User Instructions
Section 5877 (Issue AQ, January 15, 2013)
The information contained in this document is subject to change without notice and may not be
suitable for all applications. While every precaution has been taken to ensure the accuracy and
completeness of this document, Emerson Network Power, Energy Systems, North America, Inc.
assumes no responsibility and disclaims all liability for damages resulting from use of this information
or for any errors or omissions. Refer to other local practices or building codes as applicable for the correct
methods, tools, and materials to be used in performing procedures not specifically described in this document.
This document is the property of Emerson Network Power, Energy Systems, North America, Inc.
and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use or disclosure of it without the written permission
of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
©
Copyright 2013, Emerson Network Power, Energy Systems, North America, Inc.
All rights reserved throughout the world.
User Instructions Section 5877
Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B) Issue AQ, January 15, 2013
STATIC WARNING
The printed circuit cards used in this equipment contain static sensitive components. The warnings listed below
must be observed to prevent damage to these components. Disregarding any of these warnings may result in
personal injury or damage to the equipment.
1. Strictly adhere to the procedures provided in this document.
2. Before touching any static sensitive component or printed circuit card containing such a component,
discharge all static electricity from yourself by wearing a wrist strap grounded through a one megohm
resistor. Some wrist straps, such as Emerson Network Power Part Number 631810600, have a built-in
one megohm resistor; no external resistor is necessary. Read and follow wrist strap manufacturer’s
instructions outlining use of a specific wrist strap.
3. Do not touch the traces or components on a printed circuit card containing static sensitive components.
Handle the printed circuit card only by the edges that do not have connector pads.
4. After removing a printed circuit card containing a static sensitive component, place the printed circuit card
only on conductive or anti-static material such as conductive foam, conductive plastic, or aluminum foil.
Do not use ordinary Styrofoam or ordinary plastic.
5. Store and ship static sensitive devices or printed circuit cards containing such components only in static
shielding containers.
6. If necessary to repair a printed circuit card containing a static sensitive component, wear an appropriately
grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded
test equipment.
FCC INFORMATION
The MCA Interface Modem Option (if installed) has been granted a registration number by the Federal
Communications Commission, under Part 68 rules and regulations for direct connection to the telephone lines. In
order to comply with these FCC rules, the following instructions must be carefully read and applicable portions
followed completely:
a) Direct connection to the telephone lines may be made only through the standard plug- ended cord
furnished to the utility-installed jack. No connection may be made to party or coin phone lines. Prior to
connecting the device to the telephone lines, you must:
b) Call your telephone company and inform them you have an FCC registered device you desire to connect
to their telephone lines. Give them the number(s) of the line(s) to be used, the make and model of the
device, the FCC registration number and ringer equivalence. This information will be found on the device
or enclosed with instructions as well as the jack suitable for your device.
c) After the telephone company has been advised of the above you may connect your device if the jack is
available, or after the telephone company has made the installation.
d) Repairs may be made only by the manufacturer or his authorized service agency. Unauthorized repairs
void registration and warranty. Contact seller or manufacturer for details of permissible user performed
routine repairs, and where and how to have other than routine repairs.
e) If, through abnormal circumstances, harm to the telephone lines is caused, it should be unplugged until it
can be determined if your device or the telephone line is the source. If your device is the source, it should
not be reconnected until necessary repairs are effected.
f) Should the telephone company notify you that your device is causing harm, the device should be
unplugged. The telephone company will, where practicable, notify you, that temporary discontinuance of
service may be required. However, where prior notice is not practicable, the telephone company may
temporarily discontinue service, if such action is reasonably necessary, in such cases the telephone
company must (A) Promptly notify you of such temporary discontinuance, (B) Afford you the opportunity
to correct the condition and (C) Inform you of your rights to bring a complaint to the FCC under their rules.
g) The telephone company may make changes in its communications facilities, equipment, operations or
procedures, where such action is reasonably required in the operation of its business and is not
inconsistent with FCC rules. If such changes can be reasonably expected to render any customer’s
devices incompatible with telephone company facilities, or require modification or alteration, or otherwise
materially affect its performance, written notification must be given to the user, to allow uninterrupted
service.
The following information is provided here and on a label attached to the outside of the MCA Interface Modem
Option (if installed).
