Sie sind auf Seite 1von 6

Investigation of the Operational Behaviour of a

Wind Energy Conversion System including


Double Fed Induction Generator in converter's
faulty conditions
Dimitrios G.Giaourakis, Athanasios N.Safacas, Savvas Tsotoulidis

Electromechanical Energy Conversion Laboratory


Electrical and Computer Engineering Department,
University of Patras, Rio-Patras, Greece, 26504
Tel:(+30)-2610-997351, fax: (+30)-2610-997362
Email: dgkiaourakis@ece.upatras.gr
a.n.safacas@ece.upatras.gr
stsotoulidis@ece.upatras.gr

Abstract- In this paper, the wind energy conversion system that diagnosis could be done by measuring some basic quantities
uses the structure of Doubly-Fed Induction Generator (DFIG) of the system in healthy condition, registering data and
under fauIt condition is presented. Moreover, a simulation of comparing them with the corresponding of fault condition.
this wind energy conversion system under fault conditions in
So, fault diagnosis and identification could be achieved.
MATLABI SIMULINK is done and the results are evaluated.
As it is concluded by the international literature the
Two typical cases of fault, open-circuit faults in two IGBTs in
fault conditions that have been investigated mostly are:
Rotor Side Converter and in one diode in Grid Side Converter
are studied.
a)unbalanced stator conditions, b)voltage sags of the grid,
c) faults in induction motor (e.g. broken bar), d)DC link
Keywords: DFIG, simulation, back-to-back converter, PWM, fluctuation.
fault conditions in DFIG. In this work faults in the back-to-back converter are
studied, when the DFIG operates in subsynchronous mode,
I. INTRODUCTION so the Grid Side Converter (GSC) operates as a boost
rectifier and without using the upper IGBTs (Fig. 1). Two
As it is well-known wind energy owns a large types of defects can appear on IGBT-an open circuit or a
proportion of electric energy production from renewable short circuit fault. It is more possible that these faults can
energy sources. Various types of systems for wind potential appear in one IGBT only or in two IGBTs either in the same
conversion have been designed. The most important of these leg of converter, or in two different legs. In the first case, the
systems are the following [4]: system can operate for a considerable period of time but with
a)Fixed-speed wind turbine with an induction generator degraded performance and low efficiency. Open-circuit
"Danish concept", b) Variable speed wind turbine concept faults in two IGBTs in RSC and in one diode in GSC are
with variable rotor resistance, c) Variable speed concept with investigated. The investigation of the operational behavior
full-scale power, d) Variable-speed wind turbine equipped of the system, when one or more of the above faults happen,
with a doubly-fed induction generator. is important to understand the consequences in normal
In this work the behaviour of a wind energy conversion operation, to estimate the size of the corresponding
system with Doubly-Fed Induction Generator (DFIG) is disturbances and risk-assessment of the system in such fault
studied. This type of system has a lot of advantages. One of cases.
them is that the wind generator can be controlled more easily
and additionally it can be operated in the region of low wind II. SYSTEM DESCRIPTION
speeds e.g. 4m1s, in which other wind energy conversion
systems couldn' t be operated. The variable speed range of The system' s structure including the DFIG (Fig.I)
such wind energy systems is about 30% below and above the consists of an asynchronous machine that operates in
nominal synchronous speed. The rating of the power generation mode, of which the stator is connected directly to
converter which is a back-to-back voltage source converter is the grid of constant voltage and frequency and the rotor
25-35% of the generator capacity [5, 6], which made this an plugging in the grid via a back-to-back power electronic
economical choice compared to the full converter design of converter. This system is used to achieve a wide range of
most other variable speed wind turbines. For these systems operation from subsynchronous to supersynchronous
monitoring and diagnosis are important to prevent fault operation (positive and negative slip). This can be achieved
conditions that maybe have catastrophic consequences. Fault via power flow in both directions.

