Sie sind auf Seite 1von 5

2.30.

-
WIDE AREA POWER QUALITY DECISION PROCESSES AND OPTIONS
FOR SENSITIVE USERS
-
G.A. Taylor Reyrolle Projects Ltd. (Rolls-Royce Industrial Power Group), U.K.
-
A.B. Burden Scottish Power plc., U.K.

INTRODUCTION on more than one occasion. Figure 1 shows, the


responses received and indicates that the clear
The electronics revolution has steadily gathered majority of disruptions were due to partial or total
momentum over the past twenty years. Industries of loss of supply . It should also be noted, however, that
all types have benefited from the higher quality and in a number of follow-up interviews, some users were
throughput achievable with automation and unable to clearly differentiate whether disturbances
integration of processes. However, a consequence of were due to “short” outages or to voltage dip. This
this sophistication is that users have become was primarily due to low availability of data
increasingly sensitive to the fundamental quality of regarding such events. The authors suggest from
their electrical supply. Legislation and standards now experience that the impact of voltage dips on
exist to define the limits of supply quality and production is much greater than the value of 29%
reliability that a customer can expect to receive but, suggests and that due to outages significantly less.
in practice for some users, these limits are greater
than those that can be tolerated by some of their
equipment.
Quality of supply is loosely defined but can be
characterised as two principal issues. These are:
Reliability, referring to the continuity of supply (and
rapid restoration of service); and Power Quality,
relating to the fundamental condition of each cycle of
the 50 or 60 Hz sine wave received by the customers
equipment. Although there is a distinct difference to
the electrical utility, this distinction is less clear to
customers who suffer equipment downtime as a result
of either supply interruptions or quality defects.
54%
Utilities generally have options available to improve
reliability, by agreement with the customer at the Unplanned outages eJ Planned outages
design stage on the arrangements of single or multiple
Voltage dips Harmonics
circuits, and the use of network automation.
However on large interconnected networks, suppliers Voltage surges (transients)
are vulnerable to system faults (the major cause of
disturbances) and pollution generated by non-linear Figure 1 : Breakdown of cause of process disruptions
customer loads. The dilemma for utilities is how to attributable to electrical supply disturbances.
ensure that networks maintain high reliability and yet
limit the extent of disturbances when they do occur. All of the supply quality issues highlighted in figure 1
are regulated by global standards, however the scope
The complexity surrounding solutions to power and impact of these standards on any one specific
quality problems, faced by customers and utilities customer is less well defined. EN50160 is a
alike, is the subject of the paper which explores the European Standard which describes the
decision process needed to evaluate the optimum characteristics of a public electricity supply and sets
solution to power quality, and examines the options limits on supply companies and customers alike [ 11.
available. While this standard recognises the difficulties faced
by utility networks which are exposed to the types of
The Need for Supply Quality event highlighted by figures 2 and 3 and sets practical
limits for utilities, the predominant cause of
During 1995 a sample survey of 100 UK users with disruptions (i.e. outages and voltage dips) are, by
loads in excess of 1MW was conducted to determine their very nature, stochastic events [ 2 ] . For a
sensitivity to power quality issues. Of those customer trying to operate sensitive equipment within
surveyed, 69% had suffered a supply related this environment, the problem may still remain.
disruption of their process during the preceding 12
months, and of those 45% experienced such an event For utilities to guarantee a 100% perfect supply

ClRED 97,2-5 June 1997, Conference Publication No. 438,O IEE, 1997
2.30.2

through network implementation would be


impractical given the drive to provide cost-effective B. Ensure that the original equipment
supplies within the competitive and regulatory manufacturers (OEM’s) of sensitive
framework. This does not however remove the equipment build sufficient immunity to
obligation of utilities to take steps to minimise the system disturbances into their products.
risk of such events happening.
C. Seek some form of “black box” protection to
desensitise critical loads.
Option A can be determined by dialogue with the
local utility who maintain the connection to the
customer. Option B has to be enforced by users of
such equipment, but this does not constitute a
common dialogue between users and manufacturers
where functionality takes greater precedent. This has
become a major issue with the advent of micro-
processor based equipment and greater product
liability. OEM’s seem increasingly reluctant to
declare “sensible” immunity levels and prefer that the
user makes the judgement on compatibility, despite
49% the fact that the user is not normally qualified, or
sufficiently well informed to make a proper
Feeder damage/ interference f3 quantitative decision. This then is the customers
dilemma, what should be expected from a utility
Weather related faults [;3 Protection malfunction compared to what should be expected from the OEM.

