2017
Contents
The SOCOMEC group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 4 to 11
Why choose SOCOMEC? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 14
Selection guide measurement and monitoring system for electrical installations . . . . . . . p. 16
Selection guide active energy meters and pulse concentrators . . . . . . . . . . . . . . . . . . . . . p. 20
Selection guide multifunction meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 22
Selection guide current transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 24
Selection guide energy monitoring and management software . . . . . . . . . . . . . . . . . . . . . p. 136
Digital
Gateways, dataloggers and interfaces meters
p. 124
new
DIRIS G DATALOG
p. 126 p. 130
Wireless Communication
communication accessories
interfaces
p. 132 p. 134
Software suite
Embedded web server Energy management Cloud energy management
WEBVIEW software HYPERVIEW software N’VIEW
new
Software tools
Management software for
COUNTIS and DIRIS
p. 140
Catalogue 2017 3
An independent manufacturer
The benefit of a specialist
3,500 m2
of test platforms
One of the leading
independent power testing
innovative!
labs in Europe
60,000
for its primary mission: the availability,
control and safety of low voltage
electrical networks.
on-site interventions
per year
Nearly 400 experts in
As an independent manufacturer,
commissioning, technical the Group is committed to constant
audit, consultancy and innovation to improve the energy
maintenance performance of electrical installations in
infrastructures as well as industrial and
commercial sites.
10 %
and fully in keeping with international
standards.
high-quality products
MADE IN
EUROPE
4 Catalogue 2017
Your energy, our expertise
Critical Power and interruptions occurring on the primary
Ensuring the availability and power supply,
storage of high quality power • changeover of static, high availability sources
for transferring the supply to an operational
back-up source,
© Datadock
With its wide range of continuously evolving
• permanent monitoring of the electrical
products, solutions and services, Socomec
facilities to prevent failures and reduce
are recognised experts in the cutting-edge
operating losses,
technologies used for ensuring the highest
availability of the electrical power supply to • energy storage for ensuring the proper
critical facilities and buildings, including: energy mix of buildings and for stabilisation
of the power grid.
• static uninterruptible power supplies (UPS)
for high-quality power free of distortions
Power Control & Safety • isolation and on load breaking for the most
Managing power and demanding applications,
protecting persons and • continuity of the power supply to electrical
facilities facilities via manual or automatic changeover
switching systems,
APPLI 575A
Active in the industrial switching market since
• protection of persons and assets via fuse-
its foundation in 1922, Socomec is today an
based and other specialist solutions.
undisputed leader in the field of low voltage
switchgear, providing expert solutions that
ensure:
APPLI 571A
Socomec solutions, from current sensors associated tariff penalties,
through to a wide choice of innovative
• using the best available tariffs, checking utility
scalable software packages are driven by
bills and accurately distributing energy billing
experts in energy performance. They meet the
among consumer entities,
critical requirements of facility managers and
operators of commercial, industrial and local • monitoring and detecting insulation faults.
authority buildings for:
Socomec is committed to delivering a wide and support for a safe transition when
range of value-added services to ensure migrating from an old to a new generation of
the reliability and optimisation of end-users’ equipment.
equipment:
• consultancy, deployment and training from
• prevention and service operations to lower the project engineering stage through to final
the risks and enhance the efficiency of procurement.
operations,
Catalogue 2017 5
Adapted solutions
to meet your energy objectives
HEAVY
Controlling and securing your energy
SMART BUILDINGS
Reducing your energy bills and energy dependency
NAVAL SHIPS
Energy conversion in environments with harsh restrictions
SHOPPING CENTERS
Assuring your business continuity and visitor safety
SUNSYS PCS² TIPI low-voltage Auxiliary unit SIRCO and SIDER DIRIS Digiware SUNSYS PCS² INOSYS load break PV string
Power Conversion feeder pillar with with ATyS load break switches multi-circuit Power Conversion switches with enclosure
System and DIRIS multi- transfer measurement System and tripping function combiner box
Storage function meter switch system Storage
6 Catalogue 2017
POWER PLANTS
Securing the piloting of your high-security installations
and installations with seismic constraints
INDUSTRY
SHARYS IP UPS and other DIRIS Digiware
rectifier customised multi-circuit
products measurement
system
TRANSPORT
Securing the continuity of your installations
DATA CENTRES
Meeting the challenge of the availability
and performance of your energy
Catalogue 2017 7
Expert Services your partner
enabling available, safe and efficient energy
SOCOMEC is committed to
deliver a wide range of value-
added services to ensure
the availability of your critical
installation, the safety of your site
operations and the performance
optimisation of your low voltage
equipment during its life cycle.
The expertise and proximity of our
specialists are there to ensure
the reliability and durability of your
equipment.
APPLI 724 A
Key figures
More than 370 Socomec experts supported by 175 engineers and technicians from our distributors, drive the solutions to your specific needs.
Subsidiaries
CARTE 063 H
Distributors
Contact us
SITE 588 A
8 Catalogue 2017
A cutting-edge laboratory
the backing of an expert
CORpO 441 A
Proven expertise Vast range of tests International partnership
Tesla Lab is an independant laboratory The laboratory has 100 MVA The laboratory is recognised by the major
specialised in testing of LV switchgears, (Icc 100 kA rms 1 s) short-circuit platform, certification bodies worldwide: member
components and switchgear assemblies. three 10 kA overload platforms and many of ASEFA and LOVAG, it is accredited
4 M€ has been invested since 2011 in other test facilities covering 2000 m² for: by COFRAC, UL (CTDP), CSA (shared
this 2000 m² laboratory, where 30 experts • functional tests, certification) and DEKRA (WMT).
guarantee the quality of the performed tests, • mechanical tests: endurance, The partnership with many international
making the Tesla Lab one of the most modern • dielectric tests, certification bodies guarantees the quality
laboratories in Europe. and safety requirements in each country.
• environmental tests: vibrations,
• Ingress Protection (IP),
• temperature rise tests up to 60 °C ambient.
Catalogue 2017 9
a high-quality power supply
innovative solutions
range 568 B
and rectifiers comprise the most
complete ranges in the world and
cover a very wide variety of
applications for every sector of
activity.
10 Catalogue 2017
Webspace at your service
all our solutions can be adapted to your needs
www.socomec.com
Expertise, customised solutions, products and
services, downloads… All yours in a couple
of clicks! 1 2 3 4
4 Download photos,
CORPO 385 A
documentation, software and
CAD files
www.diris-digiware.com
Check out the dedicated site about DIRIS
Digiware, our measuring and monitoring
system. It gives you all the information
you need, including videos, images and
documentation on the most revolutionary
solution on today's market.
CORPO 466 A
Catalogue 2017 11
Alphabetical index
A DIRIS Digiware_____________________________________________26
DIRIS Digiware D and C_____________________________________28
Analogue meters_________________________________________ 124
DIRIS Digiware I____________________________________________34
DIRIS Digiware U___________________________________________32
D MULTIS L50_______________________________________________70
Datalogger______________________________________________ 130
Digital meters____________________________________________ 124
DIRIS A10_________________________________________________74
N
N’VIEW_________________________________________________ 139
DIRIS A14_________________________________________________78
DIRIS A20_________________________________________________82
DIRIS A40/A41____________________________________________86
DIRIS A60_________________________________________________92
O
DIRIS A80_________________________________________________98 Other electrical measurement devices_______________________ 124
DIRIS B-30________________________________________________38 Other products, measurement devices_______________________ 122
12 Catalogue 2017
P T
PTI: CT automatic short-circuiter____________________________ 122 TE sensors________________________________________________44
TF sensors________________________________________________50
R TR sensors________________________________________________48
Transducers_____________________________________________ 124
RETROFIT Line____________________________________________66
Transformer with integrated converter (CTA-VA)_______________ 122
S V
Selection guide
Voltage transformer BTV 25________________________________ 122
COUNTIS E______________________________________________20
Current transformers______________________________________24
DIRIS A_________________________________________________22
DIRIS Digiware___________________________________________16
W
Energy monitoring and management software_______________ 136 WEBVIEW_______________________________________________ 137
Catalogue 2017 13
Why choose SOCOMEC?
A leader in Energy & Power A monitoring device specialist Experts in energy performance
Management • The DIRIS G communication gateways analysis
• With the COUNTIS E, DIRIS A and and DATALOG H dataloggers centralise • Energy management software analyses
associated current sensor ranges, measurement data via hard-wired or multi-utility energy data in order to
SOCOMEC has developed one of radio link. reduce energy consumption.
the most advanced multifunction • Webserver solutions embedded in the • HYPERVIEW offers a wide range of tools
measurement ranges on the market, DIRIS A and DIRIS G products enable for raising user awareness of energy
dedicated to improving your energy the real-time monitoring of electrical consumption, creating reports and for
performance. parameters and alert users in case of dashboard display.
anomaly.
DIRIS Digiware Multi-circuit DIRIS Digiware Multi-circuit COSYS PFC Power Factor Correction
Power Monitoring Devices Power Monitoring Devices without harmonic protection
DIRIS B Wireless
Power Monitoring
Device
14 Catalogue 2017
An independent partner working closely with our customers
HYPERVIEW is hosted
on a local server.
DATALOG H Dataloggers
N’VIEW software
Catalogue 2017 15
Selection guide
Measurement and monitoring system for electrical installations
DIRIS Digiware
Multi-circuit metering
or +
+
+
Dedicated website
Find the right solution for your needs in just a few clicks
http://www.diris-digiware.com
16 Catalogue 2017
Selection guide
Measurement and monitoring system for electrical installations
DIRIS Digiware
Catalogue 2017 17
Selection guide
Measurement and monitoring system for electrical installations
DIRIS Digiware
DIRIS Digiware I I-30 I-31 I-33 I-35 I-43 I-45 I-60 I-61
p. 34 p. 34 p. 34 p. 34 p. 34 p. 34 p. 34 p. 34
Number of current inputs
3 3 3 3 4 4 6 6
Metering
± kWh, ± kvarh, kVAh • • • • • • • •
Load curves • • • •
Multi-tariff • • • •
Multi-measurement
I1, I2, I3, In, ΣP, ΣQ, ΣS, ΣPF • • • • • • • •
P, Q, S, PF per phase • • • •
Predictive power • •
Current unbalance (Inba, Idir, Iinv, Ihom, Inb) • •
Phi, cos Phi, tan Phi • •
Quality
THDi1, THDi2, THDi3, THDin • • • •
Individual harmonics I (up to level 63) • •
Overcurrents • •
Alarms
On threshold • •
Inputs/outputs 2/2 2/2
History of average values
45 days (max) • •
Format
Width/number of modules 18 mm / 1 18 mm / 1 18 mm / 1 18 mm / 1 27 mm / 1.5 27 mm / 1.5 36 mm / 2 36 mm / 2
18 Catalogue 2017
Selection guide
Measurement and monitoring system for electrical installations
DIRIS Digiware
Current sensors
Nominal current In (A) 5 … 2000 5 … 20 25 … 63 40 … 160 63 … 250 160 … 630 400 … 1000 600 … 2000
Actual coverage range (A) 0.1 … 2400 0.1 … 24 0.5 … 75.6 0.8 … 192 1.26 … 300 3.2 … 756 8 … 1200 12 … 2400
Actual coverage range (A) 0.5 … 720 0.5 … 90 0.64 … 120 1.26 … 240 4 … 720
Aperture (mm) Ø 10 Ø 16 Ø 24 Ø 36
Dimensions (mm) 25 x 39 x 71 30 x 42 x 74 45 x 44 x 95 57 x 42 x 111
Connection RJ12 RJ12 RJ12 RJ12
For demands greater than 600 A, the 5 A / RJ12 adapter guarantees the compatibility of the TCs.
Nominal current In (A) 150 … 6000 150 … 600 500 … 2000 1600 … 6000
Catalogue 2017 19
Selection guide
Active energy meters and pulse concentrators
COUNTIS E
Single-circuit metering,
Active energy meters: COUNTIS E E00 / E02 E03 / E04 E05 / E06 E10 / E11 / E12 E13 / E14 E15 / E16 E17 / E18 E20 / E21/E22 E23 / E24
p. 52 p. 52 p. 52 p. 54 p. 54 p. 54 p. 54 p. 56 p. 56
Main specifications
MID: EN 50470 module B + D certification • (E02) • (E04) • (E06) • (E12) • (E14) • (E16) • (E18) • (E22) • (E24)
RS485 Modbus • • •
M-Bus • •
Ethernet Modbus TCP/RTU •
Width 1 module 1 module 1 module 3 modules 2 modules 2 modules 2 modules 4 modules 4 modules
Input voltage 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 VAC 230 … 400 VAC 230 … 400 VAC
Functions
Total/partial energy kWh •/- •/• •/• •/• (E10, E11) •/• •/• •/• •/• •/•
Active power / Reactive power •/• •/• •/- •/• •/• •/• •/• (E22) •/•
Dual tariff for kWh • • • (E11, E12) • • • • (E21/22) •
Total/partial energy kvarh •/• •/• •/• •/• •/• • (E22) •/•
kVA via COM via COM • • • • (E22) •
Load curve
Measurement (I, V, P, Q, S, F and PF) • • • • • • (E22) •
CT connection indication
Birectional (energy consumption and production) • • • • • • (E22) •
Integrated web server •
Compatibility web server DIRIS G • • •
Accuracy
Active energy (IEC 62053-21) class 1 class 1 class 1 class 1 class 1 class 1 class 1 class 1 class 1
Reactive energy (according to IEC 62053-23) class 2 class 2 class 2 class 2 class 2 class 2 (E22) class 2
Active energy (EN 50470) class B (E02) class B (E04) class B (E06) class B (E12) class B (E14) class B (E16) class B (E18) class B (E22) class B (E24)
Characteristics
Metrological LED • • • • • • • • •
Pulse output 100 Wh 100 Wh 100 Wh 100 Wh 100 Wh 100 Wh 100 Wh 100 Wh
Sealing cover (MID version only) • (E02) • (E04) • (E06) • (E12) • (E14) • (E16) • (E18) • (E22) • (E24)
Phase/neutral inversion protection •
20 Catalogue 2017
Selection guide
Active energy meters and pulse concentrators
E25 / E26 E27/ E28 E30 / E31 / E32 E33 / E34 E35 / E36 E63 E40 / E41 / E42 E43 / E44 E45 / E46
p. 56 p. 56 p. 58 p. 58 p. 58 p. 62 p. 60 p. 60 p. 60
•/• •/• •/• (E31) •/ via COM (E34) •/ via COM (E36) •/• •/• •/ via COM (E44) •/ via COM (E46)
•/• •/• •/- •/ via COM •/ via COM •/ via COM •/- •/ via COM •/ via COM
• • • (E31 / E32) up to 4 via com up to 4 via com up to 4 via com up to 4 via com up to 4 via com
•/• •/• via COM via COM via COM via COM via COM
• • via COM via COM via COM via COM via COM
via COM via COM via COM via COM via COM
• • via COM via COM via COM via COM via COM
• • •
• • • (E33) • (E35) • (E43) • (E45)
•
• •
class 1 class 1 class 1 class 1 class 1 class 1 class 0,5s class 0,5s class 0,5s
class 2 class 2 class 2 class 2 class 2
class B (E26) class B (E28) class B (E32) class B (E34) class B (E36) class C (E42) class C (E44) class C (E46)
• • • • • • • • •
100 Wh 100 Wh configurable
• (E26) • (E28) • (E32) • (E34) • (E36) • (E42) • (E44) • (E46)
• • • • • • •
CO CO
UN UN
TIS TIS
E Ci3 E Ci3
RS485 Ethernet
COUNTIS ECi DIRIS Digiware DIRIS A COUNTIS E DIRIS B-30 RS DIRIS G-40 / G-60 HYPERVIEW
Catalogue 2017 21
Selection guide
Multifunction meters
DIRIS A
Single-circuit metering,
Which Which
application? functions?
measurement &
Multifunction metering
Application
analysis
(PMD)
new
22 Catalogue 2017
Selection guide
Multifunction meters
Which
Which Which
communication
dimensions? options?
protocol?
Power monitoring Power monitoring & Power monitoring & residual current
(PMD) events analysis (PMD) monitoring (PMD+RCM)
• • • •
• •
• •
• • • •
• • • •
by temperature sensor PT100 by temperature sensor PT100 by temperature sensor PT100
• •
• • • •
optional optional • •
• • • •
up to 6 with optional module up to 6 with optional module up to 6 with optional module
• • • •
• • • •
• • • •
optional optional • •
• • • •
Catalogue 2017 23
Selection guide
Current transformers
T2CB T2CB
0.2S version (1) (2)
26-30 32-40
p. 107 p. 109 p. 110
Rating (A)
0.5
5
10 5
…
15 20 5
20 …
25 40
30
40
50 *
60 25
25
… 40
75 …
150 …
80 150
150
100
125 60
… 60
150 300 … 50
160 400 … 80
100 750 …
200 * 500 100 75
… *
250 600 150 … …
… 150 750 1000 *
300
600 … 200
400 750 150
…
500 750 …
600 1250
750
800
1000
1200
1250
1500
1600
2000
2500
3000
4000
5000
Dimensions
Height 75.5 85.5 85 65 65 65 65 61 70 75.5 88.5 98.5
Width 61 71 135 45 45 49.5 49.5 75.5 49.9 61 71 86
Depth 35 45 60 30 30 35 50 48 68 48 58 58
Cable (Ø mm) 14 21 22.5 17.5 26 28 26 32 44
Bar 1 20x5 30x10 30x10 32x18 40x10 50x12
Bar 2 20x10 (x2) 40x12 30x5 (x2) 40x10 (x2)
Bar 3
* Class 1.
(1) Please see T2RB 115 for a primary wound 0.2S version. Dimensions are different from TRB 135.
(2) Please see T2CA 225 for a cable-through 0.2S version. Dimensions are different from TCA 22.
24 Catalogue 2017
Selection guide
Current transformers
100
…
400
250
…
200 * 200 1000 250
… 300 … …
1600 … 1600 300 1500
400 … 400
1500 … …
2000 *
2000 2000 1000 400
750 600 …
…
… … 4000 1200
1000 * 1500 …
3000 … 4000 1200
2000 1000
3000 … …
3000 5000
105.5 123.5 184.8 184.8 129 117 167 150 175 106 158 198 243
96 120 172 172 88 96 129 99 100 93 125 155 195
58 58 52 52 48 68 78 58 55 58 58 58 79
44 55 85 100
63x10 80x10 100x10 123x30 60x30 84x34 100x55 103x41 128x38 33x23 85x55 125x85 165x85
50x10 (x2) 60x30 80x10 (x3) 100x10 (x3)
60x10 (x2)
Catalogue 2017 25
DIRIS Digiware
Measurement and monitoring system for electrical installations
Multi-circuit metering
& measurement
A single connection
for communication
DIRIS_DW_011_A_1_CAT
Exclusive to Socomec,
patented
The SOCOMEC DIRIS Digiware energy measuring and monitoring solution came first in the 20th edition of the Mesure
magazine's Prize for Technology and was the overall winner in the energy efficiency category.
26 Catalogue 2017
DIRIS Digiware
Measurement and monitoring system for electrical installations
APPLI_636_A
Catalogue 2017 27
DIRIS Digiware D and C
Control and power supply interfaces
Multi-circuit metering
> Industry
> Building
> Infrastructure
> Data center
diris-dw_005_a_cat
diris-dw_006_a_cat
Strong points
Configuration
with EasyConfig, > Centralising and displaying
see page 140.
measurement data
> A single power supply for the
entire system
Function > A single RS485 or Ethernet
output for the entire system
DIRIS Digiware D-40 and D-50 DIRIS Digiware C-31
DIRIS Digiware D remote screens give you: For applications without a local display
- a local view of the data issued by the DIRIS DIRIS Digiware C-31 interfaces centralise all Conformity to standards
Digiware U and I modules, the system data.
- a power supply to the DIRIS Digiware modules, Through their RS485 Modbus output, they > IEC 61557-12
- access to this data over Ethernet (D-50) or make all this information available to energy
RS485 (D-40) efficiency software (DIRIS G communication
gateways are available to communicate via
Ethernet - Modbus TCP). > ISO 14025
Via an RS485 connection, the
DIRIS Digiware D-50 screen also acts as a DIRIS Digiware C-31 interfaces and C-32
gateway, centralizing all information issued by repeaters are 24 VDC powered.
DIRIS A, DIRIS B and COUNTIS E and making
this information available on Ethernet. > UL
DIRIS Digiware screens are 24 VDC powered.
Advantages
DIRIS Digiware D-40 and D-50 DIRIS Digiware C-31
• High-resolution graphic screen. Compact: Centralise your measurement data
• Made safe by a 24 VDC supply: elimination on 1 module without a local screen, for a
of hazardous voltage on cabinet doors. complete system
• IP65 front panel. - Single 24V power supply (no dangerous
• Ergonomic and easy to use with 10 direct voltage on Digiware modules for an
access buttons for: uninterruptible connection),
- Measurement information - A single RS485 communication.
- Selecting outputs
- Configuration equipment.
• Centralising measurement points:
- Selecting the circuit
- Displaying data.
28 Catalogue 2017
DIRIS Digiware D and C
Control and power supply interfaces
Connections
DIRIS Digiware D-40
Digiware
Digiware
Bus
LIYCY-CY
NC
RS485
RS485
120 Ω 120 Ω
SLAVE
Digiware Bus
SUPPLY
diris-dw_057_a_1_cat
24 VDC 24 VDC
24 V
*
DIRIS Digiware D-40
(*) 1A / 24 VDC fuse protection is recommended if the 24 VDC power supply is not provided by Socomec.
Ethernet
Ethernet
Digiware
Bus DIRIS Digiware D-50
24 VDC
LIYCY-CY (20 W max)
NC Digiware Bus
diris-dw_056_a_1_cat
*
MASTER
SUPPLY
24 VDC
24 V
DIRIS Digiware C
SUPPLY
diris-dw_023_b_1_x_cat
diris-dw_012_a_1_x_cat
DIGIWARE BUS
diris-dw_018_b_1_x_cat
24 V
LIYCY-CY
NC
NC
RS485
RJ45
1 2
ON
diris-dw_024_b_1_x_cat
diris-dw_013_a_1_x_cat
DIGIWARE BUS
diris-dw_057_a_1_en_cat
24 V
IN
RJ45
OUT
7 mm 7 mm
Catalogue 2017 29
DIRIS Digiware D and C
Control and power supply interfaces
Dimensions
DIRIS Digiware D-40/D-50 DIRIS Digiware C-31
90
diris-dw_037_b_1_x_cat
92
diris-dw_062_a_1_x_cat
C-3x
92 27 18 44 15
18 65
Configuration
Equipment consumption Calculation rules for the max. number of products on the Digiware Bus
Product Power delivered (W) Power consumed (W) The total power consumed by the equipment connected to the Digiware Bus
must not exceed the power from the 24 VDC supply.
Power supply The power supply must not exceed 20 W/70°C or 27 W/40°C.
P15 100-240 VAC / 24 VDC 15 Size with P15 power supply (ref: 4829 0120) delivering 15 W
Cables For example, it is possible to use
• 1 DIRIS Digiware D-50 display (2W)
50 metre package 1.5
• 1 DIRIS Digiware voltage module U-xx (0.72 W)
System interfaces • 50 metres of cable (1.5 W)
DIRIS Digiware D-x0 2 and
DIRIS Digiware C-31 0.8 • 20 DIRIS Digiware current modules I-3x (20 x 0.52 = 10.4 W)
Total power = 14.62 W
Module voltage or
DIRIS Digiware U-xx 0.72 • 9 DIRIS Digiware current modules I-4x (9 x 1.125 = 10.125 W)
Total power = 14.345 W.