978-1-4673-0342-2112/$31.00 ©2012 IEEE 1067 leIT 2012


0 ... "

Fig. 1. Schematic diagram of the investigated system-basic structure.

stator and rotor in d- and q-axis, Rs is the resistance of the


That is why the bi-directional topology of ACfDC/AC stator windings [0], Ls, LR, Lm, are the stator, rotor and
converter is used. The rotor electrical power Pr is only a mutual inductances [H), LR", LSq are the stator and rotor
fraction of stator active power output Ps (Pr=-sPs)' Since the leakage inductances [H) ,w is the speed of the reference
electromagnetic torque Mel is negative in case of power frame [radls].
generation and Qs is positive and constant for a constant By calculating the apparent power and taking the real
frequency grid voltage, the sign of Pr depends on the slip (s) parts, the following equations represent the stator-side and
sign. Pr is positive for negative slip (speed greater than rotor-side active and reactive power respectively:

Ps �(USdiSd + usqisq), PR �(URdiRd + uRqiRq),


synchronous speed), or negative for positive slip (speed
lower than synchronous speed). For supersynchronous speed = =
(5)
operation, Pr is transmitted to DC bus capacitor and tends to
raise the DC voltage. For subsynchronous speed operation, Qs �(USqiSd - USdiSq). QR �(URqiRd - URdiRq)'
= =
(6)
Pr is taken out of the DC bus capacitor C and tends to The mutual flux between rotor and stator produces
decrease the DC bus voltage. magnetic energy, which is stored in the magnetic field. This
This paper deals with the reaction of the DFlG when an energy produces an electromagnetic torque which is
open-cicruit fault happens in two IGBTs in the same leg of calculated as
the Rotor Side Converter and in one diode of the Grid Side
Mel = P(iq'l'Sd -id'l'sq)' (7)
Converter in subsynchronous mode.
where p is the number of pole pairs.
A. Doubly-Fed Induction Generator model
Equation (7) describes the torque balance in DFlG:
dO
The analysis of the DFlG operation is based on the (J M +J L ) - +Mel = M L2 .
well-known dynamical model described by the following
dt
(8)
equations (synchronously frame):
Parameter values for the laboratory asynchronous
d'PSd
· -(Os HI
USd =RS 'ISd TS +dt
machine are presented in Table 1.
q
TABLE I
d'Ps PARAMETER VALUES OF DFIG
.
q PN(kW) 6.5
USq =Rs 'ISd +OJs'l'Sd +-­
dt (1)
VN(V) 380
p 2
d'PRd Rs(il) 0.8
URd =Rs ·iRd + -«(Os -(OR)'I'Rq L,s(H) 0.005
dt RR (il) 1
(2)
. d'PR L,D (H) 0.005
q
URq =Rs . 'Rq +-- +«(Os -(OR)'I'Rd Lm(H) 0.114
dt
B.
'l'Sd = (Ls<y +Lm)iSd +LmiRd Rotor side converter (RSC)

'l'S = (Ls<y +Lm)iS +LmiR Rotor side converter acts as a PWM rectifier during the
q q q (3)
machine working in super synchronous mode and as an
'l'Rd = (LR<y +Lm)iRd +LmiSd inverter during subsynchronous mode. The purpose of the
(4) rotor side converter' s control is the independent control of
'l'R = (LR<y +Lm)iR +LmiS
q q q the rotor' s active and reactive power. To succeed it, three
phase quantities are transformed in d-, q- synchronously
where USd, USq, URd, URd, ism iSq. iRd• iRq , 'P sd, 'Psq, 'PRd, 'PRq, are reference frame, where the d-axis is aligned with the stator' s
voltages [V], currents [A] and flux linkages [Wb] of the flux vector (Fig. 2). This happens because the stator of the
DFlG is directly connected to the grid' s voltage. This means

1068
that 'l's is constant and 'l'Sq is equal to zero. So the following
relations are applied:

