Beruflich Dokumente
Kultur Dokumente
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
2
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Table of Contents
1.1 Start/stop, 4-pole motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Start/stop, 4-pole over-synchronous motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Start/stop, 4-pole motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4 Start/stop, 2-pole over-synchronous motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.5 Three preset speeds on three terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.6 Start/stop, motor thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.7 Day/night reference value switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.8 Process control, scaled in % . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.9 Process control, scaled in Pa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.10 Process control, reference value adjustment according to system attributes 13
1.11 Line contactor control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.12 Remote/local switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2 Application examples
2.1 Two preset speeds on two terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.2 Selection of 8 fixed reference values, additive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.3 Selection of 8 fixed reference values, alternative . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.4 Parameter set switching, set 1.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.5 Parameter set switching, set 1.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.6 Digital motor potentiometer, alternative . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.7 Digital motor potentiometer, additive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.8 Digital motor potentiometer, reference value adjustment . . . . . . . . . . . . . . . . . . 23
2.9 Flying start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.10 Status messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.11 Time-based switching functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.12 Constant pressure regulation in % . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2.13 Constant pressure regulation in Pascal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2.14 Day/night reverence value switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3 Process control
3.1 Flow rate controller - internal process controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.2 Outside air temperature controller - external controller 1 . . . . . . . . . . . . . . . . . . . 31
4 Types of fans
4.1 Axial fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.2 Radial fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.3 RPM, air volume, pressure, and rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.4 Drive design for a free-wheeling fan wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5 Drive sizing
5.1 Three-phase asynchronous motor with frequency converter . . . . . . . . . . . . . . . . 35
5.2 Typical asynchronous motor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.3 For power ratings < 4.0 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.4 For power ratings > 5.5 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.5 Behaviour of the asynchronous motor with frequency converter . . . . . . . . . . . . 35
5.6 87-Hz technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6 Energy conservation
6.1 Damper system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.2 Speed control using a frequency converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
7 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
*=Default setting
+10 V 50
*Optional safe stop
A IN (S201 U-I) 53
A IN (S202 U-I) 54 0...10V
Analogue Reference
COM 55
A OUT 42
A OUT 39
01
Relay 1
02 Alarm
03
04
Relay 1
05 Motor running
06
■ Information/notes/remarks
Initial operation of a 4-pole three-phase asynchronous motor with thermistor for motor temperature monitoring. The maximum
frequency is limited to 50 Hz.
The frequency converter is preset (default settings) for initial operation. For energy-optimised operation, the motor must be
adjusted using the initial operation menu.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
4
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Initial operation
+24 V 13
0-01 Language [1] German
D IN 18 Start/Stop
5-10 Terminal 18 digital input [8] Start*
D IN 19 Motor Thermistor
5-12 Terminal 27 digital input [0] No function *
COM 20
1-90 Motor thermal protection [2] Thermistor trip
D IN 27
1-93 Thermistor connection [4] Digital input 19
D IN 29
5-40.0 Relay function [9] Alarm*
D IN 32
5-40.1 Relay function [5] Motor movement*
D IN 33
1-25 Rated motor speed 1420
D IN (S.Stop) *37
3-03 Max. reference value 72
4-14 Max. frequency (Hz) 72
+10 V 50
*Optional safe stop
02 Alarm
03
04
Relay 1
05 Motor running
06
■ Information/notes/remarks
Initial operation of a 4-pole three-phase asynchronous motor with thermistor for motor temperature monitoring. The maximum
frequency is limited to 72 Hz.
The frequency converter is preset (default settings) for initial operation. For energy-optimised operation, the motor must be
adjusted using the initial operation menu.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
*=Default setting
+10 V 50
*Optional safe stop
A IN (S201 U-I) 53
A IN (S202 U-I) 54 0...10V
Analogue Reference
COM 55
A OUT 42
A OUT 39
01
Relay 1
02 Alarm
03
04
Relay 1
05 Motor running
06
■ Information/notes/remarks
Initial operation of a 2-pole three-phase asynchronous motor with thermistor for motor temperature monitoring. The maximum
frequency is limited to 50 Hz.
The frequency converter is preset (default settings) for initial operation. For energy-optimised operation, the motor must be
adjusted using the initial operation menu.
All other parameters are preset using default settings.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
6
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Initial operation
+24 V 13
0-01 Language [1] German
D IN 18 Start/Stop
5-10 Terminal 18 digital input [8] Start*
D IN 19 Motor Thermistor
5-12 Terminal 27 digital input [0] No function *
COM 20
1-90 Motor thermal protection [2] Thermistor trip
D IN 27
1-93 Thermistor connection [4] Digital input 19
D IN 29
5-40.0 Relay function [9] Alarm*
D IN 32
5-40.1 Relay function [5] Motor movement*
D IN 33
1-25 Rated motor speed 2920
D IN (S.Stop) *37
3-03 Max. reference value 72
4-14 Max. frequency [Hz] 72
+10 V 50
*Optional safe stop
02 Alarm
03
04
Relay 1
05 Motor running
06
■ Information/notes/remarks
Initial operation of a 2-pole three-phase asynchronous motor with thermistor for motor temperature monitoring. The maximum
frequency is limited to 72 Hz.
The frequency converter is preset (default settings) for initial operation. For energy-optimised operation, the motor must be
adjusted using the initial operation menu.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
■ 3 Preset speeds
Operation with 3 preset speeds selected via floating contacts
02
03
04
Relay 2
05
06
■ Information/notes/remarks
The preset reference values 3-10 are used. 0... 7 due to binary encoding, preset reference values 1, 2, and 4.
The speed is specified in % using the 3-02 and 3-03 limited reference value range.
