August 2010
Supervisors:-
1
Table of Contents
3
List of Figures
4
List of Tables
Table 6.1 Comparison of heat flux relative error values of different circuits….28
5
[1] Introduction:
(i) Systematic errors- Errors that tend to be in one direction, either positive or
negative. Some of the sources are:
Instrumental errors- Errors that arise from the imperfect design or
calibration of the measuring instrument (Zero error in the instrument).
Errors due to imperfection in experimental technique- Errors that arise
from effects of external conditions or any unfavorable conditions during
experiments.
Personal errors- Errors that arise due to an individual’s bias, lack of proper
setting of the apparatus or individual’s carelessness in taking observations
without observing proper precautions.
Systematic errors may be estimated to a certain extent and the necessary corrections may be
applied to the readings.
(ii) Random errors- Errors that occur irregularly and hence are random with respect to
sign and size. These can arise due to random and unpredictable fluctuations in
experimental conditions.
(i) Absolute error- The magnitude of the difference between the true value of the
quantity and the individual measurement value is called Absolute Error of the
measurement.
In the absence of any other method of knowing the true value normally the true
value is the arithmetic mean of the measured values.
(ii) Relative error- The ratio of the mean absolute error (ΔA mean) to the mean value of
the quantity measured is called Relative Error.
6
(1.3) Error propagation law - When several quantities are measured then errors in all the
measurements combine and so the error propagation law can be used. Actually there are rules
for addition, subtraction, product and division. Suppose we are measuring two quantities A
and B.
(i) Error of a sum or a difference- Here A and B have a measured value A±ΔA and
B±ΔB respectively, where ΔA and ΔB are their absolute errors. So the total error
for Z is Z=A+B. Thus for addition…
Z±ΔZ = (A±ΔA) + (B±ΔB) …. (1.4)
‘When two quantities are added or subtracted, the absolute error in the final
result is the sum of the absolute errors in the individual quantities’.
Z±ΔZ = (A±ΔA)(B±ΔB)
Z±ΔZ = AB ± BΔA ± AΔB ± ΔAΔB
By ignoring the quantity ΔAΔB as this product is small compared to other terms and
so
‘When two quantities are multiplied or divided, the relative error in the result is
the sum of the relative error of individual quantities’.
(1.4) DIN norms for different accuracy classes of measured quantities of CHCP-
Temperature – DIN EN 60751
Volumetric flow rate – DIN 1434
For heat flux( ) both of these accuracy classes can be used and heat flux depends on
the manufacturer of the heat flux measuring device. /1/
7
[2] List of accuracy classes and its ranges for measured quantities of
CHCP-
T = Temperature in °C
Here mainly temperature sensor pairs or a single temperature sensor are used. With the help
of a temperature sensor pair the temperature difference of any circuit can be obtained and thus
it gives us the heat flux of that circuit. In the case of temperature sensor pairs both sensors
always belong to the same accuracy class i.e. both sensors will be A and A, B and B or 1/3B
and 1/3B, and thus the accuracy limit can be calculated from the single accuracy class. From
the data sheets of the manufacturer (Thermo Sensor) accuracy limits are ±0.05% between 0°C
to 100°C. Though the accuracy limits are shown in the graphs below in the section [3]. /2/
(2.2) Volumetric flow rate - According to DIN EN ISO 5167 the measurement of
volumetric flow rate has three accuracy classes
Having an approximation about the value to be measured, DN type and accordingly the
nominal value of volumetric flow rate can be selected. The volumetric flow ranges are mainly
dependent on the particular application and the manufacturer of the device. Here mainly three
types of measuring instruments for volumetric flow rate measurement are used, which are US
(Ultrasonic device), MID (Magnetic inductive device) and Mechanical device. Accuracy
limits are shown in the graphs below and it can be seen that MID devices are the most
accurate devices for volumetric flow measurement. /3/
8
(2.3) Heat flux - Accuracy classes and ranges for heat flux mainly depend on the
manufacturer and the application of the instrument.
Here also mainly three types of instruments are used, which are dependent on the temperature
difference, volumetric flow rate and the medium and the absolute temperature of the medium.
In both the plants Ultrasonic devices are used for direct heat flux measurements in compact
conditions while magnetic devices are used for indirect heat flux measurement. Moreover the
error of heat flux measurements can be calculated with the help of the error propagation law
with two quantities which are temperature and volumetric flow rate.