'I'Sq = 0 ' dt
d'l'Sq
0,
=
(9)
i.
ABC TO '..
i'l a.
Neglecting the small stator' s resistance R,:
USd=O. Fig. 3 Block diagram of GSC's control.
The following equations are obtained solving the (3):

ISq IRq, ISd


. Lm · · 'PSa-LmiRd III. FAULTS STUDY IN DFIG
= - (Lscr+Lm) =
(Lscr+Lm)
(10)

By substituting these equations to (9), (1l), the active and In Fig. 1 the rotor side converter in faulty condition can
reactive power are given by the following equations: be seen (case Fl). If the upper switch Tl and lower switch
T4 are simultaneously opened, the defect causes a loss of
p. Lm . � 'PSd-LmiRd
-2Usq (LS<T+Lm) IRq' Qs
3
s = =
2
USq (LScr+Lm) ,
(11) reversibility in current of the two IGBTs (Tl and T4) and
appears in inverter mode by the loss of two alternation of the
From the equations (11) it is concluded that independent phase current. Thus, if the IGBT Tl is open and the current
control of active and reactive power can be succeeded. in the phase (u) is positive, the phase of induction motor
Finally, the equation that calculates the electromagnetic remains connected to the negative potential of the dc link
torque is given by the following equation: voltage by the antiparallel diode D4. In the same way, if the

Mel -
3 (P) Lm .
- -2 2 'I'dq (LScr+Lm) IRq (12)
IGBT T4 is open and the current in the phase (u) is negative,
the phase of induction motor remains connected to the
positive potential of the dc link voltage by the antiparallel
diode D1. During this modulation period, the phase current
is almost zero. Moreover, the currents of the two other
phases are modulated in amplitude and are opposite
compared to the healthy operation mode. The new degraded
mode is characterized, on the mechanical plan, by a speed
fluctuation and a strong ripple of the electromagnetic couple
of induction motor.
Fig. 2. Block diagram of RSC's control.
In Fig. 1 the grid side converter in faulty condition is
C. Grid side converter (GSC) seen (case F2). Since DS has an open-circuit fault (F2) and
bearing in mind that in our case the upper IGBTs are always
The grid side converter acts as a PWM inverter during off, either the T2 must not conduct and so the converter
the machine working in super synchronous mode and as a would operate as a two-phase converter or the modulation
rectifier during subsynchronous mode. The purpose of the technique must be changed. If T2 continues to conduct as it
grid side converter is to produce active power and feed it in had conducted in normal operation, a lot of electrical energy
the rotor side converter. In subsynchronous mode, the would be stored in the inductors. As a result of this, a dc
rotor' s power is coming from the capacitor of the DC link so component will appear in the grid currents and overheating.
the voltage interconnection is dropped down. This leads to
power transportation from the grid to the capacitor. In IV. SIMULATION RESULTS
supersynchronous mode the rotor feeds the capacitor, its
voltage increases and the grid side converter transfers active To study in detail the behaviour of a DFIG 6. S kW,
power to the grid. Moreover, reactive power that is when the open-circuit faults, that have been described before,
exchanged between grid side converter and the grid, can be happen, the whole system has been simulated in
controlled. In our case the upper IGBTs of the GSC are Matlab/Simulink environment using average models and
always off. some characteristic results are presented in each case of fault.
The control of this converter (Fig. 3) is achieved by Furthermore, FFT analysis for fault diagnosis and
transforming the three phase quantities to a d-, q­ identification has been done. It should be remarked that no
synchronously frame, in which the d-axis is aligned with the protection system is consindered and the system continues to
vector of the grid' s voltage, because grid' s voltage is operate in fault condition. A constant value of wind speed is
constant. So, the following relations are resulted: considered. So the wind turbine and rotor speed of the
asynchronous machine is specific and equal to 900rpm
_

Ugd - ud,
dUgd
dt -
_

0, Ugq - 0, dt
_ dUgq
- 0,
_

(13) (DFIG operates in subynchronous mode).