Current modules Size with a 24 VDC power supply delivering a maximum of 20 W
DIRIS Digiware I-3x 0.52 For example, it is possible to use
DIRIS Digiware I-4x 1.125 • 1 DIRIS Digiware D-50 display (2W)
DIRIS Digiware I-6x 0.7 • 1 DIRIS Digiware voltage module U-xx (0.72 W)
Repeater • 50 metres of cable (1.5 W)
and
DIRIS Digiware C-32 1.5 • 30 DIRIS Digiware current modules I-3x (30 x 0.52 = 15.6 W)
Total power = 19.82 W
or
• 14 DIRIS Digiware current modules I-4x (14 x 1.125 = 15.72)
Total power = 19.97 W.
Repeater
Whenever the power consumption is higher than 20 W or the distance is greater than 100 m, a DIRIS Digiware C-32 repeater is required.
In a DIRIS Digiware system, a maximum of 2 repeaters may be used.
30 Catalogue 2017
DIRIS Digiware D and C
Control and power supply interfaces
Specifications
Electrical characteristics DIRIS Digiware D-40/D-50 features
DIRIS Digiware C-31 Mechanical specifications
Input voltage 24 VDC ± 20 % - 20 W max Type of screen Capacitive touch-screen technology, 10 keys
Connection Removable screw terminal block, 2 positions, Screen resolution 350 x 160 pixels
stranded or solid 0.2-2.5 mm² cable Front panel protection index IP65
P15 power supply Specifications 100-240 VAC/ 24 VDC - 0,63 A - 15 W Communication
Modular format - Dimensions (H x L): 90 x 25 mm
Ethernet RJ45 10/100 Mbs Modbus TCP gateway function (D50)
Communication specifications RJ45 Digiware Control and power supply interface function
Digiware Bus Modbus RTU communication function
RS485 2-3 wires
Function Connection between DIRIS Digiware modules (D50 input / D40 output)
Cable type Specific Socomec cable with RJ45 connections Upgrade and configuration via type B micro
USB
USB connector
RS485
Electrical characteristics
Connection type 2 to 3 half duplex wires
Power supply 24 VDC +10% / -20%
Protocol Modbus RTU
Power consumption 2 VA
Baudrate 1200 … 115 200 bauds
Environmental specifications
Function Data configuration and reading
Storage temperature -20 … +70°C
Location Single-point on DIRIS Digiware C
Operating temperature -10 … +55°C
Mechanical specifications
Humidity 95% at 40°C
Casing type DIN-rail mounting module and base Installation category,
CAT III, 2
Casing protection index IP20 / IK06 degree of pollution
Front panel protection index IP40 on the nose in modular assembly / IK06 Ports D-40 D-50
Environmental specifications Digiware
Inputs Digiware
RS485
Ambient operating temperature -10 … +70°C
Outputs RS485 Ethernet
Storage temperature -25 … +70°C
Operating humidity 55 °C / 97% HR
Operating altitude < 2000 m
References
DIRIS Digiware Reference Digiware connection cables Reference
D-40 Multipoint display, RS485 output 4829 0199 Length 0.10 m 4829 0181
D-50 Multipoint display, Ethernet output 4829 0201 Length 0.20 m 4829 0188
C-31 System interface 4829 0101 Length 0.50 m 4829 0182
C-32 Repeater 4829 0103 RJ45 cables Length 1 m 4829 0183
for Digiware
Power supply Reference Bus Length 2 m 4829 0184
P15 Power supply 100-240 VAC/ 24 VDC 15 W 4829 0120 Length 5 m 4829 0186
Length 10 m 4829 0187
Accessories
Reel 50 m + 100 connectors 4829 0185
To be ordered
Description of accessories Reference Digiware bus terminating resistor (supplied with C and D devices) 4829 0180
in multiples of
Fuse circuit breakers to protect voltage USB configuration cable 4829 0050
4 5601 0017
inputs (type RM) 1 pole + neutral Single-point display Reference
gG 10x38 0.5 A fuses 10 6012 0000
DIRIS D-30(1) Single-point display for DIRIS Digiware I-4x 4829 0200
(1) DIRIS D-30 display characteristics see page 43.
Expert Services
Catalogue 2017 31
DIRIS Digiware U
Voltage measurement module
Multi-circuit metering
> Industry
> Building
> Infrastructure
> Data center
diris-dw_005_a_cat
Strong points
Configuration
with EasyConfig, > 1 single voltage
see page 140.
measurement point for the
entire system
> Plug & Play
Function > Compact
The DIRIS Digiware U module measures voltage for the entire system. This pools together all om
municatio
n
voltage measurements. RJ45 (Digiware Bus) cables
The Digiware RJ45 Bus allows you to pass voltage measurements as well as power supply and are available.
RJ45
communication to all connected products.
• 1 single voltage measurement point for the • No hazardous voltage on cabinet doors. > IEC 61557-12
entire system. • Adapted to all types of network:
• Single point of protection for voltage single-phase, three-phase.
measuring.
• A complete, dedicated solution: > ISO 14025
- metering,
- monitoring voltage,
- quality analysis of the supplied voltage.
> UL
32 Catalogue 2017
DIRIS Digiware U
Voltage measurement module
Dimensions Specifications
DIRIS Digiware U Measuring characteristics
Voltage measurement - DIRIS Digiware U
Characteristics of the network
50-300 VAC (Ph/N) - 87-520 VAC (Ph/Ph) - CAT III
measured
Frequency range 45 … 65 Hz
Frequency accuracy Class 0.02
Network type Single-phase/ Two-phase / Two-phase with
neutral / Three-phase / Three-phase with neutral
Measurement by voltage Primary: 400 000 VAC
transformer Secondary: 60, 100, 110, 173, 190 VAC
90
References
Digiware connection cables Reference DIRIS Digiware Reference
Length 0.10 m 4829 0181 U-10 Metering 4829 0105
Length 0.20 m 4829 0188 U-20 Monitoring 4829 0106
Length 0.50 m 4829 0182 U-30 Analysis 4829 0102
RJ45 cables Length 1 m 4829 0183
for Digiware
Length 2 m 4829 0184 Accessories
Bus
To be ordered
Length 5 m 4829 0186 Description of accessories Reference
in multiples of
Length 10 m 4829 0187 Fuse holder to protect voltage inputs (type
4 5601 0018
Reel 50 m + 100 connectors 4829 0185 RM) 3 pole
Digiware bus terminating resistor (supplied with C and D devices) 4829 0180 gG 10x38 0.5 A fuses 10 6012 0000
USB configuration cable 4829 0050
Catalogue 2017 33
DIRIS Digiware I
Current measurement modules
Multi-circuit metering
> Industry
> Building
> Infrastructure
> Data center
diris-dw_004_a_cat
diris-dw_007_a_cat
diris-dw_007_a_cat
DIRIS Digiware I-3x DIRIS Digiware I-4x DIRIS Digiware I-6x
Strong points
Configuration
with EasyConfig, > Multi-circuit
see page 140.
> Plug and Play
> Compact
> High-precision measurement
Function chain
DIRIS Digiware I modules measure The RJ45 and RJ12 connections allow you
consumption and monitor the system at the to connect modules very quickly and to
closest point to the loads. The flexibility of automatically configure connected current
Conformity to standards
these modules allows you to allocate the sensors:
> IEC 61557-12
loads to be measured or monitored through - communication address,
independent current inputs. - load type,
For example: - sensor type and ratio,
- 1 three-phase load, - automatic rating and verification of current > ISO 14025
- 3 single-phase loads. travel direction.
Wiring errors are also prevented and
installation is simplified.
> UL
Advantages
• RJ45 and RJ12 rapid connection. • Compliant with standard IEC 61557-12,
• Available with 3, 4 or 6 inputs. guaranteeing the quality and accuracy of
• Single-output or multi-output for maximum the system:
optimisation of the number of products. - class 0.5 for the 2 - 120% rated current
• Compact format: 1 or 2 modules sized for global measurement chain In (with TE/TF
integration at the closest point to the loads. current sensors).
• A complete, dedicated solution:
- metering,
- monitoring,
- quality analysis.
34 Catalogue 2017
DIRIS Digiware I
Current measurement modules
DIRIS Digiware I I-30 I-31 I-33 I-35 I-43 I-45 I-60 I-61
Number of current inputs
3 3 3 3 4 4 6 6
Metering
± kWh, ± kvarh, kVAh • • • • • • • •
Load curves • • • •
Multi-tariff • • • •
Multi-measurement
I1, I2, I3, In, ΣP, ΣQ, ΣS, ΣPF • • • • • • • •
P, Q, S, PF per phase • • • •
Predictive power • •
Current unbalance (Inba, Idir, Iinv,
• •
Ihom, Inb)
Phi, cos Phi, tan Phi • •
Quality
THDi1, THDi2, THDi3, THDin • • • •
Individual harmonics I (up to level 63) • •
Overcurrents • •
Alarms
On threshold • •
Inputs/outputs 2/2 2/2
History of average values
45 days (max) • •
Format
Width/number of modules 18 mm / 1 18 mm / 1 18 mm / 1 18 mm / 1 27 mm / 1.5 27 mm / 1.5 36 mm / 2 36 mm / 2
Dimensions
DIRIS Digiware I-3x / I-6x DIRIS Digiware I-4x
150
21
45
90
diris-dw_022_b_1_x_cat
diris-dw_060_a_1_x_cat
I-3x I-6x
44 15
18 36 65 27 27
45
58
72
Catalogue 2017 35
DIRIS Digiware I
Current measurement modules
Connections
Associated current sensors
Various types of current sensors are connected to the DIRIS Digiware: closed (TE), split core (TR) or flexible (TF). This range of sensors can be adapted to all types of
new or existing installations.. A rapid RJ12 connection makes wiring easy and reliable and prevents wiring errors. The DIRIS Digiware system automatically recognises
the sensor size and type. This guarantees the overall accuracy of the DIRIS Digiware + current sensor measurement chain.
For more information: voir page 44.
L1 L1
L2 L2
L3 L3
diris-dw_032_c_1_x_cat
diris-dw_033_c_1_x_cat
1 1 1 1 1 1
3 3 3
3
I4x
Three phase + neutral Single-phase
3P+N - 4CT (1 three-phase load + Neutral measured) 1P+N-1CT (4 single-phase loads)
L1 L1
L2 N
L3
N
1 1
1 1 1
diris-dw_038_c_1_x_cat
diris-b_061_a_1_x_cat
1 1 1 1
3 +N
Accessories
Digiware plug-in connector
With the Digiware plug-in connector you can disconnect a Digiware module form the Bus while ensuring the DIRIS Digiware system continues to
run downstream. This accessory is particularly useful in applications with retractable drawers or critical applications such as in data centres.
36 Catalogue 2017
DIRIS Digiware I
Current measurement modules
Specifications
References
DIRIS Digiware Reference Digiware connection cables Reference
I-30 Metering - 3 current inputs 4829 0110 Length 0.10 m 4829 0181
I-31 Metering + load curve - 3 current inputs 4829 0111 Length 0.20 m 4829 0188
I-33 Monitoring - 3 current inputs 4829 0128 Length 0.50 m 4829 0182
I-35 Analysis - 3 current inputs 4829 0130 RJ45 cables Length 1 m 4829 0183
for Digiware
I-43 Monitoring - 2 inputs/ 2 outputs - 4 current inputs 4829 0129 Bus Length 2 m 4829 0184
I-45 Analysis - 2 inputs/ 2 outputs - 4 current inputs 4829 0131 Length 5 m 4829 0186
I-60 Metering - 6 current inputs 4829 0112 Length 10 m 4829 0187
I-61 Metering + load curve - 6 current inputs 4829 0113 Reel 50 m + 100 connectors 4829 0185
Digiware bus terminating resistor (supplied with C and D devices) 4829 0180
Accessories Reference USB configuration cable 4829 0050
Digiware x 5 plug-in connector 4829 0605 voir page 43.
(1) DIRIS D-30 display characteristics
Expert Services
Catalogue 2017 37
DIRIS B-30
Wireless power monitoring devices
& wireless metering
> Industry
> Building
> Infrastructure
> Local authority
diris-b_010_a_1_cat
diris-b_009_a_1_cat
Configuration
with EasyConfig,
see page 140.
Functions
Multi-measurement Quality Load curves and history logs (130 days max.)
• Currents • Voltage Unbalance • Active, reactive and apparent power
- I1, I2, I3, In, Isystem - Vdir, Vinv, Vhom, Udir, Uinv, Unba, Vnba, Vnb, Unb • Currents, voltages and frequency
• Voltages & frequency • Current unbalance Alarms
- V1, V2, V3, VN, Vsystem, U12, U23, U31, - Idir, Iinv, Ihom, Inba, Inb • Alarms for all electrical values, events and input
Usystem, f • Total harmonic distortion status changes, possibility of boolean combination
• Power - Currents THDi1, THDi2, THDi3,THDiN Communication
- P1, P2, P3, ΣP, Q1, Q2, Q3, ΣQ, S1, S2, S3, ΣS - Phase-to-neutral voltage THDv1, THDv2, THDv3 • DIRIS B-30 RF: Radio frequency Communication
- Predictive power ΣP, ΣQ, ΣS - Phase-to-phase voltage THDu12, THDu23, THDu31 (wireless)
• Power factor • Individual harmonics up to rank 63 • DIRIS B-30 RS: RS485 Modbus,
- PF1, PF2, PF3, ΣPF - Currents: I1h, I2h, I3h, INh • Optional modules: RS485, BACnet IP, BACnet MSTP,
• Cos ϕ & tanϕ - Phase-to-neutral voltage: V1h, V2h, V3h PROFIBUS DPV1
- Instantaneous values per phase - Phase-to-phase voltage: U12h, U23h, U31h Inputs
Metering • Active (according to EN 50160) • 2 digital inputs
- Dips, interruptions, swells - Supply by the DIRIS B-30 or external supply
• Active energy: +/- kWh - Function: logic status, circuit breaker status,
• Reactive energy: +/- kvarh pulse meter or synchronisation pulse
• Apparent energy: kVAh
• Multi-tariff (8 max.)
38 Catalogue 2017
DIRIS B-30
Wireless power monitoring devices
diris-dw_037_b_1_x_cat
92
diris-d_004_a_1_x_cat
diris-d_001_a_1_cat
RJ9
DIRIS D-30
DIRIS B-30
92 27 18
Optional modules
DIRIS O
Optional modules (4 max.)*
• Digital inputs/outputs
• Analogue inputs/outputs
• Temperature inputs
• Communication protocols
diris-b_031_a
status changes of the auxiliary contacts. DIRIS B-30 for simultaneous sending of information via RS485
• 2 digital outputs can be connected to configurable alarms to two supervision stations.
warning of exceeded thresholds (power, current, etc.) or
can be piloted remotely.
DIRIS O-p
• Adds a PROFIBUS DPV1 communication port to the DIRIS B-30.
diris-o_023_a
DIRIS O-ioa
• 2 inputs (4-20 mA) centralise analogue sensors (pressure,
diris-o_018_a
DIRIS O-it
• 3 temperature inputs to be connected to PT100 or PT1000 DIRIS O-b/mstp
diris-o_020_a
Accessories
Remote radio antenna DIRIS B-30 sealing cover USB configuration cable (2 m)
• Mounted outside the enclosure of the DIRIS B-30 • Prevents access to the cabling of the monitoring • Advanced configuration of DIRIS B-30 gateways
monitoring device to increase the transmission device. can be achieved using the EASY CONFIG
distance. software via Ethernet or direct USB connection.
Catalogue 2017 39
DIRIS B-30
Wireless power monitoring devices
USB
DIRIS O
optional module
diris-d_027_b_1_gb_cat
2 digital
inputs
RS485
110-230VAC
diris-b_025_a_1_x_cat
diris-b_026_a_1_x_cat
V1 V2 V3 VN V1 VN V1 V2 V3 VN V1 V2 V3 VN V1 VN
L V1 VN
L
L
N N
N
110-230VAC
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
2 inputs supplied by the product 2 inputs with external power supply RS485 RJ9 for DIRIS D-30
(self-supply and data)
10-30 VDC
12 VDC
RS485
diris-b_024_b_1_x_cat
Slave
diris-b_022_a_1_x_cat
diris-b_023_a_1_x_cat
diris-b_019_a_1_x_cat
IN
IN
1 1
NC
2
RJ9
2
LIYCY-CY
I 04 I 04 I 01
diris-o_011_a_1_x_cat
diris-o_012_a_1_x_cat
diris-o_013_a_1_x_cat
IN1
IN1 IN2
IN2
OUTPUT OUTPUT
SUBD 9 ETH
diris-o_015_a_1_x_cat
diris-o_016_a_1_x_cat
diris-o_017_a_1_x_cat
40 Catalogue 2017
DIRIS B-30
Wireless power monitoring devices
Connections
Associated current sensors
Various types of current sensors can be connected to the DIRIS Digiware: Solid TE , split-core TR , flexible TF current sensors. This range of sensors can be adapted to
all types of new or existing installations. A rapid RJ12 connection makes wiring easy and reliable and prevents wiring errors. The DIRIS B-30 automatically recognises the
sensor size and type. This guarantees the overall accuracy of the DIRIS B-30 + current sensor measurement chain.
For more information: see page 44.
diris-t_003_a_1_cat
TF
DIRIS B-30
TR
RJ12 Connection
diris-t_014_a_1_cat
diris-t_016_a_1_cat
diris-b_033_a_cat
1 1 1 1 1 1 1
diris-b_015_b_1_x_cat
diris-b_016_b_1_x_cat
3 3
3 +N
Three-phase Single-phase
3P+N - 3CTs & 1P+N - 1CT (1 three-phase load & 1 single-phase load) 1P+N-1CT (4 single-phase loads)
L1 L1
L2 N
L3
N
1 1
1 1 1 1
1 1 1 1
diris-b_017_b_1_x_cat
diris-b_018_b_1_x_cat
3 +N 1
Catalogue 2017 41
DIRIS B-30
Wireless power monitoring devices
Dimensions (mm)
DIRIS B-30 DIRIS O optional modules
120
diris-o_001_b_1_x_cat
90
45
diris-b_004_b_1_x_cat
100
90
44 15
15
A 65
Communication architecture
Example of communication architecture with DIRIS G
gateway and WEBVIEW embedded WEB server
For more information about DIRIS G, see page 126.
WEBVIEW
Supervision
Ethernet
RS485
diris-g_003_a_1_x_cat
DIRIS B DIRIS B
RF RF DIRIS B DIRIS B DIRIS A
RS485 RS485 COUNTIS E
References
DIRIS B-30 monitoring devices Reference
DIRIS B-30 RS485 - Modbus - 230VAC 4829 0000
DIRIS B-30 RF - Modbus - 230 VAC 4829 0002
Accessories Reference
DIRIS D-30 - Single-point display 4829 0200
RJ9 cable for DIRIS D-30 display - 1.5 m 4829 0280
RJ9 cable for DIRIS D-30 display - 3 m 4829 0281
Wireless remote antenna, 868 MHz - 210 mm height 4854 0126
Cable for remote antenna - SMA connector - 3 meter length 4854 0127
DIRIS B-30 sealing cover for I/O terminals 4829 0049
USB configuration cable 4829 0050
42 Catalogue 2017
DIRIS B-30
Wireless power monitoring devices
Catalogue 2017 43
TE sensors
Solid current sensors
used with DIRIS Digiware and DIRIS B-30
new
The solution for
Current sensors
> Industry
> Building
> Infrastructure
> Data center
diris-t_003_a_1_cat
diris-t_010_a_1_cat
tore_065_a
TE solid sensors
Strong points
Function
> Plug & Play
TE smart current sensors measure the load currents of an electrical system and send the
data to meters and measurement hubs via an RJ12 plug-and-play output. Thanks to a wide > Accuracy as per standard
measurement range, TE current sensors cover the full current range of 5 to 2000 A, with IEC 61557-12
7 references. TE solid current sensors can be connected to DIRIS Digiware and DIRIS B-30 via a > Installation
rapid RJ12 connection.
Numerous accessories are available to aid the installation of sensors in any type of cabinet.
