Sie sind auf Seite 1von 2

Elite Uninterruptible Power Systems

WTC Series 700VA and 1kVA Wall Mounted


On-line sinewave power protection

Elite Uninterruptible Power Systems


The WTC range of Elite Uninterruptible Power Systems (UPS) offers reliabile, flexible and upgradeable power
protection for retail Point of Sale terminals, keyphone systems, small PBX switches and mobile applications. A

®
range of enhancements is available including battery packs, maintenance bypasses and monitoring software.
®
Spike and electrical noise u PowerShield software: Elite can
protection: built-in EMI be remotely managed using the
filters remove mains borne software package bundled with each
spikes and electrical noise. UPS. The software provides realtime
Power factor correction prevents operating and historical data, access
any generated interference from to internal UPS logs, and can
polluting the mains supply. perform an orderly system
shutdown. A general Windows
Surge, sag and brownout version of the software is supplied
protection: a wide input with each UPS on a 3.5" disk. Other
voltage range helps Elite to versions of the software can be
smooth out sags and surges downloaded from the AEL Group
without resorting to battery power. website including versions for
This remains maximised for real Windows NT, Unix, Novell and other
emergencies. popular operating platforms.

Mains power failures: u Remote monitoring: Elite


Elite generates a 'break-free' provides opto-isolator signal WTC1KVA007 wall mounted Elite UPS
sine-wave supply at all times contacts from a built-in D 9Way rear
from either its battery or the panel connector. The signals can be
mains. A built-in automatic bypass converted to 'volt-free' using an
provides further protection from ARB converter to drive an IBB series
system overload and failure. wall mounted remote panel or
connect to a Building Management
u Battery extension packs: allow System (BMS).
the WTC1KVA007 UPS to provide
®
up to 7 hours runtime at various u LinkUPS : Elite can be monitored
WTC1KVA007 rear panel connectors
loads. The battery packs can be on a 24/7 basis by the Advance-
either floor standing or 19" Galatrek service centre to offer faster Standard features include:
rackmount format, depending upon response times, and on-site
the capabilities of the 19" cabinet. monitoring. u 'Plug and Play' hot swappable
battery extension packs.
®
u PowerSwitch maintenance u Other formats: Elite is also u A two stage charging process to
bypass: an optional external bypass available in floor standing and 19" reduce battery recharge times and
allows the UPS to be powered down rackmount formats with matching enhance battery performance.
without disruption to the load for accessories. u Built-in battery and inverter tests.
maintenance or upgrade. The ®
u Built-in historical operating logs.
bypass is designed to be mounted u FlexiSafe Power Distribution u High operating efficiency and
ADVANCE-GALATREK

