I1, I2, I3, In • Hours: • Remote command of device
• Voltages & frequency Harmonic analysis • Pulse report
- instantaneous: V1, V2, V3, U12, U23, U31, F • Total harmonic distortion (level 51) Inputs
• Power - Currents: thd I1, thd I2, thd I3 • Remote status device
- instantaneous: 3P, ΣP, 3Q, ΣQ, 3S, ΣS - Phase-to-neutral voltage: thd V1, thd V2, thd V3 (1) Available as an option (see the following pages).
- maximum average: ΣP, ΣQ, ΣS - Phase-to-phase voltage: thd U12, thd U23,
- unbalance: U unb thd U31
• Power factors
- instantaneous: 3PF, Σ

70 Catalogue 2017
MULTIS L50
Digital panel meter
three phases - via CT up to 6000 A dimensions 96 x 96 mm

Front panel
1. Backlit LCD display.
2. Direct access key for currents (instantaneous and max. values), current THD.
3. Direct access key for voltages, frequency and voltage THD.
4. Pushbutton for active, reactive, and apparent power (instantaneous and max. values)
and power factor.
multi_076x_a_2_cat.eps

5. Direct access key for energies, hour meter and programming menu.

1 2 3 4 5

Case
92 +- 0.0
0.8
Type panel mounting
Dimensions W x H x D 96 x 96 x 60 mm
Case degree of protection IP30
Front degree of protection IP52
Display type backlit LCD display
Terminal block type fixed or plug-in
Voltage and other connection cross-section 0.2 … 2.5 mm2
multi_075_a_1_x_cat.eps

96
MU
LTIS
L5
0
92 +- 0.0
0.8 Current connection cross-section 0.5 … 6 mm2
Weight 400 g
I

35
>
V
F
> P

45
PF
OK
E
PR

15
OG

96

Plug-in modules
MULTIS L50
1 Output
diris_445_a_1_cat

1 output assignable to:


• Pulses: configurable (type, weight, duration) in kWh or kvarh.
• Remote command of device.
diris_773_a_1_cat

Communication
diris_447_a_1_cat

RS485 link with JBUS / MODBUS protocol


(speed up to 38400 bauds)

3 inputs, 1 output
diris_449_a_1_cat

3 inputs assignable to:


• Remote status device.
1 output assignable to:
• Pulses: configurable (type, weight, duration) in kWh or kvarh.
• Remote command of device.

Accessories
Current transformers IP65 protection Panel mounting kit
(See page 106) for a 144 x 96 mm cut-out
trafo_077_b_2_cat

diris_720_a_2_cat

diris_718_b_1_cat
trafo_024_a_2_cat

Catalogue 2017 71
MULTIS L50
Digital panel meter
three phases - via CT up to 6000 A dimensions 96 x 96 mm

Electrical characteristics
Current measurement (TRMS) Energy accuracy
Via CT primary 9 999 A Active (according to IEC 62053-21) Class 1
Via CT secondary 5A Reactive (according to IEC 62053-23) Class 2
Measurement range 0 … 11 kA Auxiliary power supply
Input consumption 0.6 VA Alternating voltage 110 … 250 VAC
Measurement updating period 1s AC tolerance ± 10 %
Direct voltage 120 … 250 VDC
Accuracy 1%
DC tolerance ± 10%
Permanent overload 6A
Frequency 50 / 60 Hz
Intermittent overload 10 In for 1 s
Consumption 10 VA
Voltage measurements (TRMS) Pulse or alarm output
Direct measurement between phases 50 … 500 VAC Number 1
Direct measurement between phase and neutral 28 … 289 VAC Type 100 VDC - 0.5 A - 10 VA
Input consumption ≤ 0.1 VA Max. number of operations ≤ 108
Measurement updating period 1s Inputs
Accuracy 1% Number 3
Permanent overload 800 VAC Power supply 10 … 30 VDC
Power measurement Minimum signal width 10 ms
Measurement updating period 1s Minimum duration between 2 pulses 18 ms
Accuracy 1% Type Phototransistors
Power factor measurement Communication
Measurement updating period 1s Link RS485
Accuracy 1% Type 2 … 3 half duplex wires
Frequency measurement Protocol MODBUS RTU
MODBUS® speed 1400 … 38400 bauds
Measurement range 45 … 65 Hz
Operating conditions
Measurement updating period 1s
Operating temperature - 10 … + 55 °C
Accuracy 0.1 %
Storage temperature - 20 … + 85 °C
Relative humidity 95 %

Terminals
multi_063_a_1_x_cat.eps

S1 - S2: current inputs.


V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2
I1 I2 I3 AUX: auxiliary power supply Us.
V1, V2, V3 & VN: voltage inputs.
MULTIS L50

Communication module Output or alarm module 3 inputs, 1 output module


multi_064_a_1_x_cat.eps

multi_065_a_1_x_cat.eps

multi_066_a_1_x_cat.eps
+ - + - + -
0V - + 1 1 8 19
1 2 13 1 4 15 1 6 17 1 9 18
0n OUT 1
RS485 R = 120 IN 3 IN 2 IN 1 OUT 1

MULTIS L50 MULTIS L50 MULTIS L50


RS485 link. 18 - 19 : output n°1
R = 120 Ω: selectable internal resistance for
RS485 end of line termination.

Connection
Recommendation:
- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.
- When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out automatically by a SOCOMEC
PTI, an accessory which is included in this catalogue. Please consult us.

Low voltage balanced network


3/4 wires with 1 CT Single-phase Two-phase
N P1 P1 L1
P1 L1
L1 S1 S2 S1 S2 L2
S1 S2 N
L2
L3

1 1 1 1 1 1
multi_073_a_1_x_cat.eps

multi_074_a_1_x_cat.eps
multi_072_a_1_x_cat.eps

V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3

Use of 1 CT reduces by 0.5% the accuracy of the phases, 1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC.

72 Catalogue 2017
MULTIS L50
Digital panel meter
three phases - via CT up to 6000 A dimensions 96 x 96 mm

Low voltage unbalanced network

3/4 wires with 3 CTs 3 wires with 2 CTs 3 wires with 2 CTs
P1 L1 P1 L1
N S1 S2 S1 P1
P1 L2 L2
L1 P1 S1 S2
S1 S2 L3 L3
L2
P1 S1 S2
L3
S1 S2
1 1 1 1 1 1

multi_070_a_1_x_cat.eps

multi_071_a_1_x_cat.eps
diris_395_d_1_x_cat.eps
1 1 1

S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
V1 V2 V3 VN
I1 I2 I3 I1 I2 I3 I1 I2 I3

1. Fuses 0.5 A gG / 0.5 A class CC. Use of 2 CTs reduces by 0.5% the accuracy of the Use of 2 CTs reduces by 0.5% the accuracy of the
phases, the current of which is worked out by vector phases, the current of which is worked out by vector
calculation. calculation.
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.

Additional information

Communication via RS485 link AC & DC auxiliary power supply

110 / 250 VAC


120 / 250 VDC

1 1
LIYCY-CY
multi_067_a_1_x_cat.eps
multi_068_a_1_x_cat.eps

0V - + A U X
ON
RS485

1. Fuses 0.5 A gG / 0.5 A class CC.

References

Basic device MULTIS L50


Reference
MULTIS L50 192J 9120
Optional plug-in modules Reference
1 output 4825 0080
RS485 MODBUS® communication 4825 0082
3 inputs, 1 output 4825 0083
Accessories
Description of accessories To be ordered in multiples of Reference
IP65 protection 1 4825 0089
Panel mounting kit for a 144 x 96 mm cut-out 1 4825 0088
Fuse holder for the protection of voltage inputs (type RM) 3 poles 4 5601 0018
Fuse holder for the protection of the auxiliary supply (type RM) 1 pole + neutral 6 5601 0017
Fuse type gG 10x38 0.5 A 10 6012 0000
Ferrite to be associated with communication modules 1 4899 0011
Current transformer range 1 see page 106

Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.

Catalogue 2017 73
DIRIS A10
Multifunction meters - PMD
modular multifunction meter
Single-circuit metering,

The solution for


measurement &

> Industry
> Infrastructures
> Data centres
analysis

diris_791_c_1_cat
DIRIS A10 Strong points
Function Principle diagram > Easy to use
The DIRIS A10 is a modular multifunction > Integrated temperature
meter for measuring electrical values in low sensor
voltage networks. > Detects wiring errors
It allows all electrical parameters to be > Compliant with IEC 61557-12
displayed and utilised for communication and/
or output functions.
Conformity to standards
Advantages
> IEC 61557-12
Easy to use
> IEC 62053-22
Five direct access pushbuttons enable all RS485 DIRIS A10
DIRIS A10 class 0.5S
measurements to be clearly viewed on its
backlit LCD display. > IEC 62053-23
485 General
measurement
class 2
ETH
Integrated temperature sensor report

It allows variations in temperature to be > UL


detected.
PC Curves for
Detects wiring errors current
per phase
An integrated test function can be utilised to PLC
diris_808_f_1_gb_cat

detect incorrect wiring and to automatically


correct CT installation errors.

Compliant with IEC 61557-12 Energy efficiency software


IEC 61557-12 is a high-level standard for
all PMDs (Performance Monitoring Devices)
that are designed to measure and monitor
electrical parameters in distribution networks.
Compliance with IEC 61557-12 ensures
a high level of equipment performance, in
terms of metrology, and the mechanical and
environmental aspects (EMC, temperature, etc.).
Functions
Multi-measurement • Metering Events
• Currents • Active energy: + kWh Alarms on all electrical values
- instantaneous: I1, I2, I3, In • Reactive energy: + kVarh Communications(1)
- maximum average: I1, I2, I3, In • Hours: RS485 with MODBUS protocol
• Voltages & frequency • Harmonic analysis Input
- instantaneous: V1, V2, V3, U12, U23, U31, F • Total harmonic distortion (level 51) • Tariff selection
• Power - Currents: thd I1, thd I2, thd I3 • Remote device status
- instantaneous: 3P, ΣP, 3Q, ΣQ, 3S, ΣS - Phase-to-neutral voltage: thd V1, thd V2, thd V3 Output
- maximum average: ΣP, ΣQ, ΣS - Phase-to-phase voltage: thd U12, thd U23, • Remote command of device
• Power factors thd U31 • Alarm report
- instantaneous: 3PF, ΣPF Dual tariff function • Pulse report
Selection of one out of 2 billing tariffs (1) Available on specific version (see the following pages).

74 Catalogue 2017
DIRIS A10
Multifunction meters - PMD
modular multifunction meter

Front panel

1. Backlit LCD display.


2. Direct access key for currents (instant and maximum), current THD and test function.
3. Direct access key for voltages, frequency and voltage THD.
4. Direct access key for active, reactive and apparent power (instantaneous and max. values) and
diris_791x_c_1_cat

power factor.
2 5. Direct access key for energies.
3 6. Pushbutton for hour meter, temperature and programming menu access.
4 7. Metrological LED.
5
6
7

Case
64
72 44
Type modular
Number of modules 4
Dimensions W x H x D 72 x 90 x 64 mm
DIRIS A 10 Case degree of protection IP 30
diris_809_a_1_x_cat

I TEST
Front degree of protection IP 52
V F
Display type backlit LCD display
45
90

P PF
E OK
Voltage and current connection
°C PROG 4 mm2
cross-section
C=0,1Wh/imp

Connection cross-section for AUX


2.5 mm2
supply, input, output and comms.
Weight 205 g (4825 0010) - 215 g (4825 0011)

Electrical characteristics
Current measurement (TRMS) Energy accuracy
Via CT primary 9 999 A Active (according to IEC 62053-22) Class 0.5 S
Via CT secondary 5A Reactive (according to IEC 62053-23) Class 2
Measurement range 0 … 11 kA Auxiliary power supply
Input consumption 0.6 VA Alternating voltage 110 … 277 VAC
Measurement updating period 1s AC tolerance ± 15 %
Accuracy 0.2 % Frequency 50 / 60 Hz
Permanent overload 6A Consumption < 3 VA
Intermittent overload 10 In for 1 s Digital output (pulses or on/off)
Voltage measurements (TRMS) Number 1
Direct measurement between phases 50 … 500 VAC Type 20 / 30 VDC - 0.5 A - 10 VA
Direct measurement between phase and neutral 28 … 289 VAC Max. number of operations ≤ 108
Input consumption ≤ 0.1 VA Input (tariff)
Measurement updating period 1s Number 1
Accuracy 0.2 % Type 0 VAC: T1 / 200-277 VAC: T2
Permanent overload 800 VAC Communication
Power measurement Link RS485
Measurement updating period 1s Type 2 … 3 half duplex wires
Accuracy 0.5 % Protocol MODBUS RTU
Power factor measurement MODBUS® speed 2400 … 38400 bauds
Measurement updating period 1s Operating conditions
Accuracy 0.5 % Operating temperature - 10 … + 55 °C
Frequency measurement Storage temperature - 20 … + 70 °C
Measurement range 45 … 65 Hz Relative humidity 85 %
Measurement updating period 1s
Accuracy 0.1 %

Catalogue 2017 75
DIRIS A10
Multifunction meters - PMD
modular multifunction meter

Connection
Recommendation:
- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.
- When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out automatically by
a SOCOMEC PTI, an accessory which is included in this catalogue. Please consult us.
- It is recommended that the earthing point for the DIRIS A10 and the current transformer secondaries are not earthed at the same time.

Low voltage balanced network


3/4 wires with 1 CT Single-phase Two-phase

N P1 P1
P1 L1 L1
L1 S1 S2 S1 S2
S1 S2 N L2
L2
L3

1 1 1 1 1 1
diris_810_a_1_gb_cat

diris_811_a_1_gb_cat

diris_812_a_1_gb_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3

1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.

Low voltage unbalanced network

3/4 wires with 3 CTs 3 wires with 2 CTs 3 wires with 2 CTs

N P1 L1 P1 L1
P1 L1 S1 S2 L2 S1 P1 L2
S1 S2 L2 P1 L3 S1 S2 L3
P1 L3 S1 S2
S1 S2
1 1 1 1 1 1
diris_813_a_1_gb_cat

diris_814_a_1_gb_cat

diris_815_a_1_gb_cat

1 1 1

V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3

1. Fuses 0.5 A gG / 0.5 A class CC. Use of 2 CTs reduces by 0.5% the accuracy of the Use of 2 CTs reduces by 0.5% the accuracy of the
phases, the current of which is worked out by vector phases, the current of which is worked out by vector
calculation. calculation.
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.

Additional information
Communication via RS485 link AC auxiliary power supply

110-277 VAC

1 1
LIYCY-CY
diris_821_e_1_x_cat
diris_820_a_1_x_cat

0V - + 20 22
AUX
RS485

1. Fuses 0.5 A gG / 0.5 A class CC.

76 Catalogue 2017
DIRIS A10
Multifunction meters - PMD
modular multifunction meter

Terminals
diris_816_a_1_x_cat

12 14 16 2 20 22 1 3 5 7 9 11 18
V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2
I1 I2 I3
DIRIS A10
AUX: auxiliary power supply Us. S1 - S2: current inputs.
V1, V2, V3 & VN: voltage inputs.

Communication terminals Pulse or alarm output terminals Input terminals

diris_819_b_1_x_cat
diris_816_a_1_x_cat

diris_818_a_1_x_cat
1 3 15 17 4 6 8 10
0V + - OUT 1 IN 1
RS485

DIRIS A10 DIRIS A10 DIRIS A10


RS485 link. 4 - 6 : output n°1 8 - 10 : input n°1

References
Basic device DIRIS A10
Description Reference
DIRIS A10 (available in light grey on request) 4825 0010
DIRIS A10 with RS485 MODBUS communication (available in light grey on request) 4825 0011
Description of accessories To be ordered in multiples of Reference
Fuse disconnect switches for the protection of voltage inputs (type RM) 3 poles 4 5601 0018
Fuse disconnect switches for the protection of the auxiliary supply (type RM) 1 pole + neutral 6 5601 0017
Fuses type gG 10x38 0.5 A 10 6012 0000
Current transformer range 1 see page 106
Management software for DIRIS see page 140

Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.

Catalogue 2017 77
DIRIS A14
Multifunction measuring unit - PMD - MID
multi-measurement
Single-circuit metering,

The solution for

new
measurement &

> Industry
> Infrastructures
> Data centers
analysis

diris_964_a_1_cat

diris_908_a_1_cat
DIRIS A14 panel mounted DIRIS A14 DIN rail mounted Strong points

Function Functional diagram > Single phase and three phase


MID certified
The DIRIS A14 is an MID approved
> Bi-directional metering
multifunction meter - for measuring electrical
values in low voltage networks. > Multi-measurement
It allows all electrical parameters to be and load curves
displayed and utilised for communication and/ > IEC 61557-12 measuring
or output functions. method
> Detection of connection errors

Advantages
DIRIS A14 Compliance with standards
Single phase and three phase MID certified RS485 door mounted
DIRIS A14
DIRIS A14 products with MID certification DIN rail mounted > IEC 61557-12
provide the guaranteed accuracy required 485 General > IEC 62053-23
for applications in which sub-billing of the ETH measurement
report class 2
electrical energy consumed is necessary, > EN50470-1
whether on a three-phase or single-phase
network. “Module B+D” certification > EN50470-3 class C
PC Curves for
guarantees that the design and manufacturing current
diris_907_c_1_fr_cat

process of products are approved by an PLC per phase


accredited laboratory.

Bi-directional metering (four quadrants)


This function is for metering energy production Energy efficiency software
or energy consumption.
IEC 61557-12 measuring method Detection of connection errors
Multi-measurement and load curve IEC 61557-12 is a high-level standard The product is protected against phase/
Display of electrical values(I, U, V, ΣP, ΣQ, ΣS, covering all PMDs (Performance Monitoring neutral inversion and detects wiring errors.
PF) and P+ load curve over a 7 day period via Devices). By using the measuring method The power supply internally derived from the
communication. of IEC 61557-12 ensures a high level voltage connections ensures realtime MID
of equipment performance, in terms of counting as soon as the mains voltage is
metrology. present.

Functions
Multi-measurement Total and partial metering Events (via communication)
• Currents • Active energy: + kWh, - kWh • Active energy consumption:
- instantaneous: I1, I2, I3, In • Reactive energy: + kvarh, - kvarh day n-1 / week n-1 / month n-1
- maximum average: I1, I2, I3, In • Active power load curves:
Harmonic analysis (via communication) P 10 minutes over 7 days with time-log
• Frequency • Total harmonic distortion (rank 63)
• Voltages Communications
- Currents: thd I1, thd I2, thd I3
- instantaneous: V1, V2, V3, U12, U23, U31, F RS485 with MODBUS protocol
- Phase-to-neutral voltage: thd V1, thd V2, thd
• Powers V3
- instantaneous: ΣP, ΣQ, ΣS Phase-to-phase voltage: thd U12, thd U23, thd
- maximum average: ΣP, ΣQ, ΣS U31
• Power factor (cos ϕ) Multi tariff function (via communication)
- instantaneous: Σ cos ϕ Selection of one out of 4 billing tariffs
- maximum average: Σ cos ϕ

78 Catalogue 2017
DIRIS A14
Multifunction measuring unit - PMD - MID
multi-measurement

Front panel
1. Backlit LCD display
2. Direct access for energies and validation key
3. Programming key
4. Navigation key for measurements
5. Metrological LED
6. MID marking
7. Serial Number
2
1 2
3
6 4 3
diris_908x_a_2_cat

diris_964x_a_2_cat
7 5
5

1 6
7

Case
DIRIS A14 DIN rail mounted
64 DIRIS A14 DIRIS A14
72 6 44 DIN rail mounted door mounted
Type modular Recessed
Number of modules 4 -
Dimensions W x H x D 72 x 90 x 64 mm 96 x 96 x 69.5 mm
diris_906_a_1_x_cat

Case degree of protection IP20


45
90

Front degree of protection IP51


Display type Backlit LCD
Rigid cable cross-section 1.5 … 10 mm2
Flexible cable cross-section 1 … 6 mm2
DIRIS A14 door mounted Weight 240 g 450 g

96 69.5 24
diris_914_a_1_x_cat

96

Electrical characteristics
Current measurement (TRMS) Energy accuracy
Via CT primary 10 … 2500 A Active (according to IEC 62053-22) Class 0.5 S
Via CT secondary 5A Reactive (according to IEC 62053-23) Class 2
Input consumption 0.6 VA Active (according to EN 50470) Class C
Startup current (Ist) 5 mA Metrological LED (EA+,EA-)
Minimum current (Imin) 50 mA Pulse weight 10000 pulses/kWh
Transmission current (Itr) 250 mA Colour Red
Reference current (Iref) 5A Auxiliary power supply
Measurement updating period 1s Self-powered Yes
Accuracy 0.5% Frequency 50 / 60 Hz
Permanent overload 6A Communication
Intermittent overload 120 A for 0.5 s Link RS485
Voltage measurements (TRMS) Type 2 to 3 half duplex wires
Direct measurement (four phases) 50 …460 VAC Protocol MODBUS® RTU
Input consumption 2 VA MODBUS® speed 4800 … 38400 bauds
Measurement updating period 1s Operating conditions
Accuracy 0.2% Operating temperature -10 … +55°C
Permanent overload 480 V (phase-to-phase measurement) Storage temperature -20 … +70°C
Power measurement Relative humidity 95% non-condensing
Measurement updating period 1s
Accuracy 0.5%
Power factor measurement (cos ϕ)
Measurement updating period 1s
Accuracy 0.01

Catalogue 2017 79
DIRIS A14
Multifunction measuring unit - PMD - MID
multi-measurement

Connection
Low voltage balanced network
Recommendation:
- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.
- When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited.
This operation can be carried out automatically by a SOCOMEC PTI, which can be found in the SOCOMEC catalogue: please consult us.

Low voltage unbalanced network

3/4 wires with 3 CTs Single-phase

N P1 L1
P1 L1 S1 S2 N
S1 S2 L2
P1 L3
S1 S2
1
diris_902_b_1_x_cat

1 1 1

diris_916_a_1_x_cat
V1 V2 V3 N S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3

1. 0.5 A gG / 0.5 A class CC fuses. 1. 0.5 A gG / 0.5 A class CC fuses.

3 wires with 2 CTs 3 wires with 2 CTs


P1 L1 P1 L1
S1 S2 L2 S1 P1 L2
P1 L3 S1 S2 L3
S1 S2

1 1 1 1 1 1
diris_918_a_1_x_cat
diris_917_a_1_x_cat

V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3

1. 0.5 A gG / 0.5 A class CC fuses. 1. 0.5 A gG / 0.5 A class CC fuses.