9
[3] Graphical representation of different accuracy classes with tolerance
ranges-
(3.1) Temperature classes – Here graphs for the temperature range between 0°C to 150°C
are shown. DIN EN 60751 for different accuracy classes. The 12 values of temperature has
been taken and the graph has been made for values between (-30°C to 300°C). These graphs
for different classes (Class A, Class B and Class 1/3B) are shown below./2/
0.8
0.6
0.4
0.2
Accuracy limits in (K)
-0.2 Temperature °C
-0.4
-0.6
-0.8
-1
-50 0 50 100 150 200 250 300 350
In class A we can see that the maximum absolute error reaches at 0.75K at 300°C. The
absolute error for this temperature range lies between 0.09K to 0.75K. From this absolute
error values the relative errors can be calculated with the help of formula given below
10
(ii) Class B – (-50°C to 500°C)
0.4
0.3
0.2
0.1
Accuracy limits in (K)
-0.1 Temperature °C
-0.2
-0.3
-0.4
0 20 40 60 80 100 120 140 160
0.4
0.3
0.2
Accuracy limits in (K)
0.1
-0.1 Temperature °C
-0.2
-0.3
-0.4
0 20 40 60 80 100 120 140 160
11
Thus from these graphs it can be seen that class 1/3B has the highest accuracy
among all the accuracy classes of temperature sensors.
(3.2) Volumetric flow classes – The graphs for volumetric flow rate depend on the
manufacturer. As shown in DIN 1434 the classes of volumetric flow rate sensors contain p
and in the formula. p is the nominal value of volumetric flow rate and as said earlier it can
be chosen according to the application.
According to DIN EN ISO 5167 Class 2 for ultrasonic volumetric flow rate measurement
device (US) [By aqua metro]. The device can be chosen in the range between 1.5m3/h to
25m3/h.
For the device used here has the nominal value of volumetric flow rate i.e. p is 2.5 m3/h, as
the device is of DN 20 type. /4/
E
r
r
o
r
(m3/h)
The method of getting absolute value volumetric flow rate curve is shown here.
Here Qp = 2.5m3/h Multiplying Qp with the first point of a logarithmic volumetric flow rate
absolute volumetric flow rate can be obtained as shown here
12
p(absolute) = p * 0.01 = 2.5m3/h * 0.01 = 0.025 m3/h
Figure 3.4 shows the logarithmic graph given by the manufacturer. Here the nominal value of
the volumetric flow rate is 2.5m3/h, and so by multiplying this value with x-axis the absolute
value of volumetric flow rate can be obtained as shown above by keeping the y-axis values
same as the manufacturer graph. From this relative error graph is made as shown below in
figure 3.5. Now onwards all the logarithmic graphs have been converted into absolute value
by the same method as shown above.
2
E
r 1
r 0
o -1 0 0.5 1 1.5 2 2.5 3 3.5 4
r
-2
% -3 (m3/h)
-4
-5
Positive accuracy limit Negative accuracy limit
Figure3.5 Relative error graph of ultrasonic device derived from the logarithmic graph
According to DIN EN ISO 5167 for magnetic inductive volumetric flow rate measuring
device (MID) [By aqua metro], the range of this device is between 1.5 m3/h to 60m3/h.
As described above the graph shown below is also a logarithmic graph given by the
manufacturer. As the nominal value of volumetric flow rate is 3.7m3/h, and the method
discussed above can be used for the absolute volumetric flow rate graph.
13
E
r
r
o
r
(m3/h)
4
E
r 2
r
0
o
0 0.5 1 1.5 2 2.5 3 3.5 4
r -2
%
-4 (m3/h)
-6
-8
Positive accuracy limit Negative accuracy limit
Figure3.7 Relative error graph of magnetic inductive device derived from the
logarithmic graph
Thus the accuracy of the volumetric flow measurement device depends on the manufacturer
of the apparatus, here it is aquametro.
14
(iii) Mechanical device 1:-
The graph of the accuracy class for mechanical device from aquametro, with water
temperature 20°C is shown below. From here graphs shown below are for DN 25 and as well
from the manufacturer data sheet.
The nominal value of volumetric flow rate p is 6.3m3/hr, as per DN25 type. The graph
shown below is having values as follows
This graph can be read by the values given and from that it is clear that accuracy limit ranges
between ± 2%. From Typische Fehlerkurve it is clear that volumetric flow rate measured
below 2 is having the highest accuracy limits fluctuation.