The logical encoding causes a stop condition when none of the speed selection inputs are active.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
8
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Initial operation
+24 V 13
5-10 Terminal 18 digital input [8] Start*
D IN 18 Start/Stop
5-12 Terminal 27 digital input [0] No function
D IN 19 Motor Thermistor
1-90 Motor thermal protection [2] Thermistor trip *
COM 20
1-93 Thermistor connection [4] Digital input 19
D IN 27
5-40.0 Relay function [9] Alarm*
D IN 29
5-40.1 Relay function [5] Motor movement*
D IN 32
D IN 33
*=Default setting
D IN (S.Stop) *37
+10 V 50
*Optional safe stop
A IN (S201 U-I) 53
A IN (S202 U-I) 54 0...10V
Analogue Reference
COM 55
A OUT 42
A OUT 39
01
Relay 1
02 Alarm
03
04
Relay 1
05 Motor running
06
■ Information/notes/remarks
Initial operation of an asynchronous three-phase motor with thermistor for motor temperature monitoring. The speed is adjusted
using an analogue steady-state 0...10 V DC signal. The output relay 1 signals all alarms which occur, and the output relay 2 signals
motor movement.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
03-10.1 80.00 %
(day) A IN (S201 U-I) 53
Saturday - Sunday A IN (S202 U-I) 54
03-10.2 Preset reference value 2 60.00 %
COM 55
(weekend)
A OUT 42
23-00.1 ON time 08:00:00
23-01.1 ON action [12] Selection of preset A OUT 39
reference value 2 01
23-02.1 OFF time 20:00:00
Relay 1
02
23-03.1 OFF action [10] Selection of preset
03
reference value 0
04
Relay 2
*=Default setting 05
06
■ Information/notes/remarks
Terminals 18/27 are shorted. On all weekdays at 6:00 am, the preset reference value 1 (80 %) is selected, and at 8:00 pm preset
reference value 0 (40 %) is selected.
On the weekend at 8:00 am, the preset reference value 2 (60 %) is selected, and at 8:00 pm preset reference value 0 (40 %) is
selected.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
10
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Initial operation
+24 V 13
5-10 Terminal 18 digital input [8] Start*
D IN 18 Start/Stop
5-12 Terminal 27 digital input [0] No function
D IN 19
Pessure
COM 20
1-00 Control method [3] PID controller
D IN 27
20-21 Reference value 1 50
D IN 29
20-94 PID integration time 0.8
D IN 32
D IN 33
*= Default setting
D IN (S.Stop) *37
+10 V 50
*Optional safe stop
A IN (S201 U-I) 53
A IN (S202 U-I) 54 0...10V
Controlled Variable
COM 55
A OUT 42
A OUT 39
01
Relay 1
02
03
04
Relay 2
05
06
■ Information/notes/remarks
A standard process controller is implemented in the frequency
converter for implementation of pressure regulation. Three
parameters must be adjusted during initial operation.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
20-12 [72] Pa
unit A IN (S201 U-I) 53
A IN (S202 U-I) 54 0...10V
Controlled Variable
*= Default setting
COM 55
A OUT 42
A OUT 39
01
Relay 1
02
03
04
Relay 2
05
06
■ Information/notes/remarks
A standard process controller is implemented in the frequency
converter for implementation of pressure regulation. Three
parameters must be adjusted during initial operation. If the pressure
is to be shown on the display of the physical system in Bar, additional
parameters must be set.
p
p
Pressure
Druck-
control
regelung
1. Maximum reference/feedback value, par. 20-14
2. Term. 54 Scaling of maximum reference/feedback value, par. 6-25
Par. 20-21
y
Pressure value
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
12
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
* = Default setting 02
03
04
Relay 1
05
06
■ Information/notes/remarks
Used in control systems with a pressure sensor installed near H
the pump. Compensation of the duct pressure loss for high con-
GDHz Pump
sumption values (control according to the system attributes). To characteristics
provide sufficient power at more distant points of consumption,
Corrected
the target pressure value for the pump controller is adjusted H ref operating point
when the function is activated. In this case the pressure follows H nann
Installation characteristics
the quadratic load characteristics. With this control method, a 0%
attributes. Q nann Q
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
01
Relay 1
02 Alarm
03
04
Relay 2
05 Motor running
06
05
MCB107
06
■ Information/notes/remarks
When the OK button is pressed, the line contactor switches on via digital output 29. The frequency converter starts and stops using
the Start/Stop switch. An external 24V DC voltage supply (MCB107) is required for this switching mode.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
14
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
■ Remote/local switching
Remote: Profibus, start, stop, reset, reference value
Local: Save reference value, preset speed (JOG), stop (reverse)
Initial operation
+24 V 13
5-11 Terminal 19 digital input [19] Save reference value
D IN 18
5-12 Terminal 27 digital input [2] Coast (reverse)* Operating Mode
D IN 19
5-13 Terminal 29 digital input [14] Preset speed (JOG)* Remote/Local
COM 20
5-14 Terminal 32 digital input Stop (reverse)
D IN 27
3-19 Preset speed (JOG) RPM 900
D IN 29
D IN 32
*=Default setting
D IN 33
D IN (S.Stop) *37
+10 V 50
*Optional safe stop
A IN (S201 U-I) 53
A IN (S202 U-I) 54
COM 55
A OUT 42
A OUT 39
01
Relay 1
02
03
04
Relay 2
05
06
■ Information/notes/remarks
Remote operation:
Terminal 27 is closed; start, stop, reset, and reference values are entered via the Profibus interface.
Local operation:
Terminal 27 is closed, and terminal 19 is used for local switching of the operating mode – the current reference value is saved.
