BASIC CALCULATION FOR PUMP & TANK SELECTION

The following are the design considered based on NFPA 13 / 14 & 24

1) FIRE HOSE REEL SYSETM

FHR Flow rate = 50 gpm


Max No of FHR in operation at any time = 2 Nos
Duration of operation = 90 mins Ordinary Hazard- II (e.g Public )

Fire hose reel TANK STORAGE CAPACITY (for Ordinary Hazard Area)

= 50 gpm * 2 No * 90 Mins 9000 gpm

Total storage volume required = 9000 gallons (Minimum)


1 galloons = 3.785 litres

Total storage volume required = 9000 gallons * 3.785 34065 litres

TOTAL STORAGE TANK VOLUME 34 m3

Pump flow rate required = 2 x 50 gpm = 100 gpm


Fire hose reel pump Head calculation
Residual Pressure required at FHR = 4.0 Bar

Pressure loss in pipe/fittings etc = 0.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar

Total head pressure required = 5.0 bar Minimum.

2) FIRE HYDRANT SYSETM

Hydrant Flow rate = 250 gpm


Max No of FH in operation at any time = 2 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)

Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)

= 250 gpm * 2 No * 90 Mins 45000 gpm

Total storage volume required = 45000 gallons (Minimum)


1 galloons = 3.785 litres

Total storage volume required = 45000 gallons * 3.785 170325 litres

TOTAL STORAGE TANK VOLUME 170 m3

Pump flow rate required = 2 x 250 gpm = 500 gpm


Fire hose reel pump Head calculation
Residual Pressure required at FHR = 4.5 Bar

Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar

Total head pressure required = 6.5 bar Minimum.

3) SPRINKLER SYSETM

Sprinkler spacing will be 3.6 meters


design density will be 0.15gpm/ft2(Ordinary Hazard)
area will be 1500 ft2 to be assumed as fire zone

1500 x 0.15 = 225 gpm


Total capacity will be 225gpm...

Sprinkler Water Storage Capacity (for Ordinary Hazard Area)


= 225 gpm * 1 No * 90 Mins 20250 gallons
1 galloons = 3.785 litres

SIMON ENGG. PARTNERS 1 OF 28


Total storage volume required = 20250 gallons * 3.785 76646 litres

TOTAL STORAGE TANK VOLUME 77 m3

4) WET RISER

Wet Riser(Landing Valve) Flow rate = 250 gpm


Max No of WR in operation at any time = 1 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)

Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)

= 250 gpm * 1 No * 90 Mins 22500 gpm

Total storage volume required = 22500 gallons (Minimum)


1 galloons = 3.785 litres

Total storage volume required = 22500 gallons * 3.785 85163 litres

TOTAL STORAGE TANK VOLUME 85 m3

Pump flow rate required = 1 x 250 gpm = 250 gpm


Fire hose reel pump Head calculation
Residual Pressure required at FHR = 4.5 Bar

Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar

Total head pressure required = 6.5 bar Minimum.

NOTE:-
1) ESFR - Early Suppression Fast Response Sprinkler (or) combination of standard sprinklers for overhead and in-racks
2) If rack sprinklers are provided, then the flow rate and number of sprinklers will vary

TANK CAPACITY PUMP CAPACITY

FHR 11 m3 FHR 100 GPM


FH 28 m3 FH 250 GPM
SPRINKLER 34 m3 SPRINKLER 300 GPM
SAFETY FACTOR 7 m3 HOSE STREAM 50 GPM
SAFETY FACTOR 50 GPM
TOTAL 80 m3
TOTAL 750 GPM

Fire Pump Capacity : 750GPM at 8Bar(Electric +Disel+Jockey)

SIMON ENGG. PARTNERS 2 OF 28


1 CALCULATION FOR PUMP & TANK SELECTION

The following are the design considered based on ROP standard Part-IV

1.1 FIRE PUMP CALCULATION

a) FIRE HOSE REEL SYSETM


Accordance with ROP. Coverage will be 30meters
FHR Flow rate(Minimum discharge rate) = 0. 5 L/s
Max No of FHR in operation at any time = 2 Nos

Pump flow rate required = 2 x 50 gpm = 100 gpm


Fire hose reel pump Head calculation
Residual Pressure required at FHR = 4.0 Bar

Pressure loss in pipe/fittings etc = 0.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar

Total head pressure required = 5.0 bar Minimum.

b) FIRE HYDRANT SYSETM


Accordance with NFPA 24.
Each FH Flow rate = 250 gpm
Pump flow rate required = 2 x 250 gpm = 500 gpm
Fire hose reel pump Head calculation
Residual Pressure required at FH = 7.0 Bar

Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar

Total head pressure required = 9.0 bar Minimum.

