Beruflich Dokumente
Kultur Dokumente
Introduction
Use of PLCC in modern electrical power system is mainly for telemetry and telecontrol. Tele means remote.
Telemetry refers to science of measurement from remote location.
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 1/17
3/29/2018 Power Line Carrier Communication (PLCC)
Power Line Carrier Communication – PLCC (photo: Zanith Transformers & Swithgears Pvt. Ltd)
Contents
Introduction
Major goal/Application of PLCC
Main Components of PLCC:
Coupling Capacitor
Line trap Unit
Transmitters and Receivers
Hybrids and Filters
Line Tuners
Master Oscillator and Amplifiers
Protection and earthing of coupling equipment
Advantages of Digital PLCC over Analog ones
Typical signal to noise ratio calculation by considering a line of 295 kilometers
SNR (Signal-to-Noise Ratio) Calculation
Different types of data transmission system can be used depending upon the network requirement and
conditions.
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 2/17
3/29/2018 Power Line Carrier Communication (PLCC)
For large power system power line carrier communication is used for data transmission as well as protection
of transmission lines. Carrier current has a frequency range of 30 to 200 kHz in USA and 80 to 500 kHz in
UK.
Each end of transmission line is provided with identical PLCC equipment consisting of equipment:
Distance protection relay in relay panel at one end of the transmission linegets the input from CT and CVT in
line. The output of relay goes to modem of PLCC.
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 3/17
3/29/2018 Power Line Carrier Communication (PLCC)
PLCC scheme
The output of PLCC goes to coupling capacitor and then to transmission line and travels to another end
where it is received through coupling capacitor and inputted to relay and control panel at that end.
Go to Content ↑
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 4/17
3/29/2018 Power Line Carrier Communication (PLCC)
Simplex
Duplex
Multiplex
Time division Multiplex
Many factors will affect the reliability of a power line carrier (PLC) channel.
The goal is to get a signal level to the remote terminal that is above the sensitivity of the receiver,
and with a signal-to-noise ratio (SNR) well above the minimum, so that the receiver can make a
correct decision based on the information transmitted.
If both of these requirements are met then the PLC channel will be reliable.
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 5/17
3/29/2018 Power Line Carrier Communication (PLCC)
The above list may not be all inclusive, but these are the major factors involved in the success or failure of a
PLC channel.
Go to Content ↑
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 6/17
3/29/2018 Power Line Carrier Communication (PLCC)
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 7/17
3/29/2018 Power Line Carrier Communication (PLCC)
Coupling capacitor connects the carrier equipment to the transmission line. The coupling capacitor’s
capacitance is of such a value that it offers low impedance to carrier frequency (1/ωC) but high impedance to
power frequency (50 Hz).
For example 2000pF capacitor offers 1.5MΩ to 50Hz but 150Ω to 500kHz.
Thus coupling capacitor allows carrier frequency signal to enter the carrier equipment.
To decrease the impedance further and make the circuit purely resistive so that there is no reactive power in
the circuit, low impedance is connected in series with coupling capacitor to form resonance at carrier
frequency.
Go to Content ↑
The line trap is usually a form of a parallel resonant circuit which is tuned to the carrier energy
frequency.
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 8/17
3/29/2018 Power Line Carrier Communication (PLCC)
A parallel resonant circuit has high impedance at its tuned frequency, and it then causes most of the carrier
energy to flow toward the remote line terminal. The coil of the line trap provides a low impedance path for
the flow of the power frequency energy.
Since the power flow is rather large at times, the coil used in a line trap must be large in terms of physical
size.
Hence a line trap unit/Wave trap is inserted between busbar and connection of coupling capacitor to the line.
It is a parallel tuned circuit comprising of inductance (L) and capacitance (C). It has low impedance (less
than 0.1?) for power frequency (50 Hz) and high impedance to carrier frequency.
This unit prevents the high frequency carrier signal from entering the neighboring line.
Go to Content ↑
This then means there is a large distance between the equipment and the tuner, and the connection between
the two is made using a coaxial cable.
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 9/17
3/29/2018 Power Line Carrier Communication (PLCC)
The coaxial cable provides shielding so that noise cannot get into the cable and cause interference. The
coaxial cable is connected to the line tuner which must be mounted at the base of the coupling capacitor.