where Ugd is the component of grid voltage in d-axis and Ugq is In the rotor side converter SPWM modulation technique
the component of grid voltage in q-axis. with f.w=IO kHz is used and in the grid side converter PWM
modulation technique with variable duty cycle and also
Through the following equations the active and reactive f.w=IO kHz is used. Parameters' value of filters: a) rotor side
power can be calculated: converter: C=lmF, L=SmH, b) grid side converter:
p. 3 . 3 .
gc = 2Ugdlgd, Q gc = -2Ugdlgq' (14) C=O.SmF, L=4rnH (it is observed via simulation that with
lower values of GSC' s LC filter a high harmonic content
It is concluded that independent active and reactive power occurs). Also, the value of the COCIink is equal to 1mF.
control can be achieved.

1069
In Fig. 4-9 some characteristic simulation' s results can In Fig. 6c normalized FFf analysis spectrum of rotor
be seen. when open-circuit fault (Fl) happens. Furthermore. faulty phase current in healthy (blue line) and faulty
the spectrum of some basic variables of the system is condition (red line) can be seen. The harmonic content of this
evaluated in order to use them for fault diagnosis and variable of the system in faulty condition is presented in
identification. Table II.
TABLE II
HARMORMONIC CONTENT OF GRID FAULTY PHASE CURRENT
FREQUENCIES (Hz) NORMALIZED AMPLITUDE
20 I
28 0.1
60 0.03

It is observed via simulation results that normalized


FFf analysis spectrum of the other two rotor phase currents
(a) is similar to this in Fig. 6c appearing a lower harmonic
content at the frequency of 28Hz and also a harmonic content
at the frequency of 100Hz appears.

(b)
Fig. 4. Grid line to line voltage in GSC filter input (a)in healthy condition
and (b)in faulty condition.
--'- '---,
1.11 1.2 1.11:2

In Fig. 5c the range of frequences (100 Hz-II5 Hz). (a)


that appears around of 110 Hz both in healthy condition and
in faulty condition. is due to the operation of DFIG.

(a)

3.17
(c)
(bi'
�--.- .. -
--,.----,--- ---,-- ---,---r- Fig. 6. (a) Rotor phase currents in (a) healthy and (b)faulty condition.
(c) Normalized FFT analysis spectrum of rotor faulty phase current
in healthy(blue line) and faulty condition(red line).

-+.
,\,----,oi.
.. .-- �
(c)
Fig. 5. Grid phase currents in GSC filter input (a)in healthy condition
and (b)in faulty condition.
(c) Normalized FFf analysis spectrum of grid phase currents 0
0

in healthy (blue line) and faulty condition (red line).


Fig. 7. DC link voltage (open-circuit fault happens in t=2sec).

1070
In Fig. 8c normalized FFT analysis spectrum of stator As it is observed when the open-circuit fault (Ft)
phase current in healthy (blue line) and faulty condition (red occurs, the only part of the system that is affected is that in
line) can be seen. The harmonic content of this system RSC' s side. More specifically, a specific harmonic content
variable in faulty condition is presented in Table III. occurs in rotor' s phase currents and in stator' s phase
TABLE III currents. This harmonic content occurs only when an open­
HARMORMONIC CONTENT OF GRID FAULTY PHASE CURRENT circuit fault happens in two IGBTs in one leg and for that
FREQUENCIES (Hz) NORMALIZED AMPLITUDE reason it could be used for fault diagnosis. A possible fault
10 1 diagnosis method of this kind of fault is measuring and
50 0.8
recording the rotor' s and stator' s phase currents in healthy
60 0.1
70 0.1 condition and comparing them with the results of
120 0.1 measurements that are done taking in faulty condition.
Moreover, fault identification about which IGBT of the RSC
It is observed via simulation results that normalized has an open-circuit fault could be done comparing the
FFT analysis spectrum of the other two stator' s phase normalized amplitude of the basic harmonic of the stator' s
currents is similar to this in Fig. 8c appearing a lower phase currents. The faulty phase current appears high
harmonic content at the frequency of 10Hz. normalized amplitude and it also is higher than the one
appearing in the currents of other phases. Furthermore, when
(FI) happens, the stator' s phase currents and the
electromagnetic torque obtain higher value-approximately
twice. This could be harmful for the whole system.
In Fig. 10-12 some characteristic simulation' s results
can be seen, when open-circuit fault (F2) happens.
Furthermore, the spectrum of some basic variables of the
system is evaluated in order to use them for fault diagnosis

