THE ILLUMINATION OF TOILET

AREA TO BE ILLUMINATED (A) =3.211M2

ILLUMINATION (E) =100 lux

TOTAL LUMENS (φ) = A * E= 3.211 * 100=321.1LUX

UTLLIZATION FACTOR (CU) =0.6

MANTENANCE FACTOR (MF) =0.8

GROSS (TOTAL) LUMEN (F) = A * E/MF *CU

F= 3.211 * 100/0.8* 0.6 =668.95LM


ASSUME
We use incandescent lamp
Power for each incandescent lamp is 40W
SINCE THE EFFICANCY IS 60 lum/w
TOTAL WATTAGE (POWER) REQUIRED=668.95LUM/60LUM/W= 11.149W

AS EACH LAMP IS=40 W


NUMBER OF LAMPS=11.149 W/40 W = 0.27 approximately 1 LAMP

THE ILLUMINATION OF LIVING & DINING ROOM

AREA TO BE ILLUMINATED (A) =40M2

ILLUMINATION (E) =200 lux

TOTAL LUMENS (φ) = A * E= 40 *200=8000 LUX

UTLLIZATION FACTOR (CU) =0.6

MANTENANCE FACTOR (MF) =0.8

GROSS (TOTAL) LUMEN (F) = A * E/MF *CU

F= 40 * 2OO/0.8* 0.6 =16666.66 LUM

ASSUME
We use florescent lamp

Power for each florescent lamp is 36W

SINCE THE EFFICANCY IS 80 lum/w


1
2

TOTAL WATTAGE (POWER) REQUIRED=16666.66LUM/80LUM/W= 208.33W

AS EACH LAMP IS= 36W


NUMBER OF LAMPS=2O8.33W/36 W = 5.78 approximately 6 LAMP

THE ILLUMINATION OF M.KITCHEN

AREA TO BE ILLUMINATED (A) =10.297M2

ILLUMINATION (E) =500 lux

TOTAL LUMENS (φ) = A * E= 10.297 * 500= 5148.5LUX

UTLLIZATION FACTOR (CU) =0.6

MANTENANCE FACTOR (MF) =0.8

GROSS (TOTAL) LUMEN (F) = A * E/MF *CU


F= 10.297 * 500/0.8* 0.6 =10726.04 LUM

ASSUME
We use incandescent lamp
Power for each incandescent lamp is 40W
SINCE THE EFFICANCY IS 60 lum/w

TOTAL WATTAGE (POWER) REQUIRED=10726.04 LUM/60 LUM/W=178.767W

AS EACH LAMP IS=40 W

NUMBER OF LAMPS=178.767W /40 W =4.46 approximately = 4 LAMP

THE ILLUMINATION OF STAIR

AREA TO BE ILLUMINATED (A) =7.96M2

ILLUMINATION (E) =150 lux

TOTAL LUMENS (φ) = A * E= 7.96 * 150=1194 LUX

UTLLIZATION FACTOR (CU) =0.6

MANTENANCE FACTOR (MF) =0.8

GROSS (TOTAL) LUMEN (F) = A * E/MF *CU

F= 7.96 * 150/0.8* 0.6 =2487.5 LUM


3

ASSUME
We use incandescent lamp
Power for each incandescent lamp is 40W
SINCE THE EFFICANCY IS 60 lum/w

TOTAL WATTAGE (POWER) REQUIRED=2487.5 LUM/60 LUM/W= 41.458W

AS EACH LAMP IS=40 W


NUMBER OF LAMPS=41.458 W/40 W = 1.03 approximately 1 LAMP

THE ILLUMINATION OF BALCONY

AREA TO BE ILLUMINATED (A) =3.8M2


ILLUMINATION (E) =100 lux

TOTAL LUMENS (φ) = A * E=3.8 * 100=380 LUX

UTLLIZATION FACTOR (CU) =0.6

MANTENANCE FACTOR (MF) =0.8

GROSS (TOTAL) LUMEN (F) = A * E/MF *CU

F= 3.8 * 100/0.8* 0.6 =791.66 LUM


ASSUME
We use incandescent lamp
Power for each incandescent lamp is 40W
SINCE THE EFFICANCY IS 60 lum/w

TOTAL WATTAGE (POWER) REQUIRED=791.66LUM/60 LUM/W=13.194W

AS EACH LAMP IS=40 W


NUMBER OF LAMPS= 13.194W/40 W = 0.32 approximately 1 LAMP

THE ILLUMINATION OF CORRIDOR

AREA TO BE ILLUMINATED (A) =6.691M2

ILLUMINATION (E) =100 lux

TOTAL LUMENS (φ) = A * E= 6.69 * 100= 669LUM


3
4

UTLLIZATION FACTOR (CU) =0.6

MANTENANCE FACTOR (MF) =0.8

GROSS (TOTAL) LUMEN (F) = A * E/MF *CU

F= 6.69 * 100/0.8* 0.6 =1393.75 LUM


ASSUME
We use florescent lamp

Power for each florescent lamp is 36W

SINCE THE EFFICANCY IS 80 lum/w

TOTAL WATTAGE (POWER) REQUIRED=1393.75 LUM/80 LUM/W= 17.42W

AS EACH LAMP IS=36 W

NUMBER OF LAMPS=17.42W/36W = 0.48 approximately = 1 LAMP

THE ILLUMINATION OF OFFICE ROOM

AREA TO BE ILLUMINATED (A) =10.77M2

ILLUMINATION (E) =200 lux

TOTAL LUMENS (φ) = A * E= 10.77 * 200=2154 LUX

UTLLIZATION FACTOR (CU) =0.6

MANTENANCE FACTOR (MF) =0.8

GROSS (TOTAL) LUMEN (F) = A * E/MF *CU

F= 10.77 * 200/0.8* 0.6 =4487.5 LUM


ASSUME
We use florescent lamp
Power for each florescent lamp is 36W
SINCE THE EFFICANCY IS 80 lum/w

TOTAL WATTAGE (POWER) REQUIRED=4487.5 LUM/80 LUM/W= 56.09W

AS EACH LAMP IS=36 W

NUMBER OF LAMPS=56.09W/36W = 1.558 approximately = 2 LAMP


MAX EXPECTED LOAD

The diversity factor depends on the branch circuit application purpose and area.