Additional information

Communication via RS485 link

LIYCY-CY
diris_903_a_1_x_cat

NC - +

RS485

80 Catalogue 2017
DIRIS A14
Multifunction measuring unit - PMD - MID
multi-measurement

Terminals
Voltage outlets Current inputs
V 12 I1 S1 1
V2 14 I1 S2 3
V3 16 I2 S1 5
N 2 I2 S2 7
ICM (Intelligent Communication Module) I3 S1 9
RS485 “+” 15 I3 S2 11
RS485 “-” 17
RS485'NC" 13

References
Basic device DIRIS A14
Description Reference
DIRIS A14 MID DIN rail mounted 4825 0020
DIRIS A14 MID door mounted 4825 0021

Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.

Catalogue 2017 81
DIRIS A20
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
Single-circuit metering,

The solution for


measurement &

> Industry
> Infrastructure
> Data centre
analysis

diris_750_a_1_cat

DIRIS A20
Strong points

> Easy to use


Function Principle diagram > Compliant with IEC 61557-12
> Detects wiring errors
DIRIS A20 are panel mounted measurement
units which ensure the user has access to all
the measurements required for successfully Conformity to standards
carrying out energy efficiency projects and
ensuring the electrical distribution is monitored. > IEC 61557-12
All this information can be analysed remotely
> IEC 62053-22
DIRIS_576_g_1_gb_cat

using an energy management software solution.


class 0.5S
> IEC 62053-23
RS485 DIRIS A20
DIRIS A20 class 2
Advantages 485
ETH
General
measurement
> UL
Easy to use report
Thanks to its large backlit LCD display and
its multiple viewing screens with direct
pushbutton access, DIRIS A20 provide clear PC Curves for Management software
readings and are easy to use. current
PLC per phase > To get the most effective
They directly display a number of multi-
use from your Socomec
measurement and metering values : + kWh,
measurement and metering
+ kvarh, I, U, V, F, P, Q, S, PF, etc.
devices, we offer a range of
Compliant with IEC 61557-12 dedicated software tools.
Energy efficiency software
IEC 61557-12 is a high-level standard for See page 140.
all PMDs (Performance Monitoring Devices) Detects wiring errors
that are designed to measure and monitor
An integrated test function can be utilised to
electrical parameters in distribution networks.
detect incorrect wiring and to automatically
Compliance with IEC 61557-12 ensures correct CT installation errors.
a high level of equipment performance, in
terms of metrology, and the mechanical and
environmental aspects (EMC, temperature, etc.).

Functions

Multi-measurement Metering Events


• Currents • Active energy: + kWh Alarms on all electrical values
- instantaneous: I1, I2, I3, In • Reactive energy: + kvarh Communications(1)
- maximum average: I1, I2, I3, In • Hours: RS485 with MODBUS protocol
• Voltages & frequency Harmonic analysis Output
- instantaneous: V1, V2, V3, U12, U23, U31, F • Total harmonic distortion (level 51) • Remote command of device
• Power - Currents: thd I1, thd I2, thd I3 • Alarm report
- instantaneous: 3P, ΣP, 3Q, ΣQ, 3S, ΣS - Phase-to-neutral voltage: thd V1, thd V2, thd V3 • Pulse report
- maximum average: ΣP, ΣQ, ΣS - Phase-to-phase voltage: thd U12, thd U23, Inputs
• Power factors thd U31 • Remote status device
- instantaneous: 3PF, Σ (1) Available as an option (see the following pages).

82 Catalogue 2017
DIRIS A20
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm

Front panel
1. Backlit LCD display.
2. Direct access key for currents (instantaneous and max. values),
current THD and test function.
3. Direct access key for voltages, frequency and voltage THD.
4. Pushbutton for active, reactive, and apparent power (instantaneous
and max. values) and power factor.
DIRIS_743x_a_2_cat

5. Direct access key for energies, hour meter and programming menu.

1 2 3 4 5

Case
92 +- 0.0
0.8
Type panel mounting
Dimensions W x H x D 96 x 96 x 60 mm
Case degree of protection IP30
Front degree of protection IP52
Display type backlit LCD display
Terminal block type Fixed or plug-in
Voltage and other connection cross-section 0.2 … 2.5 mm2
DIRIS_577_d_1_x_cat

96 DIR
IS
Current connection cross-section 0.5 … 6 mm2
A2
0
92 +- 0.0
0.8

Weight 400 g
I

35
5/TE
ST V
F
4 P

45
PF
OK
E
PR

15
OG

96

Plug-in modules
DIRIS® A20
1 Output
DIRIS_445_a_1_cat

1 output assignable to:


• Pulses: configurable (type, weight, duration) in kWh
or kvarh.
• Monitoring: 3I, In, 3V, 3U, F, ΣP, ΣQ, ΣS, ΣPFL/C,
THD 3I, THD 3V, THD 3U and timer.
DIRIS_773_a_1_cat

• Remote command of device.


DIRIS_447_a_1_cat

Communication
RS485 link with JBUS / MODBUS protocol
(speed up to 38400 bauds)

3 inputs, 1 output
diris_449_a_1_cat

3 inputs assignable to:


• Remote status device.
1 output assignable to:
• Pulses: configurable (type, weight, duration) in kWh or kvarh.
• Monitoring: 3I, In, 3V, 3U, F, ΣP, ΣQ, ΣS, ΣPFL/C, THD 3I, THD 3V,
THD 3U and timer.
• Remote command of device.

Accessories
Current transformers IP65 protection Panel mounting kit
(see page 106) for a 144 x 96 mm cut-out
DIRIS_720_a_2_cat
trafo_077_b_2_cat

DIRIS_718_b_1_cat
trafo_024_a_2_cat

Catalogue 2017 83
DIRIS A20
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm

Electrical characteristics
Current measurement (TRMS) Energy accuracy
Via CT primary 9 999 A Active (according to IEC 62053-22) Class 0.5 S
Via CT secondary 5A Reactive (according to IEC 62053-23) Class 2
Measurement range 0 … 11 kA Auxiliary power supply
Input consumption 0.6 VA Alternating voltage 110 … 400 VAC
Measurement updating period 1s AC tolerance ± 10 %
Direct voltage 120 … 350 VDC
Accuracy 0.2 %
DC tolerance ± 20 %
Permanent overload 6A
Frequency 50 / 60 Hz
Intermittent overload 10 In for 1 s
Consumption 10 VA
Voltage measurements (TRMS) Pulse or alarm output
Direct measurement between phases 50 … 500 VAC Number 1
Direct measurement between phase and neutral 28 … 289 VAC Type 100 VDC - 0.5 A - 10 VA
Input consumption ≤ 0.1 VA Max. number of operations ≤ 108
Measurement updating period 1s Inputs
Accuracy 0.2 % Number 3
Permanent overload 800 VAC Power supply 10 … 30 VDC
Power measurement Minimum signal width 10 ms
Measurement updating period 1s Minimum duration between 2 pulses 18 ms
Accuracy 0.5 % Type Phototransistors
Power factor measurement Communication
Measurement updating period 1s Link RS485
Accuracy 0.5 % Type 2 … 3 half duplex wires
Frequency measurement Protocol MODBUS RTU
MODBUS® speed 1400 … 38400 bauds
Measurement range 45 … 65 Hz
Operating conditions
Measurement updating period 1s
Operating temperature - 10 … + 55 °C
Accuracy 0.1 %
Storage temperature - 20 … + 85 °C
Relative humidity 95 %

Terminals

S1 - S2: current inputs.


DIRIS_578_a_1_x_cat

V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2
I1 I2 I3 AUX: auxiliary power supply Us.
V1, V2, V3 & VN: voltage inputs.
DIRIS A20

Communication module Output or alarm module 3 inputs, 1 output module


DIRIS_580_b_1_x_cat
DIRIS_579_a_1_x_cat

+ - + - + -
0V - + 1 1 8 19
1 2 13 1 4 15 1 6 17 1 9 18
0n OUT 1
RS485 R = 120 IN 3 IN 2 IN 1 OUT 1

DIRIS A20 DIRIS A20 DIRIS A20


RS485 link. 18 - 19 : output n°1
R = 120 Ω: selectable internal resistance for
RS485 end of line termination.

Connection
Recommendation:
- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.
- When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out automatically by a SOCOMEC
PTI, an accessory which is included in this catalogue. Please consult us.

Low voltage balanced network


3/4 wires with 1 CT Single-phase Two-phase
N P1 P1 L1
P1 L1
L1 S1 S2 S1 S2 L2
S1 S2 N
L2
L3

1 1 1 1 1 1
diris_392_d_1_x_cat

diris_393_d_1_x_cat

diris_394_d_1_x_cat

V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3

Use of 1 CT reduces by 0.5% the accuracy of the phases, 1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC.

84 Catalogue 2017
DIRIS A20
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm

Low voltage unbalanced network

3/4 wires with 3 CTs 3 wires with 2 CTs 3 wires with 2 CTs
P1 L1 P1 L1
N S1 S2 S1 P1
P1 L2 L2
L1 P1 S1 S2
S1 S2 L3 L3
L2
P1 S1 S2
L3
S1 S2

diris_396_d_1_gb_cat
1 1 1 1 1 1
diris_395_d_1_fr_cat

diris_397_d_1_x_cat
1 1 1

S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
V1 V2 V3 VN
I1 I2 I3 I1 I2 I3 I1 I2 I3

1. Fuses 0.5 A gG / 0.5 A class CC. Use of 2 CTs reduces by 0.5% the accuracy of the Use of 2 CTs reduces by 0.5% the accuracy of the
phases, the current of which is worked out by vector phases, the current of which is worked out by vector
calculation. calculation.
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.

Additional information

Communication via RS485 link AC & DC auxiliary power supply

110 / 400 VAC


120 / 350 VDC

1 1
diris_400_i_1_fr_cat

LIYCY-CY
diris_398_c_1_x_cat

0V - + A U X
ON
RS485

1. Fuses 0.5 A gG / 0.5 A class CC.

References

Basic device DIRIS A20


Auxiliary power supply Us Reference
110 … 400 VAC / 120 … 350 VDC 4825 0200
Optional plug-in modules Reference
1 output 4825 0080
RS485 MODBUS® communication 4825 0082
3 inputs, 1 output 4825 0083
Accessories
Description of accessories To be ordered in multiples of Reference
IP65 protection 1 4825 0089
Panel mounting kit for a 144 x 96 mm cut-out 1 4825 0088
Fuse disconnect switches for the protection of voltage inputs (type RM) 3 poles 4 5601 0018
Fuse disconnect switches for the protection of the auxiliary supply (type RM) 1 pole + neutral 6 5601 0017
Fuse type gG 10x38 0.5 A 10 6012 0000
Ferrite to be associated with communication modules 1 4899 0011
Current transformer range 1 See page 106
Management software for DIRIS See page 140

Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.

Catalogue 2017 85
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
Single-circuit metering,

The solution for


measurement &

> Industry
> Data centres
> Infrastructures
analysis

DIRIS A41

Function Principle diagram Strong points


DIRIS A40 and A41are panel mounted
measurement units which ensure the
DIRIS A41
> Easy to use

diris_581_f_1_gb_cat
user has access to all the measurements > Detects wiring errors
required for successfully carrying out energy Ethernet
> Customisable
efficiency projects and ensuring the electrical
> Webserver function
distribution is monitored. DIRIS A40 DIRIS A40 DIRIS A40

All this information can be analysed remotely


> Compliant with IEC 61557-12
using an energy management software solution.
The DIRIS A41 has a CT current input for RS485
Conformity to standards
General
measuring the neutral current. measurement
report
PC
> IEC 61557-12
Advantages Energy efficiency
software
Curves for
> IEC 62053-22
current
per phase class 0.5S
Easy to use > IEC 62053-23
Thanks to its large backlit LCD display and PLC
class 2
its multiple viewing screens with direct Webserver function
pushbutton access, DIRIS A4x provide clear Optional Ethernet communication modules > UL
readings and are easy to use. include a Webserver function for monitoring
They directly display a number of multi- and exploiting data remotely without additional
measurement and metering values : +/- kWh, software.
+/- kvarh, kVAh, I, U, V, F, P, Q, S, PF, etc. Compliant with IEC 61557-12
Detects wiring errors IEC 61557-12 is a high-level standard for
An integrated test function can be utilised to all PMDs (Performance Monitoring Devices)
detect incorrect wiring and to automatically that are designed to measure and monitor
correct CT installation errors. electrical parameters in distribution networks.
Customisable Compliance with IEC 61557-12 ensures
Thanks to the wide range of optional modules, a high level of equipment performance, in
the product can be customised or upgraded terms of metrology, and the mechanical and
after installation. environmental aspects (EMC, temperature, etc.).
Functions
Multi-measurement • Temperatures(1) • Individual up to level 63 Communications(1)
• Currents - internal - Currents: HI1, HI2, HI3, HIn • RS485 MODBUS RTU & PROFIBUS DP
- instantaneous: I1, I2, I3, In, Isystem - external via 3 PT100 sensors - Phase-to-neutral voltage: • Ethernet (MODBUS TCP or RTU over
- average/maximum average: Metering HV1, HV2, HV3, TCP and Web server)
I1, I2, I3, In • Active energy: +/- kWh - Phase-to-phase voltage: • Ethernet with RS485 gateway
• Voltages & frequency HU12, HU23, HU31 MODBUS RTU over TCP
• Reactive energy: +/- kvarh
- instantaneous: V1, V2, V3, U12, • Apparent power: kVAh Load curves(1) Inputs / Outputs (1)
U23, U31, F, Vsystem, Usystem • Hours: • Active and reactive power: ΣP+/- ; • Pulse metering
- average/maximum average: V1, V2, ΣQ+/- • Remote control/command
Harmonic analysis
V3, U12, U23, U31, F • Voltages & frequency: V1, V2, V3, • Alarm report
• Total harmonic distortion U12, U23, U31, F
• Power • Pulse report
- Currents: thd I1, thd I2, thd I3, Events (1)
- instantaneous: 3P, ΣP, 3Q, ΣQ, Analogue output
thd In
3S, ΣS • Alarms on all electrical values.
- Phase-to-neutral voltage: thd V1, • 0/4- 20 mA analogue output
- maximum average: ΣP, ΣQ, ΣS
thd V2, thd V3 (1) Available as an option
- predictive: (ΣP), (ΣQ), (ΣS)
- Phase-to-phase voltage: thd U12, (see the following pages).
• Power factors thd U23, thd U31
- instantaneous: 3PF, ΣPF
- average/maximum average: ΣPF

86 Catalogue 2017
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm

Front panel
1. Backlit LCD display.
2. Direct access key for currents and test function.
3. Direct access key for voltages and frequency.
4. Direct access key for active, reactive, and apparent powers and power factor.
5. Direct access key for maximum and average current and power values.
6. Direct access key for harmonic values.
7. Direct access key for energies, hour meter and programming menu.
diris_744x_a_1_cat

1 2 3 4 5 6 7

Plug-in modules
Pulse outputs
diris_445_a_1_cat

2 configurable pulse outputs (type, weight and duration)


on ± kWh, ±kvarh and kVAh.

Communication MODBUS®
diris_447_a_1_cat

DIRIS® A40 RS485 link with MODBUS® protocol


(speed up to 38400 bauds).
diris_775_a_1_cat

PROFIBUS® DP communication
SUB-D9 link with PROFIBUS® DP protocol (speed up to 12 Mbauds).
diris_773_a

diris_777_a_1_cat

Ethernet communication
• Ethernet connection with MODBUS TCP or MODBUS RTU over TCP protocol.
• Embedded Webserver function (1).

Ethernet communication with RS485 MODBUS gateway


diris_776_a_1_cat

• Ethernet connection with MODBUS TCP or MODBUS RTU over TCP protocol.
• Connection of 1 to 247 RS485 MODBUS slaves.
• Embedded Webserver function (1).

Analogue outputs
DIRIS® A41* A maximum of 2 modules may be connected, providing up to 4 analogue outputs.
diris_448_a_1_cat

Per module 2 outputs assignable to:


3I, In, 3V, 3U, F, ± ΣP, ± ΣQ, ΣS, ΣPFL/C, I sys, Vsys, Usys, Ppred, Q pred,
Spred, T°C internal, T°C 1, T°C 2, T°C3 and to 30 VDC power supply.

2 inputs - 2 outputs
A maximum of 3 modules may be connected, providing up to 6 inputs and 6 outputs.
Per module 2 outputs assignable to:
diris_449_a_1_cat

- monitoring: 3I, In, 3V, 3U, F, ±ΣP, ±ΣQ, SS, ΣPFL/C, THD 3I, THD In, THD 3V, THD
diris_774_a

3U, Ppred, Qpred, Spred, internal T°C, T°C 1, T°C2, T°C3 and hour meter,
- remote control,
- timed remote control.
- 2 inputs for pulse metering.
* with a factory fitted neutral CT module.
Memory
diris_682_a_1_cat

• Storing up to a maximum of 62 days of P+, P-, Q+, Q- with an internal or


external synchronisation signal of 5, 8, 10, 15, 20, 30 and 60 minutes.
• Storing of 10 hour-dated last alarms.
• Storing of the last minimum and maximum instantaneous values for 3U, 3V, 3I,
In, F, ΣP±, ΣQ±, ΣS, THD 3U, THD 3V, THD, 3U, THD, 3V, THD, 3I, THD In.
• Storing of 3U, 3V and F average values based on synchronisation function
(maximum 60 days).

Temperature(2)
diris_747_a_2_cat

Temperature indication:
- internal,
- external sensor PT 100 (T°C 1), (1) See "Management software for DIRIS" page 140.

- external sensor PT 100 (T°C 2), (2) See "external sensor PT 100" page 122.

- external sensor PT 100 (T°C 3),.

Catalogue 2017 87
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm

Accessories
Current transformers IP65 protection Panel mounting kit for a 144 x 96 mm cut-out
(see page 106)
trafo_077_b_2_cat
trafo_024_a_2_cat

diris_718_b_1_cat
diris_720_a_2_cat

Terminals
DIRIS A40
S1 - S2: current inputs
diris_569_a_1_x_cat

V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2
AUX: auxiliary power supplies Us
I1 I2 I3
V1- V2 - V3 - VN: voltage inputs
DIRIS A40
DIRIS A41

S1 - S2: current inputs


diris_570_a_1_x_cat

V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 IN AUX: auxiliary power supplies Us
V1- V2 - V3 - VN: voltage inputs
DIRIS A41
Communication module Pulse output module Analogue output module
diris_571_a_1_x_cat

diris_572_a_1_x_cat

1 2 3 4 5 6 7 8
diris_573_a_1_x_cat

0V - + 1
0n + - + -
RS485 R = 120 0/4-20 mA 0/4-20 mA
OUT 1 OUT 2 OUT 1 OUT 2
DIRIS A40 / A41 DIRIS A40 / A41 DIRIS A40 / A41
RS485 link. 1 - 2 : pulse output n°1. 5 - 6 : analogue output n°1.
R = 120 Ω: selectable internal resistance 3 - 4 : pulse output n°2. 7 - 8 : analogue output n°2.
for RS485 end of line termination.

2 inputs / 2 outputs module Memory module Temperature module


diris_683_a_1_x_cat

diris_753_a_1_gb_cat

19 20 21 22 23 24 25 26
9 10 11 12 17 18
sensor 1 sensor 2
OUT 1 OUT 2 + -
IN
diris_574_b_1_x_cat

A-Cd A-Cd
synchro 27 28 29 30
DIRIS A40 / A41 sensor 3
1 3 14 15 16
- + - + DIRIS A40/A41
IN 1 IN 2 17 - 18 : synchronisation input. Sensor 1 Sensor 2 Sensor 3
DIRIS A40 / A41 19 : red 23 : red 27 : red
9 - 10 : relay output n°1. 20 : red 24 : red 28 : red
11 - 12 : relay output n°2. 21 : white 25 : white 29 : white
13 - 14 : opto input n°1. 22 : white 26 : white 30 : white
15 - 16 : opto input n°2.

Ethernet Module Ethernet module + RS485 MODBUS gateway


diris_751_c_1_gb_cat
diris_752_a_1_x_cat

10 BASE T 10 BASE T 0V - + 1
100 BASE T 100 BASE T 0n
RS485
RJ45 RJ45 gateway R = 120Ω
DIRIS A40/A41 DIRIS A40/A41

88 Catalogue 2017
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm

Electrical characteristics

Current measurement on insulated inputs (TRMS) 2 inputs / 2 outputs module: Outputs (alarms / control)
Via CT primary 9 999 A Number of relays 2(1)
Via CT secondary 1 or 5 A Type 250 VAC - 5 A - 1150 VA
Measurement range 0 … 11 kA 2 inputs / 2 outputs module: Phototransistor inputs
Input consumption ≤ 0.1 VA Number 2(1)
Measurement updating period 1s Power supply 10 … 30 VDC
Accuracy 0.2 % Minimum signal width 10 ms
Permanent overload 6A Minimum duration between 2 pulses 18 ms
Intermittent overload 10 In for 1 s Type phototransistors
Voltage measurements (TRMS) Pulse output module
Direct measurement between phases 50 … 700 VAC Number of relays 2
Direct measurement between phase and neutral 28 … 404 VAC Type 100 VDC - 0.5 A - 10 VA
VT primary 500 000 VAC Max. number of operations ≤ 108
VT secondary 60, 100, 110, 173, 190 VAC Analogue output module
Frequency 50 / 60 Hz Number of outputs 2(2)
Input consumption ≤ 0.1 VA Type insulated
Measurement updating period 1s Range 0 / 4 … 20 mA
Accuracy 0.2 % Load resistance 600 Ω
Permanent overload 800 VAC Maximum current 30 mA
Current-voltage product MODBUS communication module
Limitation for 1A CT 10 000 000 Link RS485
Limitation for 5A CT 10 000 000 Type 2 … 3 half duplex wires
Power measurement Protocol MODBUS RTU
Measurement updating period 1s MODBUS® speed 4800 … 38400 bauds
Accuracy 0.5 % PROFIBUS-DP communication module
Power factor measurement Link SUB-D9
Measurement updating period 1s Protocol PROFIBUS® DP
Accuracy 0.5 % PROFIBUS® speed 9.8 kbauds … 12 Mbauds
Frequency measurement Ethernet communication module
Measurement range 45 … 65 Hz Connection RJ45
Measurement updating period 1s Speed 10 base T / 100 base T
Accuracy 0.1 % Protocol MODBUS TCP or MODBUS RTU over TCP
Energy accuracy Temperature module (inputs)
Active (according to IEC 62053-22) Class 0.5 S Type PT100
Reactive (according to IEC 62053-23) Class 2 Connection 2, 3 or 4 wires
Auxiliary power supply Dynamic - 20 ... 150 °C
Alternating voltage 110 … 400 VAC Accuracy ±1 digit
AC tolerance ± 10 % Maximum length 300 cm
Direct voltage 120 … 350 VDC / 12 … 48 VDC Operating conditions
DC tolerance ± 20 % / - 6 … + 20 % Operating temperature - 10 … + 55 °C
Frequency 50 / 60 Hz
Storage temperature - 20 … + 85 °C
Consumption ≤ 10 VA
Relative humidity 95 %
(1) Max. 3 modules / DIRIS.
(2) Max. 2 modules / DIRIS.