1.16 ---d7- -�,.,�.- �
and identification. In this case the only part of the system
(a) that is affected is the GSC and the behaviour of the
asynchronous machine. For that reason simulation results
only for some basic grid' s variables are presented (in the
input of GSC' s filter).

��
.. -----.�----�----� , ----��----�----�
..�

(b)

'"

'.

Fig. 10. DC link voltage (open-circuit fault happens in t=2sec).

In Fig. llc normalized FFT analysis spectrum of grid


(c) phase current in healthy (blue line) and faulty condition (red
Fig. 8. (a)Stator's phase currents in (a)healthy and (b)faulty condition. line) can be seen. The harmonic content of this variable of
(c) Normalized FFT analysis spectrum of rotor phase current in the system in fault condition is presented in Table IV.
healthy(blue line) and fault condition (red line).
TABLE IV
HARMORMONIC CONTENT OF ROTOR FAULTY PHASE CURRENT
FREQUENCIES (Hz) NORMALIZED AMPLITUDE
0 0.9
50 I
100 0.9
105 0.06
150 0.05

It is observed via simulation results that normalized


FFT analysis spectrum of the other two grid phase currents
is similar to this in Fig. llc appearing a lower basic
harmonic and DC component-approximately twice.
Fig. 9. Electromagnetic torque(open-circuit happens in t=2sec).

1071
protection system is consindered and the system continues to
operate in fault condition. It is concluded that when an open­
circuit fault in one diode of the GSC happens, the only part
of the system that is affected is that in GSC side. This fault
causes a specific harmonic content in the grid phase currents,
(a)
which is unique for this kind of fault and it could be used for
fault diagnosis and identification. More specifically, it causes
a DC and a basic harmonic component that in faulty phase
I�
� - - - - - -
has higher amplitude. The other parts of DFlG aren' t
affected so much when this open-circuit fault occurs.
On the other hand, when an open-circuit fault in two
IGBTs in the same leg of the RSC happens, the only part of
the system, that is affected, is the RSC's side and the
asynchronous machine' s behavior. This fault causes a
specific harmonic content of the rotor and stator phase
currents, which is unique for this kind of fault and it could be
used for fault diagnosis and identification. More specifically,
high amplitude of the basic harmonic appears in faulty
phases. A possible fault diagnosis method is the measuring
and recording the values of stator' s phase currents and
...
rotor' s phase currents and comparing their spectrum with the
--
(c)
corresponding data that have been recording in healthy
Fig. II. (a)Grid's phase currents in (a)healthy and (b)faulty condition. condition. Furthermore, the generator' s electromagnetic
(c) Normalized FFr analysis spectrum of rotor phase current in torque could be used for fault diagnosis.
healthy(blue line) and fault condition (red line).