If terminal 29 is closed, the preset speed jog is active.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
FC100StartStopFreilaufQuittierungThermistorZweiFestdrehzahlen
Two preset reference values
D IN/OUT 27 Coast/Reset
5-14 Terminal 32 [16] Preset reference bit 0
D IN/OUT 29
[17] Preset reference
5-15 Terminal 33 D IN 32 Fixed Speed 1
value bit 1
3-10.1 Preset reference value [1] 50 % D IN 33 Fixed Speed 2
Thermistor A IN COM 55
OUT(S) 02
■ Information/notes/remarks
Application: Replacement of dual-speed motors or motors with separate windings. A delta-Wye combination can be avoided
through the use of the frequency converter, even for higher power ratings. It should be possible to activate 2 freely selectable pre-
set speeds through control via floating contacts. A preset speed should be assigned to every contact.
Additional benefits: High starting currents no longer occur during start-up, so power supply equipment (e.g. uninterruptible power
supplies) no longer need to be oversized in this regard. For motors with PTC resistors or thermostat relays, these can be connected
directly to the converter so that no separate monitoring device is needed.
Solution: For two preset speeds, the application requirements (as described above) can be attained through corresponding para-
meter settings alone. The terminals 18, 27, 32, and 33 are used for control purposes.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
16
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
FC100AddierendFestsollwertAnalog
Manual mode notification D IN/OUT 27 Manual Operation
5-01 Terminal 27 function [1] Output D IN/OUT 29
Application examples
5-30 Terminal 27 [125] Drive in manual mode D IN 32 Preset Reference
*=Default setting
■ Information/notes/remarks
The example describes an application using 8 preset reference Term Term Term Term Setting
values which are added to the analogue reference value (termi- 18 19 32 33
nal 53).
Preset ref. value 0 1 0 0 0 5%
Parameter 5-01 specifies whether terminal 27 acts as an input or Preset ref. value 1 1 1 0 0 15 %
as an output. Selection of the preset reference values is done in Preset ref. value 2 1 0 1 0 25 %
accordance with the following table.
Preset ref. value 3 1 1 1 0 35 %
The alarm notification is given via the output relay 1. Preset ref. value 4 1 0 0 1 50 %
Manual mode notification is given via terminal 27. Preset ref. value 5 1 1 0 1 75 %
Preset ref. value 6 1 0 1 1 80 %
Preset ref. value 7 1 1 1 1 90 %
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
Smart Logic:
FC100AddierendFestsollwertAnalog
5-12 Terminal 27
value ON
D IN/OUT 27 Manual Operation
[17] Preset reference
5-14 Terminal 32 D IN/OUT 29
value bit 1
[18] Preset reference D IN 32 Preset Reference
5-15 Terminal 33
value bit 2
D IN 33 Preset Reference
Preset reference value selection
3-04 Reference value function [1] Multi setup
+10 V 50
3-10 Preset reference value [0] 5% Reference
A IN (S201 U-I) 53
3-10 Preset reference value [1] 15 %
A IN (S202 U-I) 54
3-10 Preset reference value [2] 25 %
A IN COM 55
3-10 Preset reference value [3] 35 %
A OUT 42
3-10 Preset reference value [4] 50 %
A OUT COM 39
3-10 Preset reference value [5] 75 %
COM 01
3-10 Preset reference value [6] 80 %
Relay 1
OUT(S) 02 Alarm
3-10 Preset reference value [7] 90 % OUT(Ö) 03
3-15 Variable reference value 1 [1] Analogue input 53* COM 04
Relay 2
Relay OUT(S) 05
5-40 Relay 1 [5] Motor ON OUT(Ö) 06
*=Default setting
■ Hinweise/Notizen/Anmerkungen
The example describes an application with switching from an Term Term Term Term Setting
analogue reference value to 8 preset reference values. 18 19 32 33
Preset ref. value 0 0 0 0 5%
Switching from the analogue reference value to preset reference
values is performed via terminal 27. Preset ref. value 1 1 0 0 15 %
Preset ref. value 2 0 1 0 25 %
Selection of the preset reference values is done in accordance
with the following table. Preset ref. value 3 1 1 0 35 %
Preset ref. value 4 0 0 1 50 %
The “motor on” notification is given via the output relay 1.
Preset ref. value 5 1 0 1 75 %
Preset ref. value 6 0 1 1 80 %
Preset ref. value 7 1 1 1 1 90 %
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
18
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Smart Logic:
FC100Parametersatzumschaltung
5-14 Terminal 32 [23] Setup select bit 0
D IN/OUT 27 Coasting
Reference value setting
D IN/OUT 29
Application examples
3-15 Variable reference value 1 [1] Analogue input 53*
D IN 32 Set-up Select
Linking setups
D IN 33
0-51 Set-up copy [2] Copy to setup 2
0-12 Link setup with [2] Setup 2
+10 V 50
3-10 Active setup [9] Multi setup Reference
A IN (S201 U-I) 53
A IN (S202 U-I) 54
*=Default setting
A IN COM 55
A OUT 42
A OUT COM 39
COM 01
Relay 1
OUT(S) 02
OUT(Ö) 03
COM 04
Relay 2
OUT(S) 05
OUT(Ö) 06
■ Information/notes/remarks
The selection of setups is done in accordance with the follow- Term. 32 (Bit 0)
ing table: Setup 1 0
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
FC100Parametersatzumschaltung4
5-14 Terminal 32 [23] Setup select bit 0
D IN/OUT 27 Coasting
5-15 Terminal 33 [24] Setup select bit 1
D IN/OUT 29
Reference value setting
D IN 32 Set-up Select
3-15 Variable reference value 1 [1] Analogue input 53*
D IN 33 Set-up Selectl
Linking setups
0-51 Set-up copy [9] Copy to all
+10 V 50
0-10 Active setup [2] Setup 2 Reference
A IN (S201 U-I) 53
0-12 Link setup with [1] Setup 1
A IN (S202 U-I) 54
0-10 Active setup [3] Setup 3
A IN COM 55
0-12 Link setup with [2] Setup 2
A OUT 42
0-10 Active setup [4] Setup 4
A OUT COM 39
0-12 Link setup with [3] Setup 3
COM 01
0-10 Active setup [9] External selection
Relay 1
OUT(S) 02
OUT(Ö) 03
*=Default setting
COM 04
Relay 2
OUT(S) 05
OUT(Ö) 06
■ Information/notes/remarks
The selection of setups is done in accordance with the follow- Term. 32 (Bit 0) Term. 33 (Bit 1)
ing table: Setup 1 0 0
A parameter setup copy (par. 0-51) is not essential. Alterna-
Setup 2 1 0
tively, terminals 32 and 33 in every setup can be set to manual
setup select. Setup 3 0 1
In order to switch between setups during operation, the se- Setup 4 1 1
tups must be linked (par. 0-12). If linking is not set up, then
switching between setups is only possible while the frequency Note:
converter is stopped. When setups are linked, all parameters which are marked as
“false” are mirrored, that is, they are the same in the linked
setups.
