Abstract. AC withstand voltage test is the most severe, the most direct and the most effective test
method of judging the XLPE Power Cable insulation Conditioning, It is of decisive significance in
determining weather the Power Cable is measured up. Traditional test transformer is bulky, it
requires high-capacity of power supply when it is used in AC withstand voltage test of high-capacity
Power Cable. This paper adopted the Frequency Conversion Series Resonance Technology in 220kV
Cable Withstand Voltage test program and accomplished the test successfully, Greatly reduced the
capacity of the power test equipment, it also helps to promote the test quality and the work efficiency,
which proved the feasibility and effectiveness in the long-distance high-voltage XLPE cables grade
AC voltage test with the Frequency Conversion Series Resonance Technology.
Introduction
With the continuous development of China's power industry, more and more how high-voltage,
large-capacity cross-linked polyethylene cable (hereinafter referred to as: XLPE cable) is widely
used, particularly in urban power grids, with XLPE cables replace overhead lines It has become a
trend. The cable is factory tested, from the transport, storage, construction, installation accessory,
during which it is possible to produce mechanical damage, or flawed installation workmanship [1],
Therefore, the completion of the field voltage cable lines acceptance test before operation is
necessary.
Practice has proved that AC voltage test can directly reflect the insulation condition of the cable,
the cable insulation strength of the most direct and most effective test methods for identification.
Cross-linking cables and accessories for AC voltage withstand test, which can effectively prevent the
occurrence of loss fault put into operation to ensure reliable XLPE cables commissioning and safe
operation [2]. This article series resonant frequency technology field AC voltage withstand test of a
long cable of 220kV Board discussed in detail. The PUC will 220kV high-voltage ground
engineering four back high voltage cable lines for transformation, cable segment circuit single-phase
total length of 7.97km, for so long 220kV cable AC voltage test site in the country are rare. The test
has an important reference value.
Figure 2. 220kV line1 pressure graph. Figure 3. Line2 220kV line2 pressure graph.
Figure 4. 220kV line3 pressure graph. Figure 5. Line2 220kV line4 pressure graph.
Table 1. The main insulation resonant frequency voltage withstand test data sheets.
Temper
Line Humidity Insulation Dielectric Phase
ature(
Number (℅) resistance(GΩ) strength(216kV/h) sequence
℃)
214.0kV,
A 108 A normal
success
220kV 214.2kV, normal
45 3 B 118 B
line1 success
215.0kV, normal
C 115 C
success
186.6 kV, normal
A 121 A
failure
220kV 169.4 kV, normal
40 7 B 115 B
line2 failure
137.9 kV, normal
C 121 C
failure
211.1kV, normal
A 108 A
success
220kV 211.1kV, normal
40 2 B 128 B
line3 success
211.2kV, normal
C 131 C
success
211.2kV, normal
A 121 A
success
220kV 211.2kV, normal
40 3 B 117 B
line4 success
211.1kV, normal
C 121 C
success
Conclusion
(1)Analysis and comparison of the main Advantages and disadvantages several AC voltage test in
XLPE cable insulation testing aspects, drawn up on the basis of technical tests with a series resonant
frequency mode FIELD TEST optimal results.
(2)Series resonant frequency means smaller power capacity required in the current AC voltage
XLPE cable test, the required power does not exceed the maximum current 150A, very suitable for
use in electric power engineering.
(3)Experimental results show that the new 220kV cable to ensure safe operation, the high-pressure
pressure test before production is necessary and effective, compared with the phase voltage load test
to better reflect the quality of the cable, the test well to avoid commissioning after the loss occurred.
(4)Experiments show that the use of series resonant frequency technology to 220 kV XLPE cable
for live AC voltage test is feasible, effective, and can avoid the adverse effects of the problem caused
by the DC voltage to the cable and DC voltage test of the effectiveness of detection, Moreover, the
frequency resonance test method in power system voltage test will be fully applied.
Acknowledgement
This research was financially supported by the State Grid Corporation of science and technology
projects (WNZ141-0013: Research on the Key Technology of Power Transmission Simulation Based
on Physical Model and Virtual Reality).
References
[1] Su Qun, Wan Junbiao. AC Voltage On-site Test of 110kV XLPE Power Cable [J]. Jiangxi Electric
Power, 2004, 28(1): 21-22.
[2] Yao Xiang, Chen Lin, Li Haisheng. On site Variable Frequency Resonance Test for HV XLPE
Power Cable and Accessories [J] High Voltage Engineering, 2005, 31(11): 61-62.
[3] Bai Yin-Hao, Wang Chao-Gang, Liu Bo, Li Xiao-Gang, Dong Li-jie. Field AC Withstand Voltage
Test and Research on 220kV Long-distance Cable [J]. Central China Electric Power, 2012, 25(1):
36-41.
[4] Fan Diming, Lv Jingshun, Wen Dingjun, et al. Interpretation of Regulations of Voltages in Long-
Duration Induced AC Voltage Withstand Test with Partial Discharge Test of Transformer in 750kV
Hand-over Procedures [J] Electrical Engineering, 2015(02): 99-105.
[5] GB/Z 18890.1~18890.36-2002 Power Cables with Cross-linked Polyethylene Insulation and
Their Accessories for Rated Voltage of 220kV(Um=252kV)[S], 2002.
[6] Xiao Lihua. AC Voltage On-site Test of 220kV XLPE Power Cable [J] Electrical Testing,
2000(02)
[7] GB/Z 50150-2006 Standard for Hand-over Test of Electric Equipment. Electric Equipment
Installation Engineering [S], 2006.