E
r
r
o
r
(m3/h)
Figure3.8 Error graph of mechanical device 1 from manufacturer
15
6
E
r 2
r
o 0
r 0 1 2 3 4 5 6 7 8
% -2
(m3/h)
-4
-6
Positive accuracy limit Negative accuracy limit
Figure3.9 Relative error graph of mechanical device 1 derived from the manufacturer
graph
The graph of accuracy class for mechanical device 2 from aquametro is shown below. Here
graphs are obtained as DN 25 and as well from the manufacturer data sheet.
The nominal value of volumetric flow rate p is 3.5m3/h, as per DN25 type. /4/
This graph can be read by the values given and from that it is clear that accuracy limit ranges
between ± 1%.
Thus from all these graphs and discussion we can conclude that MID devices are
having the highest accuracy amongst all.
16
Figure3.10 Error graph of mechanical device from manufacturer
1.2
0.8
E 0.6
r 0.4
r
0.2 (m3/h)
o
r 0
0 1 2 3 4 5 6
-0.2
%
-0.4
-0.6
Accuracy limit
Figure3.11 Relative error graph of mechanical device 2 derived from the manufacturer
graph
17
[4] List of monitored measuring data–
18
Figure4.1 Plant layout of Blumenhaus Bade /6/
19
Secondary heat Circuit outlet T17 Pt100 1/3 DIN(B)
temperature(THT-OUT-SEK)
20
(4.2) Haiger-
21
Figure4.2 Plant layout of Haiger/6/
22
Warm water heating from chiller waste T17 Pt100 (Sensor Pair) Class B
input Temperature (T_WW_VW_IN)
VGAS 1 Pulse
23
VSPK(6 m3/h) 6 Ultrasonic ±2%
Heat flow from buffer SP-2 to SP-1 Q1 Ultrasonic heat flow ±3%
(QWW)
Heat flow from SP-1 to HK-1 (QHK) Q2 Ultrasonic heat flow ±3%
Heat flow from HK-1 to buffer SP-1 Q3 Ultrasonic heat flow ±3%
(Q_SP2)
24
[5] Statement of different accuracy limits for heat flux of CHCP plants –
In both the plants i.e. Blumenhaus Bade and Haiger the accuracy limits of heat fluxes are to
be measured. Though the plants have heat flux measuring devices, the intention of the report
is to calculate the heat flux accuracy limits from the volumetric flow rate and the temperature
accuracy limits. These values can be calculated with the help of error propagation law.
The values to be analyzed are shown below in the tables and can be obtained by the accuracy
limits of temperature sensor pairs and the volumetric flow measurement devices.
The tables given below present the accuracy limits for heat fluxes to be measured and the
description is given below.
Here the accuracy limits of different heat fluxes values are to be measured in Blumenhaus
Bade CHCP plant. These are QNT, QMT, QHT, QBHKW, QWW, QHK1+2, QHK3.
The heat flux accuracy limit can be calculated from the error propagation law. Error
propagation law for multiplication and division says that
‘When two or more quantities are multiplied or divided, the relative error in the result
is the sum of the relative error of individual quantities’.
According to heat flux equation as shown below heat flux depends on four parameters and
that are temperature difference, flow rate, density and specific heat capacity.
Q = V*ρ*Cp* ΔT …. (5.1)
Density is a function of temperature and pressure. Neglecting the density error due to pressure
changes and considering density error due to temperature dependency calculation is shown
below.
As well Specific heat capacity is also a function of temperature and then in calculation
dependency of specific heat capacity on temperature is shown. Thus the error in temperature
is considered as the error in density and specific heat capacity.
According to error propagation law the accuracy limit for the heat flux can be calculated with
the relative error values of individual quantities i.e.
Thus the relative heat flux errors calculated through this law is presented in the table below.
The temperature accuracy limits are given in K.
As the maximum absolute error of temperature sensor pair is ±0.05K between 0°C to 150°C
as given by the manufacturer(Thermo Sensor AG) and so that value is considered for heat flux
25
calculation and i.e. for QNT, QMT, QHT, QBHKW for Blumenhaus Bade plant and QNT, QMT, QHT,
QBHKW, QWWV for Haiger plant.
The relative accuracy limit of temperature and volumetric flow rate can be seen in the graphs
as well the absolute values can be converted into relative value by the equation shown below.
/1/
CpBHKW …. (5.3)
Density is a function of temperature and pressure. The pressure dependency is very less and
neglecting the density changes due to pressure only temperature is taken into account. From
the table given in www.simetric.co.uk/si_water, density relative error is calculated as shown
below.