figure 2 : Results of UK survey on causes of supply Option C therefore becomes the most probable
outage leading to production disruption. solution that the customer must resolve. Clearly the
debate must then centre on what devices are
The present UK regulatory standards ensure that all available, the level of immunity to power quality
users receive a common high standard of supply, disturbances required and the cost of installation and
related to their connection arrangement, and does not subsequent operation of such systems. The business
allow utilities to differentiate between customers. case for investment needs each option to be evaluated
For sensitive users, particularly in the industrial and carefully to determine the best solution.
commercial sectors, the following alternatives exist to
protect their production processes from supply Determining the Cost of Power Quality
disturbances :
In the survey referred to earlier, the authors
17% discovered that of those users who had suffered a loss
in production, 93% of the respondees were unaware
of the real cost to their companies of production loss
due to supply disruption. In an increasingly
competitive environment where achieving maximum
efficiency is paramount, such a lack of appreciation is
surprising. The true cost to a company consists of two
main components :
Actual cost incurred
a Potential losses

In determining the actual cost of a production outage


several factors need to be accounted for. Such
Switching on nearby systems information should be readily available to most
Adjacent line failure 19 Internal disturbance companies. These are as follows :

figure 3 : Results of UK survey on causes of voltage dips Cost of scrapped materials LS


[material costs, both raw and value
leading to disruption of customer processes. added]
A. Ensure that the utility has taken all
reasonable steps to improve the quality of Cost of clean-up of contaminated plant LC
[labour time and materials, disposal
supply. costs]
2.30.3

Cost of restoring production LR The user must calculate these two costs and attribute
[engineering time to reset/ start-up a risk weighting to both PE and P s . The user can
process, waste material] then use both totals, Lactual and Pactual to calculate
the cost of downtime from experience of the annual
Cost of recovering lost production LA supply disturbances. These numbers provide an
[additional shifts, overtime bonuses, encompassing model that will properly justify the
additional plant operating cost (heating, level of investment that can be made to provide a
electricity etc.)] solution. Figure 4 shows an example of how the two
components can contribute to the annual cost of
Hence the total actual cost of a single production downtime, when the probability of the potential
stoppage, Lactual, is losses is just once in every 4 years.

