Beruflich Dokumente
Kultur Dokumente
Pa Agung
Pa Agung
Time Pv Pv
0 40.00 40
3 41.00 40.6
6 42.00 41.9
9 43.00 43
12 44.00 43.7
15 44.50 44.5
18 45.10 45.2
21 45.50 45.7
24 46.10 46.1
27 46.30 46.3
30 46.50 46.6
33 46.80 46.8
36 46.90 46.8
39 46.90 46.9
42 46.80 46.7
45 46.70 46.6
48 46.60 46.7
51 46.60 46.6
54 46.70 46.8
57 46.90 46.9
GRAFIK DATA
47
46
45
44
Pv
43
42
41
40
39
0 3 6 9 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60
Time(s)
X = 6.8
Y=9
K
x25 =5.538461
x75 = 17.571428
Tg = 10.949997
Tu = 2.384861
HASIL PERHITUNGAN NILAI PENGENDALI
ziegler-nichols
Pengendali kp Tn (Detik) Tv (Detik)
PI 5.468918971 7.94158713 off
PID 7.291891962 4.769722 1.1924305
metode cohen coon
Pengendali kp Tn (Detik) Tv (Detik)
PI 5.579206602 5.47353623 off
PID 8.43296507 5.38801114 0.834188968
kriteria minimum ITAE
Pengendali Operasi kp Tn (Detik) Tv (Detik)
PI servo 3.132944615 11.0153873 off
PI regulator 5.039962115 5.76271938 off
PID servo 4.701142418 14.3327560 0.818487976
PID regulator 7.605984356 4.22262119 0.915583172
HASIL SETTING NILAI PENGENDALI PADA PRAKTIKUM
Ziegler-nichols
Pengendali kp Tn (Detik) Tv (Detik)
PI 5.469 7.938 off
PID 7.281 4.781 1.195
metode cohen coon
Pengendali kp Tn (Detik) Tv (Detik)
PI 5.584 5.469 off
PID 8.438 5.375 dibawah 0.9 data tidak dapat diuji
kriteria minimum ITAE
Pengendali Operasi kp Tn (Detik) Tv (Detik)
PI servo 3.125 11 off
PI regulator 5.031 5.75 off
PID servo dibawah 0.9 data tidak dapat diuji
PID regulator 7.594 4.219 1
TABEL DATA PRAKTIKUM METODE OPERASI (servo dan regulator)
Ziegler- Ziegler- Choen-
Ziegler- Ziegler- Nchols Nichols Coon Choen-
Nichols PI Nichols PI PID PID PI Coon PI ITAE PI ITAE PI ITAE PID
detik (servo) (regulator) (servo) (regulator) (servo) (regulator) (servo) (regulator) (regulator)
0 25 50 25 50 25 50 25 50 50
3 30.5 53.3 29 52.1 29.3 53.2 29.6 53.4 52.1
6 36.5 52.4 37.6 51.2 36.6 52.3 37 52.6 51
9 41.2 51.2 43.3 50.6 42.5 50.6 42.9 51 50.4
12 45.2 50.8 48.2 50 48 50.1 47.8 50.3 49.9
15 48.5 50.5 52 49.9 51.7 50.2 52.3 50.3 49.9
18 51.2 50.3 54.8 50 54.7 50.1 54.5 50.2 50
21 53.4 50.3 53.8 49.9 54.4 49.9 54.9 50.1 50
24 53.6 50.1 52 50 52.2 49.9 54.6 50.1 50
27 52.7 50.1 50.6 50 50.9 50.1 53.8 50.1 50
30 51.9 50.1 50 50 50.3 50 53.3 50 50
33 51.3 50 49.9 50 50.2 50.1 52.5 50.1 50
36 50.9 50 49.7 50 50 50 52 50 50
39 50.6 50 49.8 50 50 50 51.5 50 50
42 50.4 50 50 50 50 50 51 50 50
45 50.3 50 50 50 49.9 50 50.8 50 50
48 50.1 50 50.1 50 50 50 50.5 50 50
51 50.1 50 50 50 49.9 50 50.4 50 50
54 50.1 50 49.9 50 49.9 50 50.2 50 50
57 50 50 50 50 49.9 50 50.2 50 50
60 50.1 50 50 50 50 50 50 50 50
63 50 50 49.9 50.1
66 50.1 50 50 49.9
69 50 50 49.9 50
72 50.1 49.9 50 49.9
75 50 49.9 49.9 50
78 50.1 50.1 50 49.9
81 50 50 49.9 49.9
84 50 50 50 50
87 50 50 49.9 49.9
90 50 50.1 50 49.9
GRAFIK DATA PRAKTIKUM
48
43
PV
38
33
28
23
0 10 20 30 40 50 60 70 80 90 100
Time
53
52.5
52
PV
51.5
51
50.5
50
49.5
0 10 20 30 40 50 60 70 80 90 100
Time
Metode Ziegler-Nichols (PID) Servo
60
55
50
45
PV
40
35
30
25
20
0 10 20 30 40 50 60 70 80 90 100
Time
52
51.5
PV
51
50.5
50
49.5
0 10 20 30 40 50 60 70 80 90 100
Time
Metode Cohen-Coon (PI) Servo
60
55
50
45
PV
40
35
30
25
20
0 10 20 30 40 50 60 70 80 90 100
Time
53
52.5
52
PV
51.5
51
50.5
50
49.5
0 10 20 30 40 Time50 60 70 80 90 100
Kriteria Minmum ITAE (PI) Servo
60
55
50
45
PV
40
35
30
25
20
0 10 20 30 40 50 60 70 80 90 100
Time
53.5
53
52.5
52
PV
51.5
51
50.5
50
49.5
0 10 20 30 40 50 60 70 80 90 100
Time
Kriteria Minimum ITAE (PID) Regulator
52.5
52
51.5
PV
51
50.5
50
49.5
0 10 20 30 40 50 60 70 80 90 100
Time
LAPORAN TEKNIK PENGATURAN
Tuning Pengendali PI – PID
pada Suatu Sistem Pengendalian Tekanan Tangki
Menggunakan Metode Kurva Reakssi Proses
Oleh :