Conformity to standards
44 Catalogue 2017
TE sensors
Solid current sensors
used with DIRIS Digiware and DIRIS B-30
Mounting
Linear assembly with the protective devices Staggered assembly Cable mounting
TE-25 / TE-35 / TE-45 / TE-55 / TE-90 TE-18 / TE-35 / TE-45 / TE-55
diris-t_005_a_1_cat
diris-t_005_a_1_cat
diris-t_035_a_1_cat
DIN rail mounted Back-plate mounting Bar mounting
diris-t_033_a_1_cat
diris-t_034_a_1_cat
diris-t_036_a_1_cat
diris-t_049_a
TE-90 clamps
diris-t_048_a
Connections
TE / TR / TF current sensors
DIRIS B-30 or TF
DIRIS DIGIWARE I
TR
TE
RJ12 Connection
diris-b_033_a_cat
Catalogue 2017 45
TE sensors
Solid current sensors
used with DIRIS Digiware and DIRIS B-30
Mounting accessories
Mounting accessories delivered with TE sensors:
TE-35
TE-45
Switch mounting TE-18 TE-25 TE-55 TE-90
Busbar 2 pcs
Compatible accessories
Adapter for CT with 5A secondary Coupling link Sealable cover
• With this adapter you can • Associated with the TE range, this accessory is • Using a sealable cover guarantees the immunity
use a current transformer for inter-connecting the sensors when linear or of the sensor connection on TE/TR/TF current
diris-t_041_a_1_cat
Dimensions (mm)
TE - Solid current sensors
TE-18 TE-25 / TE-35 / TE-45 / TE-55 TE-90
L 2.2 P
1
=
H
Ø
=
H
= F =
H
= F =
diris-t_023_b_1_fr_cat
diris-t_047_a_1_fr_cat
=
1
=
T
L P
L P 19.7
1. Switch mounting 36
Model Nominal current range (A) Actual coverage range (A) Pitch (mm) H x W x D (mm) F (mm) T (mm)
TE-18 5 … 20 / 25 ... 63 0.1 … 24 / 0.5 … 75 18 45 x 28 x 20 8.6 -
TE-25 40 … 160 0.8 … 192 25 65 x 25 x 32.5 13.5 x 13.5 17.5
TE-35 63 … 250 1.26 … 300 35 71 x 35 x 32.5 21 x 21 17.5
TE-45 160 … 630 3.2 … 756 45 86 x 45 x 32.5 31 x 31 19.5
TE-55 400 … 1000 8 … 1200 55 100 x 55 x 32.5 41 x 41 21.5
TE-90 600 … 2000 12 … 2400 90 126 x 90 x 24.6 64 x 64 -
46 Catalogue 2017
TE sensors
Solid current sensors
used with DIRIS Digiware and DIRIS B-30
Specifications
References
Model Nominal current range (A) Actual coverage range (A) Pitch (mm) Reference
TE-18 5 … 20 0.1 … 24 18 4829 0500
TE-18 25 … 63 0.5 … 75 18 4829 0501
TE-25 40 … 160 0.8 … 192 25 4829 0502
TE-35 63 … 250 1.26 … 300 35 4829 0503
TE-45 160 … 630 3.2 … 756 45 4829 0504
TE-55 400 … 1000 8 … 1200 55 4829 0505
TE-90 600 … 2000 12 … 2400 90 4829 0506
Accessories Reference
Coupling link (20 linear assembly parts and 10 for staggered assembly) 4829 0598
CT/5A adapter (measurements of >2000 A) (max primary current 10000 A/5/A) 4829 0599
Sealable caps (20 pieces) 4829 0600
Catalogue 2017 47
TR sensors
Split-core current sensors
used with DIRIS Digiware and DIRIS B-30
> Industry
> Building
> Infrastructure
> Data center
diris-t_012_a_1_cat
48 Catalogue 2017
TR sensors
Split-core current sensors
used with DIRIS Digiware and DIRIS B-30
Mounting Dimensions
Cable mounting TR-10 / TR-16 / TR-24 / TR-36
C
L B
Ø
diris-t_037_a_1_cat
diris-t_038_a_1_cat
H
A
diris-t_024_b_1_fr_cat
Accessories P
Sealable cover
• Using a sealable cover Nominal current Actual coverage
guarantees the immunity of Model range (A) range (A) H x W x D (mm) Ø (mm) A (mm) B (mm) C (mm)
the sensor connection on
diris-t_046_a_1_cat
Specifications
TR - Split-core sensor
Model TR-10 TR-16 TR-24 TR-36
Nominal current range In (A) 25 … 75 32 … 100 63 … 200 200 … 600
Actual coverage range (A) 0.5 … 90 0.64 … 120 1.26 … 240 4 … 720
Max. current (A) 90 120 240 720
Weight (g) 74 117 211 311
Max. voltage (phase/neutral) 300 V
Rated withstand voltage 3 kV
Frequency 50/60 Hz
Intermittent overload 10 x In for 1s
Measurement category CAT III
Protection degree IP20 / IK06
Operating temperature -10 … +70°C
Storage temperature -25 … +85°C
Relative humidity 95% RH non-condensing
Altitude < 2000 m
Connection Socomec RJ12 cable
References
Nominal current Actual coverage Accessories Reference
Model range (A) range (A) Ø (mm) Reference Sealable caps (20 pieces) 4829 0600
TR-10 25 … 75 0.5 … 90 10 4829 0551
TR-16 32 … 100 0.64 … 120 16 4829 0552
TR-24 63 … 200 1.26 … 200 24 4829 0553
TR-36 200 … 600 4 … 720 36 4829 0554
Catalogue 2017 49
TF sensors
Flexible current sensors
used with DIRIS Digiware and DIRIS B-30
> Industry
> Building
> Infrastructure
> Data center
diris-t_016_a_1_cat
TF Flexible current sensors
Strong points
50 Catalogue 2017
TF sensors
Flexible current sensors
used with DIRIS Digiware and DIRIS B-30
Mounting Connections
TE / TR / TF current sensors
Cable mounting Bar mounting
DIRIS B-30 TF
or DIRIS DIGIWARE I
diris-t_039_a_1_cat
diris-t_040_a_1_cat
TR
Accessories TE
Sealable cover
RJ12 Connection
• Using a sealable cover
diris-t_046_a_1_cat
Dimensions
TF-55 TF-120 / TF-300
1500 1500
Ø6
L Ø 85 Ø 11
85
Ø
diris-t_027_c_1_x_cat
diris-t_028_a_1_x_cat
L
38
18 18 38
Model Nominal current range (A) Actual coverage range (A) Ø loop (mm) L = Loop length (mm)
TF-55 150 … 600 3 … 720 55 182
TF-120 500 … 2000 10 … 2400 120 376
TF-300 1600 … 6000 32 … 7200 300 942
Specifications References
Model TF-55 TF-120 TF-300 Actual
Nominal current range In (A) 150 … 600 500 … 2000 1600 … 6000 Nominal current coverage Ø loop
Actual coverage range (A) 3 … 720 10 … 2400 32 … 7200 Model range (A) range (A) (mm) Reference
Weight (g) 114 142 220 TF-55 150 … 600 3 … 720 55 4829 0570
Max. voltage (phase/neutral) 600 V TF-120 500 … 2000 10 … 2400 120 4829 0571
Rated withstand voltage 3.6 kV TF-300 1600 … 6000 32 … 7200 300 4829 0572
Frequency 50 / 60 Hz
Intermittent overload 10 x In for 1 s Accessories Reference
Measurement category CAT III Sealable caps (20 pieces) 4829 0600
Protection degree IP30 / IK07
Operating temperature -10 … +70°C
Storage temperature -25 … +75°C
Relative humidity 95% RH non-condensing
Altitude < 2000 m
Socomec cable or equivalent RJ12 straight, twisted
Connection
pair, unshielded 300 V cat. III cable. -40 / +85 °C
Catalogue 2017 51
COUNTIS E0x
Active energy meters
single-phase - direct 32/40 A
Single-circuit metering,
new
The solution for
measurement &
> Industry
> Marinas
> Shopping centers
analysis
count_215_a_1
count_252_a
Strong points
> Compactness
> Output (pulses)
> MID certified B+D module
COUNTIS E04 - MID COUNTIS E02 - MID
> RS485 (MODBUS) and
M-Bus communication
MID certification
Compactness
Only 1 module wide. Conformity to standards
Output (pulses)
> IEC 62053-21
count_211_a_1_x_cat
52 Catalogue 2017
COUNTIS E0x
Active energy meters
single-phase - direct 32/40 A
Front panel
1. Terminal shrouds (COUNTIS E02/E04/E06). 1. Neutral terminal
2. MID marking (COUNTIS E02/E04/E06). 1 2. M-Bus/MODBUS connection
3. Metrological LED (2000 pulses/kWh for 2 3. Metrological LED
1 E00/E02 and 5000 pulses/kWh for 3
4. Navigation button.
E03/E04/E05/E06). 4 5. Backlit LCD display
4. kWh display. 6. Pulse output
2
4 5. Serial number (COUNTIS E02). 7. Current and voltage terminals
5
count_215x_a_2_cat
count_252x_a_1_cat
5
3 7
Case
17.5/18 61/65
47/44
COUNTIS E00/E02 COUNTIS E03 … E06
25
Type modular modular
Number of modules 1 1
Dimensions W x H x D (mm) 17.5 x 85 x 61 18 x 90 x 65
Case degree of protection IP 20 IP 20
Front degree of protection IP 50 IP 50
7 digit LCD with
85/90
backlighting
count_212_c_x_cat
Electrical characteristics
Current measurement (TRMS) COUNTIS E00/E02 COUNTIS E03 … 06 Output (pulses) COUNTIS E00/E02 COUNTIS E03 … 06
Type direct input Number 1
Input consumption < 2 VA < 0.5 VA 27 VDC - 27 mA
Type of optocoupler Max. 15 VDC
Permanent overload 32 A 40 A (IEC 62053-31)
Intermittent overload 30 Imax over 10 ms Fixed pulse weight 100 Wh
Minimum current measured 20 mA Pulse duration 100 ms
Voltage measurements (TRMS) Operating conditions
Range of measurement 196 … 264 VAC 184 … 276 VAC Operating temperature -10 … +55°C -25 … +55°C
Max. 1.5 VA for E03/04 Storage temperature -20 … +70°C -40 … +75°C
Input consumption 8 VA
Max. 1 VA for E05/06 Relative humidity 95% 80%
Permanent overload 264 VAC 280 VAC Communication COUNTIS E03/E04 COUNTIS E05/E06
Energy accuracy Link RS485 Wired
Active (according to IEC 62053-21) Class 1 Type 2 … 3 half duplex wires 2 half duplex
Active (according to EN 50470) Class B Protocol MODBUS in RTU mode M-Bus
Power supply Speed 2400 … 38400 bauds 300, 2400, 9600 bps
Self-powered yes
count_239_c_1_x_cat
count_249_a_1_x_cat
References
COUNTIS E00 COUNTIS E02 COUNTIS E03 COUNTIS E04 COUNTIS E05 COUNTIS E06
Type Reference Reference Reference Reference Reference Reference
Direct 32 A 4850 3019
Direct 32 A - MID 4850 3020
Direct 40 A - Dual tariff + RS485 MODBUS communication 4850 3039
Direct 40 A - Dual tariff + RS485 MODBUS communication + MID 4850 3040
Direct 40 A - Dual tariff + M-Bus communication 4850 3041
Direct 40 A - Dual tariff + M-Bus communication + MID 4850 3042
Catalogue 2017 53
COUNTIS E1x
Active-energy meters
single phase - direct 63/80 A
Single-circuit metering,
new
The solution for
measurement &
> Marinas
> Shopping centers
> Data centers
analysis
count_216_a_1_cat
count_253_a_1_cat
Strong points
54 Catalogue 2017
COUNTIS E1x
Active-energy meters
single phase - direct 63/80 A
Front panel
1. Terminal shrouds (COUNTIS E12/E14/E16/E18). 1. Backlit LCD display.
1 2. Backlit LCD display. 2. Navigation button.
3. MID marking (COUNTIS E12/E14/E16/E18). 3. Metrological LED (1000 pulses/kWh).
4. Serial number. 4. Voltage, current and neutral terminals.
2 5 5. Navigation button.
count_216x_a_2_cat
count_253x_a_2_cat
6
3 2
4
3 4
Case
62.5/64 COUNTIS E10 … E12 COUNTIS E13 … E18
54/36 44/44 Type modular modular
Number of modules 3 2
Dimensions W x H x D 54 x 90 x 62.5 mm 36 x 90 x 64 mm
Case degree of protection IP 20 IP 20
COUNTIS E10
45/45
count_190_c_1_x_cat
215 g E13/14/17/18
Weight 170 g
205 g E15/16
Electrical characteristics
Measurement of currents COUNTIS E10…E12 COUNTIS E13…E18 Output (pulses) COUNTIS E10 … E12 COUNTIS E13 … E16
Type single phase - direct 63 A single phase - direct 80 A Optocoupler type (IEC 62053-31) Class A (20 … 30 VDC) 27 VDC - 27 mA
Input consumption max. 0.8 VA max. 0.5 VA Number 1 1
Startup current (Ist) 40 mA 20 mA Fixed pulse weight 100 Wh
Minimum current (Imin) 0.5 A(1). 0.25 A 50 ± 2 ms ON time
Pulse duration 100 ms
Transition current (Itr) 1 A(2). 0.5 A 30 ± 2 ms min OFF time
Reference current (Iref) 10 A(3). 5A Operating conditions COUNTIS E10 … E12 COUNTIS E13 … E18
Permanent overload (Imax) 63 A 80 A Operating temperature -10 … 55°C -25 … 55°C
Intermittent overload 1890 A over 10 ms 30 Imax over 10 ms Storage temperature -20 … 70°C -25 … 75°C
Voltage measurement Relative humidity 85% 80%
Range of measurement 230 V ± 20% 230 … 240 V ± 20% Communication COUNTIS E13/14 COUNTIS E15/E16 COUNTIS E17/E18
3.5 VA max E13/14/17/18 Link RS485 Wired RJ45
Consumption (VA) Max. 0.5 VA
7.5 VA max E15/16 2 half duplex
Permanent overload 280 V phase-neutral 290 V phase-neutral Type Full duplex
2-3 half duplex (E13/E14)
Energy accuracy
MODBUS TCP,
Active (according to IEC 62053-21) Class 1 Class 1 Protocol MODBUS® RTU M-BUS
HTTP, NTP, DHCP
Active (according to EN 50470) Class B Class B
Power supply Baudrate 1200 … 57600 bauds 300 … 9600 bauds 10/100 Mbps
Self-powered Yes
Frequency 50/60 Hz
(1) I(min) ≤ 0.5 * Itr (2) Guaranteed precision class of between I(tr) and I(max).
(3) I(ref) = I(b) (base current) = 10 * I(tr) for direct connection COUNTIS devices.
Connection
N
N N N
L L’
L L’ L L’ L L’
count_241_d_1_x_cat
count_181_c_1_x_cat
count_240_c_1_x_cat
count_250_a_1_x_cat
S0 S0 M-BUS
+ - + - COM - + + -
RJ45
1 2 3 4 5 A-V A N
4 6 8 10 1 3 2 A-V A N 1 2 3 4 A-V A N
T1/2* L L’ N RS485
COUNTIS E10/E11/E12 COUNTIS E13/14 COUNTIS E15/16 COUNTIS E17/E18
* Not available on the COUNTIS E10.
References
COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS
E10 E11 E12 E13 E14 E15 E16 E17 E18
Type Reference Reference Reference Reference Reference Reference Reference Reference Reference
Direct 63 A 4850 3000
Direct 63 A - Dual tariff 4850 3001
Direct 63 A - Dual tariff + MID 4850 3002
Direct 80 A - Dual tariff + MODBUS communication via RS485 4850 3043
Direct 80 A - Dual tariff + MODBUS communication via RS485 + MID 4850 3044
Direct 80 A - Dual tariff + M-Bus communication 4850 3045
Direct 80 A - Dual tariff + M-Bus communication + MID 4850 3046
Direct 80 A - Dual tariff + Ethernet Modbus TCP communication 4850 3047
Direct 80 A - Dual tariff + Ethernet Modbus TCP communication + MID 4850 3048
Catalogue 2017 55
COUNTIS E2x
Active-energy meters
three-phase - direct 63/80 A
Single-circuit metering,
new
The solution for
measurement &
> Industry
> Infrastructure
> Data center
analysis
count_254_a_1_cat
count_232_a
COUNTIS E24 - MID COUNTIS E20 Strong points
56 Catalogue 2017
COUNTIS E2x
Active-energy meters
three-phase - direct 63/80 A
Front panel
1. Backlit LCD display. 1. Neutral terminal
2. Navigation button.
1 2. Backlit LCD display
3. Reset button. 3. Navigation button.
4. Metrological LED 4. ENTER key
(1000 pulses/kWh). 3 5. Metrological LED
count_232x_a_1_cat
count_254x_a_1_cat
2 4
2 6. Current and voltage terminals
3 5
4
6
1
(3)
Error Partial Reference current (Iref) 10 A . 5A
Permanent overload (Imax) 63 A 80 A
90
45
RESET
Intermittent overload 1890 A over 10 ms 30 Imax over 10 ms
63A
3X230(400)VAC 50/60Hz 0.5-10(63)A
C=1Wh / imp Voltage measurement
Range of measurement 230 ... 400 V ±20% 230 ... 240 V ±20%
7.5 VA max (0,5 W) per phase
Consumption (VA) Max. 2 VA E22/25/26 / 3.5 VA max (1 W)
per phase E23/24/27/28
COUNTIS E20 … E21 COUNTIS E23 …E28 280 V phase-neutral / 480 V phase-phase E20/21
Permanent overload
Type modular modular 290 V phase-neutral / 500 V phase-phase E22 ... E28
Number of modules 4 4 Energy accuracy
Dimensions W x H x D 72 x 90 x 62.5 mm 72 x 90 x 64 mm Active (according to IEC 62053-21) Class 1 Class 1
Case degree of protection IP 20 IP 20 Active (according to EN 50470) Class B Class B
Power supply
Front degree of protection IP 51 IP 51
Self-powered Yes
Display type Backlit LCD 8-digit backlit LCD
Frequency 50/60 Hz
Rigid cable cross-section 1.5 … 16 mm2 1.5 … 35 mm2 Output (pulses) COUNTIS E20 … E21 COUNTIS E22 … E28
Flexible cable cross-section 1 … 16 mm2 1.5 … 35 mm2 250 VAC/DC - 100 mA
Weight 170 g 440 g Optocoupler type (IEC 62053-31) Class A (20 ... 30 VDC) (E22) 27 VDC - 27 mA
(E23 ... E28)
2 (E22)
Number 1
1 (E23 ... E28)
Fixed pulse weight 100 Wh
50 ± 2 ms ON time
Connection Pulse duration 100 ms 30 ± 2 ms min OFF
time
Operating conditions COUNTIS E20-E21 COUNTIS E22-E28
count_182_b_1_x_cat
N
L1
L2
L1’
L2’ Operating temperature -10 … 55°C -25 … 55°C
L3 L3’ Storage temperature -20 … 70°C -25 … 75°C
+ -
Relative humidity 85% 80%
2
N
4 6 1
L1 L1’ L2
3 5 7
L2’ L3 L3’
9 11 Communication COUNTIS E23/24 COUNTIS E25/E26 COUNTIS E27/E28
COUNTIS E20 Link RS485 Wired RJ45
2 half duplex
Type Full duplex
2 to 3 half duplex (E23/24)
count_183_a_1_x_cat
N
L1 L1’ ® MODBUS TCP,
L2 L2’ Protocol MODBUS RTU M-BUS
L3 L3’ HTTP, NTP, DHCP
+ - Baudrate 1200 … 115200 bauds 300 … 9600 bauds 10/100 Mbps
2 4 6 8 10 1 3 5 7 9 11 (1) I(min) ≤ 0.5 * Itr (2) Guaranteed precision class of between I(tr) and I(max).
N T1/2 L1 L1’ L2 L2’ L3 L3’
COUNTIS E21
(3) I(ref) = I(b) (base current) = 10 * I(tr) for direct connection COUNTIS devices.
count_242_b_1_x_cat
count_323_a_1_x_cat
count_243_c_1_x_cat
count_251_a_1_x_cat
N N N N
L1 L1’ L1 L1’ L1 L1’ L1 L1’
L2 L2’ L2 L2’ L2 L2’ L2 L2’
L3 L3’ L3 L3’ L3 L3’ L3 L3’
COM - + - + M-Bus - + - +
RJ45
N 1 2 3 4 5 6 A-V A A-V A A-V A N 1 2 3 4 5 6 7 A-V A A-V A A-V A N 1 2 3 4 5 6 A-V A A-V A A-V A N 1 2 A-V A A-V A A-V A
T1/2 S0 S0 RS485 S0 T1/2 T1/2 S0 S0
COUNTIS E22 COUNTIS E22/E23/E24 COUNTIS E25/E26 COUNTIS E27/E28
References
COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS
E20 E21 E22 E23 E24 E25 E26 E27 E28
Type Reference Reference Reference Reference Reference Reference Reference Reference Reference
Direct 63 A 4850 3003
Direct 63 A - Dual tariff 4850 3004
Direct 80 A - Dual tariff + MID 4850 3049
Direct 80 A - Dual tariff + MODBUS communication via RS485 4850 3050
Direct 80 A - Dual tariff + MODBUS communication via RS485 + MID 4850 3051
Direct 80 A - Dual tariff + M-Bus communication 4850 3052
Direct 80 A - Dual tariff + M-Bus communication + MID 4850 3053
Direct 80 A - Dual tariff + Ethernet Modbus TCP communication 4850 3054
Direct 80 A - Dual tariff + Ethernet Modbus TCP + MID 4850 3055
Catalogue 2017 57
COUNTIS E3x
Active energy meters
three-phase - direct 100 A
Single-circuit metering,
> Industry
> Infrastructure
> Data centre
analysis
count_219_a
Strong points
COUNTIS E32 - MID
58 Catalogue 2017
COUNTIS E3x
Active energy meters
three-phase - direct 100 A
Error Partial
count_192_b_1_x_cat
45
Operating conditions
RESET
100A
3X230(400)VAC 50/60Hz 0.5-20(100)A
C=2Wh / imp Operating temperature -10 … 55 °C
Storage temperature -20 … 70 °C
Relative humidity 85 %
Communication COUNTIS E33/34 COUNTIS E35/E36
Link RS485 Connection
Type 2 half duplex wires 2 half duplex wires
Type modular Protocol MODBUS RTU M-BUS
Number of modules 7 Speed 4800 … 38 400 bauds 300 … 9600 bauds
Dimensions W x H x D 126 x 90 x 62.5 mm (1) I(min) ≤ 0.5 * Itr
(2) The accuracy class is guaranteed between Itr and Imax.
Case degree of protection IP20
(3) I(ref) = I(b) (base current) = 10 * I(tr) for direct connection COUNTIS.
Front degree of protection IP51
Display type backlit LCD display
Rigid cable cross-section 2.5 … 35 mm2
Flexible cable cross-section 2.5 … 35 mm2
Weight 490 g
Connection
N N N
1 1 1
L1 L1’ L1 L1’ L1 L1’
1 1 1
L2 L2’ L2 L2’ L2 L2’
1 1 1
L3 L3’ L3 L3’ L3 L3’
count_184_c_1_x_cat
count_188_e_1_x_cat
count_185_c_1_x_cat
+ - + - + -
2 4 6 1 3 5 7 9 11 2 15 17 13 1 3 5 7 9 11 2 4 6 8 10 1 3 5 7 9 11
N L1 L1’ L2 L2’ L3 L3’ N RS485 L1 L1’ L2 L2’ L3 L3’ N T1/2 L1 L1’ L2 L2’ L3 L3’
COUNTIS E30 COUNTIS E33/E34/E35/E36 COUNTIS E31/E32
1. 100 A gG / Am fuses max.
References
COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS
E30 E31 E32 E33 E34 E35 E36
Type Reference Reference Reference Reference Reference Reference Reference
100 A direct 4850 3005
100 A direct - Dual tariff 4850 3006
100 A direct - Dual tariff - MID 4850 3007
100 A direct - Dual tariff with RS485 MODBUS com. (1) 4850 3012
100 A direct - Dual tariff with RS485 MODBUS com. - MID(1) 4850 3013
100 A direct - Dual tariff with M-BUS communication (1) 4850 3025
100 A direct - Dual tariff with M-BUS communication - MID(1) 4850 3026
Management software for COUNTIS See page 140
(1) 4 tariffs through RS485 communication.
Catalogue 2017 59
COUNTIS E4x
Active energy meters
three-phase - via CT up to 6000 A
Single-circuit metering,
> Industry
> Infrastructure
> Data centre
analysis
Strong points
60 Catalogue 2017
COUNTIS E4x
Active energy meters
three-phase - via CT up to 6000 A
6
7 6. Reset key. Minimum current (Imin) 50 mA(1)
8
7. Metrological LED. Transition current (Itr) 250 mA(2)
8. Programming key. Reference current (Iref) 5 A(3)
3 4 Permanent overload (Imax) 6A
Intermittent overload 120 A for 0.5 s
Voltage measurement
Range of measurement 230 … 400 V ± 20 %
Case Consumption (VA) 2 VA
Permanent overload 280 V phase-neutral / 480 V phase-phase
62.5 Energy accuracy
72 45 Active (according to IEC 62053-21) Class 0,5s
Active (according to EN 50470) Class C (COUNTIS E42/44/E46)
Power supply
Self-supplied yes
COUNTIS E40
Error Partial
Frequency 50 / 60 Hz
count_193_b_1_x_cat
45
PROG
RESET
Number 1
3X230(400)VAC 50/60Hz 0.05-5(6)A
C=0.1Wh/imp Type of optocoupler IEC 62053-31 Class A (20 ... 30 VDC)
Pulse weight 100 Wh, 1 kWh, 10 kWh, 100 kWh
50 ms, 100 ms, 200 ms, 400 ms, 800 ms,
Pulse duration
1000 ms, 1500 ms
Operating conditions
Type modular Operating temperature -10 … 55 °C
Number of modules 4 Storage temperature -20 … 70 °C
Dimensions W x H x D 73 x 90 x 62.5 mm Relative humidity 85 %
Case degree of protection IP20 Communication COUNTIS E43/E44 COUNTIS E45/E46
Front degree of protection IP51 Link RS485 Connection
Display type backlit LCD display Type 2 half duplex wires 2 half duplex wires
Rigid cable cross-section 1.5 … 10 mm2 Protocol MODBUS RTU M-BUS
Flexible cable cross-section 1 … 6 mm2 Speed 4800 … 38400 bauds 300 … 9600 bauds
Weight 230 g (1) I(min) ≤ 0.5 * Itr
(2) The accuracy class is guaranteed between Itr and Imax.
(3) I(ref) = I(b) (base current) = 10 * I(tr) for direct connection COUNTIS.
Connection
Recommendation:
- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.
- When disconnecting the COUNTIS, the secondary of each current transformer must be short-circuited. This operation can be carried out automatically by a
SOCOMEC PTI, an accessory which is included in this catalogue. Please consult us.
N N N
L1 L1 L1
L2 L2 L2
L3 L3 L3
count_189_f_1_x_cat
count_187_d_1_x_cat
count_186_c_1_x_cat
1 1 1 1 1 1 1 1 1
+ - + - + -
4 6 12 14 16 2 1 3 5 7 9 11 RS485 12 14 16 2 1 3 5 7 9 11 4 6 8 10 12 14 16 2 1 3 5 7 9 11
U1 U2 U3 N S1 S2 S1 S2 S1 S2 U1 U2 U3 N S1 S2 S1 S2 S1 S2 T1/2 U1 U2 U3 N S1 S2 S1 S2 S1 S2
L1 L2 L3 L1 L2 L3 L1 L2 L3
COUNTIS E40 COUNTIS E43/E44/E45/E46 COUNTIS E41/E42
1. Fuses 0.5 A gG / 0.5 A class CC.
References
COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS COUNTIS
E40 E41 E42 E43 E44 E45 E46
Type Reference Reference Reference Reference Reference Reference Reference
Via CT 4850 3008
Via CT - Dual tariff 4850 3009
Via CT - Dual tariff - MID 4850 3015
Via CT - Dual tariff with RS485 MODBUS com.(1) 4850 3017
Via CT - Dual tariff with RS485 MODBUS com. - MID(1) 4850 3014
Via CT - Dual tariff with M-BUS com.(1) 4850 3027
Via CT - Dual tariff with M-BUS com. - MID(1) 4850 3028
Management software for COUNTIS See page 140
(1) 4 tariffs through RS485 communication.