All parameters which are marked as “true” can be different in
the linked setups.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
20
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
FC100Parametersatzumschaltung4
5-13 Terminal 29 [19] Store reference value
D IN/OUT 27 Coasting
5-14 Terminal 32 [21] Speed up
D IN/OUT 29
Application examples
5-15 Terminal 33 [22] Speed down
D IN 32 Speed Up
Reference value setting
D IN 33 Speed Down
3-15 Variable reference value 1 [1] Analogue input 53*
+10 V 50
*=Default setting Reference
A IN (S201 U-I) 53
A IN (S202 U-I) 54
A IN COM 55
A OUT 42
A OUT COM 39
COM 01
Relay 1
OUT(S) 02
OUT(Ö) 03
COM 04
Relay 2
OUT(S) 05
OUT(Ö) 06
■ Information/notes/remarks
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
FC100AddierendDigiPotiAnalog
5-14 Terminal 32 [56] Lower DigiPot
D IN/OUT 27 Dig. Reference Up
5-15 Terminal 33 [57] Clear DigiPot
D IN/OUT 29
Reference value setting
D IN 32 Dig. Reference Down
3-90 DigiPot step size 0.1 %
D IN 33 Dig. Reference Clear
3-91 DigiPot ramp time 1 sec.
3-92 Store at power down [0] Off*
+10 V 50
3-93 Upper limit 100 % Reference
A IN (S201 U-I) 53
3-94 Lower limit 0%
A IN (S202 U-I) 54
3-95 Ramp delay 1 s*
A IN COM 55
A OUT 42
*=Default setting
A OUT COM 39
COM 01
Relay 1
OUT(S) 02
OUT(Ö) 03
COM 04
Relay 2
OUT(S) 05
OUT(Ö) 06
■ Information/notes/remarks
The sketch shows the functionality of the digital potentiome- (Hz)
ter.
The ramp time, par. 3-91, corresponds to the nominal motor
frequency.
Parameter 3-92 can be used to specify whether the digital refe-
rence value is saved or set to zero when power is removed.
Par.3-90
Par.3-91
Par.3-95
Time
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
22
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Smart Logic:
FC100Parametersatzumschaltung4
5-12 Terminal 27 [55] Increase DigiPot
D IN/OUT 27 DigiPot Increase
5-14 Terminal 32 [56] Lower DigiPot
D IN/OUT 29
Application examples
5-15 Terminal 33 [57] Clear DigiPot
D IN 32 DigiPot Decrease
Reference value source
D IN 33 DigiPot Clear
3-15 Variable reference value 1 Analogue input 53*
[20] Digital
3-16 Variable reference value 2 +10 V 50
potentiometer*
A IN (S201 U-I) 53 Reference
Reference value limits
3-02 Min. reference value 0 A IN (S202 U-I) 54
3-03 Maximum reference value 50 A IN COM 55
*=Default setting
■ Information/notes/remarks
In this application the current analogue reference value is adjusted Reference unit
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
Smart Logic:
COM 55
A OUT 42
COM 39
01
Relay 1
02
03
04
Relay 2
05
06
■ Information/notes/remarks
A flying start is always performed when the converter is started (term. 18, 3 above, manual mode ON, auto ON, bus) and the output
frequency is zero. As soon as terminal 27 is closed, the frequency converter synchronises the output frequency with the current motor
frequency.
Start-up delay par. 1-71
The duration between a start-up signal and the actual start of acceleration can be increased by entering a time value here. During this
time a start-up function in accordance with par. 1-72 is performed.
