Product Specifications PSS 2A-1Z3 F

Model PCMV Configurator


for Use with the I/A Series®
Models IMV25 and IMV30 Multivariable Transmitters

MEASURED AND
TRANSMITTED OUTPUTS
ABSOLUTE PRESSURE (AP) - MEASURED
DIFFERENTIAL PRESSURE (DP) - MEASURED
ELECTRONICS TEMPERATURE - MEASURED
FROM INTERNAL SENSOR
SENSOR TEMPERATURE - MEASURED
FROM INTERNAL SENSOR
PROCESS TEMPERATURE - MEASURED
FROM EXTERNAL RTD
PROCESS DENSITY - CALCULATED (IMV30)
PROCESS FLOW RATE - CALCULATED (IMV30)
mA OUTPUT (IF SO CONFIGURED)

MODEL PCMV CONFIGURATOR


SOFTWARE ON CD-ROM
PC-BASED CONFIGURATOR

The Model PCMV Configurator is a Windows-based software package for use with the I/A Series IMV25 and
IMV30 Multivariable Transmitters. It displays measurements and has full calibration and configuration capability.
It also utilizes a fluid properties table and primary device parameters to calculate flow rate and process density
with the IMV30. A modem for use with either HART or FoxCom protocols is required for communication with the
transmitter.

FEATURES
• Windows-based PC software. • For use with the IMV30; it
• HART or FoxCom communication protocols. – Includes extensive fluid properties data table
• Provides all configuration and calibration of over 275 liquids, gases, and vapors.
functions, including upload and download, of – Supports multiple industry recognized flow
database parameters. equations for liquid, gas, and vapors for the
• Displays measurements of: IMV30 transmitter.
– Absolute and differential pressures (AP & DP). – Provides numerous menu-driven primary
device, flow standard, and parameter screens
– Sensor/electronics/process temperatures.
for selection and configuration.
– Process density for the IMV30.
– Contains equations to simulate and test the
– Mass and volume flow rate in EGU at density and flow rate calculations of the IMV30
flowing/standard conditions for the IMV30. transmitter.
PSS 2A-1Z3 F
Page 2

GENERAL DESCRIPTION CONFIGURABLE PARAMETERS


The Model PCMV Configurator is a software package Table 2 lists the configurable parameters when the
providing remote bidirectional communication with Model PCMV is used with the IMV25 and IMV30
Foxboro Models IMV25 and IMV30 Multivariable transmitters.
Transmitters with HART and FoxCom communication
protocols. The Configurator reads a file of current Table 1. Measurements with IMV25 and IMV30
transmitter configuration and calibration information,
With With
and allows user input of specific data unique to a new Measurement Designation IMV25 (a) IMV30 (b)
desired application. When used with the IMV30, the
mA Output M0 Yes Yes
input data includes the desired DP, AP, and process
Differential M1 Yes Yes
temperature ranges over which the density and flow
Pressure (DP)
rate equations are to apply. Features of the
Absolute M2 Yes Yes
configurator include: Pressure (AP)
• Capability to read all measurements Sensor M3 Yes Yes
• Ability to set up the transmitter for any pertinent Temperature
application Electronics M4 Yes Yes
• Capability to configure flow rate data for the Temperature
IMV30 Process M5 Yes Yes
• Test modes to read predicted flow rate and Temperature
process density for the IMV30 (External RTD)
• Accurate reranging without recalibration Flow Rate M6 No Yes
• Full screen device database display (Calculated)
• Enhanced device diagnostic capability Process Density M7 No Yes
(Calculated)
• Communication that does not affect output when
(a) Refer to PSS 2A-1C15 B for IMV25 transmitter specifications.
reading measurements
(b) Refer to PSS 2A-1C15 A for IMV30 transmitter specifications.
• User-configurable measurement data graphical
trend display
• Capability to reconfigure, copy, and clone
databases Table 2. IMV25 and IMV30 Configurable Parameters
• Capability to upload, download, and print out Parameter (a) Configuration
device databases Mode 4 to 20 mA or digital
• Unlimited device database storage on diskette or Descriptors Tag data and other general
hard disk device and site data
The software package utilizes an external modem I/A Series System Primary, secondary, tertiary,
that allows operation with a Windows-compatible PC Display or fourth (HART only)
with a serial communication port. Communication measurement/calculation
with the transmitter uses proven frequency shift mA Measurement Forward or reverse direction
keying (FSK) techniques that do not affect the device and failsafe
output signal. Differential Pressure Linear or square root, EGU
MINIMUM SYSTEM REQUIREMENTS (DP) for linear, % for square root,
LRV, URV, and damping
• 400 MHz Pentium with 128 MB RAM
Absolute Pressure Display AP or GP, EGU, LRV,
(256 MB RAM for Windows 2000 Professional)
(AP) URV, and damping
• 4X CD-ROM drive (8X recommended)
• Microsoft Mouse or compatible pointing device External Temperature On or off, units, LRV and URV
• Windows XP (SP2), Windows ME, Windows NT (RTD)
Workstation 4.0 (SP6), or Windows 2000 Flow On or off, units, LRV, URV,
Professional (SP4) (with IMV30 only) and flow cutoff
• 20 MB of available hard disk space Process Density Units, LRV and URV
• Internet Explorer 6.0 or greater (with IMV30 only)
Enable Passwords No password, configuration
MEASUREMENTS only locked, or calibration and
Once the configurator is connected to the transmitter, configuration locked
the user can display the Scan Data Screen. Table 1 Reset Database Keep or clear
lists the measurements that can be displayed when (a) Refer to applicable transmitter MI for details relating to HART
the PCMV is used with the IMV25 or IMV30. or Foxboro configuration.
PSS 2A-1Z3 F
Page 3