Lactual = Ls + LC +LR + LA SOLUTION OPTIONS


The potential losses can also be determined by There are number of options open to customers with
looking at two factors : sensitive equipment, in particular those who are
primarily vulnerable to voltage dips. Further some
Cost of replacing damaged equipment PE products may impact upon the distribution system,
[initial and subsequent costs] particularly for large users. For such users the utility
should be involved in the decision process.
Damaged equipment costs are more complex than
they appear. The obvious costs are those items which The following is a brief, but not exhaustive summary
must be replaced at the time, the less obvious being of the principal options available to sensitive
those components which have been weakened by the customers. In all cases the key to the decision
disturbance and fail some time later (e.g. drive process is that users understand and differentiate the
thyristors). Another consideration is the possible real cost of downtime compared to lost production
damage to equipment due to an uncontrolled time, and the associated risks to the company.
shutdown of the plant.
Non or Partial Plant Operation
Cost of lost sales PS
[Direct and indirect impact] Where there is an understanding of the pattern of
disturbances, the utility can forewarn sensitive users
Direct cost factors include: lost sales in full shift, high of periods when disturbances may occur (e.g. severe
production organisations with lean manufacture weather warnings). Plant operators can then choose
systems; or impact to companies operating within a to close plant down for all or part of the disturbance
Just in Time (JIT) chain. Indirect costs include loss period, or detune processes to allow continued
of sales through loss of end customer confidence. operation but at lower throughput. Both equate to a
loss of production and require advanced planning, but
does have the advantage of not requiring further
investment. Clearly though this does not provide
peace of mind to the customer or provide any
guarantee of quality, neither is it likely to eliminate
the risk of lost production over the course of a year.
c
KJ
Uninterruptible Power Supplies
0
0
The growth of the U P S market has corresponded with
the growth of the micro-processor. The term UPS,
covers a number of alternatives, but in general refers
to an inverter device coupled with a battery energy
source. Such systems vary in size from 1kW to
1MW. As devices grow larger, the predominant
market is for off-line UPS which are more efficient,
but do have the disadvantage of needing isolating the
Losses True Cost Risk Costs protected load from the system when activated. The
majority of the UPS market is focused on the
figure 4 : Illustration of actual and potential costs of protection of computer based systems to allow data to
supply related disruptions. be saved or permit continuing monitoring in the event
Hence the total potential cost of a production of power loss,
stoppage, Pactual, is
2.30.4

SMES/ Flywheel systems Distribution Statcom


New energy storage technologies are now coming to The D-Statcom is a complementary device to the
maturity, which offer a more compact form of energy DVR, but connects into the system via a shunt
storage than is achievable with batteries. Such transformer. To mitigate voltage dips the D-Statcom
systems are suitable for providing large amounts of would need to be isolated from the system and fully
power for brief periods (1-5 seconds), which is supply the load, however for applications where load
sufficient to protect large loads from short duration pollution is the predominant problem, this device
outages. provides an ideal wide area solution.

Co-generation Other Proposed Solutions


In terms of supply quality, co-generation does not The use of thyristors as high speed tap changers has
guarantee an improved quality of supply. While there been discussed for several years. Such systems
may be some benefit to the mitigation of voltage dips, potentially offer a coarse form of voltage protection
equipment will still be exposed to system with a 2 cycle response but would be limited to being
disturbances and with a reduced fault level, be more able to restore voltage dips with greater than 50%
exposed to internal disturbances and distortion. In retained voltage. The fact that such systems have not
general the decision to install co-generation is based been implemented highlights the problems still
on the operating cycle of the facility, where the use of encountered with the use of power electronics to
secondary energy (e.g. steam) is required. switch highly inductive loads. Other solutions such
as active filters provide specific functions and not
Solid-state Transfer Switch general power quality.
A new generation of solid state transfer switches are THE DECISION PROCESS
becoming available, that operate at 15 kV (and higher
voltages of up to 36kV). The principle of the solid The potential solutions discussed can be considered
state transfer switch is that two switches are as falling into two categories :
employed, which are connected to independent
distribution supplies. In the event of an outage or e local power quality solutions
voltage dip the supply is switched within half a cycle (e.g. U P S , SMES)
to the alternate supply. Clearly the success of this
system is dependent upon the availability of two e wide area power quality solutions
sufficiently independent feeders that common mode (e.g. DVR, SSTS, CO-generation, D-Statcom)
system disturbances at sub-transmission or
transmission levels will not affect both supplies Table 2 presents further data from the survey that
simultaneously. highlights that sensitivity basically divides into two
camps, those who are partially affected and those
Dynamic Voltage Restorer who are wholly affected.