Flying start par. 1-73
This function makes it possible to “catch” a motor which is spinning freely due to a mains drop-out, or to detect the speed of a freely
spinning motor before start-up and accelerating starting from this speed. The search direction for the flying start is linked to the set-
ting in par. 4-10, motor speed direction. Clockwise [0]: Flying start search in clockwise direction. If search is unsuccessful, a DC brake is
carried out. Both directions [2]: The flying start will first perform a search in the direction determined by the last reference value (direc-
tion). If the speed is not found, a search in the other direction is performed. If the search is unsuccessful, a DC brake will be activated
in the time set in par. 2-02, braking time. Start-up will then take place from 0 Hz. The operational state of terminal 27 is transmitted to
building automation via the digital output 29.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
24
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
FC100StartStoppMCB101
3-04 Reference value function [1] Additive*
D IN/OUT 27 Manual
3-10 Preset reference value [0] 55 %
D IN/OUT 29 Auto
examples
Terminal 27 digital output
D IN 32
Anwendungs-
5-01 Terminal 27 [1] Output
beispiele
D IN 33
[168] Drive in manual
Application
5-30 Terminal 27 X30COM DIN 1
mode
Terminal 29 digital output DIN 7 2
*=Default setting
■ Information/notes/remarks
The example describes an application with a start and stop si- Status messages
gnal as well as preset reference value. Terminal 27 Manual mode
Terminal 29 Drive in auto mode
Terminal X30/6 Run on reference / no warning
Terminal X30/7 Frequency converter stopped
Oparator 1
Boolsch 2 Par.1342.0 FALSCH (Par.1341.0)
disabled
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
Smart Logic:
FC100Zeitschaltfunktion
Preset reference value
D IN/OUT 27
3-10.0 Preset speed 1 100 %
D IN/OUT 29 Redox
3-10.1 Preset speed 2 50 %
D IN 32
Digital output
D IN 33
5-02 Terminal 29 [1] Output
+10 V 50
5-31 Terminal 29 [80] SL digital output A
A IN (S201 U-I) 53
Digital input
A IN (S202 U-I) 54
[16] Preset reference
5-12 Terminal 27 A IN COM 55
value bit 0
Timer A OUT 42
■ Information/notes/remarks
The frequency converter VLT HVAC Drive is operated at a maxi-
mum reference value of 100% by default.
All days
After an adjustable time delay, digital output 29 is turned on
and activates the measurement program (redox system) to de-
termine the water quality. 50 %
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
26
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
PIDDruckProzent
20-21 Reference value 1 50 %
D IN/OUT 27 Coasting
Optimisation
D IN/OUT 29
Application examples
20-94 Integration time 5s
D IN 32
D IN 33
*=Default setting
+10 V 50
A IN (S201 U-I) 53
Schematic Reference
A IN (S202 U-I) 54
Actual
A IN COM 55
A OUT 42
A OUT COM 39
COM 01
Relay 1
p
p
Pressure
Druck-
OUT(S) 02 Alarm
control
regelung
OUT(Ö) 03
COM 04 Motor Running
Relay 2
OUT(S) 05
y OUT(Ö) 06
Par. 20-21
Pressure value
■ Information/notes/remarks
A standard process controller is implemented in the frequency Y [%]
converter for implementation of pressure regulation. Three pa-
rameters must be adjusted during initial operation. If the pres-
sure is to be shown on the display of the physical system in Bar,
additional parameters must be set. Functional diagram
p [%]
Xp = Par 2093
Xn = Par 2094
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
PIDDruckProzent
20-21 Reference value 1 500
D IN/OUT 27 Coasting
Optimisation
D IN/OUT 29
20-94 Integration time 5s
D IN 32
Scale
D IN 33
20-14 Max. reference value 1000 Pa
+10 V 50
Term. 54 scale max. –
6-25 2,000.00 A IN (S201 U-I) 53
reference/feedback value
Reference
Reference/feedback value A IN (S202 U-I) 54
20-12 [72] Pa
unit Actual
A IN COM 55
A OUT 42
* Default setting
A OUT COM 39
Schematic COM 01
Relay 1
OUT(S) 02 Alarm
OUT(Ö) 03
COM 04 Motor Running
Relay 2
OUT(S) 05
OUT(Ö) 06
p
p
Pressure
Druck-
control
regelung
y
Par. 20-21
Pressure value
■ Information/notes/remarks
A standard process controller is implemented in the frequency converter for implementation of pressure regulation. Three parame-
ters must be adjusted during initial operation. If the pressure is to be shown on the display of the physical system in Bar, additional
parameters must be set. Three additional parameters must be adjusted during initial operation.
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
28
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
FC100TagNachtUmschaltung
23-00.0 On time 06:00:00
D IN/OUT 27 Coast/Reset
[11] Selection of preset
23-01.0 On action D IN/OUT 29
reference value 1
Application examples
23-00.2 Off time 20:00:00 D IN 32
[10] Selection of preset D IN 33
23-03.0 Off action
reference value 0
+10 V 50
Preset reference value 0
03-10.0 40 % A IN (S201 U-I) 53
(night)
Preset reference value 1 A IN (S202 U-I) 54
03-10.1 80%
(day) A IN COM 55
On weekends
A OUT 42
23-00.1 On time 08:00:00
A OUT COM 39
[12] Selection of preset
23-01.1 On action COM 01
reference value 2
Relay 1
OUT(S) 02
23.02.1 Off time 20:00:00
[10] Selection of preset OUT(Ö) 03
23-03.1 Off action
reference value 0 COM 04
Relay 2
* = Default setting
Par. Mode
23-01.0 Preset Reference 1
On all weekdays at 6:00 am, preset reference value 1 is selected, Par. Mode
Zeit 23-01.0 Preset Reference 1
and at 8:00 pm preset reference value 0 is selected. Par
6:00
23-00.0
20:00
23-02.0
06:00
23-00.0
Mo. - Fr.
23-03.0 Preset Reference 0
Par. Mode
On the weekend at 8:00 am, preset reference value 2 is selected, 23-01.1 Preset Reference 2
and at 8:00 pm preset reference value 0 is selected.
23-03.1 Preset Reference 0
Par. Mode
Zeit 23-01.1 Preset Reference 2
8:00 20:00 08:00
Par 23-00.1 23-02.1 23-00.1
Sa. - So.
23-03.1 Preset Reference 0
Non-binding suggestion within the framework of our general delivery and warranty conditions.
The suggestion is based on factory settings, requires proper setting of the motor data and requires subsequent verification by the user.