Catalogue 2017 61
COUNTIS E63
Active energy meters
3 x single-phase - direct 100 A
Single-circuit metering,
Strong points
COUNTIS E63
> Compact
> Advanced multi-
measurement functions
Function Principle diagram > Detection of connection errors
The COUNTIS E63 is a modular active
electrical energy meter which provides
Conformity to standards
metering for three single-phase loads, with
direct connection of up to 100 A. It directly
> IEC 62053-21
displays the total and partial energy and
class 1
power (kWh and kW) consumed by each
single-phase load. > IEC 62053-31
> IEC 62053-11
Management software
count_205_a_1_x_cat
CO
UN
TIS
E 63
COUNTIS E63 > To get the most effective
use from your Socomec
measurement and metering
devices, we offer a range of
dedicated software tools.
See page 140.
Advantages
Compact Detection of connection errors
Due to the integration of three single-phase The product is protected against
meters in the same case (7 modules wide), phase/neutral inversion and detects wiring
the COUNTIS E63 provides significant errors. This simplifies the installation and
space-saving. commissioning, thereby reducing associated
costs, and ensures that the device operates
Advanced multi-measurement functions correctly.
Advanced multi-measurement functions are
available via RS485 MODBUS communication:
• Instantaneous currents: I1, I2, I3
• Instantaneous voltages: V1, V2, V3
• Instantaneous power: 3P, 3S
• Instantaneous power factors: 3PF
• Load curves for each of the 3 phases:
Viewing of average positive active power
consumption over a programmable period.
62 Catalogue 2017
COUNTIS E63
Active energy meters
3 x single-phase - direct 100 A
Front panel
1. Backlit LCD display
2. Navigation key
3. Reset key
4. Metrological LED
count_201x_a_1_cat
2
3
4
Case
62.5 Type modular
126 45 Number of modules 7
Dimensions W x H x D 126 x 90 x 62.5 mm
Case degree of protection IP20
Front degree of protection IP51
count_203_a_1_x_cat
COUNTIS E60
Error Partial
Display type backlit LCD display
90
45
C=2Wh / imp
Flexible cable cross-section 2.5 … 35 mm2
Weight 490 g
3 x phases 100A
Electrical characteristics
Current measurement Power supply
Type 3 x single-phase - direct 100 A Self-supplied yes
Input consumption 0.5 VA max. per phase Frequency 50 / 60 Hz
Startup current (Ist) 80 mA Operating conditions
Minimum current (Imin) 0.5 A Operating temperature -10 … 55 °C
Transition current (Itr) 2A Storage temperature -20 … 70 °C
Reference current (Iref) 20 A Relative humidity 95 %
Permanent overload (Imax) 100 A Communication
Intermittent overload 3000 A max for 10 ms Link RS485
Voltage measurement Type 2 … 3 half duplex wires
Range of measurement 230 ... 400 V ± 20 % Protocol MODBUS RTU
Consumption on inrush (VA) 2 MODBUS® speed 4800 … 38400 bauds
Permanent overload 280 V phase-neutral / 480 V phase-phase
Energy accuracy
Active (according to IEC 62053-21) Class 1
Connection
N
L1 L1’
L2 L2’
L3 L3’
count_206_b_1_GB_cat
+ - 0
2 15 17 13 1 3 5 7 9 11
N RS485 L - 1 - L’ L - 2 - L’ L - 3 - L’
COUNTIS E63
References
COUNTIS E63
Type Reference
3 x single phase - 100 A direct with RS485 MODBUS communication 4850 3016
Catalogue 2017 63
COUNTIS ECix
Multi-utility pulse concentrator
Single-circuit metering,
Strong points
kWh
€
PC
Advantages
Up to 7 multi-utility meters and RS485 MODBUS communication
2 analogue sensors • Centralisation and transmission of pulse and
• 7 digital inputs + 2 analogue inputs. analogue data to a supervision station.
• Total, partial and programmable metering • Remote configuration of COUNTIS ECi
(day, week, month, year). device.
Load curves Improved customisation
Load curves are available for each of the • Selection of the measuring unit:
7 logical inputs. kWh, m3, liters.
A history of average values are available for • Selection of the currency unit: €, K€, £, $.
the 2 analogue inputs (ECi3). Values can be displayed in the unit of your
choice and energy costs can be directly
calculated.
64 Catalogue 2017
COUNTIS ECix
Multi-utility pulse concentrator
Frequency 45 / 65 Hz
2 Consumption 5 VA
Insulation voltage 3.5 kV
3 Communication
Link RS485
Type 2 … 3 half duplex wires
Protocol MODBUS RTU
1 4
MODBUS® speed 9600 … 38400 bauds
Inputs
Number 7
Case Control voltage (integrated) 10…30 VDC
Minimum signal width 10 ms
73 67 Maximum signal width 2s
44 Minimum duration between 2 pulses 30 ms
Edge triggering rising
Analogue inputs (ECi3)
Number 2
Current 25 mA
Accuracy 0.5 %
count_208_a_1_x_cat
45
Consumption 0.1 VA
Operating conditions
Operating temperature -10 … +55 °C
Storage temperature -20 … +70 °C
Relative humidity 95 %
Type modular
Number of modules 4
Dimensions W x H x D 73 x 90 x 67 mm
Case degree of protection IP20
Front degree of protection IP51
Display type backlit LCD display
Terminal blocks type fixed
Rigid cable cross-section 1 … 10 mm2
Flexible cable cross-section 0.5 … 6 mm2
Weight 215 g
Connection
Us 31 : logical input n°1. 13-15-17 : RS485 link.
32 : logical input n°2.
1 2 3 4 5 6 7 33 : logical input n°3. 5-6 : Analogue input n°1.
1 1 34 : logical input n°4. 7-8 : Analogue input n°2.
R = 120 Ω 35 : logical input n°5. 9-10 : output.
36 : logical input n°6. 20-22 : power supply
count_209_a_1_x_cat
References
COUNTIS ECi2 COUNTIS ECi3
Auxiliary power supply Us Reference Reference
230 / 400 VAC 4853 0000
230 / 400 VAC + 2 analogue inputs 4853 0001
Catalogue 2017 65
RETROFIT Line
MID active energy meter dedicated to existing installations
Single-circuit metering,
refit_002_a_1_cat
refit_010_a_1_cat
COUNTIS E44R TC0 36
400 A
Proven products
The COUNTIS products are based on
standard SOCOMEC ranges.
66 Catalogue 2017
RETROFIT Line
MID active energy meter dedicated to existing installations
Meters
Function
The COUNTIS E4xR is an active electrical energy meter designed for The COUNTIS E44R pack offers MODBUS RTU communication via
three-phase networks. It is used for connection via TCO up to 600 A. RS485 and includes 4 tariffs.
The COUNTIS E42R is a totalising meter allowing direct reading of the COUNTIS E42R and E44R are MID-certified (B + D module).
power consumed, using a pulse output. It is a dual tariff meter for dual
tariff invoicing.
Technical characteristics(1)
References
Meters Reference Current transformers Reference
COUNTIS E42R 4850 3021 TCO 24 100/1 182T 4910
COUNTIS E44R 4850 3022 TCO 24 250/1 182T 4925
TCO 36 400/1 182T 4940
TCO 36 600/1 182T 4960
Catalogue 2017 67
RETROFIT Line
MID active energy meter dedicated to existing installations
Technical characteristics
TCO 24 TCO 36
Internal diameter (mm) 24 36
Overall accuracy class(1) 1 1
Ø Dimensions H x W x D (mm) 74.5 x 45 x 34 91 x 57 x 40.5
(1) Overall accuracy of the COUNTIS RETROFIT + TCO combination: (1) Global accuracy guaranteed when associating COUNTIS Retrofit + split-
H core CT with load between 10 % to 120 % of In.
refit_017_a_1_gb_cat
D
W
68 Catalogue 2017
RETROFIT Line
MID active energy meter dedicated to existing installations
Services
Take advantage of the advice offered by an energy specialist
Socomec offers a full range of customised • Implementation
services for your energy efficiency requirements • Training
sydiv_069_a_1_gb_cat
and can help you find the best solution: • Electrical facility audit
• Project engineering.
For more details download our Service brochure available on our web site :
www.socomec.com or contact your SOCOMEC office.
Zoom
Think about it
COUNTIS Eci
count_207_a_1_cat
Catalogue 2017 69
MULTIS L50
Digital panel meter
three phases - via CT up to 6000 A dimensions 96 x 96 mm
Single-circuit metering,
new
The solution for
measurement &
> Industry
> Infrastructure
analysis
multi_076_a_1_cat.eps
Strong points
MULTIS L50
> Large backlit LCD display
> Direct display of
Function Principle diagram multimeasurement and
metering values
The MULTIS L50 is a panel mounted digital
> RS485 MODBUS
meter displaying multi-measurement and
communication
energy values directly on its large backlit
LCD display. It is designed for utilisation > Inputs/Output for control/
on three-phase or single-phase networks command ou pulses
with connection via CT and is suitable for
applications of up to 6000 A. The product can
Conformity to standards
MUL
TIS
L5
0
Advanced functionalities
The MULTIS L50 offers input/output functions
as standard and has a pulse output or RS485
MODBUS communication output.
Functions
70 Catalogue 2017
MULTIS L50
Digital panel meter
three phases - via CT up to 6000 A dimensions 96 x 96 mm
Front panel
1. Backlit LCD display.
2. Direct access key for currents (instantaneous and max. values), current THD.
3. Direct access key for voltages, frequency and voltage THD.
4. Pushbutton for active, reactive, and apparent power (instantaneous and max. values)
and power factor.
multi_076x_a_2_cat.eps
5. Direct access key for energies, hour meter and programming menu.
1 2 3 4 5
Case
92 +- 0.0
0.8
Type panel mounting
Dimensions W x H x D 96 x 96 x 60 mm
Case degree of protection IP30
Front degree of protection IP52
Display type backlit LCD display
Terminal block type fixed or plug-in
Voltage and other connection cross-section 0.2 … 2.5 mm2
multi_075_a_1_x_cat.eps
96
MU
LTIS
L5
0
92 +- 0.0
0.8 Current connection cross-section 0.5 … 6 mm2
Weight 400 g
I
35
>
V
F
> P
45
PF
OK
E
PR
15
OG
96
Plug-in modules
MULTIS L50
1 Output
diris_445_a_1_cat
Communication
diris_447_a_1_cat
3 inputs, 1 output
diris_449_a_1_cat
Accessories
Current transformers IP65 protection Panel mounting kit
(See page 106) for a 144 x 96 mm cut-out
trafo_077_b_2_cat
diris_720_a_2_cat
diris_718_b_1_cat
trafo_024_a_2_cat
Catalogue 2017 71
MULTIS L50
Digital panel meter
three phases - via CT up to 6000 A dimensions 96 x 96 mm
Electrical characteristics
Current measurement (TRMS) Energy accuracy
Via CT primary 9 999 A Active (according to IEC 62053-21) Class 1
Via CT secondary 5A Reactive (according to IEC 62053-23) Class 2
Measurement range 0 … 11 kA Auxiliary power supply
Input consumption 0.6 VA Alternating voltage 110 … 250 VAC
Measurement updating period 1s AC tolerance ± 10 %
Direct voltage 120 … 250 VDC
Accuracy 1%
DC tolerance ± 10%
Permanent overload 6A
Frequency 50 / 60 Hz
Intermittent overload 10 In for 1 s
Consumption 10 VA
Voltage measurements (TRMS) Pulse or alarm output
Direct measurement between phases 50 … 500 VAC Number 1
Direct measurement between phase and neutral 28 … 289 VAC Type 100 VDC - 0.5 A - 10 VA
Input consumption ≤ 0.1 VA Max. number of operations ≤ 108
Measurement updating period 1s Inputs
Accuracy 1% Number 3
Permanent overload 800 VAC Power supply 10 … 30 VDC
Power measurement Minimum signal width 10 ms
Measurement updating period 1s Minimum duration between 2 pulses 18 ms
Accuracy 1% Type Phototransistors
Power factor measurement Communication
Measurement updating period 1s Link RS485
Accuracy 1% Type 2 … 3 half duplex wires
Frequency measurement Protocol MODBUS RTU
MODBUS® speed 1400 … 38400 bauds
Measurement range 45 … 65 Hz
Operating conditions
Measurement updating period 1s
Operating temperature - 10 … + 55 °C
Accuracy 0.1 %
Storage temperature - 20 … + 85 °C
Relative humidity 95 %
Terminals
multi_063_a_1_x_cat.eps
multi_065_a_1_x_cat.eps
multi_066_a_1_x_cat.eps
+ - + - + -
0V - + 1 1 8 19
1 2 13 1 4 15 1 6 17 1 9 18
0n OUT 1
RS485 R = 120 IN 3 IN 2 IN 1 OUT 1
Connection
Recommendation:
- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.
- When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out automatically by a SOCOMEC
PTI, an accessory which is included in this catalogue. Please consult us.
1 1 1 1 1 1
multi_073_a_1_x_cat.eps
multi_074_a_1_x_cat.eps
multi_072_a_1_x_cat.eps
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3
Use of 1 CT reduces by 0.5% the accuracy of the phases, 1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC.
72 Catalogue 2017
MULTIS L50
Digital panel meter
three phases - via CT up to 6000 A dimensions 96 x 96 mm
3/4 wires with 3 CTs 3 wires with 2 CTs 3 wires with 2 CTs
P1 L1 P1 L1
N S1 S2 S1 P1
P1 L2 L2
L1 P1 S1 S2
S1 S2 L3 L3
L2
P1 S1 S2
L3
S1 S2
1 1 1 1 1 1
multi_070_a_1_x_cat.eps
multi_071_a_1_x_cat.eps
diris_395_d_1_x_cat.eps
1 1 1
S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
V1 V2 V3 VN
I1 I2 I3 I1 I2 I3 I1 I2 I3
1. Fuses 0.5 A gG / 0.5 A class CC. Use of 2 CTs reduces by 0.5% the accuracy of the Use of 2 CTs reduces by 0.5% the accuracy of the
phases, the current of which is worked out by vector phases, the current of which is worked out by vector
calculation. calculation.
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
Additional information
1 1
LIYCY-CY
multi_067_a_1_x_cat.eps
multi_068_a_1_x_cat.eps
0V - + A U X
ON
RS485
References
Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.
Catalogue 2017 73
DIRIS A10
Multifunction meters - PMD
modular multifunction meter
Single-circuit metering,
> Industry
> Infrastructures
> Data centres
analysis
diris_791_c_1_cat
DIRIS A10 Strong points
Function Principle diagram > Easy to use
The DIRIS A10 is a modular multifunction > Integrated temperature
meter for measuring electrical values in low sensor
voltage networks. > Detects wiring errors
It allows all electrical parameters to be > Compliant with IEC 61557-12
displayed and utilised for communication and/
or output functions.
Conformity to standards
Advantages
> IEC 61557-12
Easy to use
> IEC 62053-22
Five direct access pushbuttons enable all RS485 DIRIS A10
DIRIS A10 class 0.5S
measurements to be clearly viewed on its
backlit LCD display. > IEC 62053-23
485 General
measurement
class 2
ETH
Integrated temperature sensor report
74 Catalogue 2017
DIRIS A10
Multifunction meters - PMD
modular multifunction meter
Front panel
power factor.
2 5. Direct access key for energies.
3 6. Pushbutton for hour meter, temperature and programming menu access.
4 7. Metrological LED.
5
6
7
Case
64
72 44
Type modular
Number of modules 4
Dimensions W x H x D 72 x 90 x 64 mm
DIRIS A 10 Case degree of protection IP 30
diris_809_a_1_x_cat
I TEST
Front degree of protection IP 52
V F
Display type backlit LCD display
45
90
P PF
E OK
Voltage and current connection
°C PROG 4 mm2
cross-section
C=0,1Wh/imp
Electrical characteristics
Current measurement (TRMS) Energy accuracy
Via CT primary 9 999 A Active (according to IEC 62053-22) Class 0.5 S
Via CT secondary 5A Reactive (according to IEC 62053-23) Class 2
Measurement range 0 … 11 kA Auxiliary power supply
Input consumption 0.6 VA Alternating voltage 110 … 277 VAC
Measurement updating period 1s AC tolerance ± 15 %
Accuracy 0.2 % Frequency 50 / 60 Hz
Permanent overload 6A Consumption < 3 VA
Intermittent overload 10 In for 1 s Digital output (pulses or on/off)
Voltage measurements (TRMS) Number 1
Direct measurement between phases 50 … 500 VAC Type 20 / 30 VDC - 0.5 A - 10 VA
Direct measurement between phase and neutral 28 … 289 VAC Max. number of operations ≤ 108
Input consumption ≤ 0.1 VA Input (tariff)
Measurement updating period 1s Number 1
Accuracy 0.2 % Type 0 VAC: T1 / 200-277 VAC: T2
Permanent overload 800 VAC Communication
Power measurement Link RS485
Measurement updating period 1s Type 2 … 3 half duplex wires
Accuracy 0.5 % Protocol MODBUS RTU
Power factor measurement MODBUS® speed 2400 … 38400 bauds
Measurement updating period 1s Operating conditions
Accuracy 0.5 % Operating temperature - 10 … + 55 °C
Frequency measurement Storage temperature - 20 … + 70 °C
Measurement range 45 … 65 Hz Relative humidity 85 %
Measurement updating period 1s
Accuracy 0.1 %
Catalogue 2017 75
DIRIS A10
Multifunction meters - PMD
modular multifunction meter
Connection
Recommendation:
- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.
- When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out automatically by
a SOCOMEC PTI, an accessory which is included in this catalogue. Please consult us.
- It is recommended that the earthing point for the DIRIS A10 and the current transformer secondaries are not earthed at the same time.
N P1 P1
P1 L1 L1
L1 S1 S2 S1 S2
S1 S2 N L2
L2
L3
1 1 1 1 1 1
diris_810_a_1_gb_cat
diris_811_a_1_gb_cat
diris_812_a_1_gb_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
3/4 wires with 3 CTs 3 wires with 2 CTs 3 wires with 2 CTs
N P1 L1 P1 L1
P1 L1 S1 S2 L2 S1 P1 L2
S1 S2 L2 P1 L3 S1 S2 L3
P1 L3 S1 S2
S1 S2
1 1 1 1 1 1
diris_813_a_1_gb_cat
diris_814_a_1_gb_cat
diris_815_a_1_gb_cat
1 1 1
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3
1. Fuses 0.5 A gG / 0.5 A class CC. Use of 2 CTs reduces by 0.5% the accuracy of the Use of 2 CTs reduces by 0.5% the accuracy of the
phases, the current of which is worked out by vector phases, the current of which is worked out by vector
calculation. calculation.
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
Additional information
Communication via RS485 link AC auxiliary power supply
110-277 VAC
1 1
LIYCY-CY
diris_821_e_1_x_cat
diris_820_a_1_x_cat
0V - + 20 22
AUX
RS485
76 Catalogue 2017
DIRIS A10
Multifunction meters - PMD
modular multifunction meter
Terminals
diris_816_a_1_x_cat
12 14 16 2 20 22 1 3 5 7 9 11 18
V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2
I1 I2 I3
DIRIS A10
AUX: auxiliary power supply Us. S1 - S2: current inputs.
V1, V2, V3 & VN: voltage inputs.
diris_819_b_1_x_cat
diris_816_a_1_x_cat
diris_818_a_1_x_cat
1 3 15 17 4 6 8 10
0V + - OUT 1 IN 1
RS485
References
Basic device DIRIS A10
Description Reference
DIRIS A10 (available in light grey on request) 4825 0010
DIRIS A10 with RS485 MODBUS communication (available in light grey on request) 4825 0011
Description of accessories To be ordered in multiples of Reference
Fuse disconnect switches for the protection of voltage inputs (type RM) 3 poles 4 5601 0018
Fuse disconnect switches for the protection of the auxiliary supply (type RM) 1 pole + neutral 6 5601 0017
Fuses type gG 10x38 0.5 A 10 6012 0000
Current transformer range 1 see page 106
Management software for DIRIS see page 140
Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.
Catalogue 2017 77
DIRIS A14
Multifunction measuring unit - PMD - MID
multi-measurement
Single-circuit metering,
new
measurement &
> Industry
> Infrastructures
> Data centers
analysis
diris_964_a_1_cat
diris_908_a_1_cat
DIRIS A14 panel mounted DIRIS A14 DIN rail mounted Strong points
Advantages
DIRIS A14 Compliance with standards
Single phase and three phase MID certified RS485 door mounted
DIRIS A14
DIRIS A14 products with MID certification DIN rail mounted > IEC 61557-12
provide the guaranteed accuracy required 485 General > IEC 62053-23
for applications in which sub-billing of the ETH measurement
report class 2
electrical energy consumed is necessary, > EN50470-1
whether on a three-phase or single-phase
network. “Module B+D” certification > EN50470-3 class C
PC Curves for
guarantees that the design and manufacturing current
diris_907_c_1_fr_cat
Functions
Multi-measurement Total and partial metering Events (via communication)
• Currents • Active energy: + kWh, - kWh • Active energy consumption:
- instantaneous: I1, I2, I3, In • Reactive energy: + kvarh, - kvarh day n-1 / week n-1 / month n-1
- maximum average: I1, I2, I3, In • Active power load curves:
Harmonic analysis (via communication) P 10 minutes over 7 days with time-log
• Frequency • Total harmonic distortion (rank 63)
• Voltages Communications
- Currents: thd I1, thd I2, thd I3
- instantaneous: V1, V2, V3, U12, U23, U31, F RS485 with MODBUS protocol
- Phase-to-neutral voltage: thd V1, thd V2, thd
• Powers V3
- instantaneous: ΣP, ΣQ, ΣS Phase-to-phase voltage: thd U12, thd U23, thd
- maximum average: ΣP, ΣQ, ΣS U31
• Power factor (cos ϕ) Multi tariff function (via communication)
- instantaneous: Σ cos ϕ Selection of one out of 4 billing tariffs
- maximum average: Σ cos ϕ
78 Catalogue 2017
DIRIS A14
Multifunction measuring unit - PMD - MID
multi-measurement
Front panel
1. Backlit LCD display
2. Direct access for energies and validation key
3. Programming key
4. Navigation key for measurements
5. Metrological LED
6. MID marking
7. Serial Number
2
1 2
3
6 4 3
diris_908x_a_2_cat
diris_964x_a_2_cat
7 5
5
1 6
7
Case
DIRIS A14 DIN rail mounted
64 DIRIS A14 DIRIS A14
72 6 44 DIN rail mounted door mounted
Type modular Recessed
Number of modules 4 -
Dimensions W x H x D 72 x 90 x 64 mm 96 x 96 x 69.5 mm
diris_906_a_1_x_cat
96 69.5 24
diris_914_a_1_x_cat
96
Electrical characteristics
Current measurement (TRMS) Energy accuracy
Via CT primary 10 … 2500 A Active (according to IEC 62053-22) Class 0.5 S
Via CT secondary 5A Reactive (according to IEC 62053-23) Class 2
Input consumption 0.6 VA Active (according to EN 50470) Class C
Startup current (Ist) 5 mA Metrological LED (EA+,EA-)
Minimum current (Imin) 50 mA Pulse weight 10000 pulses/kWh
Transmission current (Itr) 250 mA Colour Red
Reference current (Iref) 5A Auxiliary power supply
Measurement updating period 1s Self-powered Yes
Accuracy 0.5% Frequency 50 / 60 Hz
Permanent overload 6A Communication
Intermittent overload 120 A for 0.5 s Link RS485
Voltage measurements (TRMS) Type 2 to 3 half duplex wires
Direct measurement (four phases) 50 …460 VAC Protocol MODBUS® RTU
Input consumption 2 VA MODBUS® speed 4800 … 38400 bauds
Measurement updating period 1s Operating conditions
Accuracy 0.2% Operating temperature -10 … +55°C
Permanent overload 480 V (phase-to-phase measurement) Storage temperature -20 … +70°C
Power measurement Relative humidity 95% non-condensing
Measurement updating period 1s
Accuracy 0.5%
Power factor measurement (cos ϕ)
Measurement updating period 1s
Accuracy 0.01
Catalogue 2017 79
DIRIS A14
Multifunction measuring unit - PMD - MID
multi-measurement
Connection
Low voltage balanced network
Recommendation:
- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.