on the wall near the UPS. A 19" Units: a range of PDUs for wall or 19" negligible heat generation.
rackmount version is also available. horizontal or vertical mounting with a u Office compatible design and
combination of sockets, meters, virtually silent in operation.
®
u StrikeSafe lightning and switches and surge protection, can u An easy to view and understand
Transient Voltage Surge further enhance the UPS installation front panel visual display with
Suppression (TVSS): Elite can be and associated power management. load and battery charge % LEDs.
installed with a separate wall mounted u Built-in RS232 and signal
TVSS module to protect both the UPS contact communications.
and connected load(s) from large
transients and the effects of nearby
lightning strikes, to BS6651.
Technical Specifications
®
Elite WTC series
u Design Topology: on-line double conversion u Short Order Codes and Runtimes:
u Rating: 700VA/450W and 1kVA/700W - the maximum
loading for extended runtimes up to 4 hours is 620W Short Model No Dimensions Weight
u Input Voltage Window: 170-276V Order Breakdown WxDxHmm Kg
u Input Frequency: 50/60Hz Code (ea) (ea)
u Input Frequency Window: ±5%
u Input Power Factor: > 0.98 W70V007B WTC700VA007 158x231x376 8
u Input Current: Sinusoidal 5m@450W FBS015 402x100x82 4
u Output Voltage: 230V±1.5%
W1K0007B WTC1KVA007 158x231x376 11
u Output Frequency: 50/60Hz auto-selection 6m@700W FBS015 402x100x82 4
u Output Waveform: Sinewave with less than 2% THD
u Load Crest Factor: up to 3:1 W1K0021B WTC1KVA007 158x231x376 11
u Protection: Excessive battery discharge, over current, 26m@700W FBS015 402x100x82 4
short circuit proof, under voltage and thermal. BEP036014A/03 158x376x231 21
u Bypass Voltage Range: 180-264V
W1K0031B WTC1KVA007 158x231x376 11
u Bypass Frequency Range: ±5Hz
45m@700W FBS015 402x100x82 4
u Controls: Rocker switch-ON/OFF, Push buttons-Standby, BEP036024B/04 205x635x250 41
On/Alarm silence/Battery test/Reset timer
u LEDs: Load%, Battery charge%, Mains present/Timer W1K0045B WTC1KVA007 158x231x376 11
activated, On battery, Check battery, On bypass, and 1h10@700W FBS015 402x100x82 4
Alarm/Fault/Standby BEP036038B/04 205x635x250 51
u Computer & Network Interface: 1x’D’ 9Way providing
RS232 communications, opto-isolator signal contacts W1K0083B WTC1KVA007 158x231x376 11
and remote shutdown after 3 seconds 2h15@700W FBS015 402x100x82 4
u Signal Contacts: On battery, Low battery and shutdown BEP036076X/04 205x635x500 103
u Alarm Indication: LED, audible, signal contacts
u Batteries: Sealed lead acid maintenance free, 5 year design W1K0107B WTC1KVA007 158x231x376 11
life with a typical recharge time of 5-7 hours 4h@620W FBS015 402x100x82 4
u Operating Temperature: 0 to 40°C BEP036076X/04 205x635x500 103
u Relative Humidity: <90% non condensing BEP036024B/01 205x635x250 41
u Audible Noise: <40dB @ 1m
Note 1: WTC=UPS, FBS=bypass, BEP=battery extension pack.
u Case Finish: RAL 7035 light grey Note 2: Mains supplies - one BS style 13A socket for the UPS
u Safety Conformity: EN50091-1, directive 73/23/EEC and a further BS style 13A socket if a '/04' battery extension
u EMC Conformity: EN50091-2cl.B, directive 89/336/EEC pack is required.
u Surge Capability: IEC 801-5, 6kV 1.2/50µs, 3kA/ 8/20µs u WTC bracket dimensions:
u Software Supplied: each UPS is supplied with UPS 198mm
monitoring and shutdown software for Windows 3.x and
9x. On standalone NT the software provides UPS
monitoring only. Other versions are available for
download from the AEL Group website. Customers can
also join a mailing list for future updates.
u UPS Connections: the mains and one of the four IEC320 4x12mm slot 344mm
243mm
load sockets have retaining clips.
u Optional FBS015 Bypass Connections: the bypass
connects to the mains supply through a BS style plug. Load
plugs into one of the 4xBS style sockets on the the bypass.
UPS input and output supplies connect to the bypass using
IEC320 cables. The FBS007/03 is an alternative bypass
providing only a single IEC plug to connect into the load on a 178mm
2m cable. The cable is hardwired into the bypass itself.
u Optional Battery Extension Pack (BEP) Connections: For more information, please visit
BEPs are floor standing. They have a 2.5m lead to connect to our web site:
the DC socket on the rear of the UPS. Further battery
extension packs connect in parallel using a 1m lead.

www.aelgroup.co.uk
Copyright © 2000, Advance Electronics Ltd. Elite is a registered tradename of Advance Electronics Ltd.
In the interests of continuing improvement, Advance Electronics Ltd reserve the right to alter specifications without notice.
ADVANCE-GALATREK sales uk email facsimile
Advance Park 0800 269 394 sales@aelgroup.co.uk 01978 810 852
Wrexham LL14 3YR international website
United Kingdom +44-1978 821 000 www.aelgroup.co.uk An AEL Group company Cert No.1760
& 1760/01