Sie sind auf Seite 1von 2

Project: 262002-1

Series 4030
1.5x1x8
Centerline Disc. End Suction Basemounted Pu

Project Number262002-1 RepresentativeProtec Inc


Name: Frionovo 6935 NW 50 ST, Miami, Fl
Reference: Mina Phone: 305-594-3684, Fax: 305-477-2514
Location: Order No: Date
Engineer: Submitted byJose L. Gonzalez Date 3/13/02
Contractor Approved by: Date

PUMP DESIGN DATA MOTOR DESIGN DATA


Tag Num: Motor Supplier: Factory Choice
Service: Motor Size: 1 hp @ 1800 rpm
Location: Frame Size: 143
No. of Pumps: 1 Enclosure: ODP
Capacity: 130 lpm Cycle/Phase/Voltage: 60/3/460
Head: 12 m Motor Eff: Std
Piping: Single Insulation: Class "B" Insulation (266.0 °F)
Suction Pressure: 0 ft Starter Config: <unknown>
Liquid: Water Full Load/Starting (A) not avail / not avail
Op. Temperature: 44 °F
Viscosity: 31 ssu
Sp.Gravity: 1.00 MECHANICAL SEAL DESIGN DATA
Suction Size: 1.5 in
Discharge Size: 1 in Manufacturer John Crane
Manu. Code [JC 21] JC 21, OP171
Seal Type Inside Unbalanced
MATERIALS OF CONSTRUCTION Rotating Face Carbon
Stationary Seat Ceramic
Construction BF (Bronze Fitted)
Secondary Seal EPDM
ANSI Flange Rating 125 lb. (Cast Iron)
Springs Stainless Steel
Impeller Bronze (B584-844)
Rotating Hardware Stainless Steel
Casing Cast Iron (A48-30)
Casing Gasket Confined Non-Asbestos Fiber
Bearing Frame Cast Iron (A48-30)
Bearings Anti-Friction Grease Lubricated
Pump Shaft Carbon Steel
Shaft Sleeve Stainless Steel
Coupler Woods Sure Flex or Equal

Pressure Operating Limits


(psi) Temperature-Pressure
180
Casing,Seal(S)
150

120

90

60

30
0
-30 30 90 150 210 270
Temperature (°F)

DIMENSIONAL DATA ( in, lbs, hp ) NOT for CONSTRUCTION


HA HB HD HE HF HG HH X Wgt.
12 30 9.25 4.5 27.5 3 0.75 6.5 138

3/13/02, 14:16:35, Jose L. Gonzalez, Protec Inc, 305-594-3684, Fax: 305-477-2514

6.1d Page 1 / 2
Project: 262002-1

Series 4030
1.5x1x8
Centerline Disc. End Suction Basemounted Pu

Head Series 4030 PT17-1-0 --- Admin Data ---


Tag Num:
(m) 1.5x1x8 @ 1740 rpm Service:
24 Location:
8.19 in 26 --- Motor Data ---
35
43
49 Motor Size: 1 hp
20 53
Motor Speed: 1800 rpm
56
57
56 --- Design Duty Point ---
53 Flow: 130 lpm
16
49
Head: 12 m
6.51 in
43 Impeller: 6.51 in
12 3 hp
6.00 in --- Performance Data ---
• NPSHR: 1.1 m
2 hp • Eff. @ Design: 46.01 %
8.0 • BHP @ Design: 0.74 hp
35%
1.5 hp • BEP @ Design Imp.:
53.27 % @ 207.0 lpm
1 hp • BHP @ Runout:
4.0 0.75 hp 1.36 hp @ 313.1 lpm
System 0.5 hp • %max imp. range: 23.42 %

0
0 80 160 240 320 400 480

Water, sg= 1.00 Flow (lpm)

3/13/02, 14:16:36, Jose L. Gonzalez, Protec Inc, 305-594-3684, Fax: 305-477-2514

6.1d Page 2 / 2