- When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited.
This operation can be carried out automatically by a SOCOMEC PTI, which can be found in the SOCOMEC catalogue: please consult us.
N P1 L1
P1 L1 S1 S2 N
S1 S2 L2
P1 L3
S1 S2
1
diris_902_b_1_x_cat
1 1 1
diris_916_a_1_x_cat
V1 V2 V3 N S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3
1 1 1 1 1 1
diris_918_a_1_x_cat
diris_917_a_1_x_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3
Additional information
LIYCY-CY
diris_903_a_1_x_cat
NC - +
RS485
80 Catalogue 2017
DIRIS A14
Multifunction measuring unit - PMD - MID
multi-measurement
Terminals
Voltage outlets Current inputs
V 12 I1 S1 1
V2 14 I1 S2 3
V3 16 I2 S1 5
N 2 I2 S2 7
ICM (Intelligent Communication Module) I3 S1 9
RS485 “+” 15 I3 S2 11
RS485 “-” 17
RS485'NC" 13
References
Basic device DIRIS A14
Description Reference
DIRIS A14 MID DIN rail mounted 4825 0020
DIRIS A14 MID door mounted 4825 0021
Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.
Catalogue 2017 81
DIRIS A20
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
Single-circuit metering,
> Industry
> Infrastructure
> Data centre
analysis
diris_750_a_1_cat
DIRIS A20
Strong points
Functions
82 Catalogue 2017
DIRIS A20
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
Front panel
1. Backlit LCD display.
2. Direct access key for currents (instantaneous and max. values),
current THD and test function.
3. Direct access key for voltages, frequency and voltage THD.
4. Pushbutton for active, reactive, and apparent power (instantaneous
and max. values) and power factor.
DIRIS_743x_a_2_cat
5. Direct access key for energies, hour meter and programming menu.
1 2 3 4 5
Case
92 +- 0.0
0.8
Type panel mounting
Dimensions W x H x D 96 x 96 x 60 mm
Case degree of protection IP30
Front degree of protection IP52
Display type backlit LCD display
Terminal block type Fixed or plug-in
Voltage and other connection cross-section 0.2 … 2.5 mm2
DIRIS_577_d_1_x_cat
96 DIR
IS
Current connection cross-section 0.5 … 6 mm2
A2
0
92 +- 0.0
0.8
Weight 400 g
I
35
5/TE
ST V
F
4 P
45
PF
OK
E
PR
15
OG
96
Plug-in modules
DIRIS® A20
1 Output
DIRIS_445_a_1_cat
Communication
RS485 link with JBUS / MODBUS protocol
(speed up to 38400 bauds)
3 inputs, 1 output
diris_449_a_1_cat
Accessories
Current transformers IP65 protection Panel mounting kit
(see page 106) for a 144 x 96 mm cut-out
DIRIS_720_a_2_cat
trafo_077_b_2_cat
DIRIS_718_b_1_cat
trafo_024_a_2_cat
Catalogue 2017 83
DIRIS A20
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
Electrical characteristics
Current measurement (TRMS) Energy accuracy
Via CT primary 9 999 A Active (according to IEC 62053-22) Class 0.5 S
Via CT secondary 5A Reactive (according to IEC 62053-23) Class 2
Measurement range 0 … 11 kA Auxiliary power supply
Input consumption 0.6 VA Alternating voltage 110 … 400 VAC
Measurement updating period 1s AC tolerance ± 10 %
Direct voltage 120 … 350 VDC
Accuracy 0.2 %
DC tolerance ± 20 %
Permanent overload 6A
Frequency 50 / 60 Hz
Intermittent overload 10 In for 1 s
Consumption 10 VA
Voltage measurements (TRMS) Pulse or alarm output
Direct measurement between phases 50 … 500 VAC Number 1
Direct measurement between phase and neutral 28 … 289 VAC Type 100 VDC - 0.5 A - 10 VA
Input consumption ≤ 0.1 VA Max. number of operations ≤ 108
Measurement updating period 1s Inputs
Accuracy 0.2 % Number 3
Permanent overload 800 VAC Power supply 10 … 30 VDC
Power measurement Minimum signal width 10 ms
Measurement updating period 1s Minimum duration between 2 pulses 18 ms
Accuracy 0.5 % Type Phototransistors
Power factor measurement Communication
Measurement updating period 1s Link RS485
Accuracy 0.5 % Type 2 … 3 half duplex wires
Frequency measurement Protocol MODBUS RTU
MODBUS® speed 1400 … 38400 bauds
Measurement range 45 … 65 Hz
Operating conditions
Measurement updating period 1s
Operating temperature - 10 … + 55 °C
Accuracy 0.1 %
Storage temperature - 20 … + 85 °C
Relative humidity 95 %
Terminals
V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2
I1 I2 I3 AUX: auxiliary power supply Us.
V1, V2, V3 & VN: voltage inputs.
DIRIS A20
+ - + - + -
0V - + 1 1 8 19
1 2 13 1 4 15 1 6 17 1 9 18
0n OUT 1
RS485 R = 120 IN 3 IN 2 IN 1 OUT 1
Connection
Recommendation:
- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.
- When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out automatically by a SOCOMEC
PTI, an accessory which is included in this catalogue. Please consult us.
1 1 1 1 1 1
diris_392_d_1_x_cat
diris_393_d_1_x_cat
diris_394_d_1_x_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3
Use of 1 CT reduces by 0.5% the accuracy of the phases, 1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC.
84 Catalogue 2017
DIRIS A20
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
3/4 wires with 3 CTs 3 wires with 2 CTs 3 wires with 2 CTs
P1 L1 P1 L1
N S1 S2 S1 P1
P1 L2 L2
L1 P1 S1 S2
S1 S2 L3 L3
L2
P1 S1 S2
L3
S1 S2
diris_396_d_1_gb_cat
1 1 1 1 1 1
diris_395_d_1_fr_cat
diris_397_d_1_x_cat
1 1 1
S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
V1 V2 V3 VN
I1 I2 I3 I1 I2 I3 I1 I2 I3
1. Fuses 0.5 A gG / 0.5 A class CC. Use of 2 CTs reduces by 0.5% the accuracy of the Use of 2 CTs reduces by 0.5% the accuracy of the
phases, the current of which is worked out by vector phases, the current of which is worked out by vector
calculation. calculation.
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
Additional information
1 1
diris_400_i_1_fr_cat
LIYCY-CY
diris_398_c_1_x_cat
0V - + A U X
ON
RS485
References
Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.
Catalogue 2017 85
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
Single-circuit metering,
> Industry
> Data centres
> Infrastructures
analysis
DIRIS A41
diris_581_f_1_gb_cat
user has access to all the measurements > Detects wiring errors
required for successfully carrying out energy Ethernet
> Customisable
efficiency projects and ensuring the electrical
> Webserver function
distribution is monitored. DIRIS A40 DIRIS A40 DIRIS A40
86 Catalogue 2017
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
Front panel
1. Backlit LCD display.
2. Direct access key for currents and test function.
3. Direct access key for voltages and frequency.
4. Direct access key for active, reactive, and apparent powers and power factor.
5. Direct access key for maximum and average current and power values.
6. Direct access key for harmonic values.
7. Direct access key for energies, hour meter and programming menu.
diris_744x_a_1_cat
1 2 3 4 5 6 7
Plug-in modules
Pulse outputs
diris_445_a_1_cat
Communication MODBUS®
diris_447_a_1_cat
PROFIBUS® DP communication
SUB-D9 link with PROFIBUS® DP protocol (speed up to 12 Mbauds).
diris_773_a
diris_777_a_1_cat
Ethernet communication
• Ethernet connection with MODBUS TCP or MODBUS RTU over TCP protocol.
• Embedded Webserver function (1).
• Ethernet connection with MODBUS TCP or MODBUS RTU over TCP protocol.
• Connection of 1 to 247 RS485 MODBUS slaves.
• Embedded Webserver function (1).
Analogue outputs
DIRIS® A41* A maximum of 2 modules may be connected, providing up to 4 analogue outputs.
diris_448_a_1_cat
2 inputs - 2 outputs
A maximum of 3 modules may be connected, providing up to 6 inputs and 6 outputs.
Per module 2 outputs assignable to:
diris_449_a_1_cat
- monitoring: 3I, In, 3V, 3U, F, ±ΣP, ±ΣQ, SS, ΣPFL/C, THD 3I, THD In, THD 3V, THD
diris_774_a
3U, Ppred, Qpred, Spred, internal T°C, T°C 1, T°C2, T°C3 and hour meter,
- remote control,
- timed remote control.
- 2 inputs for pulse metering.
* with a factory fitted neutral CT module.
Memory
diris_682_a_1_cat
Temperature(2)
diris_747_a_2_cat
Temperature indication:
- internal,
- external sensor PT 100 (T°C 1), (1) See "Management software for DIRIS" page 140.
- external sensor PT 100 (T°C 2), (2) See "external sensor PT 100" page 122.
Catalogue 2017 87
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
Accessories
Current transformers IP65 protection Panel mounting kit for a 144 x 96 mm cut-out
(see page 106)
trafo_077_b_2_cat
trafo_024_a_2_cat
diris_718_b_1_cat
diris_720_a_2_cat
Terminals
DIRIS A40
S1 - S2: current inputs
diris_569_a_1_x_cat
V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2
AUX: auxiliary power supplies Us
I1 I2 I3
V1- V2 - V3 - VN: voltage inputs
DIRIS A40
DIRIS A41
V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 IN AUX: auxiliary power supplies Us
V1- V2 - V3 - VN: voltage inputs
DIRIS A41
Communication module Pulse output module Analogue output module
diris_571_a_1_x_cat
diris_572_a_1_x_cat
1 2 3 4 5 6 7 8
diris_573_a_1_x_cat
0V - + 1
0n + - + -
RS485 R = 120 0/4-20 mA 0/4-20 mA
OUT 1 OUT 2 OUT 1 OUT 2
DIRIS A40 / A41 DIRIS A40 / A41 DIRIS A40 / A41
RS485 link. 1 - 2 : pulse output n°1. 5 - 6 : analogue output n°1.
R = 120 Ω: selectable internal resistance 3 - 4 : pulse output n°2. 7 - 8 : analogue output n°2.
for RS485 end of line termination.
diris_753_a_1_gb_cat
19 20 21 22 23 24 25 26
9 10 11 12 17 18
sensor 1 sensor 2
OUT 1 OUT 2 + -
IN
diris_574_b_1_x_cat
A-Cd A-Cd
synchro 27 28 29 30
DIRIS A40 / A41 sensor 3
1 3 14 15 16
- + - + DIRIS A40/A41
IN 1 IN 2 17 - 18 : synchronisation input. Sensor 1 Sensor 2 Sensor 3
DIRIS A40 / A41 19 : red 23 : red 27 : red
9 - 10 : relay output n°1. 20 : red 24 : red 28 : red
11 - 12 : relay output n°2. 21 : white 25 : white 29 : white
13 - 14 : opto input n°1. 22 : white 26 : white 30 : white
15 - 16 : opto input n°2.
10 BASE T 10 BASE T 0V - + 1
100 BASE T 100 BASE T 0n
RS485
RJ45 RJ45 gateway R = 120Ω
DIRIS A40/A41 DIRIS A40/A41
88 Catalogue 2017
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
Electrical characteristics
Current measurement on insulated inputs (TRMS) 2 inputs / 2 outputs module: Outputs (alarms / control)
Via CT primary 9 999 A Number of relays 2(1)
Via CT secondary 1 or 5 A Type 250 VAC - 5 A - 1150 VA
Measurement range 0 … 11 kA 2 inputs / 2 outputs module: Phototransistor inputs
Input consumption ≤ 0.1 VA Number 2(1)
Measurement updating period 1s Power supply 10 … 30 VDC
Accuracy 0.2 % Minimum signal width 10 ms
Permanent overload 6A Minimum duration between 2 pulses 18 ms
Intermittent overload 10 In for 1 s Type phototransistors
Voltage measurements (TRMS) Pulse output module
Direct measurement between phases 50 … 700 VAC Number of relays 2
Direct measurement between phase and neutral 28 … 404 VAC Type 100 VDC - 0.5 A - 10 VA
VT primary 500 000 VAC Max. number of operations ≤ 108
VT secondary 60, 100, 110, 173, 190 VAC Analogue output module
Frequency 50 / 60 Hz Number of outputs 2(2)
Input consumption ≤ 0.1 VA Type insulated
Measurement updating period 1s Range 0 / 4 … 20 mA
Accuracy 0.2 % Load resistance 600 Ω
Permanent overload 800 VAC Maximum current 30 mA
Current-voltage product MODBUS communication module
Limitation for 1A CT 10 000 000 Link RS485
Limitation for 5A CT 10 000 000 Type 2 … 3 half duplex wires
Power measurement Protocol MODBUS RTU
Measurement updating period 1s MODBUS® speed 4800 … 38400 bauds
Accuracy 0.5 % PROFIBUS-DP communication module
Power factor measurement Link SUB-D9
Measurement updating period 1s Protocol PROFIBUS® DP
Accuracy 0.5 % PROFIBUS® speed 9.8 kbauds … 12 Mbauds
Frequency measurement Ethernet communication module
Measurement range 45 … 65 Hz Connection RJ45
Measurement updating period 1s Speed 10 base T / 100 base T
Accuracy 0.1 % Protocol MODBUS TCP or MODBUS RTU over TCP
Energy accuracy Temperature module (inputs)
Active (according to IEC 62053-22) Class 0.5 S Type PT100
Reactive (according to IEC 62053-23) Class 2 Connection 2, 3 or 4 wires
Auxiliary power supply Dynamic - 20 ... 150 °C
Alternating voltage 110 … 400 VAC Accuracy ±1 digit
AC tolerance ± 10 % Maximum length 300 cm
Direct voltage 120 … 350 VDC / 12 … 48 VDC Operating conditions
DC tolerance ± 20 % / - 6 … + 20 % Operating temperature - 10 … + 55 °C
Frequency 50 / 60 Hz
Storage temperature - 20 … + 85 °C
Consumption ≤ 10 VA
Relative humidity 95 %
(1) Max. 3 modules / DIRIS.
(2) Max. 2 modules / DIRIS.
Case
+ 0.8
92 - 0.0
35
45
15
96
Catalogue 2017 89
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
Connections
Recommendation: When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out
automatically by a SOCOMEC PTI, an accessory which is included in this catalogue. Please consult us.
In TNC neutral systems it is recommended to use the functional earth module.
1 1 1 1 1 1
diris_392_d_1_x_cat
diris_393_d_1_x_cat
diris_394_d_1_x_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3
Use of 1 CT reduces by 0.5% the accuracy of the phases, 1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC.
diris_396_d_1_x_cat
diris_397_e_1_x_cat
1 1 1 1 1 1
1 1 1
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3
1. Fuses 0.5 A gG / 0.5 A class CC. Use of 2 CTs reduces by 0.5% the accuracy of the phases, Use of 2 CTs reduces by 0.5% the accuracy of the phases,
the current of which is worked out by vector calculation. the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
1 1 1
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 IN
1. Fuses 0.5 A gG / 0.5 A class CC.
Additional information
Communication via RS485 link Connection of voltage transformer for HV networks AC & DC auxiliary power supply
110 / 400 VAC
L1
120 / 350 VDC
L2
L3
1 1
LIYCY-CY
diris_399_b_1_x_cat
diris_398_c_1_x_cat
A U X
diris_400_i_1_x_cat
0V - +
ON
V1 V2 V3 N
RS485
1. Fuses 0.5 A gG / 0.5 A class CC.
90 Catalogue 2017
DIRIS A40/A41
Multifunction meters - PMD
multi-measurement meter - dimensions 96 x 96 mm
References
DIRIS A41
Basic device DIRIS A40 with CT on the
neutral
Auxiliary power supply Us Reference Reference
110 ... 400 VAC / 120 ... 350 VDC 4825 0201 4825 0202
12 ... 48 VDC 4825 1201 4825 1202
Options
Plug-in modules(1) Reference Reference
Pulse outputs 4825 0090 4825 0090
RS485 MODBUS® communication 4825 0092 4825 0092
Analogue outputs 4825 0093 4825 0093
2 inputs / 2 outputs 4825 0094 4825 0094
Communication Sub D9 PROFIBUS®DP(2) 4825 0205 4825 0205
Memory 4825 0097 4825 0097
Embedded Webserver function (2). 4825 0203 4825 0203
Ethernet communication + RS485 MODBUS gateway (Embedded Webserver function)(2) 4825 0204 4825 0204
Temperature inputs 4825 0206 4825 0206
(1) Ease of integration for additional functions (maximum 4 slots on A40 and 3 on A41).
(2) Dimension of the plug-in module: 2 slots.
Accessories
To be ordered To be ordered
Description of accessories Reference Reference
in multiples of in multiples of
IP65 protection 1 4825 0089 1 4825 0089
Panel mounting kit for a 144 x 96 mm cut-out 1 4825 0088 1 4825 0088
Fuse disconnect switches for the protection of voltage inputs (type RM) 3 poles 4 5601 0018 4 5601 0018
Fuse disconnect switches for the protection of the auxiliary supply (type RM)
6 5601 0017 6 5601 0017
1 pole + neutral
Fuse type gG 10 x 38 0.5 A 10 6012 0000 10 6012 0000
Current transformer range 1 see page 106 1 see page 106
Ferrite to be associated with communication modules 1 4899 0011 4899 0011
Temperature sensor PT100 - M6 screw type 1 4825 0208 1 4825 0208
Temperature sensor PT100 - M6 eyelet type 1 4825 0209 1 4825 0209
Management software for DIRIS see page 140
Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.
Catalogue 2017 91
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm
Single-circuit metering,
DIRIS A60
DI
RIS
> Industry
A6
> Infrastructure
0
Ethernet
analysis
RS485
General
measurement
report
PC
diris_826_c_1_gb_cat
Energy efficiency
software
Curves for
current
DIRIS A60 per phase
Strong points
PLC
Function > Easy to use
DIRIS A60 is a panel mounted multifunction meter which incorporates all functions of the > Detects wiring errors
DIRIS A40 with the addition of enhanced data logging functions, recording curves for quality
events. All this information can be analysed remotely using the Analysis software which is available > Compliant with IEC 61557-12
at no charge and can be downloaded from the SOCOMEC website www.socomec.com. > Management softwares
> Conformity to standard
Advantages EN 50160
Easy to use Management softwares
Thanks to its large backlit LCD display and • Optional Ethernet module with Webserver
its multiple viewing screens with direct key function: For measurement monitoring, data Conformity to standards
access, the DIRIS A60 provides clear readings exploitation and the export of load curves
and is easy to use. remotely without a specific software (web > IEC 61557-12
It directly displays a number of multi- browser access). > IEC 62053-22
measurement and metering values : +/- kWh, • Analysis software: For the analysis of events class 0.5S
+/- kvarh, kVAh, I, U, V, F, P, Q, S, PF, etc. data in order to improve the reliability of the
electrical installation. > IEC 62053-23
Detects wiring errors
class 2
An integrated test function can be utilised to • Easy Config software: For quick and easy
detect incorrect wiring and to automatically remote device configuration; configuration > EN 50160
correct CT installation errors. files can be copied from and sent to the
Compliant with IEC 61557-12 DIRIS A60, or they can be created without
communication and sent at a later time.
IEC 61557-12 is a high-level standard for all
Multiple devices can be configured from
PMDs (Performance Monitoring Devices) that
a single file, which is especially useful for
are designed to measure and monitor electrical
OEMs and panel builders.
parameters in distribution networks.
Conformity to standard EN 50160
Compliance with IEC 61557-12 ensures
a high level of equipment performance, in EN 50160 is a standard which defines events
terms of metrology, and the mechanical and relating to the quality of electrical networks.
environmental aspects (EMC, temperature, etc.). The DIRIS A60 captures voltage events in
accordance with this standard.
Functions
In addition to the functions of the Other functions: • Temperatures(1) Events (1)
DIRIS A40, the DIRIS A60 also: Multi-measurement - internal, • Alarms on all electrical values
• shows the current and voltage Currents - external via 3 PT100 sensors Communications(1)
unbalance - instantaneous: I1, I2, I3, In, Isystem, Metering • 0/4- 20 mA analogue output
• shows the tangent ϕ - average/maximum average: I1, I2, • Active energy: +/- kWh • RS485 MODBUS RTU
• stores the load curves (60 days I3, In, • Reactive energy: +/- kvarh • Ethernet (MODBUS TCP or
with an interval of 10 minutes) for - unbalance: I unb. MODBUS RTU over TCP and
the active, reactive and apparent • Apparent power: kVAh
• Voltages & frequency • Hours: Webserver)
power: ΣP+/- ; ΣQ+/-, ΣS
- instantaneous: V1, V2, V3, U12, U23, Harmonic analysis (level 63) • Ethernet (MODBUS TCP or
• detects and stores the last MODBUS RTU over TCP and
40 events concerning: U31, F, Vsystem, Usystem • Total harmonic distortion
- average/maximum average: V1, V2, Webserver) with RS485 MODBUS
- overvoltage - Currents: thd I1, thd I2, thd I3, RTU gateway
V3, U12, U23, U31, F thd In
- voltage dips Inputs / Outputs (1)
- unbalance: U unb. - Phase-to-neutral voltage: thd V1,
- cut-offs • Pulse metering
• Power thd V2, thd V3
- overcurrent. • Remote control/command
- instantaneous: 3P, ΣP, 3Q, ΣQ, 3S, ΣS - Phase-to-phase voltage: thd U12,
For each stored event, the DIRIS • Alarm report
A60 records the relevant RMS 10 ms - maximum average: ΣP, ΣQ, ΣS thd U23, thd U31
• Individual • Pulse report
interval curves for the voltages V1, V2, - predictive: ΣP, ΣQ, ΣS.
V3, U12, U23, U31 and the currents I1, • Power factor - PF, ΣPF - Currents: HI1, HI2, HI3, HIn
(1) Available as an option
I2, I3, In, giving a total of 400 curves. • Instantaneous total tangent ϕ - Phase-to-neutral voltage: HV1, (see the following pages).
• Instantaneous, average and max. HV2, HV3,
average unbalance - Phase to phase voltage: HU12,
HU23, HU31
92 Catalogue 2017
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm
Front panel
7. Direct access key for energies, hour meter and programming menu.
1 2 3 4 5 6 7
Pulse outputs
• 2 configurable pulse outputs (type, weight and duration)
on ± kWh, ±kvarh and kVAh.
diris_447_a_1_cat
Communication MODBUS®
• RS485 link with MODBUS® protocol (speed up to
38400 bauds).
DIRIS® A60*
diris_777_a_1_cat
Ethernet communication
• Ethernet connection with MODBUS TCP or
MODBUS RTU over TCP protocol.
• Embedded Webserver function (1).
diris_834_a
Ethernet communication
diris_776_a_1_cat
Analogue outputs
diris_448_a_1_cat
and 6 outputs.
• Per module 2 outputs assignable to:
- monitoring: 3I, In, 3V, 3U, F, ± ΣP, ± ΣQ, ΣS, ΣPFL/C, THD 3I, THD In,
THD 3V, THD 3U, Ppred, Qpred, Spred, T°C internal, T°C 1, T°C2,
T°C3 and hour meter,
- remote control,
- timed remote control,
• 2 inputs for pulse metering.
