1 Data Required:

Rated Apparent Power of the Transformer (SrT) = 630 kVA


Rated Voltage of the Transformer (UrT) = 410 V
Rated Current of the Transformer (IrT) = 887.148 A
Total Loss of Transformer in the Winding at Rated Current (PkrT) = 6.50 kW
Short Circuit Voltage at the Rated Current (UkrT) = 4.00 %
Voltage Factor for the Low Voltage side (Cmax) = 1.05

2 Network Transformer Impedance:

x
= %

ZT = 10.673 mΩ

=
RT = 2.753 mΩ

=

XT = 10.312 mΩ

ZT = 2.753+10.312j mΩ

Impedance Correction Factor


ZTK = KTZT

.
= + .

Relative Reactance of the Transformer, = /( ⁄ )

= 0.039 mΩ

= 0.975 mΩ

ZTK = 2.684+10.053j mΩ