References
[I). R. Pena, J. C. Clare, and G. M. Asher, "Doubly fed induction generator
using back-to-back PWM converters and its application to variable­
speed wind-energy generation", lEE Proc. Electr. Power Appl., vol.
143, pp. 231-241, May 1996.
(2). D. G. Giaourakis, A. Safacas, "Review of Wind Energy Conversion
Systems for Large Wind Turbines and Simulation of a back-to-back
:- Electronic Power Converter", EVER2011, Monte Carlo, Monaco, 31
Fig. 12. Electromagnetic torque(open-circuit happens in t=2sec). March- 3 April 2011, conference proceedings.
[3]. Ned Mohan, Ted K. A. Brekken, "Control of a Doubly Fed Induction
As it is observed when the open-circuit fault (F2) Wind Generator Under Unbalanced Grid Voltage Conditions", IEEE
occurs, the only part of the system that is affected is that in Transactions Energy conversion, vol.n022. I, march 2007 page 129-
135.
GSC' s side. More specifically, a specific harmonic content
[4].Muller S, Deicke M., Rik W., Doncker D.: "Doubly fed induction
occurs in grid phase currents. This harmonic content occurs generator systems for wind turbines", IEEE Trans Inds. Appl.,
only when an open-circuit fault happens in one diode of GSC Magazine 8 (3) (May/June 2002), pp. 26-33.
and for that reason it could be used for fault diagnosis. [5]. D. Kastha, B.K. Bose, "Investigation of Fault Modes of Voltage-Fed
Inverter System for Induction Motor Drive", IEEE Trans. Ind. Applic.,
Moreover, fault identification about which diode of the GSC
vol. 30, no. 4, pp. 1028-1037, 1994.
has an open-circuit fault could be done comparing the [6]. R. Peuget, S.Courtine, J.P. Rognon, "Fault Detection and Isolation on a
normalized amplitude of the basic harmonic and DC PWM Inverter by Knowledge-Based Model", IEEE Trans. Ind.
component of the grid phase currents. The faulty phase Applicat., vol. 34, No. 6, pp. 1318-1325, 1998.
(7). Francisco K. A. Lima, Alvaro Luna, Pedro Rodriguez, Edson H.
current appears a high normalized amplitude and it also is
Watanabe, and Frede Blaabjerg. "Rotor Voltage Dynamics in the
higher than the one appearing in the currents of other phases­ Doubly Fed Induction Generator During Grid Faults", IEEE
approximately two times. TRANSACTIONS ON POWER ELECTRONICS, VOL. 25, NO. I,
The above simulation results can be confirmed by JANUARY 2010.
(8). Lingling Fan, Subbaraya Yuvarajan and Rajesh Kavasseri, "Harmonic
experimental results. An experimental provision has already
Analysis of a DFIG for Wind Energy Conversion System", IEEE
been established in the laboratory. More specifically, the TRANSACTIONS ON ENERGY CONVERSION, VOL. 25, NO. I,
wind generator will be simulated through a controlled dc MARCH 2010.
machine as a motor machine to a DFlG. Finally, simulation (9). Lingling Fan, Zhixin Miao, Subbaraya Yuvarajan and Rajesh
Kavasseri,"Hybrid modeling of DFIGs for wind energy conversion
of a 1. 5 MW wind energy conversion system using DFlG has
systems", Simulation Modeling Practice and Theory 18 (2010),
been done and similar results have been obtained. Elsevier, pp. 1032-1045.
(10). M. Trabelsi, M. Boussak, M. Gossa, "Multiple IGBTs Open Circuit
V. CONCLUSION
Faults Diagnosis in Voltage Source Inverter Fed Induction Motor Using
Modified Slope Method", XIX International Conference on Electrical
In this paper a wind energy conversion system with
Machines - ICEM 2010, Rome, conference proceedings, pp. 1-6.
DFlG under faulty condition in subsynchronous mode is [II) Tsotoulidis, S., Mitronikas, E., Safacas, A., "Design of a wavelet
simulated. Open-circuit faults in two IGBTs in one leg of multiresolution controller for a fuel cell powered motor drive system",
Rotor Side Converter and in one diode in Grid Side 2010 XIX International Conference on Electrical Machines (ICEM), pp
1 - 6, September 2010.
Converter are investigated. It should be remarked that no

1072

Das könnte Ihnen auch gefallen