Temperature(2)
diris_747_a_2_cat
Temperature indication:
- Internal
- External sensor PT 100 (T°C 1)
- External sensor PT 100 (T°C 2)
- External sensor PT 100 (T°C 3).
(1) See "Management softwares for DIRIS" p. 140.
(2) See "External sensor PT 100" p. 122.
Catalogue 2017 93
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm
Accessories
Current transformers Split-core current IP65 protection Panel mounting kit
(see page 106) transformers for a 144 x 96 mm cut-out
trafo_024_a_2_cat
trafo_077_b_2_cat
DIRIS_720_a_2_cat
DIRIS_718_b_1_cat
Terminals
DIRIS A60
S1 - S2: current inputs
DIRIS_856_a_1_x_cat
V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2
AUX: auxiliary power supplies Us
I1 I2 I3 V1- V2 - V3 - VN: voltage inputs
DIRIS A60
RS485 MODBUS module Ethernet module Ethernet module + RS485 MODBUS gateway
DIRIS_857_a_1_x_cat
DIRIS_862_a_1_x_cat
DIRIS_859_b_1_gb_cat
0V - + 1 10 BASE T 10 BASE T 0V - + 1
0n
100 BASE T 100 BASE T 0n
RS485 R = 120 RS485
RJ45
RJ45 gateway R = 120Ω
DIRIS A60 DIRIS A60
DIRIS A60
RS485 link.
R = 120 Ω: selectable internal resistance RS485 gateway resistor.
for RS485 end of line termination. R = 120 Ω: selectable internal resistance
for RS485 end of line termination.
DIRIS_861_a_1_gb_cat
1 2 3 4 19 20 21 22 23 24 25 26
9 10 11 12
sensor 1 sensor 2
OUT 1 OUT 2
DIRIS_858_b_1_x_cat
A-Cd A-Cd
OUT 1 OUT 2 27 28 29 30
DIRIS A60 sensor 3
1 3 14 15 16
DIRIS A60
1 - 2 : pulse output n°1. - + - +
3 - 4 : pulse output n°2. IN 1 IN 2
DIRIS A60
9 - 10 : relay output n°1.
Analogue output module 11 - 12 : relay output n°2.
13 - 14 : opto input n°1.
DIRIS_863_a_1_x_cat
94 Catalogue 2017
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm
Electrical characteristics
Current measurement on insulated inputs (TRMS) 2 inputs / 2 outputs module: Outputs (alarms / control)
Via CT primary 9 999 A Number of relays 2(1)
Via CT secondary 1 or 5 Type 250 VAC - 5 A - 1150 VA
Measurement range 0 … 11 kA 2 inputs / 2 outputs module: Phototransistor inputs (pulse metering)
Input consumption ≤ 0.1 VA Number 2(1)
Measurement updating period 1s Power supply 10 … 30 VDC
Accuracy 0.2 % Minimum signal width 10 ms
Permanent overload 6A Minimum duration between 2 pulses 18 ms
Intermittent overload 10 In for 1 s Type phototransistors
Voltage measurements (TRMS) Pulse output module
Direct measurement between phases 50 … 700 VAC Number of relays 2
Direct measurement between phase and neutral 28 … 404 VAC Type 100 VDC - 0.5 A - 10 VA
VT primary 500 000 VAC Max. number of operations ≤ 108
VT secondary 60, 100, 110, 173, 190 VAC Analogue output module
Frequency 50 / 60 Hz Number of outputs 2(2)
Input consumption ≤ 0.1 VA Type insulated
Measurement updating period 1s Range 0 / 4 … 20 mA
Accuracy 0.2 % Load resistance 600 Ω
Permanent overload 800 VAC Maximum current 30 mA
Current-voltage product MODBUS communication module
Limitation for 1A CT 10 000 000 Link RS485
Limitation for 5A CT 10 000 000 Type 2 … 3 half duplex wires
Power measurement Protocol MODBUS RTU
Measurement updating period 1s MODBUS® speed 4800 … 38400 bauds
Accuracy 0.5 % Ethernet communication module
Power factor measurement Connection RJ45
Measurement updating period 1s Speed 10 base T / 100 base T
Accuracy 0.5 % Protocol MODBUS TCP or MODBUS RTU over TCP
Frequency measurement Temperature inputs
Measurement range 45 … 65 Hz Type PT100
Measurement updating period 1s Connection 2, 3 or 4 wires
Accuracy 0.1 % Dynamic - 20 ... 150 °C
Energy accuracy Accuracy ± 1 digit
Active (according to IEC 62053-22) Class 0.5 S Maximum length 300 cm
Reactive (according to IEC 62053-23) Class 2 Operating conditions
Auxiliary power supply Operating temperature - 10 … + 55 °C
Alternating voltage 110 … 400 VAC Storage temperature - 20 … + 85 °C
AC tolerance ± 10 % Relative humidity 95 %
Direct voltage 120 … 350 VDC (1) Max. 3 modules / DIRIS.
DC tolerance ± 20 % (2) Max. 2 modules / DIRIS.
Frequency 50 / 60 Hz
Consumption ≤ 10 VA
Case
35
45
15
96
Catalogue 2017 95
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm
Connection
Low voltage balanced network for DIRIS A60
Recommendation: When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out
automatically by a SOCOMEC PTI, which can be found in the SOCOMEC catalogue: please consult us.
1 1 1 1 1 1
diris_392_d_1_x_cat
diris_393_d_1_x_cat
diris_394_d_1_x_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3
Use of 1 CT reduces by 0.5% the accuracy of the phases, 1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC.
3/4 wires with 3 CTs 3 wires with 2 CTs 3 wires with 2 CTs
P1 L1 P1 L1
N
P1 S1 S2 S1 P1
L1 L2 L2
S1 S2 P1 S1 S2
L2 L3 L3
P1 L3 S1 S2
S1 S2
1 1 1 1 1 1
1 1 1
diris_395_d_1_x_cat
diris_396_d_1_x_cat
diris_397_d_1_x_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3
1. Fuses 0.5 A gG / 0.5 A class CC. Use of 2 CTs reduces by 0.5% the accuracy of the phases, Use of 2 CTs reduces by 0.5% the accuracy of the phases,
the current of which is worked out by vector calculation. the current of which is worked out by vector calculation.
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
Additional information
Communication via RS485 link Connection of voltage transformer for HV networks AC & DC auxiliary power supply
L1
L2 110 / 400 VAC
L3 120 / 350 VDC
1 1
LIYCY-CY
diris_399_b_1_x_cat
diris_398_c_1_x_cat
diris_400_i_1_x_cat
A U X
0V - +
ON
V1 V2 V3 N
RS485
96 Catalogue 2017
DIRIS A60
Multifunction meters - PMD
energy monitoring and event analysis - dimensions 96 x 96 mm
References
Basic device DIRIS A60
Auxiliary power supply Us Reference
110 ... 400 VAC / 120 ... 350 VDC 4825 0207
Options
Plug-in-modules(1) Reference
Pulse outputs 4825 0090
RS485 MODBUS® communication 4825 0092
Analogue outputs 4825 0093
2 inputs / 2 outputs 4825 0094
Ethernet communication (embedded Ethernet Webserver)(2) 4825 0203
Ethernet communication + RS485 MODBUS gateway (embedded Ethernet Webserver)(2) 4825 0204
Temperature inputs 4825 0206
(1) Easy integration of additional functions (maximum 3 slots per device).
(2) Dimension of the plug-in module: 2 slots.
Options
Description of accessories To be ordered in multiples of Reference
IP65 protection 1 4825 0089
Panel mounting kit for a 144 x 96 mm cut-out 1 4825 0088
Fuse disconnect switches for the protection of voltage inputs (type RM) 3 poles 4 5601 0018
Fuse disconnect switches for the protection of the auxiliary supply (type RM) 1 pole + neutral 6 5601 0017
Fuse type gG 10 x 38 0.5 A 10 6012 0000
Ferrite to be associated with communication modules 1 4899 0011
Current transformer range 1 see page 106
Temperature sensor PT100 - M6 screw type 1 4825 0208
Temperature sensor PT100 - M6 eyelet type 1 4825 0209
Management softwares for DIRIS see page 140
Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.
Catalogue 2017 97
DIRIS A80
Multifunction meters - PMD + RCM
monitoring energy and fault currents - dimensions 96 x 96 mm
Single-circuit metering,
> Industry
> Infrastructure
diris_876_a_1_cat
Strong points
> Compact
DIRIS A80
> Patent pending
Function Principle diagram > Management softwares
DIRIS A80 is a complete panel mounted > Compliant with IEC 61557-12
multifunction meter which incorporates
> Conformity to standard
RCM current monitoring (Residual Current
Monitoring), for networks with TN-S and EN 50160
diris_875_b_1_gb_cat
TT neutral systems, and enhanced data DIRIS A80 DIRIS A80
RS485
98 Catalogue 2017
DIRIS A80
Multifunction meters - PMD + RCM
monitoring energy and fault currents - dimensions 96 x 96 mm
tore_046_a
5. Direct access key for maximum and average current, voltage
and power values.
6. Direct access key for harmonic values and the connection
and RCM test functions.
7. Direct access key for energies, hour meter
and programming menu.
1 2 3 4 5 6 7
Plug-in modules
DIRIS® A80
diris_447_a_1_cat
Communication MODBUS®
• RS485 link with MODBUS® protocol
(speed up to 38400 bauds).
diris_777_a_1_cat
DIRIS_878_a_2_cat
Ethernet communication
• Ethernet connection with MODBUS TCP or MODBUS RTU over TCP
protocol.
• Embedded Webserver function(1).
diris_776_a_1_cat
Terminals
DIRIS A80
S1 - S2: current inputs
diris_849_b_1_x_cat
V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2 S1 S2
AUX: Auxiliary power supply Us
I1 I2 I3 IN V1- V2 - V3 - VN: voltage inputs
DIRIS A80
RCM module RCM module Memory module
1 input / 1 output 2 outputs
diris_853_c_1_x_cat
diris_871_a_1_x_cat
diris_872_a_1_x_cat
K L K L 33 34 37 38 K L K L 33 34 35 36 17 18
+ -
IN
I∆N IPE OUT IN I∆N IPE OUT1 OUT2
synchro
DIRIS A80 DIRIS A80 DIRIS A80
K-L / I∆N : residual current K-L / I∆N : residual current
K-L / IPE : ground fault current K-L / IPE : ground fault current
33-34 : relay outputs 33-34 : relay output n°1
37-38 : opto inputs 35-36 : relay output n°2
Ethernet module Ethernet module + RS485 MODBUS gateway RS485 MODBUS module
diris_852_c_1_gb_cat
diris_850_c_1_x_cat
diris_851_b_1_x_cat
10 BASE T 10 BASE T 0V - + 1 0V - + 1
Catalogue 2017 99
DIRIS A80
Multifunction meters - PMD + RCM
monitoring energy and fault currents - dimensions 96 x 96 mm
Connections
Additional information
Communication via RS485 link Connection of voltage transformer for HV networks AC & DC auxiliary power supply
L1 110 / 400 VAC
L2 120 / 350 VDC
L3
1 1
LIYCY-CY
diris_400_i_1_gb_cat
diris_399_b_1_x_cat
diris_398_c_1_x_cat
A U X
0V - +
V1 V2 V3 N
ON
RS485
1. Fuses 0.5 A gG / 0.5 A class CC.
1 1 1 1
diris_873_a_1_gb_cat
diris_874_a_1_gb_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 S1 S2 K L K L V1 V2 V3 VN S1 S2 S1 S2 S1 S2 S1 S2 K L K L
I1 I2 I3 IN I1 I2 I3 IN
I∆N IPE I∆N IPE
1. Fuses 0.5 A gG / 0.5 A class CC. 1. Fuses 0.5 A gG / 0.5 A class CC.
Electrical characteristics
Current measurement on insulated inputs (TRMS) Auxiliary power supply
Via CT primary 9 999 A Alternating voltage 110 … 400 VAC
Via CT secondary 1 or 5 A AC tolerance ± 10 %
Measurement range 0 … 11 kA Direct voltage 120 … 350 VDC
Input consumption ≤ 0.1 VA DC tolerance ± 20 %
Measurement updating period 1s Frequency 50 / 60 Hz
Accuracy 0.2 % Consumption ≤ 10 VA
Permanent overload 6A MODBUS communication module
Intermittent overload 10 In for 1 s Link RS485
Voltage measurements (TRMS) Type 2 … 3 half duplex wires
Direct measurement between phases 50 … 700 VAC Protocol MODBUS® RTU
Direct measurement between phase and neutral 28 … 404 VAC MODBUS® speed 4800 … 38400 bauds
VT primary 500 000 VAC Ethernet Communication Module
VT secondary 60, 100, 110, 173, 190 VAC Connection RJ45
Frequency 50 / 60 Hz Speed 10 base T / 100 base T
Input consumption ≤ 0.1 VA Protocol MODBUS TCP or MODBUS RTU over TCP
Measurement updating period 1s Fault current monitoring characteristics (I∆n and IPE)
Accuracy 0.2 % Inputs I∆n and IPE
Permanent overload 800 VAC
Number of inputs 2
Current-voltage product
Dedicated core balance transformers range ΔIC – transformer ratio 600/1
Limitation for 1A CT 10 000 000
Limitation for 5A CT 10 000 000 Measurement of fault current I∆n / IPE 6 mA … 30 A
Power measurement Accuracy 1%
Measurement updating period 1s Alarms I∆n and IPE
Accuracy 0.5 % Thresholds adjustment depending on the load currents
Power factor measurement Time setting 0 to 10 s
Measurement updating period 1s Logging values, dates, durations and curves
Accuracy 0.5 % Number of events max. 1000 events
Frequency measurement Optocoupler input
Measurement range 45 … 65 Hz Number specific to the reference
Measurement updating period 1s Power supply 5 … 24 VDC
Measurement updating period 0.1 % Minimum signal width 10 ms
Energy accuracy Minimum duration between 2 pulses 20 ms
Active (according to IEC 62053-22) Class 0.5 S Type optocoupler
Reactive (according to IEC 62053-23) Class 2
Alarm outputs
Operating conditions
Number of relays specific to the reference
Operating temperature - 10 … + 55 °C
Storage temperature - 20 … + 85 °C Type 230 VAC – 1 A
Relative humidity 95 % Max. N° of operations 104
Case
0
- 0.0
35
45
15
96
References
Accessories
Description of accessories To be ordered in multiples of Reference
IP65 protection 1 4825 0089
Panel mounting kit for a 144 x 96 mm cut-out 1 4825 0088
Fuse disconnect switches for the protection of voltage inputs (type RM) 3 poles 4 5601 0018
Fuse disconnect switches for the protection of the auxiliary supply (type RM) 1 pole + neutral 6 5601 0017
Fuses type gG 10 x 38 0.5 A 10 6012 0000
Ferrite to be associated with communication modules 1 4899 0011
Current transformer range 1 See page 106
Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts “Expert Services” offer complete support for the success
of your project.
new
The solution for
measurement &
> Industry
> Infrastructure
> Healthcare buildings
analysis
diris-q_012_a
Strong points
Functions
Measurements Logging
• Measures across 4 quadrants • EN 50160 events ½ period (10 ms): voltage dips, voltage cutouts,
• Voltage by phase, current by phase, frequency. voltage surges.
• Neutral current, differential current. • Data exported automatically via FTP.
• Neutral/earth voltage. • EN50160 compliant.
• Active, reactive and apparent power. • Transients (20 micro seconds).
• Cos phi and power factor.
• THD and spectral analysis up to the 63rd for current voltage. Inputs/outputs
• Flicker (Pst, Plt). • 4 digital inputs.
• Voltage imbalance. • 4 digital outputs.
• Remote control signals. • 4 analogue outputs.
Dimensions
191 190 6
Dimensions
183 x 135 mm
Cutout
(192 x 144 mm DIN)
Front panel (L x H) 191 x 143 mm
Enclosures (L x H x P) 183 x 135 x 190 mm
143
135
Weight 1400 g
diris_935_b_1_cat
183
Specifications
Auxiliary power supply Communication
Voltage range 85 … 285 VAC / 65 … 250 VDC Ethernet ports 2 Auto MDIX RJ45 10/100 Base Ethernet
Frequency 50/60 Hz RS485 opto-insulated port (slave) 0.5 UL 2400 to 115200 bps
Power consumption Max. 15 VA Passive WIFI antenna SMA conn.
Backup battery Li-ion 2500 mAh Active GPS antenna SMA conn.
Measurement inputs HTTP, HTTPS, FTP, SFTP, NTP, NMEA,
Protocols
Modbus RTU/TCP
P-N: max 580 V RMS CAT III
Direct voltage measurement input USB port USB 2.0
L-L: max 1000 V RMS CAT III
U4 direct voltage measurement input Max 580 V RMS CAT II Environmental conditions
Peak input power factor 2 Operating temperature (max. range) -25 … +55°C
Current inputs Max 7 A RMS Storage temperature -25 … +75°C
Current input consumption 0.04 VA Humidity Max. 95 %
Peak input current factor 3 Max.altitude 2000 m
Voltage input impedance › 6 MΩ Standards and safety
Frequency range 42.5 to 57.5 Hz/51 to 69 Hz Product comformity IEC/EN 62586-1, IEC/EN 62586-2
Voltage reference channel U1N/U12 Safety CAT III power, insulation class 2, 600 V
Sampling 51.2 kHz @50 Hz Degree of pollution 2 (EN 61010-1)
Accuracy Degree of protection IP40 front, IP20 rear
Three-phase voltage ± 0.1% Directive 2006/95/EC LV, EN 61010
4th voltage (neutral/earth) ± 0.2% 2004/108/EC EMC, EN 50081-2, EN 50082-2,
Currents ± 0.2% EMC EN 61326/A1, EN 55011: 1998+A1: 1999+A2:
2002, EN 61000-6-2/-4-2/-4-3/-4-4/-4-5/-4-6/-4-11
Power ± 0.2%
Frequency ± 8 mHz
Harmonics lC. 1 IEC/EN 61000-4-7
Active energy lC. 0.5S IEC/EN 62053-22
Reactive energy lC. 1 IEC/EN 62053-23
References
Designation Reference
DIRIS Q800 4826 0100
Terminals
2
1. Product label
2. Earth connection
3 3. RS485 MODBUS RTU communication
RS485 85-265 VAC (65-250 DC)
AUX CAT II 4. Auxiliary power supply and fuse
5. Voltage and current inputs
1 1 2 3 1 2 3 6. Auto MDIX ETHERNET port
C B- A+ L PE N 7. Battery switch
FUSE T 4
DIG. OUT - 24 VDC/max 50 mA DIG. IN - 24 VDC AN. OUT - 4-20 mA/max 500 ohm 250 VAC/500 mA 8. GPS and WIFI antenna
9 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
9. Logical outputs, analogue inputs/outputs
WIFI ant.
GPS ant.
(3.3 VDC out)
ON
L1 L2 L3 L4 N
BATT
7
OFF
3+1 Phase AC Current CH5 (EL) AC Current
1(7) A RMS 1(7) A RMS
diris_933_a_1_x_cat
ETHERNET
L1 L2 L3 L4 L5 5
10/100 Base T
Communication via RS485 link AC and DC auxiliary power supply Ethernet communication
85/265 VAC
65/250 VDC
PE
LIYCY-CY
diris_920_a_1_x_cat.eps
diris_921_a_1_x_cat.eps
diris_928_a_1_x_cat.eps
C B- A+ L PE N
Ethernet
AUX 10/100 Base T
RS485 DIRIS Q800
diris_923_a_1_x_cat.eps
diris_924_a_1_x_cat.eps
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
DIG. OUT 24 VDC / max 50 mA DIG. IN 24 VDC AN. OUT 4-20 mA / max 500 Ohm
diris_926_a_1_x_cat.eps
diris_927_a_1_x_cat.eps
L1 L2 L3 L4 N 1 2 3 4 5 6 7 8 1 2
3+1 phase AC voltage I1 I2 I3 IN I5
3+1 phase AC current Ch5 (EL) AC current
DIRIS Q800 DIRIS Q800 DIRIS Q800
L1, L2, L3, L4, N: voltage inputs 1-2: current input i1 1-2: differential core connections
3-4: current input i2
5-6: current input i3
7-8: current input iN
Connections
4 wires with 4 CT + differential measurements (1/5 A) 3 wires with 3 CT + differential measurements (1/5 A)
L1 P1 P1
L1
S1 S2 P1 S1 S2 P1
L2 L2
S1 S2 P1 S1 S2 P1
L3 L3
S1 S2 P1 S1 S2
N S1 S2
S1 S2
S1 S2
PE PE
1 1
diris_929_a_1_x_cat
diris_930_a_1_x_cat
L1 L2 L3 L4 N 1 2 3 4 5 6 7 8 1 2 L1 L2 L3 L4 N 1 2 3 4 5 6 7 8 1 2
3+1 phase AC voltage S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 3+1 phase AC voltage S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 IN I5 I1 I2 I3 IN I5
3+1 phase AC current AC current 3+1 phase AC current AC current
1. 0.5 A gG / 0.5 A class CC fuses. 1. 0.5 A gG / 0.5 A class CC fuses.
diris_932_a_1_x_cat
L1 L2 L3 L4 N 1 2 3 4 5 6 7 8 1 2 L1 L2 L3 L4 N 1 2 3 4 5 6 7 8 1 2
3+1 phase AC voltage S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 3+1 phase AC voltage S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 IN I5 I1 I2 I3 IN I5
3+1 phase AC current AC current 3+1 phase AC current AC current
1. 0.5 A gG / 0.5 A class CC fuses. 1. 0.5 A gG / 0.5 A class CC fuses.
Expert Services
> Study, definition, advice, implementation, maintenance and training…
Our experts "Expert Services" offer complete support for the success
of your project.
> Industry
> Office buildings
Current
trafo_108_a_1_cat
trafo_012_a_1_cat
Strong points
Three-phase CT
Conformity to standards
trafo_010_a_1_cat
SOCOMEC current transformers deliver to An adapted accuracy class SOCOMEC also offer
the secondary a standard current proportional In order to get the best of your DIRIS multifunction customised solutions:
to the primary current and adapted to the rating meters and COUNTIS energy meters, we can > 1 A secondary
of the associated device. They are equipped as provide current transformers with the following
standard with removable terminal covers and > Double or triple primary ratio
accuracy classes: 0.2s; 0.5 ; 1 or 3.
double terminals allowing the secondary to be A wide range of ratings and dimensions > Voltage transformer
short-circuited without any risk. Your measurement process can be optimised > Summation CTs
They are mounted using two screw-on metal whatever your needs in terms of ratings, space
brackets or, in certain cases, by a clip-on DIN- requirements, conductor sizing or accuracy class.
rail fastener. The connections are made by A wide range of combinations are available in our
screws or by fast-on terminals. standard range with specific versions available on
• Accuracy class: 0.2s — 0.5 or 1. request (other ratios, tropicalisation and specific
• Dielectric quality: 3 kV — 50 Hz — 1 min. frequency, class or burden).
• Operating frequency: 50 — 60 Hz. Quick and easy to mount
• Permanent overload: 1.2 In. Our current transformers are adapted to
• Insulation class: E (120 °C). any type of mounting: edgewise or flat
mounting, DIN-rail or back-plate mounting.
Implementation is easy and rapid.
trafo_014_b_1_cat
trafo_015_b_1_cat
Primary wound moulded Bar or cable-through CT Bar or cable-through three- Bar-through split-core CT
case CT phase CT
Accessories
TRB 60 TRB 70 TRB 135
Description of accessories Reference Reference Reference
DIN-rail mounting 192T 0003 192T 0005 (1)
Sealable cover 192T 0105 192T 0103 192T 0101 (2)
(1) Not available for 50 A rating
(2) For 125 and 150 A ratings, use reference 192T 0103.
Certificate of performance
Each class 0.2s current transformer is supplied with an individual certificate of performance,
attesting to its accuracy.