Case
+ 0.8
92 - 0.0

Type panel mounting


Dimensions W x H x D 96 x 96 x 60 mm
Case degree of protection IP30
Front degree of protection IP52
Display type backlit LCD display
Terminal blocks type fixed or plug-in
Voltage and other connection cross-section 0.2 … 2.5 mm2
Current connection cross-section 0.5 … 6 mm2
Weight 400 g
96 DIR
IS
A4
0 92
+ 0.8
- 0.0
diris_582_e_1_x_cat

35
45
15
96

Catalogue 2017 89
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm

Connections
Recommendation: When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out
automatically by a SOCOMEC PTI, an accessory which is included in this catalogue. Please consult us.
In TNC neutral systems it is recommended to use the functional earth module.

Low voltage balanced network for DIRIS A40


3/4 wires with 1 CT Single-phase Two-phase
N P1 P1 L1
P1 L1
L1 S1 S2 S1 S2 L2
S1 S2 N
L2
L3

1 1 1 1 1 1
diris_392_d_1_x_cat

diris_393_d_1_x_cat

diris_394_d_1_x_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3

Use of 1 CT reduces by 0.5% the accuracy of the phases, 1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC.

Low voltage unbalanced network for DIRIS A40


3/4 wires with 3 CTs 3 wires with 2 CTs 3 wires with 2 CTs
P1 L1 P1 L1
N S1
P1 S1 S2 L2 P1 L2
L1
S1 S2 P1 S1 S2
L2 L3 L3
P1 L3 S1 S2
S1 S2
diris_395_d_1_x_cat

diris_396_d_1_x_cat

diris_397_e_1_x_cat

1 1 1 1 1 1
1 1 1

V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2

I1 I2 I3 I1 I2 I3 I1 I2 I3

1. Fuses 0.5 A gG / 0.5 A class CC. Use of 2 CTs reduces by 0.5% the accuracy of the phases, Use of 2 CTs reduces by 0.5% the accuracy of the phases,
the current of which is worked out by vector calculation. the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.

Low voltage unbalanced network for DIRIS A41


4 wires with 4 CTs
P1 N
P1 S1 L1
S1 S2 L2
P1 L3
S1 S2
diris_575_b_1_x_cat

1 1 1

V1 V2 V3 VN S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 IN
1. Fuses 0.5 A gG / 0.5 A class CC.

Additional information
Communication via RS485 link Connection of voltage transformer for HV networks AC & DC auxiliary power supply
110 / 400 VAC
L1
120 / 350 VDC
L2
L3
1 1

LIYCY-CY
diris_399_b_1_x_cat
diris_398_c_1_x_cat

A U X
diris_400_i_1_x_cat

0V - +
ON
V1 V2 V3 N
RS485
1. Fuses 0.5 A gG / 0.5 A class CC.

90 Catalogue 2017
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm

References
DIRIS A41
Basic device DIRIS A40 with CT on the
neutral
Auxiliary power supply Us Reference Reference
110 ... 400 VAC / 120 ... 350 VDC 4825 0201 4825 0202
12 ... 48 VDC 4825 1201 4825 1202

Options
Plug-in modules(1) Reference Reference
Pulse outputs 4825 0090 4825 0090
RS485 MODBUS® communication 4825 0092 4825 0092
Analogue outputs 4825 0093 4825 0093
2 inputs / 2 outputs 4825 0094 4825 0094
Communication Sub D9 PROFIBUS®DP(2) 4825 0205 4825 0205
Memory 4825 0097 4825 0097
Embedded Webserver function (2). 4825 0203 4825 0203
Ethernet communication + RS485 MODBUS gateway (Embedded Webserver function)(2) 4825 0204 4825 0204
Temperature inputs 4825 0206 4825 0206
(1) Ease of integration for additional functions (maximum 4 slots on A40 and 3 on A41).
(2) Dimension of the plug-in module: 2 slots.

Accessories
To be ordered To be ordered
Description of accessories Reference Reference
in multiples of in multiples of
IP65 protection 1 4825 0089 1 4825 0089
Panel mounting kit for a 144 x 96 mm cut-out 1 4825 0088 1 4825 0088
Fuse disconnect switches for the protection of voltage inputs (type RM) 3 poles 4 5601 0018 4 5601 0018
Fuse disconnect switches for the protection of the auxiliary supply (type RM)
6 5601 0017 6 5601 0017
1 pole + neutral
Fuse type gG 10 x 38 0.5 A 10 6012 0000 10 6012 0000
Current transformer range 1 see page 106 1 see page 106
Ferrite to be associated with communication modules 1 4899 0011 4899 0011
Temperature sensor PT100 - M6 screw type 1 4825 0208 1 4825 0208
Temperature sensor PT100 - M6 eyelet type 1 4825 0209 1 4825 0209
Management software for DIRIS see page 140

Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.

Catalogue 2017 91
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm
Single-circuit metering,

Principle diagram The solution for


measurement &

DIRIS A60

DI
RIS
> Industry
A6

> Infrastructure
0

> Data centre

Ethernet
analysis

DIRIS A40 DIRIS A40 DIRIS A40

RS485
General
measurement
report
PC

diris_826_c_1_gb_cat
Energy efficiency
software
Curves for
current
DIRIS A60 per phase
Strong points
PLC
Function > Easy to use
DIRIS A60 is a panel mounted multifunction meter which incorporates all functions of the > Detects wiring errors
DIRIS A40 with the addition of enhanced data logging functions, recording curves for quality
events. All this information can be analysed remotely using the Analysis software which is available > Compliant with IEC 61557-12
at no charge and can be downloaded from the SOCOMEC website www.socomec.com. > Management softwares
> Conformity to standard
Advantages EN 50160
Easy to use Management softwares
Thanks to its large backlit LCD display and • Optional Ethernet module with Webserver
its multiple viewing screens with direct key function: For measurement monitoring, data Conformity to standards
access, the DIRIS A60 provides clear readings exploitation and the export of load curves
and is easy to use. remotely without a specific software (web > IEC 61557-12
It directly displays a number of multi- browser access). > IEC 62053-22
measurement and metering values : +/- kWh, • Analysis software: For the analysis of events class 0.5S
+/- kvarh, kVAh, I, U, V, F, P, Q, S, PF, etc. data in order to improve the reliability of the
electrical installation. > IEC 62053-23
Detects wiring errors
class 2
An integrated test function can be utilised to • Easy Config software: For quick and easy
detect incorrect wiring and to automatically remote device configuration; configuration > EN 50160
correct CT installation errors. files can be copied from and sent to the
Compliant with IEC 61557-12 DIRIS A60, or they can be created without
communication and sent at a later time.
IEC 61557-12 is a high-level standard for all
Multiple devices can be configured from
PMDs (Performance Monitoring Devices) that
a single file, which is especially useful for
are designed to measure and monitor electrical
OEMs and panel builders.
parameters in distribution networks.
Conformity to standard EN 50160
Compliance with IEC 61557-12 ensures
a high level of equipment performance, in EN 50160 is a standard which defines events
terms of metrology, and the mechanical and relating to the quality of electrical networks.
environmental aspects (EMC, temperature, etc.). The DIRIS A60 captures voltage events in
accordance with this standard.
Functions
In addition to the functions of the Other functions: • Temperatures(1) Events (1)
DIRIS A40, the DIRIS A60 also: Multi-measurement - internal, • Alarms on all electrical values
• shows the current and voltage Currents - external via 3 PT100 sensors Communications(1)
unbalance - instantaneous: I1, I2, I3, In, Isystem, Metering • 0/4- 20 mA analogue output
• shows the tangent ϕ - average/maximum average: I1, I2, • Active energy: +/- kWh • RS485 MODBUS RTU
• stores the load curves (60 days I3, In, • Reactive energy: +/- kvarh • Ethernet (MODBUS TCP or
with an interval of 10 minutes) for - unbalance: I unb. MODBUS RTU over TCP and
the active, reactive and apparent • Apparent power: kVAh
• Voltages & frequency • Hours: Webserver)
power: ΣP+/- ; ΣQ+/-, ΣS
- instantaneous: V1, V2, V3, U12, U23, Harmonic analysis (level 63) • Ethernet (MODBUS TCP or
• detects and stores the last MODBUS RTU over TCP and
40 events concerning: U31, F, Vsystem, Usystem • Total harmonic distortion
- average/maximum average: V1, V2, Webserver) with RS485 MODBUS
- overvoltage - Currents: thd I1, thd I2, thd I3, RTU gateway
V3, U12, U23, U31, F thd In
- voltage dips Inputs / Outputs (1)
- unbalance: U unb. - Phase-to-neutral voltage: thd V1,
- cut-offs • Pulse metering
• Power thd V2, thd V3
- overcurrent. • Remote control/command
- instantaneous: 3P, ΣP, 3Q, ΣQ, 3S, ΣS - Phase-to-phase voltage: thd U12,
For each stored event, the DIRIS • Alarm report
A60 records the relevant RMS 10 ms - maximum average: ΣP, ΣQ, ΣS thd U23, thd U31
• Individual • Pulse report
interval curves for the voltages V1, V2, - predictive: ΣP, ΣQ, ΣS.
V3, U12, U23, U31 and the currents I1, • Power factor - PF, ΣPF - Currents: HI1, HI2, HI3, HIn
(1) Available as an option
I2, I3, In, giving a total of 400 curves. • Instantaneous total tangent ϕ - Phase-to-neutral voltage: HV1, (see the following pages).
• Instantaneous, average and max. HV2, HV3,
average unbalance - Phase to phase voltage: HU12,
HU23, HU31

92 Catalogue 2017
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm

Front panel

1. Backlit LCD display.


2. Direct access key for currents, temperatures and test function.
3. Direct access key for voltages and frequency.
4. Direct access key for active, reactive, and apparent powers and power factor.
5. Direct access key for maximum and average current, voltage and power values.
6. Direct access key for harmonics values.
diris_824x_a_1_cat

7. Direct access key for energies, hour meter and programming menu.

1 2 3 4 5 6 7

Plug-in modules diris_445_a_1_cat

Pulse outputs
• 2 configurable pulse outputs (type, weight and duration)
on ± kWh, ±kvarh and kVAh.
diris_447_a_1_cat

Communication MODBUS®
• RS485 link with MODBUS® protocol (speed up to
38400 bauds).
DIRIS® A60*
diris_777_a_1_cat

Ethernet communication
• Ethernet connection with MODBUS TCP or
MODBUS RTU over TCP protocol.
• Embedded Webserver function (1).
diris_834_a

Ethernet communication
diris_776_a_1_cat

with RS485 MODBUS gateway


• Ethernet connection with MODBUS TCP or MODBUS RTU
* With integrated memory module. over TCP protocol.
• Connection of 1 to 247 RS485 MODBUS slaves.
• Embedded Webserver function (1).

Analogue outputs
diris_448_a_1_cat

• A maximum of 2 modules may be connected, providing


up to 4 analogue outputs.
• Per module 2 outputs assignable to:
3I, In, 3V, 3U, F, ± ΣP, ± ΣQ, ΣS, ΣPFL/C, Isys, Vsys, Usys,
Ppred, Q pred, Spred, T°C internal, T°C 1, T°C 2, T°C3
and to 30 VDC power supply.
2 inputs - 2 outputs
• A maximum of 3 modules may be connected, providing up to 6 inputs
diris_449_a_1_cat

and 6 outputs.
• Per module 2 outputs assignable to:
- monitoring: 3I, In, 3V, 3U, F, ± ΣP, ± ΣQ, ΣS, ΣPFL/C, THD 3I, THD In,
THD 3V, THD 3U, Ppred, Qpred, Spred, T°C internal, T°C 1, T°C2,
T°C3 and hour meter,
- remote control,
- timed remote control,
• 2 inputs for pulse metering.

Temperature(2)
diris_747_a_2_cat

Temperature indication:
- Internal
- External sensor PT 100 (T°C 1)
- External sensor PT 100 (T°C 2)
- External sensor PT 100 (T°C 3).
(1) See "Management softwares for DIRIS" p. 140.
(2) See "External sensor PT 100" p. 122.

Catalogue 2017 93
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm

Accessories
Current transformers Split-core current IP65 protection Panel mounting kit
(see page 106) transformers for a 144 x 96 mm cut-out
trafo_024_a_2_cat

trafo_077_b_2_cat

DIRIS_720_a_2_cat

DIRIS_718_b_1_cat
Terminals
DIRIS A60
S1 - S2: current inputs
DIRIS_856_a_1_x_cat

V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2
AUX: auxiliary power supplies Us
I1 I2 I3 V1- V2 - V3 - VN: voltage inputs

DIRIS A60

RS485 MODBUS module Ethernet module Ethernet module + RS485 MODBUS gateway
DIRIS_857_a_1_x_cat

DIRIS_862_a_1_x_cat

DIRIS_859_b_1_gb_cat

0V - + 1 10 BASE T 10 BASE T 0V - + 1
0n
100 BASE T 100 BASE T 0n
RS485 R = 120 RS485
RJ45
RJ45 gateway R = 120Ω
DIRIS A60 DIRIS A60
DIRIS A60
RS485 link.
R = 120 Ω: selectable internal resistance RS485 gateway resistor.
for RS485 end of line termination. R = 120 Ω: selectable internal resistance
for RS485 end of line termination.

Pulse output module Temperature module 2 inputs / 2 outputs module


DIRIS_860_a_1_x_cat

DIRIS_861_a_1_gb_cat

1 2 3 4 19 20 21 22 23 24 25 26
9 10 11 12
sensor 1 sensor 2
OUT 1 OUT 2
DIRIS_858_b_1_x_cat

A-Cd A-Cd
OUT 1 OUT 2 27 28 29 30
DIRIS A60 sensor 3
1 3 14 15 16
DIRIS A60
1 - 2 : pulse output n°1. - + - +
3 - 4 : pulse output n°2. IN 1 IN 2
DIRIS A60
9 - 10 : relay output n°1.
Analogue output module 11 - 12 : relay output n°2.
13 - 14 : opto input n°1.
DIRIS_863_a_1_x_cat

5 6 7 8 15 - 16 : opto input n°2.


+ - + -
0/4-20 mA 0/4-20 mA
OUT 1 OUT 2
DIRIS A60

5 - 6 : analogue output n°1.


7 - 8 : analogue output n°2.

94 Catalogue 2017
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm

Electrical characteristics
Current measurement on insulated inputs (TRMS) 2 inputs / 2 outputs module: Outputs (alarms / control)
Via CT primary 9 999 A Number of relays 2(1)
Via CT secondary 1 or 5 Type 250 VAC - 5 A - 1150 VA
Measurement range 0 … 11 kA 2 inputs / 2 outputs module: Phototransistor inputs (pulse metering)
Input consumption ≤ 0.1 VA Number 2(1)
Measurement updating period 1s Power supply 10 … 30 VDC
Accuracy 0.2 % Minimum signal width 10 ms
Permanent overload 6A Minimum duration between 2 pulses 18 ms
Intermittent overload 10 In for 1 s Type phototransistors
Voltage measurements (TRMS) Pulse output module
Direct measurement between phases 50 … 700 VAC Number of relays 2
Direct measurement between phase and neutral 28 … 404 VAC Type 100 VDC - 0.5 A - 10 VA
VT primary 500 000 VAC Max. number of operations ≤ 108
VT secondary 60, 100, 110, 173, 190 VAC Analogue output module
Frequency 50 / 60 Hz Number of outputs 2(2)
Input consumption ≤ 0.1 VA Type insulated
Measurement updating period 1s Range 0 / 4 … 20 mA
Accuracy 0.2 % Load resistance 600 Ω
Permanent overload 800 VAC Maximum current 30 mA
Current-voltage product MODBUS communication module
Limitation for 1A CT 10 000 000 Link RS485
Limitation for 5A CT 10 000 000 Type 2 … 3 half duplex wires
Power measurement Protocol MODBUS RTU
Measurement updating period 1s MODBUS® speed 4800 … 38400 bauds
Accuracy 0.5 % Ethernet communication module
Power factor measurement Connection RJ45
Measurement updating period 1s Speed 10 base T / 100 base T
Accuracy 0.5 % Protocol MODBUS TCP or MODBUS RTU over TCP
Frequency measurement Temperature inputs
Measurement range 45 … 65 Hz Type PT100
Measurement updating period 1s Connection 2, 3 or 4 wires
Accuracy 0.1 % Dynamic - 20 ... 150 °C
Energy accuracy Accuracy ± 1 digit
Active (according to IEC 62053-22) Class 0.5 S Maximum length 300 cm
Reactive (according to IEC 62053-23) Class 2 Operating conditions
Auxiliary power supply Operating temperature - 10 … + 55 °C
Alternating voltage 110 … 400 VAC Storage temperature - 20 … + 85 °C
AC tolerance ± 10 % Relative humidity 95 %
Direct voltage 120 … 350 VDC (1) Max. 3 modules / DIRIS.
DC tolerance ± 20 % (2) Max. 2 modules / DIRIS.
Frequency 50 / 60 Hz
Consumption ≤ 10 VA

Case

+ 0.8 Type panel mounting


92 - 0.0 Dimensions W x H x D 96 x 96 x 80 mm
Case degree of protection IP30
Front degree of protection IP52
Display type backlit LCD display
Terminal blocks type fixed or plug-in
Voltage and other terminals connection
0.2 … 2.5 mm2
cross-section
Current connection cross-section 0.5 … 6 mm2
Weight 450 g
96 DIR
IS
A6
0 92
+ 0.8
- 0.0
diris_864_c_1_x_cat

35
45
15
96

Catalogue 2017 95
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm

Connection
Low voltage balanced network for DIRIS A60
Recommendation: When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out
automatically by a SOCOMEC PTI, which can be found in the SOCOMEC catalogue: please consult us.

3/4 wires with 1 CT Single-phase Two-phase


N P1 L1 P1 L1
P1
L1 S1 S2 N S1 S2
S1 S2 L2
L2
L3

1 1 1 1 1 1
diris_392_d_1_x_cat

diris_393_d_1_x_cat

diris_394_d_1_x_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3

Use of 1 CT reduces by 0.5% the accuracy of the phases, 1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC.

Low voltage unbalanced network for DIRIS A60

3/4 wires with 3 CTs 3 wires with 2 CTs 3 wires with 2 CTs
P1 L1 P1 L1
N
P1 S1 S2 S1 P1
L1 L2 L2
S1 S2 P1 S1 S2
L2 L3 L3
P1 L3 S1 S2
S1 S2
1 1 1 1 1 1
1 1 1
diris_395_d_1_x_cat

diris_396_d_1_x_cat

diris_397_d_1_x_cat

V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2

I1 I2 I3 I1 I2 I3 I1 I2 I3

1. Fuses 0.5 A gG / 0.5 A class CC. Use of 2 CTs reduces by 0.5% the accuracy of the phases, Use of 2 CTs reduces by 0.5% the accuracy of the phases,
the current of which is worked out by vector calculation. the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.

Additional information

Communication via RS485 link Connection of voltage transformer for HV networks AC & DC auxiliary power supply

L1
L2 110 / 400 VAC
L3 120 / 350 VDC

1 1
LIYCY-CY
diris_399_b_1_x_cat

diris_398_c_1_x_cat

diris_400_i_1_x_cat

A U X
0V - +
ON
V1 V2 V3 N
RS485

1. Fuses 0.5 A gG / 0.5 A class CC.

96 Catalogue 2017
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm

References
Basic device DIRIS A60
Auxiliary power supply Us Reference
110 ... 400 VAC / 120 ... 350 VDC 4825 0207
Options
Plug-in-modules(1) Reference
Pulse outputs 4825 0090
RS485 MODBUS® communication 4825 0092
Analogue outputs 4825 0093
2 inputs / 2 outputs 4825 0094
Ethernet communication (embedded Ethernet Webserver)(2) 4825 0203
Ethernet communication + RS485 MODBUS gateway (embedded Ethernet Webserver)(2) 4825 0204
Temperature inputs 4825 0206
(1) Easy integration of additional functions (maximum 3 slots per device).
(2) Dimension of the plug-in module: 2 slots.

Options
Description of accessories To be ordered in multiples of Reference
IP65 protection 1 4825 0089
Panel mounting kit for a 144 x 96 mm cut-out 1 4825 0088
Fuse disconnect switches for the protection of voltage inputs (type RM) 3 poles 4 5601 0018
Fuse disconnect switches for the protection of the auxiliary supply (type RM) 1 pole + neutral 6 5601 0017
Fuse type gG 10 x 38 0.5 A 10 6012 0000
Ferrite to be associated with communication modules 1 4899 0011
Current transformer range 1 see page 106
Temperature sensor PT100 - M6 screw type 1 4825 0208
Temperature sensor PT100 - M6 eyelet type 1 4825 0209
Management softwares for DIRIS see page 140

Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.