Zeit 8:00 20:00 08:00
MZ.03.PF.02 – VLT is a registered trademark of Danfoss Par 23-00.1 23-02.1 23-00.1 29
Sa. - So.
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
■ Flow rate controller ference value using parameter 20-21 in the physical unit m3/h, if
The VLT HVAC Drive series of Danfoss VLT frequency converters no external reference value signal is available.
are voltage intermediate circuit converters for nominal motor
ratings of 1.1 to 400 kW. They convert a three-phase AC network Scaling
with fixed voltage and frequency into a three-phase system with The reference variable can be scaled directly in the physical vari-
variable voltage, 3-phase 0 to mains voltage and variable fre- able m3/h using parameters 20-13, 20-14.
quency 0 to 1000 Hz. They are suitable for continuously variable
speed control of pump and fan drives with speed-dependant Process optimisation
load torque. Nowadays technical systems, especially in building Start the frequency converter and bring the system to a typical
automation and process technology engineering, have reached operating state using the reference value. Check to make sure
such a size that the manual control of these systems and the that the actual value adjusts to the reference value (this may take
processes involved is impossible. For this reason, systems which some time). Now increase the proportional gain par. 20-93 un-
allow for the automatic monitoring, switching, and control of the til the feedback signal begins to oscillate. Then reduce the value
process flow are used. This automation not only allows for safe until the feedback signal stabilises. Then reduce the proportional
operation, but also results in especially efficient use of the sy- gain by 40-60%. Reduce the integration time par. 20-94 until the
stem and therefore in a high degree of profitability. To meet the feedback signal begins oscillating again. Increase the integration
above requirements, a standard process controller is implemen- time until the feedback signal stabilises. Then increase of the in-
ted in the VLT HVAC Drive series of frequency converters. tegration time by 40-70%.
V = k • ∆pw
Flow rate control
Control variable The factor k takes the specific nozzle properties into consideration:
The control variable in the control circuit is the variable which
2
must be brought to a particular value and held there. The con- k=α•ε•A ρ
troller continuously compares the control variable to the refe-
rence variable. The controller is balanced when the control varia-
ble and the reference variable are in equilibrium at all times. The α = Flow rate number
control variable is connected to terminal 54. ε = Expansion number
A = Minimum nozzle cross-sectional area
Scaling Δpw = Differential pressure
The control variable can be scaled directly in the physical varia- ρ = Air density of 1.2kg/m3 assumed
ble m3/h using parameters 6-24, 6-25 and 20-12.
Reference variable
The reference variable is the specified value to which the control
variable is adjusted – it is often called reference value as well.
30
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
■ Parameter settings
Flow Rate Control Correcting variable
▼ Par ▼ Name ▼ Setting The heating valve (Fig. 2) is controlled via terminal X42-7 and
X42-8. The control range can be adjusted using parameters 26-
100 Control method PID-controller 41 and 26-42.
2021 Reference value 1 10000
2093 PID proportional gain 0.9 Y [%]
020 Display line 1.1 Ref value [unit] ▼ Par ▼ Name ▼ Setting
Process control
022 Display line 1.3 Feedback value 2640 Term. X42/7 output Ext. PID process 1
[unit] 2641 Term. X42/7, output min. scaling 0
024 Display line 3 Feedback value 2642 Term. X42/7, output max. scaling 100
[unit]
T Ext. Reference
P 21-13
Reference Output
M
M
P 21-15
Ext. Controller 1 P 26-40
Valve Control
Actual
P 21-14
Ext. Reference
P 21-13 Ext. Controller 1 Output
Reference
Fresh Air Temp. P 26-40
P 21-15
Actual PI - Controller
P 21-14
■ Process controller
Display readout
Activating the controller The control variable, reference value, and output signal can be
▼ Par ▼ Name ▼ Setting displayed for process optimisation.
GND 2
Y1
Scaling the reference variable
FC100MCB109GRUND
6
The reference variable can be scaled directly in the physical vari- Y (0..10V)
AOUT (0..10V) 7
able using parameters 21-10. G
8 G0
▼ Par ▼ Name ▼ Setting AOUT (0..10V) 9
2110 Ext. ref./feedback value unit 1 °C 10
AOUT (0..10V) 11
12
32
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Axial fans
n = fan speed in min-1 or s-1
AXIAL
t
V
m3 V1 = n1
Air Volume: SI h V2 n2
p 2
N p1 ¾ n1¾
Pressure: SIm2 p2 =¾¾ n 2¾¾
Motor P 3
Axial Air Flow P1 =¾¾n1 ¾¾
Power: SI kW P2 ¾n2 ¾
For this type the air moves through the fan in the axial direction. Example 1
It is designed for high air volumes and low pressure. The rela- If the speed of a fan motor is changed from 1420 min-1 to 2840
tively large blades result in a high circumferential speed, which min-1, the following new data result:
inevitably leads to high noise levels. Since the flow direction is
parallel to the motor axle, this design is very easy to assemble. n2 2840min-1 2
= 2= = 2,
n1 1420min-1 1
Radial fans
In this design the air flows from the inside to the outside over so- New flow rate: V2 = V1 • 2 = 2 • Vv
called deflector plates. The radial fan achieves higher pressures New pressure: p2 = p1 • 22 = 4 • p1
and has a smaller diameter for the same air volume, which also New power at the fan shaft and, respectively, power output of
Types of fans
makes it quieter than an axial fan. the motor: P2 = P1 • 23 = 8 • P1
Example 2
AXIAL
Motor P2 =
⎛
⎜
n2 ⎛⎜3 · P = ⎛⎜ 710min-1 ⎛⎜ 3 · P = ⎛⎜ n2 ⎛⎜3 · P
1 1 1
⎝ n1 ⎝ ⎝ 1420min-1 ⎝ ⎝ n1 ⎝
1
Axial Air Flow P2 = · P1
8
1415 min-1
Example MMOT = • 20,1Nm = 13,94 Nm
2040 min-1
A free-wheeling fan wheel with the following specifications is
selected for an application:
Fan Free-wheeling wheel Since the motor is operated at 72.08 Hz in the over-synchronous
range and power consumption remains constant, a 3.0 kW motor
Air volume 9. 000 m3/h
with a VLT HVAC Drive, FC-102P3K0, 3 kW, is sized sufficiently. As
Delta p total 716 Pa a check, the torque available at 72.08 Hz can be calculated: This
Speed 2040 min-1 shows that in the over-synchronous speed range, the size is suf-
ficient for the required fan shaft power
Shaft power 2.48 kW
PW
MW = 9550 •
nV
2,48 kW
MW = 9550 • = 11,61 Nm
2040 min-1
Fan torque: MW in Nm
Fan power output: PW in kW
Fan speed: nV in min-1
34
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Types of fans
p cies between 0 Hz and the nominal frequency (50Hz), therefore
f = Mains frequency [Hz] keeping the torque constant. The converter does this by incre-
asing its output voltage as the output frequency increases. If
Typical asynchronous motor data, for power ratings < 4.0 kW: the motor is operated above 50 Hz, the converter can no longer
Voltage 230V in delta configuration, 400V in Wye configuration, increase its output voltage (since it is only supplied with 400V).