PROCESS FLUIDS SUPPORTED IMV30 Flow Rate Equations(2)


A physical properties database includes detailed The following industry standards may be selected:
information to support the selection from a list of over
• ISO-5167
275 fluids, including many common liquids, gases,
• ANSI-2530, AGA-3, API-Ch.14
and vapors. Both superheated steam and saturated
• ASME 3M
steam are supported, as is natural gas. The ability to
• ANSI 2530, AGA-3, Fluid Meters, and Spink
enter density/temperature data is also provided when
[ANSI/API 2530 (to 1995), AGA-3 (1935-1995),
configuring for fluids not listed in the database.
Spink (1935 to date)]
IMV25 TRANSMITTER CONFIGURATION WITH
MODEL PCMV IMV30 Primary Flow Devices Supported
• Orifice Plates
The IMV25 provides measurement of DP, AP, and – Concentric with Flange Taps, Corner Taps,
process temperature for configuration. Also see D and D/2 Taps, Foxboro Model IFOA(3) with
Table 2. Sensor and electronics temperature are also Square Edge or Quadrant Edge, Honed
measured. The configurable measurements may be Orifice Run with Flange or Corner Taps,
transmitted to a measurement integration workstation Quadrant Orifice, or Conic Orifice
(host computer) for a variety of applications, including – Segmental with Flange Tap at Top, or Vena
flow rate and liquid level calculations. For direct Contracta Tap at Top
calculation of flow rate, the Model IMV30 is – Eccentric with Flange Tap at Top, Flange Tap
recommended. See sections that follow. at Side, Vena Contracta Tap at Top, and Vena
IMV30 TRANSMITTER CONFIGURATION WITH Contracta Tap at Side
MODEL PCMV • Compact Orifice
• Flow Nozzle
The IMV30 provides measurement of DP, AP, and – ASME Long Radius (with or without Diffuser)
process temperature for configuration, and directly – ASME Throat Tap (with or without Diffuser)
calculates flow and density. In addition to the – ISO (ISA) (1934)
configurable parameters, the PCMV provides for a – Venturi-Nozzle (ISA Inlet-Diffuser Exit)
selection of flow rate equations and primary flow • Venturi Meter
devices. – Machined, Cast, or Welded Sheet Inlets
The user can select the units of measure, the industry – 7 or 15 Degree Exit Cones
standard equation, the fluid and fluid state, the type of • Multiport Averaging Pitot (MAP)
primary flow element, the material of primary element • V-Cone (Mfd. by McCrometer)
and adjacent piping, and the normal pressure and
temperature conditions. DEVICE AND PARAMETER SELECTION SCREENS
The output of the configurator is a data set including Refer to Figures 1, 2, and 3 for typical screens.
coefficients, which the PCMV Configurator can save
and download to an IMV30 Multivariable Transmitter
for the accurate determination of flow rate.
The PCMV configurator also provides full
configuration capability to upload and download all
configuration parameters used by the IMV30
Multivariable Transmitter.
Density and flow equations are based on Miller’s Flow
Measurement Engineering Handbook(1). Refer to the
sections that follow for a list of flow rate equations and
primary flow devices supported by the Model PCMV
Configurator.

(1) Density and Flow equations used for the calculated outputs, and Flow Terminology are from Flow Measurement Engineering Handbook,
by R. W. Miller, available from Invensys Foxboro by specifying Part Number B0150YW.
(2) ISO = International Standards Organization; ANSI = American National Standards Institute; ASME = American Society of Mechanical
Engineers; API = American Petroleum Institute; AGA = American Gas Association.
(3) IFOA = Integral Flow Orifice Assembly.
PSS 2A-1Z3 F
Page 4

DEVICE AND PARAMETER SELECTION SCREENS (Cont.)

Figure 1. Typical Device Configuration Screen


for Differential Pressure (IMV25 shown)

Figure 2. Typical Device Configuration Screen for Flow (IMV30 only)


PSS 2A-1Z3 F
Page 5

DEVICE AND PARAMETER SELECTION SCREENS (Cont.)