Catalogue 2017 97
DIRIS A80
Multifunction meters - PMD + RCM
monitoring energy and fault currents - dimensions 96 x 96 mm
Single-circuit metering,

The solution for


measurement &

> Industry
> Infrastructure
diris_876_a_1_cat

> Health care buildings


analysis

> Data centre

Strong points

> Compact
DIRIS A80
> Patent pending
Function Principle diagram > Management softwares
DIRIS A80 is a complete panel mounted > Compliant with IEC 61557-12
multifunction meter which incorporates
> Conformity to standard
RCM current monitoring (Residual Current
Monitoring), for networks with TN-S and EN 50160

diris_875_b_1_gb_cat
TT neutral systems, and enhanced data DIRIS A80 DIRIS A80

logging functions for recording curves for DI


RIS
DI
RIS
Conformity to standards
quality and RCM events. The DIRIS A80
A8 A8
0 0

supplies all the measurements required > IEC 62053-22


Ethernet

RS485

for energy efficiency projects while its Main


meter panel class 0.5S
RCM function provides preventative PC
earth leakage information, essential in Energy efficiency
> IEC 62053-23
critical applications to avoid installation software class 2
Currents
shutdowns. per phase
> IEC 61557-12
curve

> IEC 62020


PLC

Advantages > EN 50160

Compact Patent pending Management softwares


The DIRIS A80 combines two complementary Automatic adjustment of the leakage current • Optional Ethernet module with Webserver
products within a single 96 x 96 mm panel alarm threshold in accordance with the load function: For measurement monitoring, data
mounted case, enabling faster installation and current to avoid false alarms. exploitation and the export of load curves
utilising less space. The DIRIS A80 comprises: Compliant with IEC 61557-12. remotely without a specific software (web
- a multifunction meter with enhanced event browser access).
IEC 61557-12 is a high-level standard for
logging functions which records curves for • Analysis software: For the analysis of events
all PMDs (Performance Monitoring Devices)
quality events. data in order to improve the reliability of the
that are designed to measure and monitor
electrical installation.
- an RCM fault current monitoring device electrical parameters in distribution networks.
• Easy Config software: For quick and easy
(Residual Current Monitoring). Compliance with IEC 61557-12 ensures remote device configuration; configuration
Conformity to standard EN 50160 a high level of equipment performance, in files can be copied from and sent to the
- EN 50160 is a standard which defines terms of metrology, and the mechanical and DIRIS A80, or they can be created without
events relating to the quality of electrical environmental aspects (EMC, temperature, etc.). communication and sent at a later time.
networks. The DIRIS A80 captures voltage Multiple devices can be configured from
events in accordance with this standard. a single file, which is especially useful for
OEMs and panel builders.
Functions
The DIRIS A80 offers the following Multi-measurement • Power factor PF, ΣPF Events
functions: • Currents • Instantaneous total tangent phi • Alarms on all electrical values
• The monitoring of fault currents - instantaneous: I1, I2, I3, In, Isystem, • Instantaneous, average and max. average • Detection and storing of the last 60 events:
• (Residual Current Monitoring) - average/maximum average: I1, I2, I3, In, unbalance - overvoltage
• Multi-measurement (current, - unbalance: I unb Metering - voltage dips
voltage, frequency, power, …) Voltages & frequency • Active energy: +/- kWh - cut-offs
• Energy metering • Reactive energy: +/- kvarh - overloads.
- instantaneous: V1, V2, V3, U12, U23,
• Harmonic analysis U31, F, Vsystem, Usystem • Apparent power: kVAh For each stored event, the DIRIS A80 records
• Event detection the relevant RMS 10 ms interval curves for
- average/maximum average: V1, V2, V3, • Hours the voltages V1, V2, V3, U12, U23, U31, the
Fault currents (RCM) U12, U23, U31, F Harmonic analysis (level 63) currents I1, I2, I3 and In. These curves can be
• Measurement of currents IΔn (I1+I2+I3+In) - unbalance: U unb • Total harmonic distortion synchronised with the event curves IΔn and IPE.
and IPE (protection conductor) • Power - Currents: thd I1, thd I2, thd I3, thd In Communications(1)
• Permanent monitoring of IΔn and IPE - instantaneous: 3P, ΣP, 3Q, ΣQ, 3S, ΣS - Phase-to-neutral voltage: thd V1, • RS485 MODBUS RTU
- Fault current alarms depending on the - maximum average: ΣP, ΣQ, ΣS thd V2, thd V3 • Ethernet (MODBUS TCP or MODBUS RTU
load current - predictive: ΣP, ΣQ, ΣS - Phase-to-phase voltage: thd U12, over TCP and Webserver)
- Record of events IΔn and IPE (time, - storing of load curves (60 days with an thd U23, thd U31. • Ethernet (MODBUS TCP or MODBUS
duration and curves stored) interval of 10 minutes) for the active, • Individual RTU over TCP and Webserver) with RS485
- Alarm report output reactive and apparent power: - Currents: HI1, HI2, HI3, HIn MODBUS RTU gateway
ΣP+/- ; ΣQ+/-, ΣS - Phase-to-neutral voltage: HV1, HV2, HV3 (1) Available as an option
- Phase-to-phase voltage: HU12, HU23, (see the following pages).
HU31.

98 Catalogue 2017
DIRIS A80
Multifunction meters - PMD + RCM
monitoring energy and fault currents - dimensions 96 x 96 mm

Front panel Accessories


Core balance transformer ∆IC
1. Backlit LCD display.
See general catalogue.
2. Direct access key for the currents, RCM function
and alarm reset.
3. Direct access key for voltages and frequency.
4. Direct access key for active, reactive, and apparent powers
and power factor.
diris_876x_a_1_cat

tore_046_a
5. Direct access key for maximum and average current, voltage
and power values.
6. Direct access key for harmonic values and the connection
and RCM test functions.
7. Direct access key for energies, hour meter
and programming menu.

1 2 3 4 5 6 7

Plug-in modules
DIRIS® A80
diris_447_a_1_cat

Communication MODBUS®
• RS485 link with MODBUS® protocol
(speed up to 38400 bauds).
diris_777_a_1_cat
DIRIS_878_a_2_cat

Ethernet communication
• Ethernet connection with MODBUS TCP or MODBUS RTU over TCP
protocol.
• Embedded Webserver function(1).
diris_776_a_1_cat

Ethernet communication with RS485 MODBUS gateway


• Ethernet connection with MODBUS TCP or MODBUS RTU over TCP protocol.
• Connection of 1 to 247 RS485 MODBUS slaves.
• Embedded Webserver function(1).
(1) See “Management softwares for DIRIS” page 140.

Terminals
DIRIS A80
S1 - S2: current inputs
diris_849_b_1_x_cat

V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2 S1 S2
AUX: Auxiliary power supply Us
I1 I2 I3 IN V1- V2 - V3 - VN: voltage inputs

DIRIS A80
RCM module RCM module Memory module
1 input / 1 output 2 outputs
diris_853_c_1_x_cat

diris_871_a_1_x_cat

diris_872_a_1_x_cat

K L K L 33 34 37 38 K L K L 33 34 35 36 17 18
+ -
IN
I∆N IPE OUT IN I∆N IPE OUT1 OUT2
synchro
DIRIS A80 DIRIS A80 DIRIS A80
K-L / I∆N : residual current K-L / I∆N : residual current
K-L / IPE : ground fault current K-L / IPE : ground fault current
33-34 : relay outputs 33-34 : relay output n°1
37-38 : opto inputs 35-36 : relay output n°2

Ethernet module Ethernet module + RS485 MODBUS gateway RS485 MODBUS module
diris_852_c_1_gb_cat

diris_850_c_1_x_cat
diris_851_b_1_x_cat

10 BASE T 10 BASE T 0V - + 1 0V - + 1

100 BASE T 100 BASE T RS485


0n 0n
RS485 R = 120Ω
RJ45 gateway R = 120Ω
RJ45
DIRIS A80 DIRIS A80 DIRIS A80

RS485 gateway resistor. RS485 link


R = 120 Ω: selectable internal resistance for RS485 R = 120 Ω: selectable internal resistance
end of line termination. for RS485 end of line termination.

Catalogue 2017 99
DIRIS A80
Multifunction meters - PMD + RCM
monitoring energy and fault currents - dimensions 96 x 96 mm

Connections
Additional information
Communication via RS485 link Connection of voltage transformer for HV networks AC & DC auxiliary power supply
L1 110 / 400 VAC
L2 120 / 350 VDC
L3
1 1

LIYCY-CY

diris_400_i_1_gb_cat
diris_399_b_1_x_cat
diris_398_c_1_x_cat

A U X
0V - +
V1 V2 V3 N
ON
RS485
1. Fuses 0.5 A gG / 0.5 A class CC.

Three-phase + N network with RCM Single-phase network with RCM


PE
P1 N
P1 S1 L1 PE
S1 S2 L2 N
P1 L3 P1
S1 S2 L1
S1 S2

1 1 1 1
diris_873_a_1_gb_cat

diris_874_a_1_gb_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 S1 S2 K L K L V1 V2 V3 VN S1 S2 S1 S2 S1 S2 S1 S2 K L K L
I1 I2 I3 IN I1 I2 I3 IN
I∆N IPE I∆N IPE

1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.

Electrical characteristics
Current measurement on insulated inputs (TRMS) Auxiliary power supply
Via CT primary 9 999 A Alternating voltage 110 … 400 VAC
Via CT secondary 1 or 5 A AC tolerance ± 10 %
Measurement range 0 … 11 kA Direct voltage 120 … 350 VDC
Input consumption ≤ 0.1 VA DC tolerance ± 20 %
Measurement updating period 1s Frequency 50 / 60 Hz
Accuracy 0.2 % Consumption ≤ 10 VA
Permanent overload 6A MODBUS communication module
Intermittent overload 10 In for 1 s Link RS485
Voltage measurements (TRMS) Type 2 … 3 half duplex wires
Direct measurement between phases 50 … 700 VAC Protocol MODBUS® RTU
Direct measurement between phase and neutral 28 … 404 VAC MODBUS® speed 4800 … 38400 bauds
VT primary 500 000 VAC Ethernet Communication Module
VT secondary 60, 100, 110, 173, 190 VAC Connection RJ45
Frequency 50 / 60 Hz Speed 10 base T / 100 base T
Input consumption ≤ 0.1 VA Protocol MODBUS TCP or MODBUS RTU over TCP
Measurement updating period 1s Fault current monitoring characteristics (I∆n and IPE)
Accuracy 0.2 % Inputs I∆n and IPE
Permanent overload 800 VAC
Number of inputs 2
Current-voltage product
Dedicated core balance transformers range ΔIC – transformer ratio 600/1
Limitation for 1A CT 10 000 000
Limitation for 5A CT 10 000 000 Measurement of fault current I∆n / IPE 6 mA … 30 A
Power measurement Accuracy 1%
Measurement updating period 1s Alarms I∆n and IPE
Accuracy 0.5 % Thresholds adjustment depending on the load currents
Power factor measurement Time setting 0 to 10 s
Measurement updating period 1s Logging values, dates, durations and curves
Accuracy 0.5 % Number of events max. 1000 events
Frequency measurement Optocoupler input
Measurement range 45 … 65 Hz Number specific to the reference
Measurement updating period 1s Power supply 5 … 24 VDC
Measurement updating period 0.1 % Minimum signal width 10 ms
Energy accuracy Minimum duration between 2 pulses 20 ms
Active (according to IEC 62053-22) Class 0.5 S Type optocoupler
Reactive (according to IEC 62053-23) Class 2
Alarm outputs
Operating conditions
Number of relays specific to the reference
Operating temperature - 10 … + 55 °C
Storage temperature - 20 … + 85 °C Type 230 VAC – 1 A
Relative humidity 95 % Max. N° of operations 104

100 Catalogue 2017


DIRIS A80
Multifunction meters - PMD + RCM
monitoring energy and fault currents - dimensions 96 x 96 mm

Case

+ 0.8 Type panel mounting


92 - 0.0
Dimensions W x H x D 96 x 96 x 80 mm
Case degree of protection IP30
Front degree of protection IP52
Display type backlit LCD display
Terminal blocks type fixed or plug-in
Current connection cross-section 0.5 … 6 mm2
Cable cross-section for currents ∆In and IPE 0.14 … 1.5 mm2
Voltage and other connection cross-section 0.2 … 2.5 mm2
Weight 560 g
96 DI
RIS
A8
92
+ 0.8
diris_855_e_1_x_cat

0
- 0.0

35
45
15
96

References

Basic device DIRIS A80


Type Reference
With 2 outputs 4825 0213
With 1 input / 1 output 4825 0214
Options
Plug-in modules Reference
RS485 MODBUS® communication 4825 0092
Ethernet communication (embedded Ethernet Webserver)(1) 4825 0203
Ethernet communication + RS485 MODBUS gateway (embedded Ethernet Webserver)(1) 4825 0204
(1) Dimensions: 2 slots.

Accessories
Description of accessories To be ordered in multiples of Reference
IP65 protection 1 4825 0089
Panel mounting kit for a 144 x 96 mm cut-out 1 4825 0088
Fuse disconnect switches for the protection of voltage inputs (type RM) 3 poles 4 5601 0018
Fuse disconnect switches for the protection of the auxiliary supply (type RM) 1 pole + neutral 6 5601 0017
Fuses type gG 10 x 38 0.5 A 10 6012 0000
Ferrite to be associated with communication modules 1 4899 0011
Current transformer range 1 See page 106

Core balance transformer ∆IC


Type Toroid diameter (mm) Reference
∆IC Ø15 15 4950 6015
∆IC Ø30 30 4950 6030
∆IC Ø50 50 4950 6050
∆IC Ø80 80 4950 6080
∆IC Ø120 120 4950 6120
∆IC Ø200 200 4950 6200
∆IC Ø300 300 4950 6300
Management softwares for DIRIS See page 140

Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.

Catalogue 2017 101


DIRIS Q800
Network quality analysis
quality analysis of electrical energy and power grids
Single-circuit metering,

new
The solution for
measurement &

> Industry
> Infrastructure
> Healthcare buildings
analysis

> Data centers

diris-q_012_a
Strong points

DIRIS Q > Large colour touchscreen


> High performance and
Function accuracy
> Regulatory compliance
The DIRIS Q800 is a multifunction network To achieve these objectives, the DIRIS Q800
analyser for all energy efficiency projects. It does the following: > Multiple communication
helps to actively ensure the electrical system • Measures electrical parameters and status channels
runs continuously and at optimised rates. (via auxiliary contacts).
As such, with this system you can: • Analyses the quality of energy according to
• Improve the efficiency of your facility. Compliance with standards
class A IEC 61000-4-30.
• Reduce production losses. • Measures differential current. > IEC 61000-4-30
• Optimise running costs. • GPS synchronisation. class A
• Reduce maintenance costs.
> IEC 62586-2
> IEC 62053-22
> IEC 62053-23
Advantages > EN 50160
Large colour touchscreen Multiple communication channels
The 192 x 144 mm color touchscreen is With its multiple communication options, the
tactile, easy to operate and provides intuitive DIRIS Q800 can be integrated into any type of
navigation. communication infrastructure:
• 1 rear Ethernet port for permanent cable
Regulatory compliance connection.
By its compliance with IEC 61000-4-30 Class • 1 front Ethernet for local diagnostics.
A and IEC 62586-2 , you have the assurance • 1 Wifi port.
of a certified and high quality product . • 1 RS485 port.
• 1 USB port.
• GPS synchronisation.
• Built-in Webserver.
• Protocols: HTTP, HTTPS, FTP, NTP,
MODBUS, PQDIF.

102 Catalogue 2017


DIRIS Q800
Network quality analysis
quality analysis of electrical energy and power grids

Functions
Measurements Logging
• Measures across 4 quadrants • EN 50160 events ½ period (10 ms): voltage dips, voltage cutouts,
• Voltage by phase, current by phase, frequency. voltage surges.
• Neutral current, differential current. • Data exported automatically via FTP.
• Neutral/earth voltage. • EN50160 compliant.
• Active, reactive and apparent power. • Transients (20 micro seconds).
• Cos phi and power factor.
• THD and spectral analysis up to the 63rd for current voltage. Inputs/outputs
• Flicker (Pst, Plt). • 4 digital inputs.
• Voltage imbalance. • 4 digital outputs.
• Remote control signals. • 4 analogue outputs.

Dimensions
191 190 6
Dimensions
183 x 135 mm
Cutout
(192 x 144 mm DIN)
Front panel (L x H) 191 x 143 mm
Enclosures (L x H x P) 183 x 135 x 190 mm
143

135

Weight 1400 g
diris_935_b_1_cat

183

Specifications
Auxiliary power supply Communication
Voltage range 85 … 285 VAC / 65 … 250 VDC Ethernet ports 2 Auto MDIX RJ45 10/100 Base Ethernet
Frequency 50/60 Hz RS485 opto-insulated port (slave) 0.5 UL 2400 to 115200 bps
Power consumption Max. 15 VA Passive WIFI antenna SMA conn.
Backup battery Li-ion 2500 mAh Active GPS antenna SMA conn.
Measurement inputs HTTP, HTTPS, FTP, SFTP, NTP, NMEA,
Protocols
Modbus RTU/TCP
P-N: max 580 V RMS CAT III
Direct voltage measurement input USB port USB 2.0
L-L: max 1000 V RMS CAT III
U4 direct voltage measurement input Max 580 V RMS CAT II Environmental conditions
Peak input power factor 2 Operating temperature (max. range) -25 … +55°C
Current inputs Max 7 A RMS Storage temperature -25 … +75°C
Current input consumption 0.04 VA Humidity Max. 95 %
Peak input current factor 3 Max.altitude 2000 m
Voltage input impedance › 6 MΩ Standards and safety
Frequency range 42.5 to 57.5 Hz/51 to 69 Hz Product comformity IEC/EN 62586-1, IEC/EN 62586-2
Voltage reference channel U1N/U12 Safety CAT III power, insulation class 2, 600 V
Sampling 51.2 kHz @50 Hz Degree of pollution 2 (EN 61010-1)
Accuracy Degree of protection IP40 front, IP20 rear
Three-phase voltage ± 0.1% Directive 2006/95/EC LV, EN 61010
4th voltage (neutral/earth) ± 0.2% 2004/108/EC EMC, EN 50081-2, EN 50082-2,
Currents ± 0.2% EMC EN 61326/A1, EN 55011: 1998+A1: 1999+A2:
2002, EN 61000-6-2/-4-2/-4-3/-4-4/-4-5/-4-6/-4-11
Power ± 0.2%
Frequency ± 8 mHz
Harmonics lC. 1 IEC/EN 61000-4-7
Active energy lC. 0.5S IEC/EN 62053-22
Reactive energy lC. 1 IEC/EN 62053-23

References
Designation Reference
DIRIS Q800 4826 0100

Catalogue 2017 103


DIRIS Q800
Network quality analysis
quality analysis of electrical energy and power grids

Terminals
2
1. Product label
2. Earth connection
3 3. RS485 MODBUS RTU communication
RS485 85-265 VAC (65-250 DC)
AUX CAT II 4. Auxiliary power supply and fuse
5. Voltage and current inputs
1 1 2 3 1 2 3 6. Auto MDIX ETHERNET port
C B- A+ L PE N 7. Battery switch
FUSE T 4
DIG. OUT - 24 VDC/max 50 mA DIG. IN - 24 VDC AN. OUT - 4-20 mA/max 500 ohm 250 VAC/500 mA 8. GPS and WIFI antenna
9 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
9. Logical outputs, analogue inputs/outputs
WIFI ant.
GPS ant.
(3.3 VDC out)

8 3+1 Phase AC Voltage - max. 3x580/1000 V CAT III

ON
L1 L2 L3 L4 N
BATT
7
OFF
3+1 Phase AC Current CH5 (EL) AC Current
1(7) A RMS 1(7) A RMS

diris_933_a_1_x_cat
ETHERNET
L1 L2 L3 L4 L5 5
10/100 Base T

Communication via RS485 link AC and DC auxiliary power supply Ethernet communication

85/265 VAC
65/250 VDC
PE

LIYCY-CY
diris_920_a_1_x_cat.eps

diris_921_a_1_x_cat.eps

diris_928_a_1_x_cat.eps

C B- A+ L PE N
Ethernet
AUX 10/100 Base T
RS485 DIRIS Q800

Digital outputs Digital inputs Analogue outputs


diris_922_a_1_x_cat.eps

diris_923_a_1_x_cat.eps

diris_924_a_1_x_cat.eps

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
DIG. OUT 24 VDC / max 50 mA DIG. IN 24 VDC AN. OUT 4-20 mA / max 500 Ohm

DIRIS Q800 DIRIS Q800 DIRIS Q800


1-2: optocoupler output 1 1-2: optocoupler input 1 1-2: analogue output 1
3-4: optocoupler output 2 3-4: optocoupler input 2 3-4: analogue output 2
5-6: optocoupler output 3 5-6: optocoupler input 3 5-6: analogue output 3
7-8: optocoupler output 4 7-8: optocoupler input 4 7-8: analogue output 4

Current and voltage inputs


diris_925_a_1_x_cat.eps

diris_926_a_1_x_cat.eps

diris_927_a_1_x_cat.eps

L1 L2 L3 L4 N 1 2 3 4 5 6 7 8 1 2
3+1 phase AC voltage I1 I2 I3 IN I5
3+1 phase AC current Ch5 (EL) AC current
DIRIS Q800 DIRIS Q800 DIRIS Q800
L1, L2, L3, L4, N: voltage inputs 1-2: current input i1 1-2: differential core connections
3-4: current input i2
5-6: current input i3
7-8: current input iN

104 Catalogue 2017


DIRIS Q800
Network quality analysis
quality analysis of electrical energy and power grids

Connections

4 wires with 4 CT + differential measurements (1/5 A) 3 wires with 3 CT + differential measurements (1/5 A)
L1 P1 P1
L1
S1 S2 P1 S1 S2 P1
L2 L2
S1 S2 P1 S1 S2 P1
L3 L3
S1 S2 P1 S1 S2
N S1 S2
S1 S2
S1 S2
PE PE
1 1

diris_929_a_1_x_cat

diris_930_a_1_x_cat
L1 L2 L3 L4 N 1 2 3 4 5 6 7 8 1 2 L1 L2 L3 L4 N 1 2 3 4 5 6 7 8 1 2
3+1 phase AC voltage S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 3+1 phase AC voltage S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 IN I5 I1 I2 I3 IN I5
3+1 phase AC current AC current 3+1 phase AC current AC current
1. 0.5 A gG / 0.5 A class CC fuses. 1. 0.5 A gG / 0.5 A class CC fuses.

3 wires with 2 CT + differential measurements Single-phase with 2 CT + differential measurements (1/5 A)


L1 P1 L P1
S1 S2 S1 S2
L2
P1
L3
S1 S2 P1
S1 S2 N S1 S2
S1 S2
PE PE
1
diris_931_a_1_x_cat

diris_932_a_1_x_cat
L1 L2 L3 L4 N 1 2 3 4 5 6 7 8 1 2 L1 L2 L3 L4 N 1 2 3 4 5 6 7 8 1 2
3+1 phase AC voltage S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 3+1 phase AC voltage S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 IN I5 I1 I2 I3 IN I5
3+1 phase AC current AC current 3+1 phase AC current AC current
1. 0.5 A gG / 0.5 A class CC fuses. 1. 0.5 A gG / 0.5 A class CC fuses.

Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts "Expert Services" offer complete support for the success
of your project.