K L K L
K L
75.5
85.5
107
trafo_036_a_1_x_cat
trafo_038_a_1_x_cat
trafo_162_a_1_x_cat
40 50
60 70 50 50
(1) different dimensions 70 67
for 40 and 50 A ratings 82
T2RB115 TRB 135
64 43 70
k I
1
k l
100
85
5
K L
31
40
L–H2–P2
trafo_037_a_1_x_cat
trafo_113_a_1_x_cat
0.5
52 50
65 70 50
92 112
1 25 to 100 A: M8 x 25
115 135
(2) Dimensions are different for TRB 135 with 125 and 150 A ratings.
35
trafo_166_a_1_x
50 60
70 77
92
86
116
136
Associated transducers
Transducer to be associated with adapted
current transformers:
• Class 0.5.
• Input: 1 or 5 A. UH - 8 4 +
• Output: IA
- 0-20 mA, 0-10 V (type CEA-VA) + 7 3 -
trafo_060_a_1_x_cat
W D
Dimensions (mm)
trafo_071_a_1_gb_cat
Cable-through CT
References
TCA 14 TCA 21 TCA 22 T2CA 225
Class Class Class Class
Primary Secondary(1) 1 Reference 1 Class 0.5 Reference 1 Reference 0.2s Reference
40 A 5A 1 192T 1404
50 A 5A 1 192T 1405
60 A 5A 1.5 192T 1406 1 VA 192T 2006
75 A 5A 1.5 192T 1407 1.5 VA 192T 2007
80 A 5A 1.5 VA 192T 2008
100 A 5A 2.5 192T 1410 1.5 VA 192T 2010 1 VA 192T 2022
125 A 5A 2.5 192T 1412 1.5 VA 192T 2012
150 A 5A 2.5 192T 1415 1.5 VA 192T 2015 1.5 VA 192T 2023 1.5 VA 192U 2215
200 A 5A 2.5 VA 192T 2020 2.5 VA 192T 2024 2.5 VA 192U 2220
250 A 5A 2.5 VA 192T 2016 3.75 VA 192T 2025 5 VA 192U 2225
300 A 5A 2.5 VA 192T 2017 3.75 VA 192T 2030 5 VA 192U 2230
400 A 5A 5 VA 192T 2034 5 VA 192U 2240
500 A 5A 5 VA 192T 2035 (2) 10 VA 192U 2250
600 A 5A 5 VA 192T 2036 (2) 10 VA 192U 2260
(1) Secondary 1 A: on request. (2) Dimensions of T2CA 225
Accessories
TCA 14 TCA 21 TCA 22 T2CA 225
Description of accessories Reference Reference Reference Reference
DIN-rail mounting 192T 0006 192T 0006 192T 0007 192T 0003
Guide tube Ø 8.5 mm (1) 192T 0020
Guide tube Ø 12.5 mm(1) 192T 0021 192T 0023
Guide tube Ø 16.5 mm(1) 192T 0024
Sealable cover 192T 0105
(1) For centralising cables within the CT aperture.
Dimensions
TCA 14 TCA 21 TCA 22 T2CA 225
45 45 49.5 61
k I
k I
k I
65
k I
Ø 22.5
65
65
ø14
trafo_164_a_1_x_cat
trafo_039_a_1_x_cat
trafo_042_a_1_x_cat
78.5
75.5
27
K – P1 ø21 ø22.5
27
27
K – P1 K – P1
24
trafo_110_a_1_x_cat
30
31
44 47 24 28.5
62 44 48.5 K–P1
40
60
Bar or cable-through CT
References
TCB 17-20 TCB 26-30 T2CB 26-30 TCB 28-30
Class Class Class Class Class Class
Primary Secondary(1) 1 Reference 0.5 1 Reference 0.2s Reference 0.5 1 Reference
50 A 5A 1 VA 192T 2305
60 A 5A 1 VA 192T 2106 1 VA 192T 2306
75 A 5A 1 VA 192T 2107 1.5 VA 192T 2307
80 A 5A 1.25 VA 192T 2108 1.5 VA 192T 2308 1.25 VA 192T 2408
100 A 5A 1.5 VA 192T 2110 1.5 VA 192T 2310 1.5 VA 192T 2410
125 A 5A 1.5 VA 192T 2112 1.5 VA 192T 2312 2.5 VA 192T 2412
150 A 5A 2.5 VA 192T 2115 1.5 VA 192T 2315 1.5 VA 192U 2315 2.5 VA 192T 2415
160 A 5A 2.5 VA 192T 2116
200 A 5A 2.5 VA 192T 2120 2.5 VA 192T 2320 2.5 VA 192U 2320 2.5 VA 192T 2420
250 A 5A 5 VA 192T 2125 5 VA 192T 2325 2.5 VA 192U 2325 2.5 VA 192T 2425
300 A 5A 5 VA 192T 2130 5 VA 192T 2330 5 VA 192U 2330 2.5 VA 192T 2430
400 A 5A 5 VA 192T 2140 5 VA 192T 2340 5 VA 192U 2340 5 VA 192T 2440
500 A 5A 5 VA 192T 2350 5 VA 192U 2350 5 VA 192T 2450
600 A 5A 5 VA 192T 2360 5 VA 192U 2360
750 A 5A 5 VA 192T 2375 5 VA 192U 2375
(1) Secondary 1 A: on request.
Accessories
TCB 17-20 TCB 26-30 TCB 26-40 TCB 32-40
Description of accessories Reference Reference Reference Reference
DIN-rail mounting 192T 0007 192T 0003 192T 0003 192T 0005
Sealable cover 192T 0105 192T 0105 192T 0103
References
TCB 44-50 TCB 44-63 T2CB 44-63
Class Class Class
Primary Secondary(1) 0.5 Reference 0.5 Reference 0.2s Reference
150 A 5A 1.5 VA 192T 5015
200 A 5A 2.5 VA 192T 5020 1.5 VA 192T 6420
250 A 5A 5 VA 192T 5025 1.5 VA 192T 6425
300 A 5A 5 VA 192T 5030 2.5 VA 192T 6430 5 VA 192U 6430
400 A 5A 10 VA 192T 5040 5 VA 192T 6440 5 VA 192U 6440
500 A 5A 10 VA 192T 5050 10 VA 192T 6450 10 VA 192U 6450
600 A 5A 10 VA 192T 5060 10 VA 192T 6460 10 VA 192U 6460
750 A 5A 10 VA 192T 5075 10 VA 192T 6475 10 VA 192U 6475
800 A 5A 15 VA 192T 5080 10 VA 192T 6480
1000 A 5A 15 VA 192T 5090 15 VA 192T 6490 10 VA 192U 6490
1200 A 5A 15 VA 192T 5092 15 VA 192T 6492 10 VA 192U 6492
1250 A 5A 15 VA 192T 5095 15 VA 192T 6493 10 VA 192U 6493
1500 A 5A 15 VA 192T 6495 10 VA 192U 6495
1600 A 5A 15 VA 192T 6494
(1) Secondary 1 A: on request.
Accessories
TCB 44-50 TCB 44-63 TCB 55-80 TCB 85-100 TCB 100-125
Description of accessories Reference Reference Reference Reference Reference
Sealable cover 192T 0102 192T 0102 192T 0102 192T 0106 192T 0106
k I
10.5
k I
k I
65
70
75.5
ø2 k I
20.5
30.5
ø2
6
10.5
75.5
27
29
trafo_045_a_1_x_cat
12.5
18.5
K – P1
K – P1
6
32
ø2
trafo_044_a_1_x_cat
K – P1
trafo_041_a_1_x_cat
15.5 10.5
33
trafo_055_b_1_x_cat
K – P1
20.5 30.5 20.5
28.5 40 30.5 32
48.5 60 40
60
TCB 32-40 and T2CB 32-40 TCB 44-50 TCB 44-63 and T2CB 44-63
71 86 96
k I k I k I
88.5
105.5
98.5
32
30.5
30.5
16
30.5
12.5
10.5
4
4
ø4
36.75
ø4
43.25
48.25
K – P1
trafo_040_a_1_x_cat
K–P1
K–P1
trafo_043_a_1_x_cat
10.5
trafo_046_a_1_x_cat
40.5 40.5
50.5 50.5
50
65 63.5
70
85 70
95
k I
184.8
184.8
10.5
123.5
30.5
31
51
31
51
0
10
5
5
ø5
ø8
Ø
58.5
82
82
trafo_048_a_1_x_cat
K–P1
trafo_049_a_1_x_cat
k-P1
k-P1
trafo_047_a_1_x_cat
60.5 95
80.5 81
95 95 101
120 101 121
122 172
172
Bar or cable-through CT TCB 17-20 TCB 26-30 T2CB 26-30 TCB 26-40 TCB 28-30 TCB 32-40 T2CB 32-40
30 x 10 (x 1) / 30 x 10 (x 1) / 40 x 12 (x 1) / 40 x 10 (x 1) / 40 x 10 (x 1) /
Bar (mm) 20 x 5 (x 1) 30 x 10 (x 1)
20 x 10 (x 1…2) 20 x 10 (x 1…2) 32 x 18 (x 1) 30 x 5 (x 1…2) 30 x 5 (x 1…2)
Ø cable (mm) 17.5 26 26 26 28 32 32
H x W x D (mm) 65 x 49.5 x 50 75.5 x 61 x 48 75.5 x 61 x 48 75.5 x 61 x 48 70 x 49.9 x 68 88.5 x 71 x 58 88.5 x 71 x 58
DIN-rail mounting yes yes yes yes yes yes
Bar or cable-through CT TCB 44-50 TCB 44-63 T2CB 44-63 TCB 55-80 TCB 85-100 TCB 100-125
80 x 10 (x 1)/
50 x 12 (x 1)/ 63 x 10 (x 1)/ 63 x 10 (x 1)/ 100 x 10 (x 1…2) / 123 x 30 (x 1)/
Bar (mm) 60 x 30 (x 1) /
40 x 10 (x 1…2) 50 x 10 (x 1…2) 50 x 10 (x 1…2) 80 x 10 (x 1…3) 100 x 10 (x 1…3)
60 x 10 (x 1…2)
Ø cable (mm) 44 44 44 55 85 100
H x W x D (mm) 98.5 x 86 x 58 105.5 x 96 x 58 105.5 x 96 x 58 123.5 x 120 x 58 184.5 x 172 x 52 184.5 x 172 x 52
Associated transducers
trafo_060_a_1_x_cat
• Output:
- 0-20 mA, 0-10 V (model CEA-VA),
l 6 2 +
trafo_074_a_1_cat
W D
Dimensions (mm)
Converter For CT Height (mm) Width (mm) Depth (mm)
Type 1 TCB 26-30 50.5 60 32.5
Type 1 TCB 26-40 50.5 60 32.5
Type 2 TCB 32-40 50 70 43
trafo_071_a_1_gb_cat
Bar-through CT
References
TBA 60 TBA 80 TBA 100 T2BA 100
Class Class Class Class Class
Primary Secondary 0.5 1 Reference 0.5 Reference 0.5 Reference 0.2s Reference
200 A 5A 2.5 VA 192T 7020
250 A 5A 2.5 VA 192T 7025
300 A 5A 2.5 VA 192T 7030 2.5 VA 192T 7530
400 A 5A 5 VA 192T 7040 5 VA 192T 7540
500 A 5A 5 VA 192T 7050 5 VA 192T 7550
600 A 5A 10 VA 192T 7060 5 VA 192T 7560 5 VA 192T 8060
750 A 5A 10 VA 192T 7075 5 VA 192T 7575 5 VA 192T 8075
800 A 5A 10 VA 192T 7080 10 VA 192T 7580 5 VA 192T 8080
1000 A 5A 15 VA 192T 7090 15 VA 192T 7590 5 VA 192T 8090
1200 A 5A 15 VA 192T 7092 15 VA 192T 7592 10 VA 192T 8092 5 VA 192U 8092
1250 A 5A 15 VA 192T 7093 15 VA 192T 7593 10 VA 192T 8093 5 VA 192U 8093
1500 A 5A 15 VA 192T 7095 15 VA 192T 7595 15 VA 192T 8095 5 VA 192U 8095
1600 A 5A 15 VA 192T 7094 15 VA 192T 7594 15 VA 192T 8094
2000 A 5A 15 VA 192T 7596 15 VA 192T 8096 5 VA 192U 8096
2500 A 5A 30 VA 192T 8097 10 VA 192U 8097
3000 A 5A 30 VA 192T 8098 (1) 10 VA 192U 8098
4000 A 5A 30 VA 192T 8099 (1)
(1) Dimensions are different for TBA 100 with 3000 and 4000 A primary.
Accessories
TBA 60 TBA 80 TBA 100 T2BA 100 TBA 103 T2BA 103 TBA 127 T2BA 127
Description of accessories Reference Reference Reference Reference Reference Reference Reference Reference
Sealable cover 192T 0102 192T 0102 192T 0102 192T 0102 192T 0102
Dimensions
TBA 60 TBA 80 TBA 100 600 to 2500 A(1)
300 to 2000 A T2BA 100 1200 to 3000 A
86 96
S2 S1
S1 S2
k I
k I
117
84
129
31
167
55.5
59
60
trafo_050_a_1_x_cat
trafo_059_a_1_x_cat
trafo_082_a_1_x_cat
S2 S1
77.5
k-P1
50 34 k-P1
60.5 69
88 96
95
100.5
129
TBA 103 and T2BA 103 TBA 127 and T2BA 127
S2 S1
150
38
103
175
128
69
trafo_054_a_1_x_cat
trafo_052_a_1_x_cat
17.5
L–P2
41
17
99
17.7 42.8 17.7
100
Bar-through CT TBA 60 TBA 80 TBA 100 T2BA 100 TBA 103 T2BA 103 TBA 127 T2BA 127
Bar (mm) 60 x 30 84 x 34 100 x 55 100 x 55 103 x 41 103 x 41 128 x 38 128 x 38
H x W x D (mm) 129 x 88 x 78 117 x 96 x 68 167 x 129 x 78 (1) 167 x 129 x 78 150 x 99 x 58 150 x 99 x 58 175 x 100 x 55 175 x 100 x 55
(1) TBA 100, 3000 and 4000 A: 214 x 129 x 78 mm.
Dimensions
TCB3 18-20 TCB3 22-30
35 35 45 45
k I k I k I
Ø 18 k I k I k I Ø 22
75
65
10
5
trafo_111_a_1_x_cat
trafo_112_a_1_x_cat
L1 K–P1 L2 L3
L1 K–P1 L2 L3
20 30
115 150
References
TCA 13 — 3P
Class
Primary Secondary(1) 1 Reference
3 x 50 A 5A 1 VA 192T 1905
3 x 60 A 5A 1.25 VA 192T 1906
3 x 75 A 5A 1.5 VA 192T 1907
3 x 80 A 5A 1.5 VA 192T 1908
3 x 100 A 5A 2.5 VA 192T 1910
3 x 125 A 5A 2.5 VA 192T 1912
3 x 150 A 5A 2.5 VA 192T 1915
3 x 160 A 5A 2.5 VA 192T 1916
(1) Secondary 1 A: on request.
Dimensions
TCA 13 — 3P
54
44
L 7
Number of modules Front degree of protection Terminal degree of protection L (mm) Mounting
6 IP65 IP20 105 35 mm DIN-rail
Split-core CT
References
TO 23 TO 58 TO 812 TO 816
Class Class
Primary Secondary Class 1 Class 3 Reference 0.5 Class 1 Reference 0.5 Class 1 Reference Class 0.5 Reference
100 A 5A 1.25 VA 192T 4601
150 A 5A 1.5 VA 192T 4602
200 A 5A 2.5 VA 192T 4603
250 A 5A 1.5 VA 192T 4604 1.5 VA 192T 4625 1.5 VA 192T 4725
300 A 5A 3.75 VA 192T 4605 2.5 VA 192T 4630 2.5 VA 192T 4730
400 A 5A 5 VA 192T 4606 1 VA 192T 4640 2.5 VA 192T 4740
500 A 5A 2.5 VA 192T 4650 2.5 VA 192T 4750
600 A 5A 2.5 VA 192T 4660 2.5 VA 192T 4760
750 A 5A 2.5 VA 192T 4675 2.5 VA 192T 4775
800 A 5A 2.5 VA 192T 4680 2.5 VA 192T 4780
1000 A 5A 5 VA 192T 4610 5 VA 192T 4710 10 VA 192T 4810
1250 A 5A 7.5 VA 192T 4712 10 VA 192T 4812
1500 A 5A 7.5 VA 192T 4715 10 VA 192T 4815
1600 A 5A 10 VA 192T 4814
2000 A 5A 10 VA 192T 4820
2500 A 5A 10 VA 192T 4825
3000 A 5A 15 VA 192T 4830
4000 A 5A 15 VA 192T 4840
5000 A 5A 15 VA 192T 4850
Dimensions
B C Dimensions (mm)
D
Type A (mm) B (mm) C (mm) D (mm) E (mm)
TO 23 106 93 58 23 33
TO 58 158 125 58 55 85
TO 812 198 155 58 85 125
trafo_078_e_1_x_cat
Fixed by M5 screw
Summation CT
Reference
BSA 02 BSA 03 BSA 04
Primary Secondary Reference Reference Reference
5 + 5/5 A 5A 192T 0802
5A + 5+ 5/5 5A 192T 0803
5 + 5 + 5 + 5/5 A 5A 192T 0904
Dimensions
BSA 02 and BSA 03 BSA 04
57 65
136.5
90
29.5
54
trafo_073_b_1_x_cat
trafo_069_b_1_x_cat
50 55 95 60
80 122
127 156
shunt_008_a_1_cat
shunt_007_b_1_cat
shunt_006_b_1_cat
Function Characteristics
SOCOMEC shunts provide indirect • Voltage drop: 100 mV
measurement of direct current by creating a for nominal rating.
standardised voltage drop. • Accuracy class: 0,5.
• Permanent overload: 1.2 In.
• 10 In / 5s rating ≤ 500 A
5 In / 5s rating 600 to 1500 A
2 In / 5s rating ≥ 2500 A.
References
DIN series
Rating (A)(1) Secondary voltage drop Reference
1A 100 mV 192S 2101
4A 100 mV 192S 2104
6A 100 mV 192S 2106
10 A 100 mV 192S 2110
15 A 100 mV 192S 2112
25 A 100 mV 192S 2114
40 A 100 mV 192S 2116
60 A 100 mV 192S 2118
100 A 100 mV 192S 2120
150 A 100 mV 192S 2125
200 A 100 mV 192S 2220
250 A 100 mV 192S 2235
300 A 100 mV 192S 2230
400 A 100 mV 192S 2240
600 A 100 mV 192S 2250
1000 A 100 mV 192S 2255
1500 A 100 mV 192S 2260
2500 A 100 mV 192S 2165
4000 A 100 mV 192S 2170
6000 A 100 mV 192S 2175
(1) Other rating: please consult us.
Dimensions
DIN Series 1 to 25 A
Fig. 1
B Rating (A)(1) Figure A B C D E F G H I
1 1 90 28 20 8 78
11 F
4 1 90 28 20 8 78
6 1 90 28 20 8 78
10 1 90 28 20 8 78
15 1 90 28 20 8 78
25 1 90 28 20 8 78
shunt_011_a_1_x_cat
135
40 2 123 33 20 8 103
115 60 2 123 33 20 8 103
A 100 2 123 33 20 8 103
H 150 2 123 33 20 8 103
200 2 168 55 30 15 10 10 128 30
250 2 168 55 30 15 10 10 128 30
300 2 168 55 40 20 10 10 128 30
400 2 168 55 40 20 10 10 128 30
30
C
9
F
F
shunt_010_a_1_x_cat
shunt_009_a_1_x_cat
C
E
C
D
H
A H
A
Other regulations
Characteristics Dimensions
H1 L
Case degree of protection IP55
H F
Terminal protection degree IP20
Connection cross-section 2.5 mm2
Weight 82 g
pti_003_a_1_x_cat
Rating (A) D1 E F H H1 I L
5 4.2 47 9.6 32 44 41 34.7
E
øD1
References
Products Reference
Temperature sensor PT100 - M6 screw type 4825 0208
Temperature sensor PT100 - eyelet type 4825 0209
Dimensions
trans_117_a_1_x_cat
20 5 3000
Ø 6,5
30 10 3000
500 A 192Y 0450 192Y 0550 192Y 0850 192Y 0650 on request
600 A 192Y 0460 192Y 0560 on request on request 192Y 0960
750 A 192Y 0475 on request 192Y 0875 192Y 0675 192Y 0975
800 A 192Y 0480 192Y 0580 192Y 0880 192Y 0680 192Y 0980
Applications Recommendation
trafo_062_a_1_cat
Measurement and conversion of the input Voltage transformers are used specifically for supplying measurement
value read at the primary of a transformer in a equipment, therefore it is not recommended to connect other components
directly proportional voltage signal. which could affect accuracy. This is due to the effect of the phase shift error. If
BTV 25 products are voltage transformers. the consumption is greater than 25 VA, another transformer must be added.
Characteristics References
Primary Secondary Power Reference
Accuracy class 1% 230 VAC 100 VAC 25 VA 192M 2020
Dielectric quality 3 kV for 1 min. 400 VAC 100 VAC 25 VA 192M 2030
Operating frequency 50 - 60 Hz 440 VAC 100 VAC 25 VA 192M 2044
Permanent overload 1.2 Un 500 VAC 100 VAC 25 VA 192M 2050
600 VAC 100 VAC 25 VA 192M 2060
660 VAC 100 VAC 25 VA 192M 2066
Connection 800 VAC 100 VAC 25 VA Please consult us
Dimensions
Secondary a b 103
trafo_072_a_1_gb_cat
70 112
trafo_070_a_1_x_cat
97
Primary A B
R
R 3.25
100
104
56
83
N(S)
70
96
Transducers
They provide conversion of an AC electrical value (A, V, Hz, Cos phi, W, Var)
into a DC signal, with standardised current or voltage.
They are available in surface-mount casings (CS range).
trans_071_a_2_cat
These devices are designed for DIN rail or back plate mounting.
Type CS transducers are available in two sizes:
• 75 mm for current, voltage and frequency converters,
• 150 mm for power or three-phase converters.
Consult us.
Modular transducers
Available in:
• 3-DIN module housings (52.5 mm) for current,
voltage and frequency converters,
trans_076_a_2_cat
• 6-DIN module housings (105 mm) for current (output 4-20 mA),
voltage (output 4-20 mA) converters,
• 9-DIN module housings (157.5 mm) for power or three-phase converters.
Consult us.
Analogue meters
With pointer deflections of 90° and 240°, they can be flush-mounted into
cubicles, enclosures or other equipment.
Consult us.
Selector switches
Digital meters
They measure all types of electrical values (A, V, Hz, Cos phi, P, Q...).
The range:
amper_032_a_2_cat
cosph_001_a_2_cat
voltm_019_a_2_cat
Hour counters
Often combined with analogue meters in an electrical panel, hour counters count
compt_001_a_2_cat
> Industry
> Building
interfaces
> Infrastructure
> Local authority
diris-g_004_a_1_cat
Strong points
Function > WEBVIEW embedded
With communication gateways DIRIS G The gateway has an embedded WEBVIEW web server
all the information from meters and power web server, allowing real time monitoring of > Scalable
monitors, communicating by radio frequency electrical values and analysis of consumption > Plug & Play
or RS485, is centralized and made available data. The user can be alerted of any alarms
on the Ethernet Modbus (TCP). via email.
