ASSUME
We use florescent lamp
ASSUME
We use incandescent lamp
Power for each incandescent lamp is 40W
SINCE THE EFFICANCY IS 60 lum/w
ASSUME
We use incandescent lamp
Power for each incandescent lamp is 40W
SINCE THE EFFICANCY IS 60 lum/w
The diversity factor depends on the branch circuit application purpose and area.
DESIGNED LOAD
NOTE:-
Since the total expected load is 14.696 kw which is greater than 8 kw, therefore the
required supply voltage is three phase (380 v).
5
6
CONSIDER
Ib = 27.91 A
From table 9.1. 27.91 A rated circuit breaker can be selected for protection
In = 32 Amp
There for the maximum MAIN CIRCUIT BREAKER size that can be chosen is 32 A
available in the market.
LET TAKE
Average ambient temperature is 250C
Iz = in/ca x cg
= 32/1.03 = 31.067A
From table B.2 voltage drop for 6mm2 conductor size = 6.4 mv/Am
7
Since the actual voltage drop is less than from the allowable
maximum voltage drop, selected feeder cable size is 6 mm2.
MATERIAL REQUIRED
7
8
7926 birr
Total cost
9
9
10
12
Project on Electrical Installation Design