Catalogue 2017 105


Current transformers
Measurement devices
from 5 to 5000 A
The solution for
transformers

> Industry
> Office buildings
Current

trafo_108_a_1_cat

trafo_012_a_1_cat

Strong points
Three-phase CT

> An adapted accuracy class


> A wide range of ratings and
Bar-through CT
dimensions
> Quick and easy to mount
trafo_077_b_1_cat

Conformity to standards
trafo_010_a_1_cat

> IEC 61869-2


> IEC 61439-1
Split-core transformer Cable-through CT

Function Advantages Available on request

SOCOMEC current transformers deliver to An adapted accuracy class SOCOMEC also offer
the secondary a standard current proportional In order to get the best of your DIRIS multifunction customised solutions:
to the primary current and adapted to the rating meters and COUNTIS energy meters, we can > 1 A secondary
of the associated device. They are equipped as provide current transformers with the following
standard with removable terminal covers and > Double or triple primary ratio
accuracy classes: 0.2s; 0.5 ; 1 or 3.
double terminals allowing the secondary to be A wide range of ratings and dimensions > Voltage transformer
short-circuited without any risk. Your measurement process can be optimised > Summation CTs
They are mounted using two screw-on metal whatever your needs in terms of ratings, space
brackets or, in certain cases, by a clip-on DIN- requirements, conductor sizing or accuracy class.
rail fastener. The connections are made by A wide range of combinations are available in our
screws or by fast-on terminals. standard range with specific versions available on
• Accuracy class: 0.2s — 0.5 or 1. request (other ratios, tropicalisation and specific
• Dielectric quality: 3 kV — 50 Hz — 1 min. frequency, class or burden).
• Operating frequency: 50 — 60 Hz. Quick and easy to mount
• Permanent overload: 1.2 In. Our current transformers are adapted to
• Insulation class: E (120 °C). any type of mounting: edgewise or flat
mounting, DIN-rail or back-plate mounting.
Implementation is easy and rapid.

Composition of the range


trafo_126_a_1_x_cat
trafo_013_b_1_cat

trafo_014_b_1_cat

trafo_015_b_1_cat

Primary wound moulded Bar or cable-through CT Bar or cable-through three- Bar-through split-core CT
case CT phase CT

106 Catalogue 2017


Current transformers
Measurement devices
from 5 to 5000 A

Primary wound moulded case CT


References
TRB 60 TRB 70 T2RB 115 TRB 135
Class Class Class Class
Primary Secondary(1) 0.5 Reference 0.5 Reference 0.2s Reference 0.5 Reference
5A 5A 2.5 VA 192T 0505 10 VA 192T 0521
10 A 5A 2.5 VA 192T 0510 10 VA 192T 0522
15 A 5A 2.5 VA 192T 0515 10 VA 192T 0523
20 A 5A 2.5 VA 192T 0520 10 VA 192T 0524
25 A 5A 10 VA 192T 0525 7.5 VA 192U 0402 10 VA 192T 0603
30 A 5A 5 VA 192T 0530 7.5 VA 192U 0403 10 VA 192T 0607
40 A 5A 5 VA 192T 0541 7.5 VA 192U 0404 10 VA 192T 0604
50 A 5A 5 VA 192T 0551 7.5 VA 192U 0405 10 VA 192T 0605
60 A 5A 7.5 VA 192U 0406 10 VA 192T 0606
75 A 5A 7.5 VA 192U 0407 10 VA 192T 0608
80 A 5A 7.5 VA 192U 0408 10 VA 192T 0609
100 A 5A 10 VA 192T 0610
125 A 5A 7.5 VA 192U 0412 10 VA 192T 0612
150 A 5A 7.5 VA 192U 0415 10 VA 192T 0615
(1) Secondary 1 A: on request.

Accessories
TRB 60 TRB 70 TRB 135
Description of accessories Reference Reference Reference
DIN-rail mounting 192T 0003 192T 0005 (1)
Sealable cover 192T 0105 192T 0103 192T 0101 (2)
(1) Not available for 50 A rating
(2) For 125 and 150 A ratings, use reference 192T 0103.

CT Plug-in transducer (CEA-VA)


TRB 60 TRB 70
Power supply Output Reference Reference
Self-supplied 0-20 mA / 0-10 VDC 192Y 0015 192Y 0025 (1)
230 VAC 0-20 mA / 0-10 VDC 192Y 0215 192Y 0225 (1)
24 VDC 0-20 mA / 0-10 VDC 192Y 0115 192Y 0125 (1)
(1) Not available for ratings 40 and 50 A

CT Plug-in transducer (CEA-VA4)


TRB 60 TRB 70
Power supply Output Reference Reference
230 VAC 4-20 mA / 0-10 VDC 192T 0255 192Y 0265 (1)
24 VDC 4-20 mA / 0-10 VDC 192Y 0155 192Y 0165 (1)
(1) Not available for ratings 40 and 50 A

Certificate of performance

Each class 0.2s current transformer is supplied with an individual certificate of performance,
attesting to its accuracy.

Catalogue 2017 107


Current transformers
Measurement devices
from 5 to 5000 A

Primary wound moulded case CT (continued)


Dimensions
TRB 60 TRB 70(1) TRB 70 (for 40 and 50 A)
61 71 71 55

K L K L
K L
75.5

85.5

107
trafo_036_a_1_x_cat

trafo_038_a_1_x_cat

trafo_162_a_1_x_cat
40 50
60 70 50 50
(1) different dimensions 70 67
for 40 and 50 A ratings 82
T2RB115 TRB 135
64 43 70

k I
1
k l
100

85

5
K L
31

40

L–H2–P2
trafo_037_a_1_x_cat
trafo_113_a_1_x_cat

0.5

52 50
65 70 50
92 112
1 25 to 100 A: M8 x 25
115 135

TRB 135 (for 125 and 150 A)


71 45
Primary
wound CT TRB 60 TRB 70 (1) T2RB 115 TRB 135 (2)
H x W x D (mm) 75.5 x 61 x 35 85.5 x 71 x 45 115 x 100 x 70 85 x 135 x 60
DIN-rail mounting yes yes no no
85.5

(1) Dimensions are different for TRB 70 with 40 and 50 A ratings.


5

(2) Dimensions are different for TRB 135 with 125 and 150 A ratings.
35
trafo_166_a_1_x

50 60
70 77
92
86
116
136

Associated transducers
Transducer to be associated with adapted
current transformers:
• Class 0.5.
• Input: 1 or 5 A. UH - 8 4 +
• Output: IA
- 0-20 mA, 0-10 V (type CEA-VA) + 7 3 -
trafo_060_a_1_x_cat

- 4-20 mA, 0-10 V (type CEA-VA4)


trafo_074_a_1_cat

• Self-supplied or auxiliary power supply l 6 2 +


A UA
24 VDC or 230 VAC. k 5 1 -
• 3 sizes according to the CT: type 1, 2 or 3.

W D

Dimensions (mm)
trafo_071_a_1_gb_cat

Converter For CT Height (mm) Width (mm) Depth (mm)


Type 1 TRB 60 50.5 60 32.5
Type 2 TRB 70 50 70 43

108 Catalogue 2017


Current transformers
Measurement devices
from 5 to 5000 A

Cable-through CT
References
TCA 14 TCA 21 TCA 22 T2CA 225
Class Class Class Class
Primary Secondary(1) 1 Reference 1 Class 0.5 Reference 1 Reference 0.2s Reference
40 A 5A 1 192T 1404
50 A 5A 1 192T 1405
60 A 5A 1.5 192T 1406 1 VA 192T 2006
75 A 5A 1.5 192T 1407 1.5 VA 192T 2007
80 A 5A 1.5 VA 192T 2008
100 A 5A 2.5 192T 1410 1.5 VA 192T 2010 1 VA 192T 2022
125 A 5A 2.5 192T 1412 1.5 VA 192T 2012
150 A 5A 2.5 192T 1415 1.5 VA 192T 2015 1.5 VA 192T 2023 1.5 VA 192U 2215
200 A 5A 2.5 VA 192T 2020 2.5 VA 192T 2024 2.5 VA 192U 2220
250 A 5A 2.5 VA 192T 2016 3.75 VA 192T 2025 5 VA 192U 2225
300 A 5A 2.5 VA 192T 2017 3.75 VA 192T 2030 5 VA 192U 2230
400 A 5A 5 VA 192T 2034 5 VA 192U 2240
500 A 5A 5 VA 192T 2035 (2) 10 VA 192U 2250
600 A 5A 5 VA 192T 2036 (2) 10 VA 192U 2260
(1) Secondary 1 A: on request. (2) Dimensions of T2CA 225

Accessories
TCA 14 TCA 21 TCA 22 T2CA 225
Description of accessories Reference Reference Reference Reference
DIN-rail mounting 192T 0006 192T 0006 192T 0007 192T 0003
Guide tube Ø 8.5 mm (1) 192T 0020
Guide tube Ø 12.5 mm(1) 192T 0021 192T 0023
Guide tube Ø 16.5 mm(1) 192T 0024
Sealable cover 192T 0105
(1) For centralising cables within the CT aperture.

Dimensions
TCA 14 TCA 21 TCA 22 T2CA 225
45 45 49.5 61

k I
k I
k I
65

k I
Ø 22.5
65

65

ø14
trafo_164_a_1_x_cat

trafo_039_a_1_x_cat

trafo_042_a_1_x_cat

78.5
75.5
27

K – P1 ø21 ø22.5
27

27

K – P1 K – P1
24
trafo_110_a_1_x_cat

30
31

44 47 24 28.5
62 44 48.5 K–P1

40
60

Cable-through CT TCA 14 TCA 21 TCA 22(1) T2CA 225


Ø cable (mm) 14 21 22.5 22.5
H x W x D (mm) 65 x 45 x 30 65 x 45 x 30 65 x 49.5 x 35 78.5 x 61 x 35
DIN-rail mounting yes yes yes yes
(1) Dimensions are different for 600 A: 78.5x61x35.

Catalogue 2017 109


Current transformers
Measurement devices
from 5 to 5000 A

Bar or cable-through CT
References
TCB 17-20 TCB 26-30 T2CB 26-30 TCB 28-30
Class Class Class Class Class Class
Primary Secondary(1) 1 Reference 0.5 1 Reference 0.2s Reference 0.5 1 Reference
50 A 5A 1 VA 192T 2305
60 A 5A 1 VA 192T 2106 1 VA 192T 2306
75 A 5A 1 VA 192T 2107 1.5 VA 192T 2307
80 A 5A 1.25 VA 192T 2108 1.5 VA 192T 2308 1.25 VA 192T 2408
100 A 5A 1.5 VA 192T 2110 1.5 VA 192T 2310 1.5 VA 192T 2410
125 A 5A 1.5 VA 192T 2112 1.5 VA 192T 2312 2.5 VA 192T 2412
150 A 5A 2.5 VA 192T 2115 1.5 VA 192T 2315 1.5 VA 192U 2315 2.5 VA 192T 2415
160 A 5A 2.5 VA 192T 2116
200 A 5A 2.5 VA 192T 2120 2.5 VA 192T 2320 2.5 VA 192U 2320 2.5 VA 192T 2420
250 A 5A 5 VA 192T 2125 5 VA 192T 2325 2.5 VA 192U 2325 2.5 VA 192T 2425
300 A 5A 5 VA 192T 2130 5 VA 192T 2330 5 VA 192U 2330 2.5 VA 192T 2430
400 A 5A 5 VA 192T 2140 5 VA 192T 2340 5 VA 192U 2340 5 VA 192T 2440
500 A 5A 5 VA 192T 2350 5 VA 192U 2350 5 VA 192T 2450
600 A 5A 5 VA 192T 2360 5 VA 192U 2360
750 A 5A 5 VA 192T 2375 5 VA 192U 2375
(1) Secondary 1 A: on request.

TCB 26-40 TCB 32-40 T2CB 32-40


Class Class Class Class
Primary Secondary(1) 1 Reference 0.5 1 Reference 0.2s Reference
75 A 5A 1.5 VA 192T 4007
100 A 5A 1.5 VA 192T 3210 1.5 VA 192T 4010
125 A 5A 2.5 VA 192T 3212 1.5 VA 192T 4012
150 A 5A 2.5 VA 192T 3215 2.5 VA 192T 4015
160 A 5A 2.5 VA 192T 3216
200 A 5A 2.5 VA 192T 3220 5 VA 192T 4020 2.5 VA 192U 4020
250 A 5A 2.5 VA 192T 3225 5 VA 192T 4025 5 VA 192U 4025
300 A 5A 5 VA 192T 3230 10 VA 192T 4030 5 VA 192U 4030
400 A 5A 5 VA 192T 3240 10 VA 192T 4040 5 VA 192U 4040
500 A 5A 5 VA 192T 3250 10 VA 192T 4050 5 VA 192U 4050
600 A 5A 5 VA 192T 3260 10 VA 192T 4060 5 VA 192U 4060
750 A 5A 10 VA 192T 3275 10 VA 192T 4075 5 VA 192U 4075
800 A 5A 10 VA 192T 4080
1000 A 5A 10 VA 192T 4090
(1) Secondary 1 A: on request.

Accessories
TCB 17-20 TCB 26-30 TCB 26-40 TCB 32-40
Description of accessories Reference Reference Reference Reference
DIN-rail mounting 192T 0007 192T 0003 192T 0003 192T 0005
Sealable cover 192T 0105 192T 0105 192T 0103

CT Plug-in transducer (CEA-VA)


TCB 26-30 TCB 26-40 TCB 32-40
Power supply Output Reference Reference Reference
Self-supplied 0-20 mA / 0-10 VDC 192Y 0015 192Y 0015 192Y 0035
230 VAC 0-20 mA / 0-10 VDC 192Y 0215 192Y 0215 192Y 0235
24 VDC 0-20 mA / 0-10 VDC 192Y 0115 192Y 0115 192Y 0135

CT Plug-in transducer (CEA-VA4)


TCB 26-30 TCB 26-40 TCB 32-40
Power supply Output Reference Reference Reference
230 VAC 4-20 mA / 0-10 VDC 192T 0255 192T 0255 192Y 0275
24 VDC 4-20 mA / 0-10 VDC 192Y 0155 192Y 0155 192Y 0175

110 Catalogue 2017


Current transformers
Measurement devices
from 5 to 5000 A

References
TCB 44-50 TCB 44-63 T2CB 44-63
Class Class Class
Primary Secondary(1) 0.5 Reference 0.5 Reference 0.2s Reference
150 A 5A 1.5 VA 192T 5015
200 A 5A 2.5 VA 192T 5020 1.5 VA 192T 6420
250 A 5A 5 VA 192T 5025 1.5 VA 192T 6425
300 A 5A 5 VA 192T 5030 2.5 VA 192T 6430 5 VA 192U 6430
400 A 5A 10 VA 192T 5040 5 VA 192T 6440 5 VA 192U 6440
500 A 5A 10 VA 192T 5050 10 VA 192T 6450 10 VA 192U 6450
600 A 5A 10 VA 192T 5060 10 VA 192T 6460 10 VA 192U 6460
750 A 5A 10 VA 192T 5075 10 VA 192T 6475 10 VA 192U 6475
800 A 5A 15 VA 192T 5080 10 VA 192T 6480
1000 A 5A 15 VA 192T 5090 15 VA 192T 6490 10 VA 192U 6490
1200 A 5A 15 VA 192T 5092 15 VA 192T 6492 10 VA 192U 6492
1250 A 5A 15 VA 192T 5095 15 VA 192T 6493 10 VA 192U 6493
1500 A 5A 15 VA 192T 6495 10 VA 192U 6495
1600 A 5A 15 VA 192T 6494
(1) Secondary 1 A: on request.

TCB 55-80 TCB 85-100 TCB 100-125


Class Class Class
Primary Secondary(1) 0.5 Reference 0.5 Reference 0.5 Reference
400 A 5A 2.5 VA 192T 8140
500 A 5A 5 VA 192T 8150
600 A 5A 5 VA 192T 8160
750 A 5A 10 VA 192T 8175 2.5 VA 192T 9675
800 A 5A 10 VA 192T 8180 5 VA 192T 9680
1000 A 5A 15 VA 192T 8190 10 VA 192T 9690 5 VA 192T 9590
1200 A 5A 15 VA 192T 8192 10 VA 192T 9692 10 VA 192T 9592
1250 A 5A 15 VA 192T 8193 15 VA 192T 9693 10 VA 192T 9593
1500 A 5A 15 VA 192T 8195 15 VA 192T 9695 15 VA 192T 9595
1600 A 5A 15 VA 192T 8194 15 VA 192T 9694
2000 A 5A 15 VA 192T 8196 30 VA 192T 9696 30 VA 192T 9596
2500 A 5A 30 VA 192T 9697 30 VA 192T 9597
3000 A 5A 30 VA 192T 9698 30 VA 192T 9598
(1) Secondary 1 A: on request.

Accessories
TCB 44-50 TCB 44-63 TCB 55-80 TCB 85-100 TCB 100-125
Description of accessories Reference Reference Reference Reference Reference
Sealable cover 192T 0102 192T 0102 192T 0102 192T 0106 192T 0106

CT Plug-in transducer (CEA-VA)


TCB 44-50 TCB 44-63 TCB 55-80
Power supply Output Reference Reference Reference
Self-supplied 0-20 mA / 0-10 VDC 192Y 0045 192Y 0045
230 VAC 0-20 mA / 0-10 VDC 192Y 0245 192Y 0245
24 VDC 0-20 mA / 0-10 VDC 192Y 0145 192Y 0145

CT Plug-in transducer (CEA-VA4)


TCB 44-50 TCB 44-63 TCB 55-80
Input Output Reference Reference Reference
230 VAC 4-20 mA / 0-10 VDC 192Y 0285 192Y 0285
24 VDC 4-20 mA / 0-10 VDC 192Y 0185 192Y 0185

Catalogue 2017 111


Current transformers
Measurement devices
from 5 to 5000 A

Bar or cable-through CT (continued)


Dimensions
TCB 17-20 TCB 26-30 and T2CB 26-30 TCB 28-30 TCB 26-40
49.5 61 49.9
61
40.5
ø 17.5

k I

10.5
k I
k I
65

70
75.5

ø2 k I

20.5
30.5

ø2
6

10.5

75.5
27

29
trafo_045_a_1_x_cat

12.5
18.5
K – P1
K – P1

6
32

ø2
trafo_044_a_1_x_cat

K – P1
trafo_041_a_1_x_cat

15.5 10.5

33
trafo_055_b_1_x_cat
K – P1
20.5 30.5 20.5
28.5 40 30.5 32
48.5 60 40
60

TCB 32-40 and T2CB 32-40 TCB 44-50 TCB 44-63 and T2CB 44-63
71 86 96

k I k I k I
88.5

105.5
98.5

32
30.5

30.5
16

30.5
12.5

10.5
4
4

ø4
36.75

ø4
43.25

48.25
K – P1
trafo_040_a_1_x_cat

K–P1
K–P1
trafo_043_a_1_x_cat

10.5
trafo_046_a_1_x_cat

40.5 40.5
50.5 50.5
50
65 63.5
70
85 70
95

TCB 55-80 TCB 85-100 TCB 100-125


99
99
96
k I
k I

k I
184.8
184.8
10.5
123.5

30.5

31
51
31
51

0
10
5

5
ø5

ø8

Ø
58.5

82
82
trafo_048_a_1_x_cat

K–P1
trafo_049_a_1_x_cat

k-P1
k-P1
trafo_047_a_1_x_cat

60.5 95
80.5 81
95 95 101
120 101 121
122 172
172

Bar or cable-through CT TCB 17-20 TCB 26-30 T2CB 26-30 TCB 26-40 TCB 28-30 TCB 32-40 T2CB 32-40
30 x 10 (x 1) / 30 x 10 (x 1) / 40 x 12 (x 1) / 40 x 10 (x 1) / 40 x 10 (x 1) /
Bar (mm) 20 x 5 (x 1) 30 x 10 (x 1)
20 x 10 (x 1…2) 20 x 10 (x 1…2) 32 x 18 (x 1) 30 x 5 (x 1…2) 30 x 5 (x 1…2)
Ø cable (mm) 17.5 26 26 26 28 32 32
H x W x D (mm) 65 x 49.5 x 50 75.5 x 61 x 48 75.5 x 61 x 48 75.5 x 61 x 48 70 x 49.9 x 68 88.5 x 71 x 58 88.5 x 71 x 58
DIN-rail mounting yes yes yes yes yes yes

Bar or cable-through CT TCB 44-50 TCB 44-63 T2CB 44-63 TCB 55-80 TCB 85-100 TCB 100-125
80 x 10 (x 1)/
50 x 12 (x 1)/ 63 x 10 (x 1)/ 63 x 10 (x 1)/ 100 x 10 (x 1…2) / 123 x 30 (x 1)/
Bar (mm) 60 x 30 (x 1) /
40 x 10 (x 1…2) 50 x 10 (x 1…2) 50 x 10 (x 1…2) 80 x 10 (x 1…3) 100 x 10 (x 1…3)
60 x 10 (x 1…2)
Ø cable (mm) 44 44 44 55 85 100
H x W x D (mm) 98.5 x 86 x 58 105.5 x 96 x 58 105.5 x 96 x 58 123.5 x 120 x 58 184.5 x 172 x 52 184.5 x 172 x 52

112 Catalogue 2017


Current transformers
Measurement devices
from 5 to 5000 A

Associated transducers

Transducer to be associated with adapted


current transformers:
• Class 0.5. UH - 8 4 +
IA
• Input: 1 or 5 A + 7 3 -

trafo_060_a_1_x_cat
• Output:
- 0-20 mA, 0-10 V (model CEA-VA),
l 6 2 +
trafo_074_a_1_cat

- 4-20 mA, 0-10 V (model CEA-VA4), A UA


• Self-supplied or auxiliary power supply k 5 1 -
24 VDC or 230 VAC.
• 3 sizes according to the CT: type 1, 2 or 3.