SIMON ENGG. PARTNERS 3 OF 28


c) SPRINKLER SYSETM
Accordance with NFPA 13. Maximum hazard 1500sq.feet will be occur in Ordinary hazard
Sprinkler spacing will be 3.6 meters
design density will be 0.15gpm/ft2
1500 x 0.15 = 225 gpm
Total capacity will be 225gpm...
Residual Pressure required at Sprinkler = 3.5 Bar

Pressure loss in pipe/fittings etc = 0.5 bar


Safety = 0.5 bar

Total head pressure required = 4.5bar Minimum.

NOTE:-
1) ESFR - Early Suppression Fast Response Sprinkler (or) combination of standard sprinklers for overhead and in-ra
2) If rack sprinklers are provided, then the flow rate and number of sprinklers will vary

d) WET RISER
Accordance with NFPA 13.
Wet Riser(Landing Valve) Flow rate = 250 gpm
Max No of WR in operation at any time = 1 No
Pump flow rate required = 1 x 250 gpm = 250 gpm
Fire hose reel pump Head calculation
Residual Pressure required at WR = 4.5 Bar

Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar

Total head pressure required = 6.5 bar Minimum.

SIMON ENGG. PARTNERS 4 OF 28


e) Table

ITEM FLOW RATE (GPM)

FHR 100 GPM


FH 500 GPM
SPRINKLER 225 GPM
LANDING VALVE 250 GPM
HOSE STREAM( 5%) 54 GPM
SAFETY FACTOR(5%) 56 GPM
TOTAL 1185 GPM

FIRE PUMP CAPACITY = 1185 =1250GPM @ 11 BAR(pressure required + 20% )

f) Result : 1250 US GPM ELECTRICAL PUMP AT 11 BAR PRESSURE


1250 US GPM DISEL PUMP AT 11 BAR PRESSURE
125 US GPM JOCKEY PUMP AT 11 BAR PRESSURE

1.2 HIGH PRESSURE WATER MIST PUMP CALCULATION

The system is designed as NFPA standard 750, in ordinary Hazard -II(area of operation - 144Sq.meter)
Number of nozzles to protect the area of 144 sq.mtr: 12nos of Nozzle will be operate.
Nozzle Flow rate = 28.8 Lpm
Max No of Nozzle in operation at any time = 12 Nos

Pump flow rate required = 12 x 28.8Lpm = 316.8 L/min

Each pump can discharge 120 lpm @ 120 bar pressure


Hence no. of pump required = 316.8/120 = 2.6 ~ 3 nos.
Each Motor Drive 1 pump, hence we choose main 3x120 L/min + stand by 1x120 L/min. Total
pump capacity on duty of 360 lpm @ 120 bar + 120 lpm @ 120 bar stand by, utilizing 4 nos. Of
30 kW electric driven motor.

pump capacity = 3x120L/min at 120 bar pressure +standby 1x120 L.min at 120bar

1.3 FIRE TANK CALCULATION

a) FIRE HOSE REEL SYSETM

FHR Flow rate = 50 gpm


Max No of FHR in operation at any time = 2 Nos
Duration of operation = 90 mins Ordinary Hazard- II (e.g Public )

Fire hose reel TANK STORAGE CAPACITY (for Ordinary Hazard Area)

= 50 gpm * 2 No * 90 Mins 9000 gpm

Total storage volume required = 9000 gallons (Minimum)


1 galloons = 3.785 litres

Total storage volume required = 9000 gallons * 3.785

TOTAL STORAGE TANK VOLUME

SIMON ENGG. PARTNERS 5 OF 28


b) FIRE HYDRANT SYSETM

Hydrant Flow rate = 250 gpm


Max No of FH in operation at any time = 2 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)

Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)

= 250 gpm * 2 No * 90 Mins 45000 gpm

Total storage volume required = 45000 gallons (Minimum)


1 galloons = 3.785 litres

Total storage volume required = 45000 gallons * 3.785

TOTAL STORAGE TANK VOLUME

c) SPRINKLER SYSETM

Sprinkler spacing will be 3.6 meters


design density will be 0.15gpm/ft2(Ordinary Hazard)
area will be 1500 ft2 to be assumed as fire zone

1500 x 0.15 = 225 gpm


Total capacity will be 225gpm...