If temperature changes by 0.1°C, the density changes in small amount. From the data given in
the web-site shown above 10 density readings are taken into account and by deriving the
mean value relative error is calculated and the maximum value of relative error of density is
±0.01% at 80°C. This temperature is maximum possible temperature in the circuits of CHCP
plants. /8/
Specific heat capacity is a function of temperature also. The relative error in specific heat
capacity can be calculated by two methods as shown below.
(I) From the data given in Heat and mass transfer book by Domkundwar.
(II) From the differentiation of the equation shown below.
Cp = Cp0 + αT + αT2
T = Temperature
By taking the simple way of finding relative error from method (I) and with same procedure
as shown for the density, the specific heat capacity relative error value is ±0.04%. The method
is to notice the specific heat capacity change with 0.1°C temperature change. /7/
26
The volumetric flow rate device used here is Ultrasonic device and relative error value for that
is ±2%.
The method shown here is used for the relative error calculation of all the heat fluxes in
different circuits. /6/
Heat Temperat Tem Temper Density Specific Volumetric Flow Heat flux
flux ure Sensor pera ature relative heat flow rate rate relative
Pair ture relative accuracy capacity device relative accuracy
diffe accurac limit relative accurac limit
renc y limit accuracy y limit
e limit
(K)
QNT T23 - T22 5 ±1% ±0.01 ±0.04% V8 ±2% ±3.05%
(MID)
27
(5.2) Haiger:-
Here the accuracy limits of different heat fluxes values are to be measured in Haiger CHCP
plant. These are QNT, QMT, QHT, QBHKW, QWW, QHK, QWWV.
The heat flux accuracy limit can be calculated from the error propagation law. Error
propagation law for multiplication and division says that
‘When two or more quantities are multiplied or divided, the relative error in the result
is the sum of the relative error of individual quantities’.
According to heat flux equation as shown below heat flux depends on four parameters and
that are temperature, flow rate, density and specific heat capacity.
Q = V*ρ*cp* ΔT …. (5.1)
Density is a function of temperature and pressure. Neglecting the density error due to pressure
changes and considering density error due to temperature dependency calculation is shown
below.
As well Specific heat capacity is also a function of temperature and then in calculation
dependency of specific heat capacity on temperature is shown. Thus the error in temperature
is considered as the error in density and specific heat capacity.
According to error propagation law the accuracy limit for the heat flux can be calculated with
the relative error values of individual quantities i.e.
Thus the relative heat flux errors calculated through this law is presented in the table below.
The temperature accuracy limits are given in K.
As the maximum absolute error of temperature sensor pair is ±0.05° C between 0°C to 150°c
as given by the manufacturer(Thermo Sensor AG) /5/ and so that value is considered for heat
flux calculation and i.e. for QNT, QMT, QHT, QBHKW for Blumenhaus Bade plant and QNT, QMT,
QHT, QBHKW, QWWV for Haiger plant.
The relative accuracy limit of temperature and volumetric flow rate can be seen in the graphs
as well the absolute values can be converted into relative value by the equation shown below.
/1/
28
Table 5.2 Calculated heat fluxes at Haiger
Heat Tempera Temp Temperat Density Specifi Volumetric Flow Heat flux
flux ture eratu ure relative c heat flow rate rate relative
Sensor re relative accura capacit device relativ accuracy
Pair differ accuracy cy limit y e limit
ence limit relative accur
(K) accura acy
cy limit limit
QNT T23 - T24 5 ±1% ±0.01% ±0.04% V5 ±2% ±3.05%
(US)
QMT T21 - T22 5 ±1% ±0.01% ±0.04% V4 ±2% ±3.05%
(US)
QHT T19 – T20 7 ±0.7% ±0.01% ±0.04% V3 ±2% ±2.75%
(US)
QBHKW T09 – T10 12 ±0.4% ±0.01% ±0.04% V2 ±2% ±2.45%
(US)
QWW T20 – T21 20 ±0.2% ±0.01% ±0.04% V6 ±2% ±2.25%
(US)
QHK T22 – T23 10 ±0.5% ±0.01% ±0.04% V3 ±2% ±2.55%
(US)
QWWV T17 – T18 20 ±0.2% ±0.01% ±0.04% V1 ±2% ±2.25%
(Mechanical)
29
[6] Energy/Heat balance of Blumenhaus Bade CHCP plant and error
calculation from the data
Theoretically and i.e. with the help of the error propagation laws the values of relative errors
for different heat fluxes are shown and discussed. Now from the actual data of Blumenhaus
Bade plant the relative error calculation is shown below.