W D
Dimensions (mm)
Converter For CT Height (mm) Width (mm) Depth (mm)
Type 1 TCB 26-30 50.5 60 32.5
Type 1 TCB 26-40 50.5 60 32.5
Type 2 TCB 32-40 50 70 43
trafo_071_a_1_gb_cat

Type 3 TCB 44-63 50.5 95 43


Type 3 TCB 55-80 50.5 95 43

Catalogue 2017 113


Current transformers
Measurement devices
from 5 to 5000 A

Bar-through CT
References
TBA 60 TBA 80 TBA 100 T2BA 100
Class Class Class Class Class
Primary Secondary 0.5 1 Reference 0.5 Reference 0.5 Reference 0.2s Reference
200 A 5A 2.5 VA 192T 7020
250 A 5A 2.5 VA 192T 7025
300 A 5A 2.5 VA 192T 7030 2.5 VA 192T 7530
400 A 5A 5 VA 192T 7040 5 VA 192T 7540
500 A 5A 5 VA 192T 7050 5 VA 192T 7550
600 A 5A 10 VA 192T 7060 5 VA 192T 7560 5 VA 192T 8060
750 A 5A 10 VA 192T 7075 5 VA 192T 7575 5 VA 192T 8075
800 A 5A 10 VA 192T 7080 10 VA 192T 7580 5 VA 192T 8080
1000 A 5A 15 VA 192T 7090 15 VA 192T 7590 5 VA 192T 8090
1200 A 5A 15 VA 192T 7092 15 VA 192T 7592 10 VA 192T 8092 5 VA 192U 8092
1250 A 5A 15 VA 192T 7093 15 VA 192T 7593 10 VA 192T 8093 5 VA 192U 8093
1500 A 5A 15 VA 192T 7095 15 VA 192T 7595 15 VA 192T 8095 5 VA 192U 8095
1600 A 5A 15 VA 192T 7094 15 VA 192T 7594 15 VA 192T 8094
2000 A 5A 15 VA 192T 7596 15 VA 192T 8096 5 VA 192U 8096
2500 A 5A 30 VA 192T 8097 10 VA 192U 8097
3000 A 5A 30 VA 192T 8098 (1) 10 VA 192U 8098
4000 A 5A 30 VA 192T 8099 (1)
(1) Dimensions are different for TBA 100 with 3000 and 4000 A primary.

TBA 103 T2BA 103 TBA 127 T2BA 127


Class Class Class Class
Primary Secondary 0.5 Reference 0.2s Reference 0.5 Reference 0.2s Reference
400 A 5A 2.5 VA 192T 9340 2.5 VA 192T 9740
500 A 5A 2.5 VA 192T 9350 2.5 VA 192T 9750
600 A 5A 2.5 VA 192T 9360 2.5 VA 192T 9760
750 A 5A 2.5 VA 192T 9375 2.5 VA 192T 9775
800 A 5A 5 VA 192T 9380 5 VA 192T 9780
1000 A 5A 10 VA 192T 9390 5 VA 192U 9390 10 VA 192T 9790
1200 A 5A 10 VA 192T 9392 5 VA 192U 9392 10 VA 192T 9792 5 VA 192U 9792
1250 A 5A 10 VA 192T 9393 5 VA 192U 9393 10 VA 192T 9793 5 VA 192U 9793
1500 A 5A 15 VA 192T 9395 5 VA 192U 9395 15 VA 192T 9795 5 VA 192U 9795
1600 A 5A 10 VA 192T 9394 15 VA 192T 9794
2000 A 5A 15 VA 192T 9396 15 VA 192T 9796 5 VA 192U 9796
2500 A 5A 15 VA 192T 9797
3000 A 5A 25 VA 182T 9798 (1)
4000 A 5A 30 VA 182T 9799 (1)
(1) Replacement model TRA 127 for this rating.

Accessories
TBA 60 TBA 80 TBA 100 T2BA 100 TBA 103 T2BA 103 TBA 127 T2BA 127
Description of accessories Reference Reference Reference Reference Reference Reference Reference Reference
Sealable cover 192T 0102 192T 0102 192T 0102 192T 0102 192T 0102

CT Plug-in transducer (CEA-VA) CT Plug-in transducer (CEA-VA4)


TBA 100 TBA 100
Power supply Output Reference Power supply Output Reference
Self-supplied 0-20 mA / 0-10 VDC 192Y 0045 230 VAC 4-20 mA / 0-10 VDC 192Y 0285
230 VAC 0-20 mA / 0-10 VDC 192Y 0245 24 VDC 4-20 mA / 0-10 VDC 192Y 0185
24 VDC 0-20 mA / 0-10 VDC 192Y 0145

114 Catalogue 2017


Current transformers
Measurement devices
from 5 to 5000 A

Dimensions
TBA 60 TBA 80 TBA 100 600 to 2500 A(1)
300 to 2000 A T2BA 100 1200 to 3000 A

86 96
S2 S1
S1 S2

k I

k I

117
84
129

31

167

55.5
59
60

trafo_050_a_1_x_cat

trafo_059_a_1_x_cat

trafo_082_a_1_x_cat
S2 S1

77.5
k-P1

50 34 k-P1

60.5 69
88 96
95
100.5
129

(1) TBA 100, 3000 and 4000 A: 214 x 129 x 78 mm.

TBA 103 and T2BA 103 TBA 127 and T2BA 127

S2 S1
150

38
103

175
128
69

trafo_054_a_1_x_cat

trafo_052_a_1_x_cat
17.5

L–P2

41
17

99
17.7 42.8 17.7
100

Bar-through CT TBA 60 TBA 80 TBA 100 T2BA 100 TBA 103 T2BA 103 TBA 127 T2BA 127
Bar (mm) 60 x 30 84 x 34 100 x 55 100 x 55 103 x 41 103 x 41 128 x 38 128 x 38
H x W x D (mm) 129 x 88 x 78 117 x 96 x 68 167 x 129 x 78 (1) 167 x 129 x 78 150 x 99 x 58 150 x 99 x 58 175 x 100 x 55 175 x 100 x 55
(1) TBA 100, 3000 and 4000 A: 214 x 129 x 78 mm.

Catalogue 2017 115


Current transformers
Measurement devices
from 5 to 5000 A

Three-phase bar or cable-through CT


References
TCB3 18-20 TCB3 22-30
Class Class
Primary Secondary(1) 1 Reference 1 Reference
3 x 100 A 3x5A 1 VA 192T 3310
3 x 150 A 3x5A 1.25 VA 192T 3315
3 x 200 A 3x5A 1.5 VA 192T 3320
3 x 250 A 3x5A 2.5 VA 192T 3325 2.5 VA 192T 3425
3 x 300 A 3x5A 3.75 VA 192T 3430
3 x 400 A 3x5A 5 VA 192T 3440
3 x 500 A 3x5A 5 VA 192T 3450
3 x 600 A 3x5A 5 VA 192T 3460
(1) Secondary 1 A: on request.

Dimensions
TCB3 18-20 TCB3 22-30

35 35 45 45

k I k I k I
Ø 18 k I k I k I Ø 22

75
65

10
5
trafo_111_a_1_x_cat

trafo_112_a_1_x_cat

L1 K–P1 L2 L3
L1 K–P1 L2 L3

20 30
115 150

Three-phase bar or cable-through CT TCB3 18-20 TCB3 22-30


Ø cable (mm) 18 22
Bar-through 20 x 5 30 x 10
H x W x D (mm) 115 x 65 x 37 150 x 75 x 37
DIN-rail mounting no no

116 Catalogue 2017


Current transformers
Measurement devices
from 5 to 5000 A

References
TCA 13 — 3P
Class
Primary Secondary(1) 1 Reference
3 x 50 A 5A 1 VA 192T 1905
3 x 60 A 5A 1.25 VA 192T 1906
3 x 75 A 5A 1.5 VA 192T 1907
3 x 80 A 5A 1.5 VA 192T 1908
3 x 100 A 5A 2.5 VA 192T 1910
3 x 125 A 5A 2.5 VA 192T 1912
3 x 150 A 5A 2.5 VA 192T 1915
3 x 160 A 5A 2.5 VA 192T 1916
(1) Secondary 1 A: on request.

Dimensions
TCA 13 — 3P
54
44
L 7

K K/P2 I K K/P2 I K K/P2 I


45
64
90
trafo_009_a_1_x_cat

K/P1 K/P1 K/P1

(1) Cable-through aperture Ø 13.5 mm.


13.5
1

Number of modules Front degree of protection Terminal degree of protection L (mm) Mounting
6 IP65 IP20 105 35 mm DIN-rail

Catalogue 2017 117


Current transformers
Measurement devices
from 5 to 5000 A

Split-core CT
References

TO 23 TO 58 TO 812 TO 816
Class Class
Primary Secondary Class 1 Class 3 Reference 0.5 Class 1 Reference 0.5 Class 1 Reference Class 0.5 Reference
100 A 5A 1.25 VA 192T 4601
150 A 5A 1.5 VA 192T 4602
200 A 5A 2.5 VA 192T 4603
250 A 5A 1.5 VA 192T 4604 1.5 VA 192T 4625 1.5 VA 192T 4725
300 A 5A 3.75 VA 192T 4605 2.5 VA 192T 4630 2.5 VA 192T 4730
400 A 5A 5 VA 192T 4606 1 VA 192T 4640 2.5 VA 192T 4740
500 A 5A 2.5 VA 192T 4650 2.5 VA 192T 4750
600 A 5A 2.5 VA 192T 4660 2.5 VA 192T 4760
750 A 5A 2.5 VA 192T 4675 2.5 VA 192T 4775
800 A 5A 2.5 VA 192T 4680 2.5 VA 192T 4780
1000 A 5A 5 VA 192T 4610 5 VA 192T 4710 10 VA 192T 4810
1250 A 5A 7.5 VA 192T 4712 10 VA 192T 4812
1500 A 5A 7.5 VA 192T 4715 10 VA 192T 4815
1600 A 5A 10 VA 192T 4814
2000 A 5A 10 VA 192T 4820
2500 A 5A 10 VA 192T 4825
3000 A 5A 15 VA 192T 4830
4000 A 5A 15 VA 192T 4840
5000 A 5A 15 VA 192T 4850

Dimensions
B C Dimensions (mm)
D
Type A (mm) B (mm) C (mm) D (mm) E (mm)
TO 23 106 93 58 23 33
TO 58 158 125 58 55 85
TO 812 198 155 58 85 125
trafo_078_e_1_x_cat

TO 816 243 195 79 85 165


E
A

Fixed by M5 screw

Split-core CT TO 23 TO 58 TO 812 TO 816


H x W x D (mm) 106 x 93 x 58 158 x 125 x 58 198 x 155 x 58 243 x 195 x 75

118 Catalogue 2017


Current transformers
Measurement devices
from 5 to 5000 A

Summation CT
Reference
BSA 02 BSA 03 BSA 04
Primary Secondary Reference Reference Reference
5 + 5/5 A 5A 192T 0802
5A + 5+ 5/5 5A 192T 0803
5 + 5 + 5 + 5/5 A 5A 192T 0904

Dimensions
BSA 02 and BSA 03 BSA 04
57 65

136.5
90

29.5

54
trafo_073_b_1_x_cat

trafo_069_b_1_x_cat
50 55 95 60
80 122
127 156

Summation CT BSA 02 BSA 03 BSA 04


H x W x D (mm) 90 x 127 x 57 90 x 127 x 57 136.5 x 156 x 65
DIN-rail mounting no no no

Catalogue 2017 119


Measurement shunts
Measurement devices

Composition of the range


shunt_005_a_1_cat
transformers

> 20 ratings available from 1 to


6000 A, with 100 mV output
> Other ratings and secondary
Current

voltages are available. Please


contact us

shunt_008_a_1_cat
shunt_007_b_1_cat

shunt_006_b_1_cat

Function Characteristics
SOCOMEC shunts provide indirect • Voltage drop: 100 mV
measurement of direct current by creating a for nominal rating.
standardised voltage drop. • Accuracy class: 0,5.
• Permanent overload: 1.2 In.
• 10 In / 5s rating ≤ 500 A
5 In / 5s rating 600 to 1500 A
2 In / 5s rating ≥ 2500 A.

References
DIN series
Rating (A)(1) Secondary voltage drop Reference
1A 100 mV 192S 2101
4A 100 mV 192S 2104
6A 100 mV 192S 2106
10 A 100 mV 192S 2110
15 A 100 mV 192S 2112
25 A 100 mV 192S 2114
40 A 100 mV 192S 2116
60 A 100 mV 192S 2118
100 A 100 mV 192S 2120
150 A 100 mV 192S 2125
200 A 100 mV 192S 2220
250 A 100 mV 192S 2235
300 A 100 mV 192S 2230
400 A 100 mV 192S 2240
600 A 100 mV 192S 2250
1000 A 100 mV 192S 2255
1500 A 100 mV 192S 2260
2500 A 100 mV 192S 2165
4000 A 100 mV 192S 2170
6000 A 100 mV 192S 2175
(1) Other rating: please consult us.

120 Catalogue 2017


Measurement shunts
Measurement devices

Dimensions

DIN Series 1 to 25 A
Fig. 1
B Rating (A)(1) Figure A B C D E F G H I
1 1 90 28 20 8 78
11 F

4 1 90 28 20 8 78
6 1 90 28 20 8 78
10 1 90 28 20 8 78
15 1 90 28 20 8 78
25 1 90 28 20 8 78
shunt_011_a_1_x_cat

135
40 2 123 33 20 8 103
115 60 2 123 33 20 8 103
A 100 2 123 33 20 8 103
H 150 2 123 33 20 8 103
200 2 168 55 30 15 10 10 128 30
250 2 168 55 30 15 10 10 128 30
300 2 168 55 40 20 10 10 128 30
400 2 168 55 40 20 10 10 128 30
30
C
9

600 2 168 55 40 20 10 10 128 30


1000 2 188 65 60 30 10 10 138 30
1500 3 188 65 90 21 48 10 10 138 30
2500 3 188 65 120 30 60 10 10 138 30
4000 3 188 65 120 30 60 15 10 138 60
6000 3 188 65 180 30 60 15 10 138 60
(1) Connection: 2 M5 screws x 8 and 2 washers Ø 5.3 mm.

DIN Series 40 to 1000 A DIN Series 1500 to 6000 A


Fig. 2 Fig. 3
G B
G B
I
I

F
F

shunt_010_a_1_x_cat
shunt_009_a_1_x_cat

C
E
C
D

H
A H
A

Catalogue 2017 121


Other products
Measurement devices

PTI: CT automatic short-circuiter Conformity to standards


transformers

> NF C 15-100 articles


Use 473.1.4-556.3
This device provides automatic short-circuiting > GAM EG 13.C
Current

of the CT: if the measuring circuit is opened. (military standard)


pti_005_a_2_cat

Other regulations

> Decree n° 88-1056


from 14-11-88: protection
References of workers
> Complies with the Mines and
Operating Max. differential
Rating (A) Trigger voltages frequency voltage Reference Quarries decree n° 91-986
5A 21 VAC 45 … 400 Hz 600 VAC 4990 0521
5A 25 VAC 45 … 400 Hz 600 VAC 4990 0525(1)
(1) DCN approved (French State Naval Construction Company).

Characteristics Dimensions
H1 L
Case degree of protection IP55
H F
Terminal protection degree IP20
Connection cross-section 2.5 mm2
Weight 82 g
pti_003_a_1_x_cat

Rating (A) D1 E F H H1 I L
5 4.2 47 9.6 32 44 41 34.7
E

øD1

Sensor PT100 - screw type


• Element sensitivity as per standard IEC 751 • Tolerance class A:
class A. - Accuracy at -50 °C: ± 0.14 °C,
• 4 wire mounting. - Accuracy at 0 °C: ± 0.13 °C,
• 3 meter length output of Teflon isolated cable. - Accuracy at +50 °C: ± 0.25 °C,
- Accuracy at +100 °C: ± 0.26 °C,
- Accuracy at +150 °C: ± 0.33 °C.

References
Products Reference
Temperature sensor PT100 - M6 screw type 4825 0208
Temperature sensor PT100 - eyelet type 4825 0209

Dimensions
trans_117_a_1_x_cat

20 5 3000

Ø 6,5
30 10 3000

122 Catalogue 2017


Other products
Measurement devices

Transformer with integrated converter (CTA-VA)


References
Compact measurement converter with 0-20 mA / 0-20 mA / 0-20 mA / 4-20 mA / 4-20 mA /
cable-through transformer (Ø 27 mm) 0-10 VDC 0-10 VDC 0-10 VDC 0-10 VDC 0-10 VDC
or bar transformer (40 x 10 mm). Self supplied 230 VAC 24 VDC 230 VAC 24 VDC
Primary Reference Reference Reference Reference Reference
• Input:
trafo_057_a_1_cat

1A 192Y 0401 192Y 0501 192Y 0801 192Y 0601 on request


- Direct Connection 0 to 10 A, 5A 192Y 0402 192Y 0502 192Y 0802 192Y 0602 192Y 0902
- CT primary of 40 to 800 A (self-supplied) 10 A 192Y 0503 192Y 0803 192Y 0603 on request
- CT primary of 15 to 800 A (auxiliary supply) 15 A 192Y 0504 192Y 0804 192Y 0604 192Y 0904
20 A 192Y 0505 on request 192Y 0605 192Y 0905
• Output: 25 A on request on request 192Y 0606 192Y 0906
30 A 192Y 0507 192Y 0807 192Y 0607 192Y 0907
- 0-20 mA, 0-10 V (type CTA-VA) 40 A 192Y 0408 192Y 0508 on request 192Y 0608 192Y 0908
- 4-20 mA and 0-10 V (type CTA-VA4). 50 A 192Y 0409 192Y 0509 192Y 0809 192Y 0609 192Y 0909
• Self-supplied or auxiliary power supply 24 VDC or 230 VAC. 60 A 192Y 0410 192Y 0510 on request 192Y 0610 192Y 0910
• Dimension: 135 x 80 x 50 mm. 75 A 192Y 0411 192Y 0511 192Y 0811 192Y 0611 192Y 0911
100 A 192Y 0412 192Y 0512 192Y 0812 192Y 0612 192Y 0912
150 A 192Y 0415 on request 192Y 0815 192Y 0615 on request
IA - + 230 V~ / 24 V 200 A 192Y 0420 192Y 0520 on request 192Y 0620 on request
0/4-20 mA + - UH
250 A 192Y 0425 192Y 0525 192Y 0825 192Y 0625 192Y 0925
UA - K
L IE < 10 A 192Y 0430 192Y 0530 192Y 0830 192Y 0630 192Y 0930
0-10 V + 300 A
400 A 192Y 0440 192Y 0540 192Y 0840 192Y 0640 192Y 0940
trafo_058_b_1_x_cat

500 A 192Y 0450 192Y 0550 192Y 0850 192Y 0650 on request
600 A 192Y 0460 192Y 0560 on request on request 192Y 0960
750 A 192Y 0475 on request 192Y 0875 192Y 0675 192Y 0975
800 A 192Y 0480 192Y 0580 192Y 0880 192Y 0680 192Y 0980

Voltage transformer BTV 25

Applications Recommendation
trafo_062_a_1_cat

Measurement and conversion of the input Voltage transformers are used specifically for supplying measurement
value read at the primary of a transformer in a equipment, therefore it is not recommended to connect other components
directly proportional voltage signal. which could affect accuracy. This is due to the effect of the phase shift error. If
BTV 25 products are voltage transformers. the consumption is greater than 25 VA, another transformer must be added.

Characteristics References
Primary Secondary Power Reference
Accuracy class 1% 230 VAC 100 VAC 25 VA 192M 2020
Dielectric quality 3 kV for 1 min. 400 VAC 100 VAC 25 VA 192M 2030
Operating frequency 50 - 60 Hz 440 VAC 100 VAC 25 VA 192M 2044
Permanent overload 1.2 Un 500 VAC 100 VAC 25 VA 192M 2050
600 VAC 100 VAC 25 VA 192M 2060
660 VAC 100 VAC 25 VA 192M 2066
Connection 800 VAC 100 VAC 25 VA Please consult us

Dimensions
Secondary a b 103
trafo_072_a_1_gb_cat

70 112
trafo_070_a_1_x_cat

97
Primary A B
R
R 3.25
100

104
56

83

N(S)
70
96

A and B : primary connection a and b : secondary connection

Catalogue 2017 123


Other electrical measurement devices
Measurement devices
Indicators &
transducers

Transducers

They provide conversion of an AC electrical value (A, V, Hz, Cos phi, W, Var)
into a DC signal, with standardised current or voltage.
They are available in surface-mount casings (CS range).
trans_071_a_2_cat

These devices are designed for DIN rail or back plate mounting.
Type CS transducers are available in two sizes:
• 75 mm for current, voltage and frequency converters,
• 150 mm for power or three-phase converters.
Consult us.

Modular transducers

Available in:
• 3-DIN module housings (52.5 mm) for current,
voltage and frequency converters,
trans_076_a_2_cat

• 6-DIN module housings (105 mm) for current (output 4-20 mA),
voltage (output 4-20 mA) converters,
• 9-DIN module housings (157.5 mm) for power or three-phase converters.
Consult us.

Analogue meters

SOCOMEC ferromagnetic ammeters and voltmeters measure the AC


current/voltage of any electrical circuit. SOCOMEC vibrating reed or needle
phase_002_b_3_cat

type frequency meters have a converter either integrated or in a separate


freq_002_a_1_cat

casing and measure the frequency of any electrical circuit.


freq_003_a_3_cat

The wattmeters, varmeters and phase-meters consist of an analogue meter


and a separate converter. They are available in 3 types of casing: Rotex
round barrel model in 72 or 96, in a DIN 48 to 144 body or a modular casing
(3 modules).
amper_033_a_2_cat
amper_027_a_1_cat

With pointer deflections of 90° and 240°, they can be flush-mounted into
cubicles, enclosures or other equipment.
Consult us.

124 Catalogue 2017


Other electrical measurement devices
Measurement devices

Selector switches

Voltmeter and ammeter switches that allow phase selection on a three-phase


circuit for voltage and current measurement.
They are available in three different casings:
comut_015_b_1_cat

• for screw mounting,


• with a central Ø 22 mm mounting,
• for DIN rail mounting.
Consult us.

Digital meters

They measure all types of electrical values (A, V, Hz, Cos phi, P, Q...).
The range:
amper_032_a_2_cat
cosph_001_a_2_cat

• 2 different types of casing: rectangular or square:


- 2 sizes of rectangular casing,
- 2 sizes of square casing.
• direct measurement or connection to a current or voltage transformer,
• 2000-point (3.5 digits) or 20000-point (4.5 digits) display,
freq_004_a_2_cat

voltm_019_a_2_cat

• possibility of having 2 or 3 different types of measurement in the same square


casing (AAA-VVV-AVF...),
• multi-indicator version,
• RMS-value.
Consult us.

Hour counters

Often combined with analogue meters in an electrical panel, hour counters count
compt_001_a_2_cat

the total operating time of machines or electrical equipment.


Consult us.

Catalogue 2017 125


DIRIS G
Wireless and cabled RS485 to Ethernet communication gateways

The solution for


Communication

> Industry
> Building
interfaces

> Infrastructure
> Local authority
diris-g_004_a_1_cat

DIRIS G-30 diris-g_006_a_1_cat DIRIS G-40


Configuration
RS485 / Ethernet RS485 - wireless / Ethernet
with EasyConfig,
see page 140.