Sprinkler Water Storage Capacity (for Ordinary Hazard Area)


= 225 gpm * 1 No * 90 Mins
1 galloons = 3.785 litres
Total storage volume required = 20250 gallons * 3.785

TOTAL STORAGE TANK VOLUME

d) WET RISER

Wet Riser(Landing Valve) Flow rate = 250 gpm


Max No of WR in operation at any time = 1 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)

Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)

= 250 gpm * 1 No * 90 Mins 22500 gpm

Total storage volume required = 22500 gallons (Minimum)


1 galloons = 3.785 litres

Total storage volume required = 22500 gallons * 3.785

TOTAL STORAGE TANK VOLUME

SIMON ENGG. PARTNERS 6 OF 28


e) HIGH PRESSURE WATER MIST SYSTEM

Water Tank for 316 lpm with 90 minutes operation = 360 x 90 minute = 28000 litre effective

Total storage volume required = 28000

TOTAL STORAGE TANK VOLUME

e) Table

ITEM CAPACITY (M3)

FHR 34 M3
FH 170 M3
SPRINKLER 77 M3
LANDING VALVE 85 M3
WATER MIST SYSTEM 28 M3
TOTAL 394 M3

WATER TANK CAPACITY = 394 =400M2(Only for fire)

f) Result : 400M3 Water Tank Capacity only for fire


Fire tank to maintain an individual dedicated fire tank. This fire tank should be separated into two divisions, One for f
system & fire hose reel and the other for fire hydrants

SIMON ENGG. PARTNERS 7 OF 28


SIMON ENGG. PARTNERS 8 OF 28
rs for overhead and in-racks

SIMON ENGG. PARTNERS 9 OF 28


34065 litres

34 m3

SIMON ENGG. PARTNERS 10 OF 28


170325 litres

170 m3

20250 gallons

76646 litres

77 m3

85163 litres

85 m3

SIMON ENGG. PARTNERS 11 OF 28


28000 litres

28 m3

o two divisions, One for fire sprinkler

SIMON ENGG. PARTNERS 12 OF 28


PROJECT NO: 1091
PROJECT NAME:

PUMP POWER

BHP = GPM * PUMP HEAD (Feet) * SP GRAVITY


3960 * % OF PUMP EFFICIENCY

SAMPLE CALCULATION = 750 GPM * 93 * 1


3960 * 0.7

= 69750
2772

= 25.16

1 hp = 750 Watts 18872


= 19

1) FIRE PUMP FOR PASFR ADMIN BUILDING

= 400 GPM * 352 * 1


3960 * 0.7

= 140800
2772

= 50.79

1 hp = 750 Watts 38095

= 38

2) UTILITY PUMP FOR PASFR ADMIN BUILDING

For total loading unit of 8 corresponding design flow rate is =

6 Litre / Sec 360

95.11

95 GPM * 192 * 1
3960 * 0.7

= 18240
2772
= 6.58

= 4935

= 5

3) SUMP PUMP

15 GPM * 200 * 1
3960 * 0.7

= 3000
2772

= 1.08

= 812

= 0.812
D (Feet) * SP GRAVITY SP GRAVITY = SPECIFIC GRAVITY OF LIQUI
P EFFICIENCY NORMAL WATER = 1

hp

Watts
kW

110 meter
352 feet

hp

Watts

kW

6 l/s

Litre / Mins 1 galloons = 3.785 litres

gallons / min

60 meter
192 feet
hp

Watts

kW

200 feet

hp

Watts

kW
PECIFIC GRAVITY OF LIQUID
ORMAL WATER = 1
Each pump can discharge 120 lpm @ 120 bar pressure
Hence no. of pump required = 316.8/120 = 2.6 ~ 3 nos.
Each Motor Drive 1 pump, hence we choose main 3x120 L/min + stand by 1x120 L/min. Total
pump capacity on duty of 360 lpm @ 120 bar + 120 lpm @ 120 bar stand by, utilizing 4 nos. Of
30 kW electric driven motor.
Water Tank for 360 lpm with 30 minutes operation = 360 x 30 minute = 10800 litre effective
water capacity, therefore water tank capacity with 20% allowance which is of 12960 litre shall
be the minimum water capacity.
ng 4 nos. Of
WET RISER

Wet Riser(Landing Valve) Flow rate = 250 gpm


Max No of WR in operation at any time = 1 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)

Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)

= 250 gpm * 1 No * 90 Mins 22500 gpm

Total storage volume required = 22500 gallons (Minimum)


1 galloons = 3.785 litres

Total storage volume required = 22500 gallons * 3.785

TOTAL STORAGE TANK VOLUME

b) FIRE HYDRANT SYSETM

Hydrant Flow rate = 250 gpm


Max No of FH in operation at any time = 2 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)

Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)

= 250 gpm * 2 No * 90 Mins 45000 gpm

Total storage volume required = 45000 gallons (Minimum)


1 galloons = 3.785 litres

Total storage volume required = 45000 gallons * 3.785

TOTAL STORAGE TANK VOLUME

TOTAL WATER FOR FIRE REQUIREMENT

PUMP POWER

BHP = GPM * PUMP HEAD (Feet) * SP GRAVITY


3960 * % OF PUMP EFFICIENCY

SAMPLE CALCULATION = 750 GPM * 93 * 1


3960 * 0.7

= 69750
2772

= 25.16 hp

1 hp = 750 Watts 18872 Watts


= 19 kW
67500

85163 litres

85 m3

170325 litres

170 m3

255 m3
BASIC CALCULATION FOR PUMP & TANK SELECTION

The following are the design considered based on NFPA 13 / 14 & 24

1) FIRE HOSE REEL SYSETM

FHR Flow rate = 50 gpm


Max No of FHR in operation at any time = 2 Nos
Duration of operation = 90 mins Ordinary Hazard- II (e.g Public )