50Hz. This results in under-magnetising of the motor, which results in
reduced torque (field weakening range). Two different motor
For power ratings > 5.5 kW: operating behaviours are defined in this manner:
Voltage 400V in delta configuration, 690V in Wye configuration, 1. Operation from 0 Hz to the nominal motor frequency (50Hz),
motor start using delta-Wye to reduce start-up current. also called sub-synchronous operation. Attributes: Constant tor-
que, motor output power increases with increasing output fre-
Note that on the basis of the relationship for equivalent-power quency.
motors, motors with a higher number of pole pairs (lower speed) 2. Operation above the nominal motor frequency, also called
have higher torque. Therefore, a 2-pole motor can only generate over-synchronous or field shunting range. Attributes: Constant
half the torque of a 4-pole motor with the same power rating. motor power output (up to approx. 100Hz), with 1/n falling tor-
que.
The following figures show the motor voltage curve, motor po- Under nominal load the nominal current specified for delta-
wer curve, and the torque curve with respect to the converter configuration is drawn. If the frequency is increased to 87 Hz,
output frequency. the converter is now able to increase the output voltage as well,
thereby maintaining the optimal magnetisation of the motor.
U[V] The motor current draw (under nominal load) remains constant
despite increased voltage, since the motor’s inductive resistance
also increases due to the higher frequency. Even though the mo-
tor can generate 1.73 times its rated power at the shaft at 87 Hz,
U/f breakpoint
it is not overloaded, since the motor current still does not exceed
the nominal current specified for a delta connection. Only the
line-to-line voltage is increased from 230V to 400V. This is not
a problem for a standard motor which was tested at 1500V to
2000V. With this “technique”, the motor for a fan which has to be
operated at 87 Hz can be sized one manufactured size lower. This
results in a space and cost savings for the motor. However, the
frequency converter must be sized so that it can provide the no-
50 f[Hz] minal motor current for delta switching..
Weak-field region
U[V]
50 87 f[Hz]
Weak-field region
Fig. 3: Torque and power output (at constant current over the
entire RPM range)
1,73 * PNenn
P
87 Hz-Technique MNenn 1/n
When a motor with a motor voltage of 230/400 V is used and M
the frequency converter is supplied with 400 volt, it is possible to PNenn
50 87 f[Hz]
Method:
The motor is connected in delta configuration (230V). The con- Weak-field region
verter is programmed with the following data: Figure 5: Torque and power output (at constant current over the
entire RPM range)
- Motor voltage = 400Volt (230V · √3 )
- Motor frequency = 87 Hz (50V · √3 )
36
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Due to the cubic relationship between speed and power output, 1,73 * P Nenn
P
it becomes apparent that a considerable savings in energy can M Nenn 1/n
be attained for fan applications in the partial load range. For the-
M
se applications, a frequency converter with a so-called „quadra- ~n 2
tic torque response curve“ is available. The frequency converter
does not increase its output voltage linearly, but rather quadrati-
~n 3
cally with the frequency. The motor is intentionally under-excited
and can therefore not maintain constant torque in the range of 0
to 50Hz. In this way, the cos J of the motor is kept relatively con-
stant even under low load (at low speeds). Therefore the motor is 50 f[Hz]
operated at its nominal efficiency even in the partial load range. (87)
In this way the motor power consumption
Weak-field region
~n 2 ⎛ n[min-1] ⎛3
P[kW] = ⎜ n ⎜ · PNenn[kW]
⎝ Nenn[min-1] ⎝
Weak-field region
Drive design examples: The following converter power rating can be calculated for con-
stant torque:
Example1:
A fan with the following specifications is selected for an appli- M·n 35,9Nm · 2150min-1
P = = = 8,1kW
9550 9550
cation:
⎛ n ⎛3 ⎛ 2150min-1 ⎛3
A standard 4-pole motor with the following specifications is P= ⎜ n ⎜ · PNenn = ⎜ -1 ⎜
· 11kW = 4,35kW
⎝ Nenn ⎝ ⎝ 2930min ⎝
selected: Size 160M-4, P=11kW, U=400V, l=21.0A, Nominal
speed=1460 min-1. Nominal torque = 72.0Nm. In this case it is easier to look at the required fan torque and
compare it to the nominal torque of the motor, since the torque
The motor must be operated at: can be maximally constant in the sub- synchronous range (for
converters with constant torque). It is therefore apparent that a
2150min-1 motor with a nominal torque of 35.9 Nm cannot drive a fan with
· 50Hz = 73,6Hz
1460min-1
a torque requirement of 45.3 Nm. In this case the motor and con-
verter must be one size larger.
