Sie sind auf Seite 1von 1

Project DEDURUOYA WATER SUPPLY PROJECT

Structure FLASH MIXER,FLOCCULATION TANK & LAMELLA CLARIFIER


Document Title DESIGN OF WALL FOOTING FOR FLOCCULATOR WALLS

DESIGN OF WALL FOOTING

Conside the critical strip along grid 6


Size of Footing = 15.6 x 1.80 x 0.45
Size of wall = 13.8 x 0.3

FOOTING REACTION (SAP 2000 OUTPUT)


Footing reactions were obtained at nodes of the strip and summed up to obtain the total footing reaction.

Total SLS force under the strip = 3176 kN


Total ULS force under the strip = 4743 kN
2
Area of the strip base = 28.08 m
SLS Pressure at bottom of footing = 113.11 kN/m2
2
ULS Pressure at bottom of footing -(W) = 168.91 kN/m

Thereore, SLS pressure is well below the allowable soil bearing capacity

2
Moment - ULS = WL / 2 = 47.5 kNm/m
Shear Force - ULS = = WL = 126.7 kN/m

Reinforcement-ULS
Moment-ULS Mu 47.51
Bredth of Section B 1000
Depth of Section h 450
Main Bar dia T 12
Cover to main rebar C 40
Eff. Depth d 392
2
K = M/fcu bd 0.0124
Hence, z / d 0.950
Lever arm z 372.4
As reqd, M = M / 0.87 fy z 319
Bar dia T 12 @
Bar Spacing 150
As Provided 754

Amin 585
Shear Check
Shear Force - ULS Vu 126.7
Shear Stress = Vu/b.d v 0.32
As provided As 754
Shear Capacity, vc
/ γm
1/3 1/4 1/3
0.79{100As/(bvd)} [400/d] [fcu/25] 0.37

Shear Check OK

Provide T12 @ 150 both ways - bottom. Provide T10 @ 150 both ways - top