If there is more than one transmitter involved per terminal the signal must go through isolation circuits,
typically hybrids, before connection to the line tuner.
Go to Content ↑
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 10/17
3/29/2018 Power Line Carrier Communication (PLCC)
The hybrid circuits can, of course, cause large losses in the carrier path and must be used appropriately.
High/low-pass and band-pass networks may also be used, in some applications, to isolate carrier equipment
from each other.
5. Line Tuners
The purpose of the line tuner in conjunction with the coupling capacitor is to provide low impedance
path for the carrier energy to the transmission line and a high impedance path to the power
frequency energy.
The line tuner/coupling capacitor combination provides a low impedance path to the power line by forming a
series resonant circuit tuned to the carrier frequency.
On the other hand, the capacitance of the coupling capacitor is high impedance to the power frequency
energy. Even though the coupling capacitor has high impedance at power frequencies, there must be a path
to ground in order that the capacitor may do its job. This function is provided by the drain coil, which is in the
base of the coupling capacitor. The drain coil is designed to be low impedance at the power frequency and
because of its inductance it will have high impedance to the carrier frequency.
Thus the combination of the line tuner, coupling capacitor, and the drain coil provide the necessary tools for
coupling the carrier energy to the transmission line and blocking the power frequency energy. One last
function of the line tuner is to provide matching of impedance between the carrier coaxial cable, usually 50 to
75 ohms, and the power line which will have an impedance of 150 to 500 ohms.
Go to Content ↑
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 11/17
3/29/2018 Power Line Carrier Communication (PLCC)
Oscillator can be crystal oscillator with which operation for a particular bandwidth can be achieved. The
output voltage of a oscillator is held constant by voltage stabilizer.
The output of oscillator is fed to amplifier so that loses in transmission can be compensated. Losses
occurring in carrier current is termed as attenuation of carrier signal.
They are mainly: Losses in coupling equipment which are constant losses for a given carrier frequency
bandwidth.
Line losses vary with length line, size of line, weather condition etc…These losses for underground line is
more than overhead line.
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 12/17
3/29/2018 Power Line Carrier Communication (PLCC)
Frequency spacing is a process using different carrier frequency in two adjacent transmission lines. Wave
trap/Line trap help in accomplishing this.
Go to Content ↑
They produce stress on coupling equipment and line trap units. Non linier resistor in series with
protective gap is connected across the line trap unit and inductor of coupling unit.
Coupling unit and PLCC equipment are earthed through a separate and dedicated system, so that ground
potential rise of station earthing system does not affect the reference voltage level/Power supply common
ground of the PLCC equipment.
In this regard that is earthing of PLCC and other communication/Instrumentation/Electronic equipment please
refer to NEC Article 645 for data centers (IT equipment.)
Power Line Carrier (PLC) Signal propagation along high voltage lines depends entirely on the construction
of transmission lines, mainly on the configuration and characteristics of all conductors and on the ground
resistance optimum coupling allows to make the best use of a given transmission line.
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 14/17
3/29/2018 Power Line Carrier Communication (PLCC)
Transposition may introduce additional attenuation which can generally not be predicted with simple rules.
Most transposition schemes result in high attenuation poles at certain frequencies such frequencies cannot
be used for PLC communications.
Forbidden Frequency Ranges may be determined as explained in CIGRE Paper 35-02, Senn/Morf –
Optimum PLC Arrangement on Transposed Single Circuit power Lines – (August, 1984)
In critical cases, however, computer calculation may be necessary, for which the following data is
required:
Go to Content ↑
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 15/17
3/29/2018 Power Line Carrier Communication (PLCC)
Where:
http://electrical-engineering-portal.com/power-line-carrier-communication-plcc 16/17
3/29/2018 Power Line Carrier Communication (PLCC)
a1 = 0.029 dB/Km
Coupling Loss = Loss in Coupling equipment + tapping loss + paralleling loss + by pass losses in
case of bypasses + cable loss.
= 2 + 2.6 + 1 + 0 + 0.5
= 6.1 dB
Go to Content ↑