Since the motor is operated in the oversynchronous range where
the power output remains constant, an 11kW motor with an Option 3: 87 Hz technique
11kW frequency converter is sufficiently large. As a check, the
torque available at 73.6 Hz can be calculated again: GA standard 4-pole, 230V motor with the following specifica-
tions is selected:
MMOT = 1460min · MNenn = 1460min · 72,0Nm = 48,9Nm
-1 -1
2150min-1 2150min-1
Size 132M-4, P=7.5kW, U=230V, I=25. 3A, nominal
speed=1455min-1, nominal torque=49.2Nm
But only 45.3 Nm are required.
At 87 Hz this motor has the following nominal ratings:
This shows that sizing according to the required fan power rating
is sufficient in the oversynchronous range, since the power out- P = 7,5kW · √3 = 13kW
put remains constant (up to approx. 100 Hz). U = 230V · √3 = 400V
I = 25,3A
n = 1455-1 · √3 = 2520min-1
Option 2, sub-synchronous operation
2150min-1
· 50Hz = 36,7Hz 24,0A
2930min-1 M = · 49,2Nm = 46,6Nm
25,3A
24,0A
P = · 13kW = 12,3kW
25,3A
Since the motor is operated in the sub-synchronous range in
which the power output is dependant on the output frequency,
one has to calculate the power generated by the motor at 36.7
Hz.
38
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Conclusion
Energy savings
Control
With Danfoss frequency converters, you quickly get energy costs Fan and Control Curve Data Fan
Pa
300
250
200
Butterfly Valve Control 150
100
50
0
n = konstant 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
10.00
kW
6.00
4.00
n = konstant
2.00
0.00
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
Flow (%)
Variable flow-rate system with speed control
Amortisation
Annual Energy Consumption Frequency Converter
4,000
3,500
3,000
15,000
2,500 14,000
2,000 13,000
1,500
Payback (€)
1,000
12,000
500 11,000
0 10,000
-500
9,000
kWh
-1,000
-1,500 8,000
-2,000 7,000
-2,500
6,000
0 1 2 3 4 5
Year 5,000
4,000
3,000
2,000
1,000
Duty Cycle 0
30 10 20 30 40 50 60 70 80 90 100
28
26
24
22
20
18
Time (%)
16
14
12
10
8
6
4
2
0
0 10 20 30 40 50 60 70 80 90 100
flow rate (%)
40
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Design pressure: 550.00 Pa Flux (%) Time (%) Time (Hrs.) kW-h/Year kW-h/Year
Flow rate at point B: 72,000 m3/h 100 10 300 5,599 5,573
Efficiency at point B: 65 % 90 30 900 15,976 13,596
Pressure reduction: 200.00 Pa 80 20 600 10,108 7,338
AC motor data 70 10 300 4,773 2,956
Motor power rating: 18.5 kW 60 10 300 4,465 2,367
Efficiency: 90.5 % 50 10 300 4,102 1,883
FC data: 40 5 150 1,827 742
FC power rating: 18.5 kW 30 5 150 1,541 577
FC efficiency: 96.0 % 20 0 0 0 0
FC costs: € 2,100 10 0 0 0 0
Electricity:
Cost per kWh: € 0.100 Sum 3,000 48,390 35,033
Utility incentive: 0 €/kW
kWh savings 13,357
Yearly cost savings € 1,336
Energy savings
* Calculations are based on available data, Danfoss does not assume any responsibility for the accuracy of the provided data or the results reported above.
Notes:
42
FROM REAL-WORLD APPLICATIONS, FOR THE REAL WORLD
Index
The drive specialist frequency converters are customised from Danfoss Drives support our cu-
Danfoss Drives is one of the leading to the respective customer require- stomers with comprehensive specia-
manufacturers of drive technology in ments and delivered fully assembled. lised knowledge about the respective
the world. Back in 1968 Danfoss pre- In this way we ensure that your VLT® application. Comprehensive consul-
sented the world’s first mass-produ- is always delivered to you with the ting and fast service add up to the
ced frequency converter for three- most current technology. optimum solution with the highest
phase AC motors and has specialised degree of reliability and availability. A
in solutions for drive applications Trust the professionals - worldwi- job is not finished until you, the cu-
ever since. Today VLT® is synonymous de stomer, are satisfied with the drive
with reliable technology, innovation In order to ensure the quality of our solution.
and know-how in drive solutions for a products at all times, Danfoss Drives
wide range of industries. oversees and monitors the develop-
ment of each major element in the
Innovative and intelligent frequen- products. The group has its own re-
cy converters search and software development
From its headquarters in Graasten, departments as well as modern pro-
Denmark, Danfoss Drives employs duction facilities for hardware, power
2000 staff in over 100 countries wor- modules, circuit boards and accesso-
king on Danfoss drive solutions in de- ries. VLT® frequency converters are
velopment, manufacturing, consul- deployed in a wide range of applica-
ting, sales and service. The modular tions all over the world. The experts
Danfoss cannot accept any liability for errors or mistakes in catalogues, brochures or other printed documents. Danfoss reserves the right to make modifications to its products without prior notification, including modifications to products
for which orders have already been placed, insofar as said modifications do not alter any technical specifications already agreed upon. All trademarks contained in this publication are the property of the respective firms. Danfoss and the
Danfoss logo are trademarks of Danfoss A/S. All rights reserved