The DVR is one of a family of devices collectively Percentage of Operations


known as Custom Power systems [3] which are Disrupted
designed for connection to the distribution system
(6.6 - 36 kV). The DVR differs from other devices in Less than 10%
that it is permanently in the system, but does not 10 - 30%
directly interact with the load unless required.
Having no inertia, the DVR can react within a 31 - 60%
fraction of a cycle enabling it to inject a continuously
variable voltage that supplements the remaining
voltage allowing restoration to the tolerance level.
Because it uses its own energy storage system, the
voltage injected is not affected by the remaining
61 - 99%
100% I
Table 2 :Results of UK survey, % of operations
8
44

voltage. Thus for a system with a DVR rated to disrupted due to a power supply disturbance.
provide 50% support, a dip leaving only a 20%
retained voltage would be restored to 70% by the Those users who suffer minor disruption and whose
DVR. Because the DVR uses a high speed inverter critical processes are easily isolated are best protected
configuration it can provide a complex power quality by discrete equipment. For those with large loads
function (e.g. harmonic cancellation, phase (> 1MW total) whose production is wholly affected
balancing) that is more suited to complex loads. the decision process is not as straightforward. Plants
may have complex supplies, both at utilisation and
distribution voltages. In these cases the isolation of
all critical loads onto a common feeder is difficult to
achieve. The option may be to place discreet power
quality devices about the site, an option normally
2.30.5

Duration (sec) Duration (sec)

figure 5a : Recorded voltage dip profile over a two year figure 5b :Effect of a 50% rated DVR, with 200ms
period at UK site. energy storage capability to protect supply.
taken with UPS solution routes. or shut-down during supply disturbances. The results
and discussion of the power quality survey presented
To highlight the problem of taking a distributed here suggests voltage dips are the prime cause of
solution path, the authors experience indicates that supply related downtime. Defining compatibility
industries investing in devices to protect process levels between supply and equipment is a difficult
control systems loads tend to progressively invest in process which is usually left to the user who
several units, as subsequent power quality events frequently lacks the information necessary to reach a
reveal the next weak link in the chain. This satisfactory decision. The utility does have a role to
programme means that downtime occurs each time a play in this determination by aiding customer
disturbance occurs incurring the type of losses understanding and supporting the decision process.
discussed earlier. A further net result of such an However the decision ultimately must be made by the
approach is that maintenance, reliability and the customer who must fully understand the true costs of
pollution that such distributed devices can create, downtime..
adds to the complexity of the facility management.
For large users, wide area protection of supplies, that,
Taking a wide area approach such as Custom Power in particular, decrease sensitivity to voltage dips may
means that large or whole sections of a users load can provide the simplest solution to large scale users,
be protected at the distribution voltage with a single while providing minimum impact on surrounding
device. The decision has then to be whether to distribution networks.
completely protect the system from both outages and
voltage dips, or whether to trade off the likelihood of Acknowledgements
one event being more disruptive to production than
the other. The evidence of the survey presented here The authors would like to thank Mr Neil Woodley of
suggests that voltage dips are more likely to cause Westinghouse Electric Corporation for additional
production downtime than any other electrical cause. information and support.

By determining the voltage dip profile such as the References


one illustrated in figure 5a, the user will be better
placed make an economic decision as to the level of [11 “Voltage Characteristics of Electricity
immunity to voltage dips required. For instance by Supplied by Public Distribution Systems”,
installing a DVR capable of injecting an additional BS EN 50160,1995
50% rated voltage for a short duration, the voltage dip
profile is reduced to that shown in figure 5b [4]. [21 “Proposed Chapter 9 for Predicting Voltage
Clearly, having systems that are not fully rated to the Sags (Dips) in Revision to IEEE Std 493,
load requirements, and can provide simultaneous the Gold Book”, L Conrad et al, Proc. E E E
power quality functions are worth considering, as a Transmission & Distribution Conf., 1994
more economically viable option compared to the
alternative of complete system-wide back-up to [31 N H Woodley, M Sarkozi, G A Taylor, A
protect critical plant. Sundaram “Custom Power : The Utility
Solution”, CIRED 1995
CONCLUSIONS
[41 “Voltage Sag Relief : Guidelines to
Modern production equipment increasingly needs Estimate DVR Equipment Ratings”, R J
some form of external protection to prevent damage Nelson et al, Proc. American Power Conf.,
Chicago, 1996

Das könnte Ihnen auch gefallen