DIRIS G gateways can retrieve data from Compliance with standards
meters or Socomec remote measuring points
via Ethernet. > IEC 61010
Selection guide
Gateway DIRIS G-30 DIRIS G-40 DIRIS G-50 DIRIS G-60
RS485 Modbus • • • •
Radio frequency
Communication • •
Communication (wireless)
Ethernet • • • •
WEBVIEW embedded Power Monitoring • • • •
web server. Power & Energy Monitoring • •
Architecture
Example of communication architecture with DIRIS G gateway and WEBVIEW embedded WEB server
WEBVIEW
diris-g_019_a_1_fr_cat
CO
UN
TIS
E Ci3
diris-b_029_a
Accessories
DIRIS G terminals
Battery (supplied)
Power supply
DIRIS O Micro
optional module USB
diris-g_020_b_1_gb_cat
RS485 Ethernet
1 digital
input
Power supply Input powered by the product Input with external power supply RS485
Master
110-230 VAC NC NC NC
RS485
RS485
RS485
diris-g_015_a_1_x_cat
diris-g_016_a_1_x_cat
diris-g_017_a_1_x_cat
diris-g_018_a_1_x_cat
10 - 30 VDC
12 VDC
LIYCY-CY
L
IN
IN
Dimensions (mm)
DIRIS G-30 / G-40 / G-50 / G-60 DIRIS O optional modules
120
90
diris-o_001_b_1_x_cat
45
diris-g_001_b_1_x_cat
100
90
44 15
15
A 65
Specifications
References
DIRIS G gateways Reference
DIRIS G-30 RS485 / Ethernet - WEBVIEW Power Monitoring 4829 0300
DIRIS G-40 RS485-RF / Ethernet - WEBVIEW Power Monitoring 4829 0301
DIRIS G-50 RS485 / Ethernet - WEBVIEW Power & Energy Monitoring 4829 0302
DIRIS G-60 RS485-RF / Ethernet - WEBVIEW Power & Energy Monitoring 4829 0303
DIRIS O optional modules Reference
DIRIS O-iod 2 digital inputs / 2 digital outputs 4829 0030
DIRIS O-ioa 2x 4-20 mA analogue inputs / 2x 4-20 mA analogue outputs 4829 0031
DIRIS O-it 3 temperature inputs, PT100/PT1000 4829 0032
DIRIS O-m RS485 modbus slave communication 4829 0033
To be ordered
Accessories in multiples of Reference
Wireless remote antenna, 868 MHz - 210 mm height 4854 0126
Cable for remote antenna - SMA connector - 3 meter length 4854 0127
USB configuration cable 4829 0050
Fuse circuit breakers to protect the auxiliary power supply (type RM) 1 pole + neutral 6 5601 0017
gG 10x38 0.5 A fuses 10 6012 0000
new >
>
Industry
Building
interfaces
> Infrastructure
datal_017_a
> Local authority
DATALOG H80
datal_003_a
DATALOG H60
Strong points
Function
DATALOG H60 and H80 dataloggers associated with Socomec wireless interfaces enable you > Easy to install
to create a smart energy data communication network in order to: > Reliable collection and
• Remotely and automatically read multi-fluid energy meters and multi-function meters, isolated transmission
or not. > Advanced functions
• Pool, secure, store and provide the data to a computer application.
• Connect your meters and multi-function measurement units in a 2G/3G/GPRS network.
Expert Services
> Study, definition, advice,
Advantages commissioning, maintenance
and training... Our experts
Easy to install Advanced functions “Expert Services” offer
• Quick installation on DIN rail or door mounting. • Extended data storage capacity (1 year for complete support for the
• Compact. index data and 2 months for load curves). success of your project.
• Remote configuration. • Auto-detects meters and measuring
• Configuration services (SOCOMEC services). equipment.
Reliable collection and transmission • Sends regular activity reports.
• Configurable collection frequency for each • Event alerts (communication errors, data
energy and multi-function meter. quality, remote server connection).
• Secure, regular transmission
(daily, weekly, etc.).
• Multiple communication protocols (Modbus
RTU/TCP, Wireless M-Bus, HTTP(s), FTP(s)).
• Collection interfaces: Ethernet - RS232/485
or Wireless.
• Transmission interface: Ethernet or
2G/3G/GPRS.
DATALOGGER
Pulse N’VIEW
Hosted on Cloud
DIRIS B-30 RF DIRIS G-40
Ethernet
2G/3G
DIRIS B-30 RF
CO
RS485 Lan/Wan
UN
TIS
E Ci3
COUNTIS E
RS485 Ethernet
DIRIS B-30 RS
DIRIS G-30
HYPERVIEW
Hosted on
RS485 local server
DIRIS A
WEBVIEW
verte_122_c_gb
Embedded
in the DIRIS G gateway
DIRIS Digiware
Specifications
DATALOG H60 DATALOG H80
Input/output interfaces
Input 3 digital or pulse inputs
Output 1 digital output (relay)
Serial interfaces
Input 1 port (Modbus)
Output 1 port (Modbus or M-Bus)
Wireless interface
Wireless M-Bus 868.3 - 868.95 MHz
Network interface
Ethernet 1 10/100 Mb port 2 10/100/1000 Mb port
GSM/GPRS 850/900/1800/1900 MHz 850/900/1800/1900 MHz
3G 900/2100 MHz 900/2100 MHz
Protocols
Data collection Modbus RTU and TCP/Wireless Mbus Ethernet/Modbus TCP:
Data transmission FTP FTP(s)/ HTTP(s)
Configuration
Local Yes Yes
Distant by text message by FTP
References
Datalogger Reference
DATALOG H60 (power supply included) 4854 0001
DATALOG H80 (without 3G connection) 4854 0010
DATALOG H81 (with 3G connection) 4854 0011
DATALOG H60 accessory description Reference
5 m remote antenna extension 4854 0105
10 m remote antenna extension 4854 0110
20 m remote antenna extension 4854 0120
> Industry
> Building
interfaces
> Infrastructure
> Local authority
datal 004 a
datal 005a
Wireless M-Bus Modem ARF868 Modem
Function
Wireless M-Bus Modem ARF868 wireless modem
Wireless M-Bus AMR (Automatic ARF868 wireless modems convert data from
Meter Reading) plug-and-play modems a serial link into a wireless frame to send to Strong points
automatically collect energy data from water a similar device in the frequency range 863-
and gas meters. They autonomously read 870 MHz. The power and sensitivity allow the Wireless M-Bus Modem
data (index) from water and gas meters. data to be transmitted over distances of up > Battery life
100% compatible with the Wireless M-Bus to 20 km. > Ease of installation
standard (EN13757-3 and EN13757-
> Long range
4), device open protocols ensure full
interoperability with other Wireless M-Bus > 2 pulse inputs
products on the market. > Transmitter
> Repeater
> Receiver
ARF868 wireless modem
Advantages > Sensitivity, transmission/
reception quality
Wireless M-Bus Modem ARF868 wireless modem
Battery life Sensitivity, transmission/reception quality > Ease of installation
• Runs on battery for up to 12 years. • Power 25 mW or 500 mW at 868 MHz. > Long range
Ease of installation • Licence-free frequencies on European > Several types of
• Factory pre-programmed. bands (863 - 870 MHz) or frequencies communication
• Quick installation. subject to license (410 - 470 MHz).
• Robust IP65. Ease of installation
• Quick installation. Expert Services
Long range
• Up to 1 km. Range can be increased by • User-friendly and configuration with intuitive > Study, definition, advice,
installing repeaters. software. implementation, maintenance
2 pulse inputs • The product can be configured as a and training... Our experts
transmitter, receiver or repeater. “Expert Services” offer
• A single transmitter can handle two meters.
• Compatible with all water and gas meters.
Long range complete support for the
• 1 to 20 km. success of your project.
Transmitter
Several types of communication
• Wireless transmission of metering data
(consumption) every 10 minutes • RS485, RS232 or USB serial port.
(10s or 12hrs optional).
Repeater
• Wireless M-Bus wireless relay of metering
data (consumption).
• Multiple repeaters can be used to extend
the range.
Receiver
• Wireless M-Bus metering data
(consumption) wireless receiver.
• RS485, RS232 or USB serial port.
• Remote antenna.
Accessories
• 1-, 3- and 5-metre remote antenna. • TNC converter pack.
• Antenna mount & adaptor. • Sub D9 connector.
• Power supply unit + connector (required). • IP53 and IP67 ingress protection rating.
Specifications
Modem ARF868
(transmitter/repeater/ Wireless M-Bus transmitter Wireless M-Bus transmitter Wireless M-Bus repeater Wireless M-Bus
receiver model) modem: Water/Gas modem: Temperature modem receiver modem
Up to 1/4/7/20 km
Scope Up to 1000 m Up to 1000 m Up to 1000 m
according to model
Wireless frequencies 863-870 MHz 863-870 MHz 863-870 MHz 863-870 MHz 863-870 MHz
Interfaces
2 temperature inputs:
Inputs - 2 pulse inputs - 1 pre-equipped input - -
- 1 free input
RS232 - RS485 - USB
Communication - - - RS232 - RS485 - USB
optional
Leak detection - Fraud
Alerts - - - -
detection - Battery spent
Index bufferisation
Storage capability - - - -
(consumption history)
Sappel Izar, Itron Cyble,
Compatibility - - - -
Itron Gallus 2000, Elster BK
General characteristics
Dimensions W x H x D 135 x 75 x 35 mm 210 x 103.1 x 37.2 mm 210 x 103.1 x 37.2 mm 210 x 103.1 x 37.2 mm 210 x 103.1 x 37.2 mm
Operating temperature -30 … +70°C -40 … +85°C -40 … +85°C -40 … +85°C -40 … +85°C
3.6 V. Power supply block
3.6V Li-SOCl2 battery. Battery 3.6V Li-SOCl2 battery. Battery
Power supply 4.5 … 36 V supplied, model with battery 4.5 … 36 VDC
life up to 12 years guaranteed life up to 12 years guaranteed
optional
Protection degree IP53, IP67 (optional) IP65 IP53 IP65 IP65
Standards EN300-220 V2010 / EN301-489 / EN 60950
References
Wireless M-Bus modem
Reference
Wireless M-Bus Modem - Water 4854 0054
Wireless M-Bus Modem - Gas 4854 0055
Wireless M-Bus Modem - Temperature 4854 0056
Wireless M-Bus receiver modem – RS232 4854 0057
Wireless M-Bus receiver modem – RS485 4854 0058
Wireless M-Bus receiver modem – USB 4854 0059
Wireless M-Bus repeater modem 4854 0060
ARF868 wireless modem
Reference
Modbus wireless modem, distance 20 km 4854 0050
Modbus wireless modem, distance 7 km 4854 0051
Modbus wireless modem, distance 4 km 4854 0052
Modbus wireless modem, distance 1 km 4854 0053
List of accessories for ARF868 wireless modem Reference
Power supply (mandatory) 4854 0202
RS232/USB cable (mandatory to configure ARF868 wireless modems) 4854 0400
RS485 connector (mandatory for use with RS485) 4700 9993
0.5 dB remote antenna + 1 m extension 4854 0121
0.1 dB remote antenna + 3 m extension 4854 0122
1.5 dB remote antenna + 5 m extension 4854 0123
Wall bracket for remote antenna 4854 0124
IP53 protection 4854 0300
IP67 protection 4854 0301
< 1200 m
Function < 31 devices(1)
Laptop
RS485
If the PC is not equipped USB
inter_002_a_2_cat
inter_142_g_1_gb_cat
RS485 communication port.
CO
UN
TIS
E Ci3
installation.
(1) Beyond these characteristics, use an " RS422 / RS485 repeater".
References
Description of accessories Reference
External USB / RS485 interface unit 4899 0110
STON
RE P
S X1
RUN
MMC
STOP
RES
DIAG
APL SYS
DIA
G
Modbus Modbus
LINK
L/A
Profinet
Advantages
ACT X2
APL SYS
Rx/Tx
IN
LINK
L/A
CH0
ACT
Rx/Tx
RTU
OUT
LINK
TCP
CH1
X3
ACT
DIRIS B-30
DIRIS G Logic
inter_150_b
LIN
AC
Rx T
/Tx
X2
controllers
diagnostic with a unique configuration
LIN
L/AK
Modbus
IN
CH0
AC
RTU
K
CH1
inter_151_b_gb
AC
T
PWR RDA
RDB BLA
BLB T+ T- R+ R- be exceeded. One solution to this technical
LINE-B
restriction is to install an interface which DIRIS A40 COUNTIS ECi
RS232 / RS485
amplifies the signal over a further 1200 m (at
PWR RDA PWR RDA
RDB BLA RDB BLA
BLB T+ BLB T+
OR
T- R+ T- R+
R- R-
LINE-B LINE-B
RS422/RS48
REPEATER 5
programmable Interface RS422/RS485
REPEATER
CO
UN
TIS
RS422/RS485
REPEATER
logic controllers R-
LINE-A
R+ T- T+
POWER
N
L
R-
LINE-A
R+ T- T+
POWER
N
L
1200 m
1200 m
systems
R-
R+ T- T+
inter_143_h_1_gb_cat
DIRIS A40 DIRIS A40
cabling.
References
CO
UN
DIRIS
A40 The accessories listed in these pages represent a selection from our range.
C
COUNTIS
We can supply many other solutions upon request, such as SHDSL interfaces,
C
COUNTIS
fibre optics/RS485, GSM/GPRS and protocol converter interfaces.
DIRIS E00
A40 E40
DIRIS
A10
M
DIRIS
A20
C
COUNTIS Need something integrating into your network?
mesur_112_d_1_gb_cat
E50 PLC
Gateway
your staff on its use.
For further information, please contact your nearest SOCOMEC branch.
TCP/IP RS485
B TM
M
C
S
/
Functions Power monitoring Power & Energy Monitoring Energy management Energy management
Realtime Data log Data log
Data management Realtime
Data log Analysis Analysis
Embedded in the DIRIS G Embedded in the DIRIS G
Hosting Installed on local server Cloud hosting
gateway gateway
Size of installation Small to medium Small to medium Medium to large Medium to large
Architecture
DATALOGGER
Pulse N’VIEW
Hosted on Cloud
DIRIS B-30 RF DIRIS G-40
Ethernet
2G/3G
DIRIS B-30 RF
CO
RS485 Lan/Wan
UN
TIS
E Ci3
COUNTIS E
RS485 Ethernet
DIRIS B-30 RS
DIRIS G-30
HYPERVIEW
Hosted on
RS485 local server
DIRIS A
WEBVIEW
verte_122_c_gb
Embedded
in the DIRIS G gateway
DIRIS Digiware
Expert Services
> Industry
> Building
> Infrastructure
> Local authority
soft_027_a_1_fr_cat
Function
The WEBVIEW web server embedded in Pre-set alarms defined by the user can sent Strong points
DIRIS G gateways enables measurement by e-mail.
monitoring up to 32 devices and displays the > Plug & Play
User can access WEBVIEW via a web
energy consumptions by usage. browser on a PC or a tablet. > Easy to use
> Various functions
Advantages
Plug & Play Various functions
Automatic detection of connected devices WEBVIEW ensures real time monitoring of
facilitates the WEBVIEW configuration. In all electrical parameters measured thanks
order to achieve the consumption distribution, to summary pages showing graphs or
the user is assisted in the metering plan charts. Time-logged alarms are recorded
definition. and displayed by usage, type, nature and
criticality. The user receives alarm notification
Easy to use
by email.
WEBVIEW centralises all the devices
Energy consumption breakdown is displayed
measurements via a unique, clear and easy-
per utility (electricity, water, gas…) and usage
to-use interface.
(heating, lightning…).
It provides easy and rapid monitoring of the
devices by displaying the parameters and
events on summary pages.
Functions
2 versions available:
Power Monitoring Power & Energy Monitoring
Monitor Alarm View
• Automatic detection of connected devices. • Alarms for overloads, events and input status • Historical measurements and consumption (one
• Summary of the parameters measured on the changes. year of data).
electrical network and the loads. • Display of alarm history. • Distribution of consumption by usage and by
• Measurements of voltage, current, power, • Sorting by type, nature, criticality or state. utility (water, gas, electricity, etc.).
power factor, harmonic distortion rate (THD) and • Alarm displayed on the main page. • Export of consumption data in CSV format.
harmonics per rank. • Sending of alarm by email (SMTP).
• Display of average/instantaneous values with min/
max limits depending on the devices. Power & Energy Monitoring also includes the
• Total and partial energy consumption per load. "Monitoring" and "Alarm" functions.
• Input / output status.
• Synchronisation of device clocks.
• Graphical or table representation.
References
Type Reference
DIRIS G-30 RS485 / Ethernet - WEBVIEW Power Monitoring 4829 0300
DIRIS G-40 RS485-RF / Ethernet - WEBVIEW Power Monitoring 4829 0301
DIRIS G-50 RS485 / Ethernet - WEBVIEW Power & Energy Monitoring 4829 0302
DIRIS G-60 RS485-RF / Ethernet - WEBVIEW Power & Energy Monitoring 4829 0303
> Industry
> Building
> Infrastructure
> Local authority
soft_030_a_1_cat
Strong points
Function
HYPERVIEW software is for consolidating all A simple and user friendly web interface > Energy cost management
the data collected by measuring and metering enables access to various analysis and power > Rapid results
devices. consumption optimisation functions. > Advanced analysis functions
Based on open-ended technologies, it can be
easily integrated into the IT environment.
Advantages
Energy cost management Rapid results Advanced analysis functions
The HYPERVIEW software provides summary HYPERVIEW is an intuitive and user-friendly Management of SOCOMEC device load
on energy savings achieved following the tool. Data can always be accessed thanks to curves ensures a precise analysis of
implementation of energy efficiency actions. the web portal displaying analysis reports with consumption and enables the detection of
Data about energy contracts and bills are dashboards or graphs. maximums and overflows for active and
registered into the system in order to reduce The HYPERVIEW software allows users to reactive power.
the energy costs. Functions for optimising the subscribe to reports and receive them by Thanks to calculated measurement points,
subscribed power enable the identification regular email. consumptions that cannot be measured can
of overcosts, and thus the possibility adapt be deducted through calculations.
usage and/or the subscription. Customised consumption models
based on relevant indicators facilitate
the implementation of a performance
measurement and verification protocol.
Functions
Energy management
Monitor and analyse Follow up your results Communicate
• Measurement and consumption history. • Integration of external data (temperature, etc.). • Display of customised full screen dashboards in
• Alerts for overloads, events and input status • Definition of energy consumption models. key areas.
changes. • Estimation of the results of your energy • Subscribe to reports and receive them by regular
• Display and export the data collected. performance actions. email.
• Distribution of consumption by area, usage, utility • Identification of gains and losses by comparing • Presentation of the data in a concise manner
and period. consumption over a reference period. to communicate and report environmental
• Identification of energy saving opportunities. performance.
• Comparison of consumption between different
sites and periods.
• Calculation and view of energy costs.
References
Type Reference Options Reference
HYPERVIEW on Server + software license contact us Graph creation tool contact us
Electrical powers contact us
Measurements and verifications contact us
> Industry
> Building
> Infrastructure
> Local authority
soft_043_a_1_fr_cat
Strong points
Function
The online service, N’VIEW, gives you To meet specific needs, the N'VIEW platform > Easy to use
an intuitive analysis of all your energy can extend its functional coverage by > Multi-user access
consumption. interfacing with existing or upcoming multiple > Various functions
Compatible with all leading commercial energy applications (energy apps).
gateways, including SOCOMEC dataloggers,
the N'VIEW platform manages multi-utility
data collection.
Advantages
Easy to use Multi-user access Various functions
Cloud-based hosting on a scalable and The N'VIEW service appeals to operational The N'VIEW service offers a wide range of
secure platform ensures the project is easily actors directly involved in energy features for monitoring measures, analysing
implemented, and offers great flexibility with performance, such as Energy Managers and energy consumption and managing costs.
an N'VIEW subscription. technical users (Facilities Managers). It also All these features are part of a continuous
Without the usual technical infrastructure provides services to help the management improvement plan for energy performance, as
problems, the user can concentrate on team define the energy strategy, and to help defined in standard ISO 50001.
managing their energy use. management controllers optimise and allocate
energy spending.
Functions
Energy management
Display Analyser Alert and communicate
• Display collected data. • Analysis and comparison of multi-fluid energy • Automatically generated or on-demand,
• Multiple viewing options (widgets) suitable for the consumption according to multiple criteria customizable reports.
type of data. (timeframe, site, fluid). • Programming multiple alerts (loss of data,
• Customisable dashboards. • Analyse energy costs. thresholds, overrun costs, excess consumption).
• Graphic presentation of the scope of analysis • Tariff simulation and comparison. • Manage and log alerts.
(hierarchy, plan of sites and buildings, industrial • Break down your energy bills depending on the
process diagram). provider.
• Set up indicators for measuring energy efficiency.
• Manage external influence factors (temperature,
surface, occupancy rate, production).
• Measure and verify according to the IPMVP
method.
• Manage and archive customizable queries.
References
Type Reference
N'VIEW Subscribe to the N'VIEW online service contact us
Function COUNTIS E
To get the most effective use from your Socomec measurement and metering devices, we can
provide dedicated software tools:
Easy Config software Webserver function
The Easy Config software enables quick and The DIRIS A’s optional Ethernet modules integrate
easy remote device configuration for DIRIS HTML pages, enabling the Webserver function
Digiware, DIRIS B, DIRIS G, DIRIS BCMS 720, to be directly accessed through a standard web
COUNTIS E and DIRIS A devices. Configuration browser (Internet Explorer, Firefox....), eliminating
files can be copied from and sent to these devices, the need for software installation.
or they can be created without communication and The Webserver function enables: DIRIS A
sent at a later time. - monitoring of electrical values,
Multiple devices can be configured from a single - viewing of energy consumption,
file which is especially useful for OEMs and panel
- managing alarms,
builders, saving time when having to program
many devices with the same configuration. - configuration of the main parameters
of installation
Analysis software
- viewing and extracting load curves
On the basis of an event log and the displayed
(through a .CSV file).
curves, the Analysis software allows the analysis
and extraction of quality data, as well as fault
current monitoring (Residual Current Monitoring).
DIRIS Digiware
Principle diagram
Software
Ethernet
RS485
Easy Config
DIRIS B30
verte_885_a_1_gb_cat
PC Software
Webserver
Software
Analysis
IEW
g
nfi
IEW
rve
RV
sis
Co
se
BV
PE
PLC
aly
sy
WE
HY
We
An
Ea
diris_886_a_1_gb_cat
The Easy Config software enables quick and easy remote
configuration of DIRIS Digiware, DIRIS B, DIRIS G, DIRIS
BCMS 720, COUNTIS E and DIRIS A devices.
Configuration of loads
diris_883_a_1_gb_cat
Analysis software
Improvement to the reliability of your electrical installation can be achieved with this software through the analysis of displayed event curves
generated from the event log.
This software can be connected to the DIRIS using either an RS485 MODBUS or Ethernet communication module.
The Analysis software can be downloaded from the SOCOMEC website: www.socomec.com
Event log
diris_837_a_1_gb_cat
Webserver function
The Webserver function comprises HTML pages embedded within the optional Ethernet
communication module of the DIRIS A's multifunction meter. These pages can be accessed via
an internet browser, simply by entering the DIRIS A IP address.
The Webserver offers the following functions:
• Monitoring of electrical values.
• Viewing of energy consumption.
diris_776_a_1_cat
• Management of alarms.
• Remote configuration of the main parameters for meters within the installation.
• Viewing and extracting load curves (through a .CSV file).
diris_869_a_1_gb_cat
Display for viewing instantaneous and average electrical values. Display for viewing instantaneous and average power measurements
and energy consumption.
diris_884_a_1_gb_cat
The latest alarms are date and time registered. The duration and value for
each alarm (low limit value / high limit value), as well as the related output
alarm number, are also displayed. Data can be extracted in *.csv format.
Non contractual document. © 2016, Socomec SAS. All rights reserved. - document printed on paper from sustainably managed forests.
Critical Power / Power Control & Safety /
Critical Power Energy Efficiency
Tel. +48 22 825 73 60 Tel. +90 216 540 71 20-21-22
Fax. +48 22 825 73 70 Fax +90 216 540 71 27
info.ups.pl@socomec.com info.tr@socomec.com
Power Control & Safety / Energy Efficiency
Tel. +48 91 442 64 11 UNITED KINGDOM
Fax +48 91 442 64 19 Critical Power
info.scp.pl@socomec.com Tel. +44 1285 863 300
Fax +44 1285 862 304
info.uk@socomec.com
Power Control & Safety / Energy Efficiency
Tel. +44 1462 440 033
Fax +44 1462 431 143
info.uk@socomec.com
www.socomec.com