The data measured have temperature and volumetric flow rate values for different circuits and
so one can calculate heat flux (Q) with the formula
= *cp* ΔT …… (6.1)
Here with the values of the volumetric flow rate the mass flow rate can be calculated easily if
the density of heat transfer fluid is known from the formula
= *ρ …… (6.2)
And so
In these plants two circuits i.e. HT circuit and MT circuit have water and glycol mixtures as
heat transfer fluid. The percentage of water in the mixture is 80% while 20% is glycol. The
remaining circuits use water as heat transfer fluid. Specific heat capacity and density of the
mixture can be calculated from the formula given below.
x1 and x2 are the percentages of the component in the mixture. From these formulas cp and ρ of
the mixture can be calculated if these two values for an individual component are known.
From this formula density and specific heat capacity value for the mixture of water (80%) and
glycol (20%) are shown below.
30
cp mix = 3.35 kJ/kg*K
The circuits HK1+2 and HK3 are not in use during summer because of no need of heating.
Thus the heat flux values in these circuits are zero. /6/
Here heat flux values for all circuits have been calculated with the help of equation (6.3). For
particular time heat flux value relative accuracy is calculated as shown below.
By determining the temperature difference and volumetric flow rate value at the particular
point relative error can be found as shown in section /5/. Eight points have been taken into
consideration to find out the maximum and minimum relative error values from the one day
data of Blumenhaus Bade plant. From these eight points two points are at maximum and
minimum heat flux values. It has been seen that at the minimum heat flux values accuracy of
measurement is not good.
Here time interval during which the device is on stand still is neglected and the values at
steady state are considered. The example of relative error calculation from measured data is
shown below.
CpBHKW …. (6.4)
The temperature difference at peak point of heat flux curve is 11.52 K from the data of
measurement. Relative error of temperature is
As well density and specific heat capacity are the functions of temperature and so these both
quantities have the relative error as described above.
The volumetric flow rate device used here is Ultrasonic device and measured value of
volumetric flow rate is 0.632m3/h. From the graph of the US device the relative error value is
±2.5 %.
The method shown here is used for the relative error calculation of all the heat fluxes in
different circuits. /6/
31
Table 6.1 Comparison of heat flux relative error values of different circuits
Heat flux ( ) Average heat Maximum heat Minimum heat Relative error
(kW) flux value ) flux relative flux relative as per
(kW) error% error% theoretical law
in %
QBHKW 9.6978 ±2.98 ±2.35 ±2.45
The heat flux values for the WW circuit varies too much because it is only used when hot
water is required for domestic application e.g. for taking bath. /7/
As well volumetric flow rate measuring device of NT circuit is not working at the moment
and so heat flux in NT circuit is calculated by doing heat balance of adsorption chiller and
obtained by the formula
32
[7] Conclusion
Here conclusion can be made that results obtained of relative error by doing energy balance
are quite reliable and one can make prediction of an error value from this work. Even though
there is a variation in the relative error value obtained by energy balance of the plant and
reasons for that are shown below.
Here density is a function of temperature and pressure while specific heat capacity is a
function of temperature. But effect due to pressure change is neglected here.
As well in calculation of heat flux value for NT circuit, heat loss is ignored while heat
balancing around the adsorption chiller.
As well due to periodic operation of an adsorption chiller the mean value and error
from data is high.
Uncertainty of WW circuit as discussed earlier.
As well imperfection in experimental technique/procedure and personal errors.
As well table shown below is the recommendation for temperature sensor pair and volumetric
flow rate device for different heating circuits.
The recommendations are mainly based on the measured values and by keeping in mind that,
the values to be measured are high then high accuracy class devices are to be used and the
values to be measured are low then low accuracy class devices should be used.
Thus the error calculation of the whole CHCP plant can be done easily with the help of the
work shown here.
33
References
http://www.amazon.com/Handbook-Physics-Walter-Benenson/dp/0387952691
Measurement of fluid flow by means of pressure differential devices inserted in circular cross-
section conduits running full -- Part 1: General principles and requirements, 2003
/4/ Aquametro data sheets for volumetric flow rate
/6/ Solar Institute Jülich data sheet for plants of CHCP plants
/7/Arora, Domkundwar
Dhanpat Rai and company, 4779/23, Ansari Road Darya Ganj, New Delhi –
110002, 2004
/8/ www.simetric.co.uk/si_water
34