Generally the diversity factor taken to be for


5

LIGHTING CIRCUIT = 0.6 – 0.8

GENERAL SOCKET = 0.3

SPCEIFIC SOCKET = 0.9 OR 1

DESIGNED LOAD

For each incandescent lamp is taken 40w

7 incandescent lamps x 40 w = 280w

For each fluorescent lamp is taken 36 w

9 fluorescent lamps x 36 w= 324 w

For each general purpose socket outlet is taken

8 Socket outlets, 220v x 5 A = 1.1kw

2 special socket outlet, 220v x 15A = 3.3 kW

FOR LIGHTING CIRCUIT = 2 X 10 A X 220V = 4400 W = 4.4 KW

FOR GENERAL PURPOSE SOCKET = 1 X 16 A X 220V = 3520 W = 3.52 KW

FOR SPCEIFIC PURPOSE SOCKET = 2 X 25 A X 220V =11000 W = 11 KW

TOTAL DESIGNED LOAD = 18.92 KW

MAX EXPECTED LOAD

FOR LIGHTING CIRCUIT = 4.4 KW X 0.6 = 2.64 KW

FOR GENERAL PURPOSE SOCKET = 3.52 KW X 0.3 = 1.056 KW

FOR SPCEIFIC PURPOSE SOCKET = 11 KW X 1 = 11 KW

TOTAL EXPECTED LOAD = 14.696 KW

NOTE:-

Since the total expected load is 14.696 kw which is greater than 8 kw, therefore the
required supply voltage is three phase (380 v).

5
6

CONSIDER

In = Maximum normal current.

Ib =current setting for circuit breaker of fuse (design current).

Iz =current carrying capacity of the conductor.

TO DETERMINE THE FEEDER CABLE SIZE AND CHOOSE SWITCHABLE


CIRCUIT BREAKER

Considering of power factor =0.8 for the main feeder cable

Ib = (14.696 x 1000)/ √3 x 380 x 0.8

Ib = 27.91 A

In>Ib. this value may be taken from IEE or EEPCO regulations.

From table 9.1. 27.91 A rated circuit breaker can be selected for protection

In = 32 Amp

There for the maximum MAIN CIRCUIT BREAKER size that can be chosen is 32 A
available in the market.

LET TAKE
Average ambient temperature is 250C

General purpose p.v.c Type of insulation.

And from Table A.4 correction factor for250C = 1.03 Ca = 1.03

Therefore the required cable rating is:-

Iz = in/ca x cg

= 32/1.03 = 31.067A

From EBCS-10 Table B.1 reference method 4(enclosed in conduit in thermal


installation including wall) our Iz is 31.067 A, but we took the previous value
available in the table which is 31 A. Therefore 6 mm2 conductor which carries 31 A.

Testing for Voltage drop = (mV/Am) * I * L

From table B.2 voltage drop for 6mm2 conductor size = 6.4 mv/Am
7

maximum current through cables = 27.91A

Voltage drop on cable = 6.4 mv/Am * 27.91 * 10 m =1.786V


where 10m= is long run meter from the pole to the kilowwatt meter

Maximum allowable voltage drop = 2.5% of 380 V = 9.5V.

Since the actual voltage drop is less than from the allowable
maximum voltage drop, selected feeder cable size is 6 mm2.

MATERIAL REQUIRED

No Specification unit Unit price quantity Total cost


(birr) (birr)

1 Incandescent lamp pcs 15 7 105

2 Lamp holder(Philips) pcs 5 7 35

3 Fluorescent lamp with holder 36 w pcs 230 9 2070

4 Two way(change over switch) pcs 38 9 342

5 Four way (intermediate switch) pcs 0 0 0

6 S.p.s.t switch (6A) pcs 24 4 96

7 GPSocket out let 16 A ,220V ,2 Pin pcs 45 8 384

7
8

8 SPSocket out let 25 A, 220 ,3pin pcs 45 2 90

9 Junction box 65mm for switch pcs 6 24 144

Junction box 85mm for socket pcs 8 50 400

10 Conduit 11 mm for connection pcs 30 7 210

Conduit 13.5 mm for connection pcs 30 8 240

Conduit 16 mm for connection pcs 30 9 270

11 Circuit breaker 6A pcs 0 0 0

Circuit breaker 10 A pcs 75 2 150

Circuit breaker 16 A pcs 90 1 90

Circuit breaker 25 A pcs 120 2 240

Circuit breaker 32 A pcs 0 0 0

Reserve Circuit breaker 10 and 16 A pcs 165 2 165

Solid copper wire 2.5mm2 100m 4 500 2000

Solid copper wire 4 mm2 100m 1/2 15 750

Solid copper wire 10mm2 20m - 25 500

7926 birr
Total cost
9

9
10
12
Project on Electrical Installation Design