Figure 3. Orifice Plate Type Selection Screen (IMV30 only)

FUNCTIONAL BLOCK DIAGRAMS (SEE FIGURES 4 AND 5)


CONNECTION WITH POWER SUPPLY OPTION CONNECTION WITHOUT POWER SUPPLY OPTION
120 V ac TO 24 V dc BNC CABLE 250-OHM
TRANSFORMER RISISTER

OPTIONAL + MULTIVARIABLE USER + +MULTIVARIABLE


POWER SUPPLY TRANSMITTER POWER
SUPPLY TRANSMITTER
WITH 250-OHM
SERIES RESISTOR

POWER
CONNECTOR RS-232 RS-232
FoxCom CABLE PC-BASED FoxCom CABLE PC-BASED
MODEM CONFIGURATOR MODEM CONFIGURATOR
SERIAL SERIAL
PORT PORT
PCMV SOFTWARE PACKAGE (CD-ROM)

Figure 4. Functional Block Diagram with FoxCom Modem, with and without Optional Power Supply

CONNECTION WITH POWER SUPPLY OPTION CONNECTION WITHOUT POWER SUPPLY OPTION
120 V ac TO 24 V dc BNC CABLE 250-OHM
TRANSFORMER RISISTER

OPTIONAL +MULTIVARIABLE USER + +MULTIVARIABLE


POWER SUPPLY POWER
TRANSMITTER SUPPLY TRANSMITTER
WITH 250-OHM
SERIES RESISTOR

POWER
CONNECTOR
HART PC-BASED HART PC-BASED
COAX
MODEM CONFIGURATOR MODEM CONFIGURATOR
CONNECTOR
NOT USED RS-232 CONNECTOR PCMV SOFTWARE
RS-232 CONNECTOR PCMV SOFTWARE
TO SERIAL PORT PACKAGE (CD-ROM) TO SERIAL PORT PACKAGE (CD-ROM)

Figure 5. Functional Block Diagram with HART Modem, with and without Optional Power Supply
PSS 2A-1Z3 F
Page 6

OPTIONAL SELECTIONS

Modems - FoxCom or HART Selections The HART modem plugs directly into the PC (a
FoxCom and HART modems are used with a standard RS-232 cable can be used, if preferred).
Windows-compatible PC that has a serial The modem weighs approximately 0.04 kg (0.1 lb).
communications port. Communications with Its dimensions are approximately 67 x 34 x 16 mm
Intelligent Devices use proven frequency shift keying (2.6 x 1.3 x 0.6 in). Specify Modem Code T for a
(FSK) techniques that do not affect the device output HART modem.
signal.
Power Supply Option
The FoxCom modem is provided with a 0.3 or 1.5 m The power supply is used to power the transmitter
(1 or 5 ft) cable assembly for connection to a PC- during calibration and configuration if a separate
based configurator. The modem weighs transmitter power source is not available. It is not
approximately 0.1 kg (0.25 lb), and can be attached required to power the modem because modem
to the PC or any convenient flat, hard surface using power is obtained through the serial port connection
the fabric fasteners with loops and hooks provided to the PC. The supply comprises a 120 V ac to 24 V
with the modem kit. Specify Modem Code D for a dc converter with an integral cable that connects to
FoxCom modem. the 24 V dc supply unit. A cable assembly
interconnecting the power supply and field device is
also provided. Specify Optional Selection -C.

MODEL CODE
Description Model
PCMV Configurator for use with IMV25 and IMV30 Multivariable Transmitters (a) PCMV

Software Language
English -AE

Modem Selection
FoxCom Modem D
HART Modem T
Both FoxCom and HART Modems B
None - User Supplied N

Optional Selection
Power Supply (b) -C

Example: PCMV-AED-C
(a) The PCMV Configurator software package is supplied on CD.
(b) Power supply for transmitter is 120 V ac, 60 Hz-to-24 V dc converter; for use during calibration and configuration.
PSS 2A-1Z3 F
Page 7
PSS 2A-1Z3 F
Page 8

ORDERING INSTRUCTIONS

1. Model Number
2. Tag and Application

REFERENCE DOCUMENTS

PSS 2A-1C15 A IMV30 Multivariable Transmitter


PSS 2A-1C15 B IMV25 Multivariable Transmitter

OTHER M&I PRODUCTS

Invensys Foxboro provides a broad range of measurement


and instrument products, including solutions for pressure,
flow, analytical, positioners, temperature, controlling and
recording. For a listing of these offerings, visit the Invensys
Foxboro web site at:

www.foxboro.com/instrumentation

33 Commercial Street Invensys, Foxboro, FoxCom, and I/A Series are trademarks of Invensys plc, its subsidiaries, and
Foxboro, MA 02035-2099 affiliates.
United States of America All other brand names may be trademarks of their respective owners.