Live Load Distribution Factors for Moment in Interior Beams Cross Section Type ‘k’
LRFD Table 4.6.2.2.2b-1
Live Load Distribution Factors for Moments in Exterior Beams Cross Section Type ‘k’
LRFD Table 4.6.2.2.2d-1
Distribution factor for moment for 1 design lane loaded (lever rule) - calculate how many wheels fit
between beams:
𝑑𝑒 515
𝐷𝐹𝑚𝑒2 = (0.77 + ) 𝐷𝐹𝑠𝑡𝑟𝑎𝑖𝑔ℎ𝑡_𝑚𝑖 = (0.77 + ) × 0.702 = 0.669
2800 2800
Moment Skew Correction Factor for Girders Cross Section Type ‘k’ LRFD 4.6.2.2.2e
O.K.
Internal girder:
External girder:
Live Load Distribution Factors for Shear in Interior Beams Cross Section Type ‘k’
LRFD Table 4.6.2.2.3a-1
𝑆 2390
𝐷𝐹𝑣𝑖1 = 0.36 + = 0.36 + = 0.674
7600 7600
Live Load Distribution Factors for Shear in Exterior Beams Cross Section Type ‘k’
LRFD Table 4.6.2.2.3b-1
- Verify overhang de. The curb is located 400mm from the exterior edge of the top slab. The exterior
edge of the top slab is 915mm away from the centerline of exterior web.
O.K.
Use lever rule results calculated for exterior beam moment distribution factor:
𝐷𝐹𝑣𝑒1 = 0.693
𝑑𝑒 515
𝐷𝐹𝑣𝑒2 = (0.6 + ) × 𝐷𝐹𝑠𝑡𝑟𝑎𝑖𝑔ℎ𝑡_𝑣𝑖 = (0.6 + ) × 0.803 = 0.618
3000 3000
Shear Skew Correction Factor for Girders Cross Section Type ‘k’ LRFD 4.6.2.2.3c-1
Internal girder:
External girder: