Beruflich Dokumente
Kultur Dokumente
SF6 RMU/USS
upto 22kV 12 kV 26.3 kA Indoor VCB
12 kV Outdoor Kiosk
12 kV 20 kA Indoor VCB
12 kV Indoor
Vertical Isolation Upto 36 kV
VCB Outdoor VCB
Indoor Medium Voltage Switchgear upto 36kV
Salient features
Modular design. Same pedigree for the full range.
Configurable paneling features to suit various site conditions.
2 Clas
Total compartmentalisations with earthed metal partitions.
Panel with built -in base frame.Hence no separate base frame required.
s
Inaccessible live parts eliminating accidental Contact.
Self powered tripping devices (optional ).
Vacuum Contractor for motor feeder Application. Certification
Removable shrouds at main busbar joints/tap off.
Artful combination of ruggedness and simplicity.
Reliable interruption with low chopping current.
Compatible with state of art protection system including SCADA.
Full interchangeability and high application freedom.
Horizontal / Vertical isolation and horizontal withdrawal from panel.
Easy operation .
Electrostatic powder coated and ergonomically designed fascia.
We take great pleasure to inform you that based on
Floor rolling Breaker Trolley.
Combination of positive mechanical and electrical interlocks. the requirement of IEC 62271-100 for Extended
Ensures total operator safety. Mechanical Endurance for frequently operated
Flush front design. Circuit Breakers, we have successfully qualified
Speedy installation. all our Breakers for "CLASS M2" compliance,
Easily re-locatable / extensible on either sides. which consist of 10,000 operating sequences of
Compact design with less floor space. the Circuit Breaker as against 2000 operations
Rack-in / Rack-out of Breaker truck with front door closed (Optional). (M1 Class). .
Earthing truck with positive interlocking and live line indicator for
alarm(Optional). The performance and reliability of the Circuit
Emergency Mechanical Tripping arrangement (Optional). Breakers has increased manifolds and CGL is
Power pack (Optional). amongst few Companies Worldwide which
meets the stringent requirements of Class M2
as per IEC 62271-100. .
Test & Performance
Type tested for rapid autoreclosing duty.
Type tested for Extended Mech Endurance (M2 Class)
as per IEC 62271-100.
VCB panel design based on air clearance & unforced cooling basis.
12kV VCB Panel type tested for Internal Arc fault tested as per IEC - 62271-100.
TECHNICAL SPECIFICATIONS
Type of Isolation Horizontal Isolation and Horizontal Isolation and Vertical Isolation and Horizontal Isolation and
Horizontal Drawout Horizontal Drawout Horizontal Drawout Horizontal Drawout
Rated Voltage kV Upto 12 Upto 12 Upto 12 Upto 36
No of poles Nos 3 3 3 3
Frequency Hz 50 50 50 50
Symmetrical Breaking Capacity kA-rms 26.3 31.5 40 13.1 20 26.3 13.1/18.4 25
Rated Current Amp 1250/ Upto 1250 /1600 800 800 800 Upto 800 630/1250/2000
1600 / 2000 1250 2000/ 2500/ & &
1250 1250
3150
Making Capacity kApk 65.75 78.75 100 32.75 50 65.75 33/47 65.75
DC Component % <50 <50 <50 <50
Duration of Short Time Current Sec. 3 3 3 3
Impulse Withstand Voltage kVpk 95 75 75 75 75 170
JV 40kA Trolley
Univac Trolley
TABLE
GROUND
REF DIM-"C" DIM- " D" LEVEL
1 425 2300
2 725 2600
FRONT VIEW SIDE VIEW (SIDE SHEETS REMOVED)
' Univac'
va
ac' Panel
(compact
pact
act Version)
V
GROUND LEVEL
CU BUSBARS
(6mm X 38mm)
2 Nos/PHASE
AL BUSBARS
(6mm X 38mm)
3 Nos/PHASE
613
'R'
'Y'
'B'
435 610
ON 75 930
G/L
287 287 300 560
574 1120
TECHINICAL SPECIFICATIONS
Model Roof bushing
Rated Voltage kV 12
No of poles Nos 3
Frequency Hz 50
48 2
415
4 82
2850
PH-EARTH
CLARANCE
ITEM DESCRIPTION
VCB MECHANISM - MOTORISED
TECHINICAL SPECIFICATIONS
Model Line up
Rated Voltage kV 12
No of poles Nos 3
Frequency Hz 50
180
180
2350
832
40 40
855*
1906
FRONT VIEW SIDE VIEW
VCB KIOSK PANEL WIDTH SHALL BE 705MM FOR RATING UPTO 1250A
11
9 4
PT
2 7 8
10
CT
5
3
6
3130
* 2066MM HEIGHT PANEL IS ALSO AVAILABLE
SIDE VIEW
36 kV VCB