Strong points
Function > WEBVIEW embedded
With communication gateways DIRIS G The gateway has an embedded WEBVIEW web server
all the information from meters and power web server, allowing real time monitoring of > Scalable
monitors, communicating by radio frequency electrical values and analysis of consumption > Plug & Play
or RS485, is centralized and made available data. The user can be alerted of any alarms
on the Ethernet Modbus (TCP). via email.
DIRIS G gateways can retrieve data from Compliance with standards
meters or Socomec remote measuring points
via Ethernet. > IEC 61010

> ISO 14025


Advantages
WEBVIEW(1) embedded web server Plug & Play
DIRIS G gateways include an embedded web • Connected metering and measurement
> UL
server. Two versions are available: devices are automatically addressed and
• Power Monitoring: detected by the DIRIS G gateway. These
- Realtime measurements and alerts. integrate the following:
• Power & Energy Monitoring: - Automatic time synchronisation (SNTP)
with battery recording
- Realtime measurements and alerts.
- Synchronisation of connected devices
- Trends for selected parameters and
energy consumption history and analysis. - Warning messages in the event of an alert
(e-mail SMTP)
Scalable
- Automatic recording and storage of
Several optional modules are available:
measurements and consumption data
• Digital inputs/outputs.
- Automatic tariff changes (multi-tariff).
• Analogue inputs/outputs.
• Data exported automatically via FTP server.
• Temperature inputs.
(1) See page 137.

Selection guide
Gateway DIRIS G-30 DIRIS G-40 DIRIS G-50 DIRIS G-60
RS485 Modbus • • • •
Radio frequency
Communication • •
Communication (wireless)
Ethernet • • • •
WEBVIEW embedded Power Monitoring • • • •
web server. Power & Energy Monitoring • •

126 Catalogue 2017


DIRIS G
Wireless and cabled RS485 to Ethernet communication gateways

Architecture
Example of communication architecture with DIRIS G gateway and WEBVIEW embedded WEB server

MEASURE CENTRALISE ANALYSE

DIRIS B-30 RF DIRIS B-30 RF

WEBVIEW
diris-g_019_a_1_fr_cat

CO
UN
TIS
E Ci3

RS485 Ethernet HYPERVIEW


DIRIS Digiware DIRIS A COUNTIS E DIRIS B-30 RS DIRIS G-40 or G-60

Embedded web server


WEBVIEW(1) embedded web server
• Version Power Monitoring:
embedded in DIRIS G-30 and G-40
• Version Power & Energy Monitoring:
embedded in DIRIS G-50 and G-60
• 32 devices max (RS485 and wireless indifferently)
soft_027_a_1_fr_cat

(1) For further details see page 137.

DIRIS O optional modules


a maximum of 4 optional modules can be connected to a DIRIS G
gateway in order to integrate controls/ commands.

DIRIS O-iod 2 digital inputs / 2 digital outputs


DIRIS O-ioa 2 analogue inputs / 2 analogue outputs
diris-b_031_a

diris-b_029_a

DIRIS O-it 3 temperature inputs


DIRIS O-m Additional slave RS485 communication
For more information see "DIRIS O optional modules" page 39. Optional module DIRIS B-30

Accessories

Remote radio antenna USB configuration cable


• Allows the antenna to be mounted outside the • Configuration of DIRIS G gateways can be
enclosure to increase the transmission distance achieved using EASY CONFIG software via
up to 300 m if there are no obstacles. Ethernet or direct USB connection.

Catalogue 2017 127


DIRIS G
Wireless and cabled RS485 to Ethernet communication gateways

DIRIS G terminals

Battery (supplied)

Power supply

DIRIS O Micro
optional module USB
diris-g_020_b_1_gb_cat

RS485 Ethernet

1 digital
input

Power supply Input powered by the product Input with external power supply RS485

Master
110-230 VAC NC NC NC
RS485

RS485

RS485
diris-g_015_a_1_x_cat

diris-g_016_a_1_x_cat

diris-g_017_a_1_x_cat

diris-g_018_a_1_x_cat
10 - 30 VDC
12 VDC

LIYCY-CY
L
IN

IN

NC: not connected

Terminals of DIRIS O optional modules


Optional modules are common to the DIRIS B-30 monitoring device.
For a description of the terminals see page 40.

Dimensions (mm)
DIRIS G-30 / G-40 / G-50 / G-60 DIRIS O optional modules
120

90
diris-o_001_b_1_x_cat
45
diris-g_001_b_1_x_cat

100
90

44 15
15

A 65

62 44 15 36 DIRIS O optional modules A


65 DIRIS O-iod - DIRIS O-ioa - DIRIS O-it - DIRIS O-m 45 mm

128 Catalogue 2017


DIRIS G
Wireless and cabled RS485 to Ethernet communication gateways

Specifications

Mechanical specifications Ethernet


Link Ethernet 10/100 base-T, 2 RJ45 bases with integrated switch
Casing type DIN-rail mounting module and base
Modbus TCP (port 502), Modbus RTU over TCP (port 503),
Case degree of protection IP20 / IK06 Protocol
HTTP, SMTP, SNTP, DHCP, FTP (G-50/G-60)
Front degree of protection IP40 on the nose in modular assembly / IK08
Clock Internal
DIRIS G-30, G-50 = 190 g
Weight Gateway time updating from an NTP server.
DIRIS G-40, G-60 = 215 g SNTP protocol
Connected PMDs time updating.
Electrical characteristics SMTP protocol Sending of alarm emails from the gateway
Power supply Configuration of the gateway, connected PMDs and meters
Function
Alternative voltage 110-230 VAC ±15% (Ph/N or Ph/Ph) Cat III Access to the WEBVIEW web server, data centralisation
Frequency 50/60 Hz USB
Power consumption 6 VA Connection type USB 2 (required installation of Easy Config)
Battery CR 1220 3 V lithium button cell battery Protocol Modbus RTU on USB
Input Function Configuration of the gateway, connected PMDs and meters
Number 1 Connection Type B micro USB connector
Type / Power Optocoupler internal polarisation (12 VDC ±10%) Memory characteristics
supply or external (10-30 VDC ±10%)
Consumption history
Input function Logic status, pulse meter or synchronisation pulse status 1 year (1 hour period)
(memory extension for meters and measurement units)
Communication specifications Electrical values 2 months (10 min period)
DIRIS G Alarms 1000
Number of events
Network quality according to EN 50160: 1000
Link RS485
Connection type 2 … 3 half duplex wires  Environmental specifications
Protocol Modbus RTU Ambient operating temperature -10 … +70°C
Baudrate 2400 … 115200 bauds Storage temperature -25 … +85°C
Function Communication with PMDs and meters Operating humidity 55°C / 97% HR
DIRIS G-40 and DIRIS G-60
Link Radio-frequency (RF)
Frequency range 868 MHz (low frequency: 868.1 MHz and high: 869.5875 MHz)
Baudrate 38400 bauds
Function Communication with DIRIS B-30 RF
Scope 300 m (open field)

References
DIRIS G gateways Reference
DIRIS G-30 RS485 / Ethernet - WEBVIEW Power Monitoring 4829 0300
DIRIS G-40 RS485-RF / Ethernet - WEBVIEW Power Monitoring 4829 0301
DIRIS G-50 RS485 / Ethernet - WEBVIEW Power & Energy Monitoring 4829 0302
DIRIS G-60 RS485-RF / Ethernet - WEBVIEW Power & Energy Monitoring 4829 0303
DIRIS O optional modules Reference
DIRIS O-iod 2 digital inputs / 2 digital outputs 4829 0030
DIRIS O-ioa 2x 4-20 mA analogue inputs / 2x 4-20 mA analogue outputs 4829 0031
DIRIS O-it 3 temperature inputs, PT100/PT1000 4829 0032
DIRIS O-m RS485 modbus slave communication 4829 0033
To be ordered
Accessories in multiples of Reference
Wireless remote antenna, 868 MHz - 210 mm height 4854 0126
Cable for remote antenna - SMA connector - 3 meter length 4854 0127
USB configuration cable 4829 0050
Fuse circuit breakers to protect the auxiliary power supply (type RM) 1 pole + neutral 6 5601 0017
gG 10x38 0.5 A fuses 10 6012 0000

Catalogue 2017 129


Datalogger

The solution for


Communication

new >
>
Industry
Building
interfaces

> Infrastructure

datal_017_a
> Local authority

DATALOG H80
datal_003_a

DATALOG H60

Strong points
Function
DATALOG H60 and H80 dataloggers associated with Socomec wireless interfaces enable you > Easy to install
to create a smart energy data communication network in order to: > Reliable collection and
• Remotely and automatically read multi-fluid energy meters and multi-function meters, isolated transmission
or not. > Advanced functions
• Pool, secure, store and provide the data to a computer application.
• Connect your meters and multi-function measurement units in a 2G/3G/GPRS network.
Expert Services
> Study, definition, advice,
Advantages commissioning, maintenance
and training... Our experts
Easy to install Advanced functions “Expert Services” offer
• Quick installation on DIN rail or door mounting. • Extended data storage capacity (1 year for complete support for the
• Compact. index data and 2 months for load curves). success of your project.
• Remote configuration. • Auto-detects meters and measuring
• Configuration services (SOCOMEC services). equipment.
Reliable collection and transmission • Sends regular activity reports.
• Configurable collection frequency for each • Event alerts (communication errors, data
energy and multi-function meter. quality, remote server connection).
• Secure, regular transmission
(daily, weekly, etc.).
• Multiple communication protocols (Modbus
RTU/TCP, Wireless M-Bus, HTTP(s), FTP(s)).
• Collection interfaces: Ethernet - RS232/485
or Wireless.
• Transmission interface: Ethernet or
2G/3G/GPRS.

130 Catalogue 2017


Datalogger

The SOCOMEC communicating energy-efficiency solution

MEASURE CENTRALISE ANALYSE

DATALOGGER

Pulse N’VIEW
Hosted on Cloud
DIRIS B-30 RF DIRIS G-40

Ethernet

2G/3G
DIRIS B-30 RF

CO
RS485 Lan/Wan
UN
TIS
E Ci3

COUNTIS E

RS485 Ethernet

DIRIS B-30 RS
DIRIS G-30

HYPERVIEW
Hosted on
RS485 local server

DIRIS A

WEBVIEW
verte_122_c_gb

Embedded
in the DIRIS G gateway

DIRIS Digiware

Specifications
DATALOG H60 DATALOG H80
Input/output interfaces
Input 3 digital or pulse inputs
Output 1 digital output (relay)
Serial interfaces
Input 1 port (Modbus)
Output 1 port (Modbus or M-Bus)
Wireless interface
Wireless M-Bus 868.3 - 868.95 MHz
Network interface
Ethernet 1 10/100 Mb port 2 10/100/1000 Mb port
GSM/GPRS 850/900/1800/1900 MHz 850/900/1800/1900 MHz
3G 900/2100 MHz 900/2100 MHz
Protocols
Data collection Modbus RTU and TCP/Wireless Mbus Ethernet/Modbus TCP:
Data transmission FTP FTP(s)/ HTTP(s)
Configuration
Local Yes Yes
Distant by text message by FTP

References
Datalogger Reference
DATALOG H60 (power supply included) 4854 0001
DATALOG H80 (without 3G connection) 4854 0010
DATALOG H81 (with 3G connection) 4854 0011
DATALOG H60 accessory description Reference
5 m remote antenna extension 4854 0105
10 m remote antenna extension 4854 0110
20 m remote antenna extension 4854 0120

Catalogue 2017 131


Wireless communication interfaces

The solution for


Communication

> Industry
> Building
interfaces

> Infrastructure
> Local authority
datal 004 a

datal 005a
Wireless M-Bus Modem ARF868 Modem

Function
Wireless M-Bus Modem ARF868 wireless modem
Wireless M-Bus AMR (Automatic ARF868 wireless modems convert data from
Meter Reading) plug-and-play modems a serial link into a wireless frame to send to Strong points
automatically collect energy data from water a similar device in the frequency range 863-
and gas meters. They autonomously read 870 MHz. The power and sensitivity allow the Wireless M-Bus Modem
data (index) from water and gas meters. data to be transmitted over distances of up > Battery life
100% compatible with the Wireless M-Bus to 20 km. > Ease of installation
standard (EN13757-3 and EN13757-
> Long range
4), device open protocols ensure full
interoperability with other Wireless M-Bus > 2 pulse inputs
products on the market. > Transmitter
> Repeater
> Receiver
ARF868 wireless modem
Advantages > Sensitivity, transmission/
reception quality
Wireless M-Bus Modem ARF868 wireless modem
Battery life Sensitivity, transmission/reception quality > Ease of installation
• Runs on battery for up to 12 years. • Power 25 mW or 500 mW at 868 MHz. > Long range
Ease of installation • Licence-free frequencies on European > Several types of
• Factory pre-programmed. bands (863 - 870 MHz) or frequencies communication
• Quick installation. subject to license (410 - 470 MHz).
• Robust IP65. Ease of installation
• Quick installation. Expert Services
Long range
• Up to 1 km. Range can be increased by • User-friendly and configuration with intuitive > Study, definition, advice,
installing repeaters. software. implementation, maintenance
2 pulse inputs • The product can be configured as a and training... Our experts
transmitter, receiver or repeater. “Expert Services” offer
• A single transmitter can handle two meters.
• Compatible with all water and gas meters.
Long range complete support for the
• 1 to 20 km. success of your project.
Transmitter
Several types of communication
• Wireless transmission of metering data
(consumption) every 10 minutes • RS485, RS232 or USB serial port.
(10s or 12hrs optional).
Repeater
• Wireless M-Bus wireless relay of metering
data (consumption).
• Multiple repeaters can be used to extend
the range.
Receiver
• Wireless M-Bus metering data
(consumption) wireless receiver.
• RS485, RS232 or USB serial port.
• Remote antenna.

132 Catalogue 2017


Wireless communication interfaces

Accessories
• 1-, 3- and 5-metre remote antenna. • TNC converter pack.
• Antenna mount & adaptor. • Sub D9 connector.
• Power supply unit + connector (required). • IP53 and IP67 ingress protection rating.

Specifications
Modem ARF868
(transmitter/repeater/ Wireless M-Bus transmitter Wireless M-Bus transmitter Wireless M-Bus repeater Wireless M-Bus
receiver model) modem: Water/Gas modem: Temperature modem receiver modem
Up to 1/4/7/20 km
Scope Up to 1000 m Up to 1000 m Up to 1000 m
according to model
Wireless frequencies 863-870 MHz 863-870 MHz 863-870 MHz 863-870 MHz 863-870 MHz

Interfaces
2 temperature inputs:
Inputs - 2 pulse inputs - 1 pre-equipped input - -
- 1 free input
RS232 - RS485 - USB
Communication - - - RS232 - RS485 - USB
optional
Leak detection - Fraud
Alerts - - - -
detection - Battery spent
Index bufferisation
Storage capability - - - -
(consumption history)
Sappel Izar, Itron Cyble,
Compatibility - - - -
Itron Gallus 2000, Elster BK

General characteristics
Dimensions W x H x D 135 x 75 x 35 mm 210 x 103.1 x 37.2 mm 210 x 103.1 x 37.2 mm 210 x 103.1 x 37.2 mm 210 x 103.1 x 37.2 mm
Operating temperature -30 … +70°C -40 … +85°C -40 … +85°C -40 … +85°C -40 … +85°C
3.6 V. Power supply block
3.6V Li-SOCl2 battery. Battery 3.6V Li-SOCl2 battery. Battery
Power supply 4.5 … 36 V supplied, model with battery 4.5 … 36 VDC
life up to 12 years guaranteed life up to 12 years guaranteed
optional
Protection degree IP53, IP67 (optional) IP65 IP53 IP65 IP65
Standards EN300-220 V2010 / EN301-489 / EN 60950

References
Wireless M-Bus modem
Reference
Wireless M-Bus Modem - Water 4854 0054
Wireless M-Bus Modem - Gas 4854 0055
Wireless M-Bus Modem - Temperature 4854 0056
Wireless M-Bus receiver modem – RS232 4854 0057
Wireless M-Bus receiver modem – RS485 4854 0058
Wireless M-Bus receiver modem – USB 4854 0059
Wireless M-Bus repeater modem 4854 0060
ARF868 wireless modem
Reference
Modbus wireless modem, distance 20 km 4854 0050
Modbus wireless modem, distance 7 km 4854 0051
Modbus wireless modem, distance 4 km 4854 0052
Modbus wireless modem, distance 1 km 4854 0053
List of accessories for ARF868 wireless modem Reference
Power supply (mandatory) 4854 0202
RS232/USB cable (mandatory to configure ARF868 wireless modems) 4854 0400
RS485 connector (mandatory for use with RS485) 4700 9993
0.5 dB remote antenna + 1 m extension 4854 0121
0.1 dB remote antenna + 3 m extension 4854 0122
1.5 dB remote antenna + 5 m extension 4854 0123
Wall bracket for remote antenna 4854 0124
IP53 protection 4854 0300
IP67 protection 4854 0301

Catalogue 2017 133


Communication accessories

Connecting the RS485 link


Communication

USB / RS485 interface


interfaces

< 1200 m
Function < 31 devices(1)
Laptop
RS485
If the PC is not equipped USB
inter_002_a_2_cat

with a serial port, this


interface can be connected
via a USB port to obtain an

inter_142_g_1_gb_cat
RS485 communication port.
CO
UN
TIS
E Ci3

Recommended for local Casing


use and not for permanent USB / RS485 COUNTIS ECi DIRIS A20 DIRIS A40

installation.
(1) Beyond these characteristics, use an " RS422 / RS485 repeater".

References
Description of accessories Reference
External USB / RS485 interface unit 4899 0110

Modbus/Profinet communication gateway


Function
The PROFINET communication Configuration
gateway enables SOCOMEC
communicating products in TCP
X1 modbus to be connected to a
Ethernet Ethernet
RU

PROFINET network. RS485


MMC

STON
RE P
S X1
RUN

MMC
STOP
RES

DIAG

APL SYS
DIA
G
Modbus Modbus
LINK
L/A

Profinet
Advantages
ACT X2
APL SYS

Rx/Tx

IN
LINK
L/A

CH0
ACT
Rx/Tx

RTU

OUT
LINK

TCP

CH1
X3
ACT

DIRIS B-30
DIRIS G Logic
inter_150_b

LIN

Implementation, maintenance and RS485


L/AK

AC
Rx T
/Tx
X2
controllers
diagnostic with a unique configuration
LIN
L/AK

Modbus
IN
CH0

AC

software (Sycon.net), which is downloadable


Rx T
/Tx
LIN
OUT

RTU
K
CH1

from SOCOMEC website. DIRIS A


X3

inter_151_b_gb
AC
T

• Several communication ports.


• IP20 DIN-rail mounting.
• Slot for MMC memory card. DIRIS Digiware
• Configuration via USB port using a PC.
• Operation signalling Leds.
8 MB SDRAM
• Modbus data conversion up to 512 bytes
data with Profinet Memory 4 MB serial Flash
(Modbus slave). MMC card (optional) 2 GByte max
Voltage 24 V ± 6 V DC - reverse pole protected
24 V current (typical) 130 mA
Power supply
3.2 W power consumption
Mini-COMBICON, 2-pin connector
Configuration interface USB
Operating temperature 0 … + 60 °C
Dimensions W x H x D 100 x 70 x 52 mm (without connector)
Description of accessories Reference
Profinet / Modbus-TCP interface 4899 0301

134 Catalogue 2017


Communication accessories

RS422 / RS485 repeater


Function < 1200 m
< 31 devices

In some applications the maximum distance PC


RS232 RS485
and/or the maximum number of devices can RS485 CO
UN
TIS
E Ci3

PWR RDA
RDB BLA
BLB T+ T- R+ R- be exceeded. One solution to this technical
LINE-B
restriction is to install an interface which DIRIS A40 COUNTIS ECi
RS232 / RS485
amplifies the signal over a further 1200 m (at
PWR RDA PWR RDA
RDB BLA RDB BLA
BLB T+ BLB T+

OR
T- R+ T- R+
R- R-

LINE-B LINE-B

RS422/RS48
REPEATER 5
programmable Interface RS422/RS485
REPEATER
CO
UN
TIS
RS422/RS485
REPEATER

9600 bauds) for 31 devices.


E Ci3

logic controllers R-
LINE-A

R+ T- T+
POWER

N
L
R-
LINE-A

R+ T- T+
POWER

N
L

In addition, it allows you to introduce a new


inter_011_a

RS485 DIRIS A40 COUNTIS ECi RS485


branch to the network, thereby making it OR
LINE-A
others
POWE
R
possible to reduce the length of connection

1200 m

1200 m
systems
R-
R+ T- T+

cable required by avoiding back and forth


N
L

inter_143_h_1_gb_cat
DIRIS A40 DIRIS A40
cabling.
References
CO
UN

COUNTIS ECi COUNTIS ECi


TIS CO
E Ci3 UN
TIS
E Ci3

Auxiliary power supply Us Frequency Reference


95 … 240 VAC / 110 … 250 VDC 50 Hz 4899 0120

Other solutions and services

DIRIS
A40 The accessories listed in these pages represent a selection from our range.
C
COUNTIS
We can supply many other solutions upon request, such as SHDSL interfaces,
C
COUNTIS
fibre optics/RS485, GSM/GPRS and protocol converter interfaces.
DIRIS E00
A40 E40

DIRIS
A10
M

DIRIS
A20

C
COUNTIS Need something integrating into your network?
mesur_112_d_1_gb_cat

OUNTIS E30 Gateway


ECi
C
CO
UNT
TIS
TIS
TCP/IP RS485
No problem for our Expert Services team. They will fully integrate all your
SOCOMEC devices, audit your system, commission selected equipment and train
C
COUNTIS
E 50

E50 PLC

Gateway
your staff on its use.
For further information, please contact your nearest SOCOMEC branch.
TCP/IP RS485
B TM
M
C

S
/

Catalogue 2017 135


Selection guide
Energy monitoring and management software

What are the Where is the data For what size


Software suite

features? stored? of project?

WEBVIEW WEBVIEW HYPERVIEW N'VIEW


DIRIS G-30/G-40 DIRIS G-50/G-60

Functions Power monitoring Power & Energy Monitoring Energy management Energy management
Realtime Data log Data log
Data management Realtime
Data log Analysis Analysis
Embedded in the DIRIS G Embedded in the DIRIS G
Hosting Installed on local server Cloud hosting
gateway gateway
Size of installation Small to medium Small to medium Medium to large Medium to large

Architecture

MEASURE CENTRALISE ANALYSE

DATALOGGER

Pulse N’VIEW
Hosted on Cloud
DIRIS B-30 RF DIRIS G-40
Ethernet

2G/3G

DIRIS B-30 RF

CO
RS485 Lan/Wan
UN
TIS
E Ci3

COUNTIS E

RS485 Ethernet

DIRIS B-30 RS
DIRIS G-30

HYPERVIEW
Hosted on
RS485 local server

DIRIS A

WEBVIEW
verte_122_c_gb

Embedded
in the DIRIS G gateway

DIRIS Digiware

Expert Services

Require integration onto your network?