Fire hose reel TANK STORAGE CAPACITY (for Ordinary Hazard Area)

= 50 gpm * 2 No * 90 Mins 9000 gpm

Total storage volume required = 9000 gallons (Minimum)


1 galloons = 3.785 litres

Total storage volume required = 9000 gallons * 3.785 34065 litres

TOTAL STORAGE TANK VOLUME 34 m3

Pump flow rate required = 2 x 50 gpm = 100 gpm


Fire hose reel pump Head calculation
Residual Pressure required at FHR = 4.0 Bar

Pressure loss in pipe/fittings etc = 0.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar

Total head pressure required = 5.0 bar Minimum.

2) FIRE HYDRANT SYSETM

Hydrant Flow rate = 250 gpm


Max No of FH in operation at any time = 2 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)

Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)

= 250 gpm * 2 No * 90 Mins 45000 gpm

Total storage volume required = 45000 gallons (Minimum)


1 galloons = 3.785 litres

Total storage volume required = 45000 gallons * 3.785 170325 litres

TOTAL STORAGE TANK VOLUME 170 m3

Pump flow rate required = 2 x 250 gpm = 500 gpm


Fire hose reel pump Head calculation
Residual Pressure required at FHR = 4.5 Bar

Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar

Total head pressure required = 6.5 bar Minimum.

4) WET RISER

Wet Riser(Landing Valve) Flow rate = 250 gpm


Max No of WR in operation at any time = 1 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)

Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)

= 250 gpm * 1 No * 90 Mins 22500 gpm

Total storage volume required = 22500 gallons (Minimum)

SIMON ENGG. PARTNERS 25 OF 28


1 galloons = 3.785 litres

Total storage volume required = 22500 gallons * 3.785 85163 litres

TOTAL STORAGE TANK VOLUME 85 m3

Pump flow rate required = 1 x 250 gpm = 250 gpm


Fire hose reel pump Head calculation
Residual Pressure required at FHR = 4.5 Bar

Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar

Total head pressure required = 6.5 bar Minimum.

NOTE:-
1) ESFR - Early Suppression Fast Response Sprinkler (or) combination of standard sprinklers for overhead and in-racks
2) If rack sprinklers are provided, then the flow rate and number of sprinklers will vary

TANK CAPACITY PUMP CAPACITY

FHR 11 m3 FHR 100 GPM


FH 28 m3 FH 250 GPM
SAFETY FACTOR 7 m3 HOSE STREAM 50 GPM
SAFETY FACTOR 50 GPM
TOTAL 80 m3
TOTAL 750 GPM

Fire Pump Capacity : 750GPM at 8Bar(Electric +Disel+Jockey)

SIMON ENGG. PARTNERS 26 OF 28


1 CALCULATION FOR PUMP & TANK SELECTION

The following are the design considered based on ROP standard Part-IV

1.1 FIRE PUMP CALCULATION

a) FIRE HOSE REEL SYSETM


Accordance with ROP. Coverage will be 30meters
FHR Flow rate(Minimum discharge rate) = 0. 5 L/s
Max No of FHR in operation at any time = 2 Nos

Pump flow rate required = 2 x 50 gpm = 100 gpm


Fire hose reel pump Head calculation
Residual Pressure required at FHR = 4.0 Bar

Pressure loss in pipe/fittings etc = 0.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar

Total head pressure required = 5.0 bar Minimum.

b) FIRE HYDRANT SYSETM


Accordance with NFPA 24.
Each FH Flow rate = 250 gpm
Pump flow rate required = 2 x 250 gpm = 500 gpm
Fire hose reel pump Head calculation
Residual Pressure required at FH = 7.0 Bar

Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs more pressure)
Safety = 0.5 bar

Total head pressure required = 9.0 bar Minimum.

e) Table

ITEM FLOW RATE (GPM)

FHR 100 GPM


FH 500 GPM
HOSE STREAM( 5%) 30 GPM
SAFETY FACTOR(5%) 32 GPM
TOTAL 662 GPM

FIRE PUMP CAPACITY =650GPM @ 11


BAR(pressure required + 20% )
ore pressure)

ore pressure)

SAMPLE CAL = 750 GPM * 93 * 1

3960 * 0.7

= 60450
2772

= 25.16 hp

1 hp = 750 Watts 18872 Watts


= 19 kW