March 15, 2018 [MS OF OUTSIDE SCAFFOLDING FOR PODIUM FLOORS]

METHOD STATEMENT
CONSTRUCTION WORK OF EXTERNAL SCAFFOLDINGS
FOR PODIUM FLOORS

CHINA CONSTRUCTION (S.E.A) (CAMBODIA) CORPORATION Ltd


PROJECT: ORKIDE THE ROYAL CONDOMINIUM

March, 2018

Page 1
March 15, 2018 [MS OF OUTSIDE SCAFFOLDING FOR PODIUM FLOORS]

Table of Content

1. General information

2. Design of the scaffolding

3. Calculation sheet

Page 2
March 15, 2018 [MS OF OUTSIDE SCAFFOLDING FOR PODIUM FLOORS]

1. General information

For the outside scaffolding of podium floors, we will install one H1700 – frame
system supported by a cantilever I150x75 beam system anchored on 1st floor.

Parameter Value
Cantilever I beam I150x75
Floor to anchor the cantilever I beam 1st floor
Length of cantilever I beam 1800mm
Maximum spacing among cantilever I150x75 beams 1600mm
Width of working platform 1250mm
Total Height of the scaffolding set ~14200mm
Distance from structure to scaffolding 300mm

2. Design of the scaffolding

 Detail of H frame formwork

Figure 1: Detail of H frame formwork

Page 3
March 15, 2018 [MS OF OUTSIDE SCAFFOLDING FOR PODIUM FLOORS]

 Typical section of the scaffolding

For more detail, please check in the attached drawings.

Page 4
March 15, 2018 [MS OF OUTSIDE SCAFFOLDING FOR PODIUM FLOORS]

CALCULATION SHEET

1. Design Codes & References

 TCVN 5575 : 2012 – Steel Structures – Design Standard


 TCXDVN 296 – 2004 – Scaffolding – Safety Requirements

2. Loadings and Calculation Modeling.


The formwork system will be modeled by Etabs software to get the internal
force induce by loadings listed in this table.

Parameter Value Coefficient Unit


Calculated by
Dead Load 1.1 kN
Etabs
Live Load 2.5 1.3 kN/m2

Note:

Live load will be allowed to act on maximum 4 levels of H formwork system


at the same time.

There will be an anchorage on each structure floor to fix the formwork


system with structure. Therefore, wind load is not considered for this
calculation.

On the modeling, the hung end of I150 beam will be considered as a


simple support and the other end is fixed support.

Load combination: W = 1.1*DL + 1.3*LL

Please see the modeling attached below:

Page 5
ETABS by adguard

ETABS v9.7.4 - File: podium - March 18,2018 23:11


3-D View - KN-m Units
March 15, 2018 [MS OF OUTSIDE SCAFFOLDING FOR PODIUM FLOORS]

3. Results & Checking


a) Checking the strength of cantilever I150X75 beam
Cross section of I150x75 beam

Bending moment diagram I150x75 beam

Unit: kN.m
Shear force diagram I150x75 beam

Unit: kN

Page 6
March 15, 2018 [MS OF OUTSIDE SCAFFOLDING FOR PODIUM FLOORS]

Parameter Symbol Value Unit

Section Modulus WI150 56.2 cm3

Allowable stress (Grade: CT3) [Rs] 205 MPa

Maximum bending moment Mmax 6.49 kN.m

Shear force on fixed end F1 21.87 kN

Shear force on hung end F2 15.60 kN

Maximum stress: Rmax = Mmax / W I150 = 6.49*106/ 56200= 115 MPa

So, Rmax = 115 MPa < [Rs] = 205Mpa

 I150x75 beam has enough strength!

b) Checking the embedded length of Tension Bolt D25M16L150

Parameter Symbol Value Unit


Diameter of embedded bolt De 16 mm

Length of embedment on concrete Le 150 mm

RC Characteristic cylinder strength f’c 32 Mpa

Maximum bending moment Mmax 6.49 kN.m


Pull-out force acting on 1 tension bolt:

M max .Ymax 6.49* 0.07


Po    46kN
2 yi2 2* 0.07 2
Required anchorage length of tension bolt D25:

Ln  Po / [ * D*0.7 * f c' ]  46*103 / [3.14* 25*0.7 * 32]  148mm

Select, Ln = 150mm

Page 7
March 15, 2018 [MS OF OUTSIDE SCAFFOLDING FOR PODIUM FLOORS]

c) Checking strength of connection bolt M16

Parameter Symbol Value Unit

Designation -- M16
---
Grade - 8.8

Total number of bolts per connection nv 4 pcs

Cross Area Ab 200 mm2

Tensile Strength ftb 400 MPa

Shear strength fvb 320 Mpa

Shear force at fixed end of I150 beam F1 21.87 kN

Pull-out force acting on 1 bolt Po 46 kN

Working condition coefficient yb 1.0 -

 Checking the tensile strength of 1 bolt

[N]tb = ftb..Abn = 400*200 = 80 kN > Po = 46kN  OK!

 Checking the shear strength of 4 bolts per connection

[N]vb = fvb.yb.Ab.nv = 320*1*200*4 = 256 kN > F1 = 21.87kN  OK!

Conclusion: Connection bolt M16 has enough strength!

d) Checking tensile strength of wire cable D16

Parameter Symbol Value Unit


Nominal Diameter D 16 mm
Minimum breaking strength [Fc] 145 kN
Safety coefficient y 6 -
Reaction force at hung end of I150 beam F2 15.60 kN

Page 8
March 15, 2018 [MS OF OUTSIDE SCAFFOLDING FOR PODIUM FLOORS]

Axial force acting on the cable:

Tc = F2 /cos (150) = 15.60 /cos (150) = 16.15 kN


So we have,

Tc = 16.15 kN < [Fc] / y = 145 / 6 = 24.2 kN  OK!

e) Checking welding connection of I150X75 beam with steel plate

Parameter Symbol Value Unit


Welding stick -- N42 --
Shear strength of welding line fwf 180 Mpa
Welding height hw 6 mm

Maximum bending moment Mmax 6.49 kN.m

Shear force F1 21.87 kN

Total area of welding line:

Awf = 0.7*hw*2*(150+75-2*9.5+75-5.5)= 2318 mm2


Moment of inertia:

Iwf =2*0.7*6*((150- 2*9.5)3/12+ (100-5.5)*(150-9.5)2/2) = 9408568 mm4

 W wf = 9408568 / 150 = 62724mm3

M 2 R 6.49*106 2 21.87 *103 2


 td  ( )  ( 1 )2  ( ) ( )  103 Mpa < fwf = 180Mpa
Wwf Awf 62724 2318

 Welding connection has enough strength!