No problem for our "Expert Services" team. They will fully integrate all your SOCOMEC devices, audit your system, commission selected
equipment and train your staff on its use.
For further information, please contact your nearest SOCOMEC branch.

136 Catalogue 2017


WEBVIEW
Web server embedded in the DIRIS G communication gateway

The solution for


Software suite

> Industry
> Building
> Infrastructure
> Local authority

soft_027_a_1_fr_cat
Function
The WEBVIEW web server embedded in Pre-set alarms defined by the user can sent Strong points
DIRIS G gateways enables measurement by e-mail.
monitoring up to 32 devices and displays the > Plug & Play
User can access WEBVIEW via a web
energy consumptions by usage. browser on a PC or a tablet. > Easy to use
> Various functions
Advantages
Plug & Play Various functions
Automatic detection of connected devices WEBVIEW ensures real time monitoring of
facilitates the WEBVIEW configuration. In all electrical parameters measured thanks
order to achieve the consumption distribution, to summary pages showing graphs or
the user is assisted in the metering plan charts. Time-logged alarms are recorded
definition. and displayed by usage, type, nature and
criticality. The user receives alarm notification
Easy to use
by email.
WEBVIEW centralises all the devices
Energy consumption breakdown is displayed
measurements via a unique, clear and easy-
per utility (electricity, water, gas…) and usage
to-use interface.
(heating, lightning…).
It provides easy and rapid monitoring of the
devices by displaying the parameters and
events on summary pages.

Functions
2 versions available:
Power Monitoring Power & Energy Monitoring
Monitor Alarm View
• Automatic detection of connected devices. • Alarms for overloads, events and input status • Historical measurements and consumption (one
• Summary of the parameters measured on the changes. year of data).
electrical network and the loads. • Display of alarm history. • Distribution of consumption by usage and by
• Measurements of voltage, current, power, • Sorting by type, nature, criticality or state. utility (water, gas, electricity, etc.).
power factor, harmonic distortion rate (THD) and • Alarm displayed on the main page. • Export of consumption data in CSV format.
harmonics per rank. • Sending of alarm by email (SMTP).
• Display of average/instantaneous values with min/
max limits depending on the devices. Power & Energy Monitoring also includes the
• Total and partial energy consumption per load. "Monitoring" and "Alarm" functions.
• Input / output status.
• Synchronisation of device clocks.
• Graphical or table representation.

References
Type Reference
DIRIS G-30 RS485 / Ethernet - WEBVIEW Power Monitoring 4829 0300
DIRIS G-40 RS485-RF / Ethernet - WEBVIEW Power Monitoring 4829 0301
DIRIS G-50 RS485 / Ethernet - WEBVIEW Power & Energy Monitoring 4829 0302
DIRIS G-60 RS485-RF / Ethernet - WEBVIEW Power & Energy Monitoring 4829 0303

Catalogue 2017 137


HYPERVIEW
Energy management software

The solution for


Software suite

> Industry
> Building
> Infrastructure
> Local authority

soft_030_a_1_cat
Strong points
Function
HYPERVIEW software is for consolidating all A simple and user friendly web interface > Energy cost management
the data collected by measuring and metering enables access to various analysis and power > Rapid results
devices. consumption optimisation functions. > Advanced analysis functions
Based on open-ended technologies, it can be
easily integrated into the IT environment.

Advantages
Energy cost management Rapid results Advanced analysis functions
The HYPERVIEW software provides summary HYPERVIEW is an intuitive and user-friendly Management of SOCOMEC device load
on energy savings achieved following the tool. Data can always be accessed thanks to curves ensures a precise analysis of
implementation of energy efficiency actions. the web portal displaying analysis reports with consumption and enables the detection of
Data about energy contracts and bills are dashboards or graphs. maximums and overflows for active and
registered into the system in order to reduce The HYPERVIEW software allows users to reactive power.
the energy costs. Functions for optimising the subscribe to reports and receive them by Thanks to calculated measurement points,
subscribed power enable the identification regular email. consumptions that cannot be measured can
of overcosts, and thus the possibility adapt be deducted through calculations.
usage and/or the subscription. Customised consumption models
based on relevant indicators facilitate
the implementation of a performance
measurement and verification protocol.

Functions

Energy management
Monitor and analyse Follow up your results Communicate
• Measurement and consumption history. • Integration of external data (temperature, etc.). • Display of customised full screen dashboards in
• Alerts for overloads, events and input status • Definition of energy consumption models. key areas.
changes. • Estimation of the results of your energy • Subscribe to reports and receive them by regular
• Display and export the data collected. performance actions. email.
• Distribution of consumption by area, usage, utility • Identification of gains and losses by comparing • Presentation of the data in a concise manner
and period. consumption over a reference period. to communicate and report environmental
• Identification of energy saving opportunities. performance.
• Comparison of consumption between different
sites and periods.
• Calculation and view of energy costs.

References
Type Reference Options Reference
HYPERVIEW on Server + software license contact us Graph creation tool contact us
Electrical powers contact us
Measurements and verifications contact us

138 Catalogue 2017


N'VIEW
Online energy management service

The solution for


Software suite

> Industry
> Building
> Infrastructure
> Local authority

soft_043_a_1_fr_cat
Strong points
Function
The online service, N’VIEW, gives you To meet specific needs, the N'VIEW platform > Easy to use
an intuitive analysis of all your energy can extend its functional coverage by > Multi-user access
consumption. interfacing with existing or upcoming multiple > Various functions
Compatible with all leading commercial energy applications (energy apps).
gateways, including SOCOMEC dataloggers,
the N'VIEW platform manages multi-utility
data collection.

Advantages
Easy to use Multi-user access Various functions
Cloud-based hosting on a scalable and The N'VIEW service appeals to operational The N'VIEW service offers a wide range of
secure platform ensures the project is easily actors directly involved in energy features for monitoring measures, analysing
implemented, and offers great flexibility with performance, such as Energy Managers and energy consumption and managing costs.
an N'VIEW subscription. technical users (Facilities Managers). It also All these features are part of a continuous
Without the usual technical infrastructure provides services to help the management improvement plan for energy performance, as
problems, the user can concentrate on team define the energy strategy, and to help defined in standard ISO 50001.
managing their energy use. management controllers optimise and allocate
energy spending.

Functions
Energy management
Display Analyser Alert and communicate
• Display collected data. • Analysis and comparison of multi-fluid energy • Automatically generated or on-demand,
• Multiple viewing options (widgets) suitable for the consumption according to multiple criteria customizable reports.
type of data. (timeframe, site, fluid). • Programming multiple alerts (loss of data,
• Customisable dashboards. • Analyse energy costs. thresholds, overrun costs, excess consumption).
• Graphic presentation of the scope of analysis • Tariff simulation and comparison. • Manage and log alerts.
(hierarchy, plan of sites and buildings, industrial • Break down your energy bills depending on the
process diagram). provider.
• Set up indicators for measuring energy efficiency.
• Manage external influence factors (temperature,
surface, occupancy rate, production).
• Measure and verify according to the IPMVP
method.
• Manage and archive customizable queries.

References
Type Reference
N'VIEW Subscribe to the N'VIEW online service contact us

Catalogue 2017 139


COUNTIS and DIRIS
management software tools
Compatible with:
Software suite

Easy Config software Analysis software

Function COUNTIS E

To get the most effective use from your Socomec measurement and metering devices, we can
provide dedicated software tools:
Easy Config software Webserver function
The Easy Config software enables quick and The DIRIS A’s optional Ethernet modules integrate
easy remote device configuration for DIRIS HTML pages, enabling the Webserver function
Digiware, DIRIS B, DIRIS G, DIRIS BCMS 720, to be directly accessed through a standard web
COUNTIS E and DIRIS A devices. Configuration browser (Internet Explorer, Firefox....), eliminating
files can be copied from and sent to these devices, the need for software installation.
or they can be created without communication and The Webserver function enables: DIRIS A
sent at a later time. - monitoring of electrical values,
Multiple devices can be configured from a single - viewing of energy consumption,
file which is especially useful for OEMs and panel
- managing alarms,
builders, saving time when having to program
many devices with the same configuration. - configuration of the main parameters
of installation
Analysis software
- viewing and extracting load curves
On the basis of an event log and the displayed
(through a .CSV file).
curves, the Analysis software allows the analysis
and extraction of quality data, as well as fault
current monitoring (Residual Current Monitoring).
DIRIS Digiware
Principle diagram

COUNTIS E43 DIRIS A80

Software
Ethernet

RS485
Easy Config
DIRIS B30
verte_885_a_1_gb_cat

PC Software
Webserver

Software
Analysis
IEW
g
nfi

IEW
rve

RV
sis
Co

se

BV

PE

PLC
aly
sy

WE

HY
We

An
Ea

COUNTIS E with RS485 communication • •(1) • •


COUNTIS ECi • •(1) • •
DIRIS A10, A14, A17 and A20 with RS485 communication • •(1) • •
DIRIS A40 with RS485 communication • •(1) • •
DIRIS A40 with Ethernet communication module • • • •
DIRIS A60 and A80 with RS485 communication module • •(1) • • •
DIRIS A60 and A80 with Ethernet communication module • • • • •
DIRIS B • • •
DIRIS Digiware • • •
DIRIS G • • •
DIRIS BCMS 720 • • •
(1) through DIRIS A fitted with an Ethernet communication module with RS485 gateway.

140 Catalogue 2017


COUNTIS and DIRIS
management software tools

Easy Config software

diris_886_a_1_gb_cat
The Easy Config software enables quick and easy remote
configuration of DIRIS Digiware, DIRIS B, DIRIS G, DIRIS
BCMS 720, COUNTIS E and DIRIS A devices.

It offers the following functions:


• Creating the configuration of devices prior to their connection
(configuration template).
• Saving a configuration to a PC.
• Loading the configuration to devices through USB, RS485 or
Ethernet.
• Retrieving the configuration of a device through USB, RS485 or
Ethernet for saving, copying or modification purposes.

Configuration of loads
diris_883_a_1_gb_cat

Configuration of Quality events


diris_884_b_1_gb_cat

Catalogue 2017 141


COUNTIS and DIRIS
management software tools

Analysis software
Improvement to the reliability of your electrical installation can be achieved with this software through the analysis of displayed event curves
generated from the event log.

It offers the following functions:


• A list of voltage dips, cut-offs, overvoltages and overcurrents.
• A list of alarms I∆n and IPE for DIRIS A80.
• A display of 10 curves (3V, 3U, 3I, In) linked to the event with a zoom functionality.
• The classification of events according to the EN 50160 standard.
• Exporting of pictures or curve files.

This software can be connected to the DIRIS using either an RS485 MODBUS or Ethernet communication module.
The Analysis software can be downloaded from the SOCOMEC website: www.socomec.com

Event log
diris_837_a_1_gb_cat

Event display and analysis


diris_845_b_1_gb_cat

142 Catalogue 2017


COUNTIS and DIRIS
management software tools

Webserver function
The Webserver function comprises HTML pages embedded within the optional Ethernet
communication module of the DIRIS A's multifunction meter. These pages can be accessed via
an internet browser, simply by entering the DIRIS A IP address.
The Webserver offers the following functions:
• Monitoring of electrical values.
• Viewing of energy consumption.
diris_776_a_1_cat

• Management of alarms.
• Remote configuration of the main parameters for meters within the installation.
• Viewing and extracting load curves (through a .CSV file).

DIRIS A Ethernet communication module


with RS485 gateway

Instantaneous report of measurements Power and energy


diris_867_a_1_gb_cat

diris_869_a_1_gb_cat

Display for viewing instantaneous and average electrical values. Display for viewing instantaneous and average power measurements
and energy consumption.

Configuration of the devices Alarms


diris_868_a_1_gb_cat

diris_884_a_1_gb_cat

The latest alarms are date and time registered. The duration and value for
each alarm (low limit value / high limit value), as well as the related output
alarm number, are also displayed. Data can be extracted in *.csv format.

Catalogue 2017 143


References list

References Pages References Pages References Pages References Pages


182T 4xxx 67 192Y 0035 110 4829 0033 42, 129 4850 3013 63
182T 9xxx 114 192Y 0045 111, 114 4829 0034 42 4850 3014 61
192J 8015 65 192Y 0115 107, 110 4829 0035 42 4850 3015 61
192J 9120 73 192Y 0125 107 4829 0036 42 4850 3016 65
192M xxxx 123 192Y 0135 110 4829 004x 42 4850 3017 61
192S xxxx 120 192Y 0145 111, 114 4829 0050 31, 33, 37, 42, 129 4850 3019 53
192T 0003 107, 109, 110 192Y 0155 107, 110 4829 0101 31 4850 3020 53
192T 0005 107, 110 192Y 0165 107 4829 0102 33 4850 3021 67
192T 0006 109 192Y 0175 110 4829 0103 31 4850 3022 67
192T 0007 109, 110 192Y 0185 111, 114 4829 0105 33 4850 3025 63
192T 002x 109 192Y 0215 107, 110 4829 0106 33 4850 3026 63
192T 0101 107 192Y 0225 107 4829 011x 37 4850 3027 61
192T 0102 111, 114 192Y 0235 110 4829 0120 31 4850 3028 61
192T 0103 107, 110 192Y 0245 111, 114 4829 0128 37 4850 303x 53
192T 0105 107, 109, 110 192Y 0265 107 4829 0129 37 4850 3040 53
192T 0106 111 192Y 0275 110 4829 013x 37 4850 3041 53
192T 0255 107, 110 192Y 0285 111, 114 4829 018x 31, 33, 37 4850 3042 53
192T 05xx 107 192Y 04xx 123 4829 0199 31 4850 3043 55
192T 06xx 107 192Y 05xx 123 4829 0200 31, 42 4850 3044 55
192T 08xx 119 192Y 06xx 123 4829 0201 31
4850 3045 55
192T 09xx 119 192Y 08xx 123 4829 028x 42
4850 3046 55
192T 14xx 109 192Y 09xx 123 4829 03xx 129, 137
4850 3047 55
192T 19xx 117 4700 9993 133 4829 050x 47
4850 3048 55
192T 20xx 109 4825 001x 77 4829 055x 49
4850 3049 57
192T 21xx 110 4825 002x 81 4829 057x 51
4850 305x 57
192T 23xx 110 4825 0080 73, 85 4829 058x 47, 49, 51
4853 xxxx 65
192T 24xx 110 4825 0082 73, 85 4829 0590 47, 49, 51
4854 000x 131
192T 32xx 110 4825 0083 73, 85 4829 0591 47, 49, 51
4854 001x 131
192T 33xx 116 4825 0088 73, 85, 91, 97, 101 4829 0592 47, 49, 51
4854 005x 133
192T 34xx 116 4825 0089 73, 85, 91, 97, 101 4829 0593 47, 49, 51
4854 006x 133
192T 40xx 110 4825 0090 91, 97 4829 0594 47, 49, 51
4854 010x 131
192T 46xx 118 4825 0092 91, 97, 101 4829 0595 47, 49, 51
4854 011x 131
192T 47xx 118 4825 0093 91, 97 4829 0596 47, 49, 51
4854 0120 131
192T 48xx 118 4825 0094 91, 97 4829 0597 47, 49, 51
192T 5xxx 111 4825 0097 91 4829 0598 47 4854 0121 133
192T 6xxx 111 4825 0200 85 4829 0599 47 4854 0122 133
192T 7xxx 114 4825 0201 91 4829 0600 47, 49, 51 4854 0123 133
192T 80xx 114 4825 0202 91 4829 0601 47, 49, 51 4854 0124 133
192T 81xx 111 4825 0203 91, 97, 101 4829 0602 47, 49, 51 4854 0126 42, 129
192T 93xx 114 4825 0204 91, 97, 101 4829 0603 47, 49, 51 4854 0127 42, 129
192T 95xx 111 4825 0205 91 4829 0605 37 4854 02xx 133
192T 96xx 111 4825 0206 91, 97 4850 3000 55 4854 03xx 133
192T 97xx 114 4825 0207 97 4850 3001 55 4854 04xx 133
192U 0xxx 107 4825 0208 91, 97, 122 4850 3002 55 4899 0011 73, 85, 91, 97, 101
192U 22xx 109 4825 0209 91, 97, 122 4850 3003 57 4899 0110 134
192U 23xx 110 4825 021x 101 4850 3004 57 4899 0120 135
192U 4xxx 110 4825 1xxx 91 4850 3005 63 4899 0301 134
192U 6xxx 111 4826 0100 103 4850 3006 63 495x xxxx 101
192U 8xxx 114 4829 000x 42 4850 3007 63 499x xxxx 122
192U 9xxx 114 4829 0030 42, 129 4850 3008 61 5601 0017 31, 73, 77, 85, 91, 97, 101, 129
192Y 0015 107, 110 4829 0031 42, 129 4850 3009 61 5601 0018 33, 73, 77, 85, 91, 97, 101
192Y 0025 107 4829 0032 42, 129 4850 3012 63 6012 0000 31, 33, 73, 77, 85, 91, 97, 101, 129

144 Catalogue 2017


Note

Catalogue 2017 145


Note

146 Catalogue 2017


Maquette : SOCOMEC
Réalisation : SOCOMEC
Photographie : Martin Bernhart et Studio Objectif
Impression : ???????
Socomec worldwide
IN EURoPE IN ASIA PACIfIC IN MIddlE EAST

BELGIUM PORTUGAL AUSTRALIA UNITED ARAB EMIRATES


Critical Power / Power Control & Safety / Critical Power / Power Control & Safety / Critical Power / Power Control & Safety Critical Power / Power Control & Safety /
Energy Efficiency Energy Efficiency Tel. +61 2 9325 3900 Energy Efficiency
Tel. +32 2 340 02 30 Tel.+351 261 812 599 Fax +61 2 9888 9544 Tel. +971 4 29 98 441
Fax +32 2 346 28 99 Fax +351 261 812 570 info.ups.au@socomec.com Fax +971 4 29 98 449
info.be@socomec.com info.ups.pt@socomec.com info.ae@socomec.com
CHINA
FRANCE ROMANIA Critical Power / Power Control & Safety /
Critical Power / Power Control & Safety / Critical Power / Power Control & Safety / Energy Efficiency IN AMERICA
Energy Efficiency Energy Efficiency Tel. +86 21 52 98 95 55
Tel. +33 1 45 14 63 00 Tel. +40 21 319 36 88 Fax +86 21 62 28 34 68 USA, CANADA & MEXICO
Fax +33 1 48 67 31 12 Fax +40 21 319 36 89 info.cn@socomec.com Power Control & Safety / Energy Efficiency
dcm.ups.fr@socomec.com info.ro@socomec.com Tel. +1 617 245 0447
INDIA
GERMANy SERBIA Critical Power / Power Control & Safety / Fax +1 617 245 0437
Critical Power Critical Power / Power Control & Safety / Energy Efficiency info.us@socomec.com
Tel. +49 621 71 68 40 Energy Efficiency Tel. +91 44 39215400
Fax +49 621 71 68 444 Tel. +381 11 40 43 246 Fax +91 44 39215450 & 51 oThER CoUNTRIES
info.ups.de@socomec.com Fax +381 11 40 43 245 info.in@socomec.com
Power Control & Safety / Energy Efficiency info.rs@socomec.com NORTH AFRICA
SINGAPORE
Tel. +49 7243 65292 0
SLOvENIA Critical Power / Power Control & Safety / Algeria / Morocco / Tunisia
Fax +49 7243 65292 13 info.naf@socomec.com
Critical Power / Power Control & Safety / Energy Efficiency
info.scp.de@socomec.com
Energy Efficiency Tel.+65 6506 7600
AFRICA
ITALy Tel. +386 1 5807 860 Fax +65 64 58 7377
Other countries
Critical Power Fax +386 1 561 11 73 info.sg@socomec.com
info.africa@socomec.com
Tel.+39 02 98 242 942 info.si@socomec.com
THAILAND
Fax +39 02 98 240 723 SOUTH EUROPE
SPAIN Critical Power
info.ups.it@socomec.com Cyprus / Greece / Israel / Malta
Critical Power / Power Control & Safety / Tel. +66 2 941 1644 7
Power Control & Safety / Energy Efficiency info.se@socomec.com
Energy Efficiency Fax +66 2 941 1650
Tel.+39 02 98 49 821 Tel. +34 93 540 75 75 info.ups.th@socomec.com SOUTH AMERICA
Fax +39 02 98 24 33 10 Fax +34 93 540 75 76 Tel. +34 93 540 75 75
info.scp.it@socomec.com info.es@socomec.com info.es@socomec.com
NETHERLANDS SwITZERLAND MORE DETAILS
Critical Power / Power Control & Safety / Critical Power www.socomec.com/worldwide
Energy Efficiency Tel. +41 44 745 40 80
Tel. +31 30 760 0900 Fax +41 44 745 40 85
Fax +31 30 637 2166 info@socomec.ch
info.nl@socomec.com
TURKEy
POLAND

Non contractual document. © 2016, Socomec SAS. All rights reserved. - document printed on paper from sustainably managed forests.
Critical Power / Power Control & Safety /
Critical Power Energy Efficiency
Tel. +48 22 825 73 60 Tel. +90 216 540 71 20-21-22
Fax. +48 22 825 73 70 Fax +90 216 540 71 27
info.ups.pl@socomec.com info.tr@socomec.com
Power Control & Safety / Energy Efficiency
Tel. +48 91 442 64 11 UNITED KINGDOM
Fax +48 91 442 64 19 Critical Power
info.scp.pl@socomec.com Tel. +44 1285 863 300
Fax +44 1285 862 304
info.uk@socomec.com
Power Control & Safety / Energy Efficiency
Tel. +44 1462 440 033
Fax +44 1462 431 143
info.uk@socomec.com

hEAd offICE YoUR dISTRIBUToR / PARTNER


SOCOMEC GROUP
SAS SOCOMEC capital 10 686 000 €
R.C.S. Strasbourg B 548 500 149
B.P. 60010 - 1, rue de Westhouse
F-67235 Benfeld Cedex - FRANCE
Tel. +33 3 88 57 41 41
Fax +33 3 88 74 08 00
info.scp.isd@socomec.com
Réf: DCG 143 04 3 - 10/16

www.socomec.com