TABLE OF CONTENTS
CONTENTS PAGE
CHAPTER 1 SYSTEM OVERVIEW ....................................................................................... 1-1
Preface ............................................................................................................................................................. 1-2
System Description .......................................................................................................................................... 1-3
System Overview Illustrations .......................................................................................................................... 1-6
Power/Distribution Bay .............................................................................................................................. 1-6
Power Only Bay ......................................................................................................................................... 1-7
Distribution Only Bay ................................................................................................................................. 1-8
Detail A - Distribution Bus Monitoring Circuit Card .................................................................................... 1-9
Detail B - System Monitoring and Control Section .................................................................................. 1-10
Detail C - Monitoring and Control Section (Distribution Only Bays) ........................................................ 1-11
Detail D - Front Door (Primary Power/Distribution and Power Only Bays) MCA Control Panel and
Display ..................................................................................................................................................... 1-12
Detail E - MCA Circuit Card (Primary Power/Distribution and Power Only Bays) and Router Circuit
Card (Secondary Power/Distribution and Power Only Bays and Distribution Only Bays) ...................... 1-13
Detail F .................................................................................................................................................... 1-14
Details G - MCA I/O Circuit Cards ........................................................................................................... 1-15
Detail H - LMS I/O Circuit Cards.............................................................................................................. 1-16
Detail J - Rectifier .................................................................................................................................... 1-24
CHAPTER 2 NAVIGATING THE MCA................................................................................... 2-1
CHAPTER 3 SYSTEM OPERATING PROCEDURES ........................................................... 3-1
LMS Operating Procedures.............................................................................................................................. 3-2
LMS Local Port ................................................................................................................................................. 3-2
Installing the USB Device Driver from the Furnished CD .......................................................................... 3-2
Downloading the USB Driver from the Web .............................................................................................. 3-3
Setting up your Computer to Access the Power System........................................................................... 3-3
Local Controls and Indicators........................................................................................................................... 3-3
Location and Identification ......................................................................................................................... 3-3
LMS Main/Expansion CPU Circuit Card (if furnished) Controls and Indicators ........................................ 3-3
Bay LED Indicator ...................................................................................................................................... 3-4
Distribution Bus LED Indicator ................................................................................................................... 3-4
MCA Component LED Indicator ................................................................................................................ 3-4
Bay Monitoring and Control Section Indicators ......................................................................................... 3-4
MCA Controls and Indicators ..................................................................................................................... 3-5
MCA Display .............................................................................................................................................. 3-6
Surge Suppression Alarms (available only if a Surge Suppression Option is furnished) .......................... 3-6
Rectifier Controls and Indicators ............................................................................................................... 3-7
208V and 480V Input Rectifiers .......................................................................................................... 3-7
External Alarms ................................................................................................................................................ 3-8
Starting and Stopping System Operation ......................................................................................................... 3-8
Rectifier Normal Starting Procedure .......................................................................................................... 3-8
Rectifier Stopping Procedure (Local)......................................................................................................... 3-8
Setting the Alternate Current Limit Initial Capacity Limit ................................................................... 3-26
CHAPTER 4 MCA SYSTEM ADJUSTMENTS ....................................................................... 4-1
Adjustment Location and Identification ............................................................................................................ 4-2
Adjusting Float Output Voltage ........................................................................................................................ 4-3
Adjusting Test/Equalize Output Voltage .......................................................................................................... 4-4
Adjusting High Voltage Shutdown .................................................................................................................... 4-5
Adjusting Rectifier Current Limit ...................................................................................................................... 4-6
Adjusting System High Voltage Alarm 1 .......................................................................................................... 4-7
Adjusting System High Voltage Alarm 2 .......................................................................................................... 4-8
Adjusting System Battery On Discharge Alarm ............................................................................................... 4-9
Adjusting System Very Low Voltage Alarm .................................................................................................... 4-10
Adjusting Total Distribution Load Alarm ......................................................................................................... 4-11
Adjusting Distribution Group A Load Alarm ................................................................................................... 4-12
Adjusting Distribution Group B Load Alarm ................................................................................................... 4-13
Adjusting Battery Ambient High Temperature #1 Alarm (if Battery Charge Digital Temperature
Compensation Probe is installed) .................................................................................................................. 4-14
Adjusting Battery Ambient High Temperature #2 Alarm (if Battery Charge Digital Temperature
Compensation Probe is installed) .................................................................................................................. 4-15
Adjusting Battery Ambient Low Temperature #1 Alarm (if Battery Charge Digital Temperature
Compensation Probe is installed) .................................................................................................................. 4-16
Adjusting Battery Ambient Low Temperature #2 Alarm (if Battery Charge Digital Temperature
Compensation Probe is installed) .................................................................................................................. 4-17
Configuring Battery Charge Digital Temperature Compensation Slope ........................................................ 4-18
Configuring Battery Charge Digital Temperature Compensation Maximum Voltage .................................... 4-19
Configuring Battery Charge Digital Temperature Compensation Minimum Voltage ..................................... 4-20
Configuring Degree Units Displayed ( F or C) ............................................................................................. 4-21
Configuring the System Date and Time ......................................................................................................... 4-22
Configuring MCA I/O Circuit Card Analog Input(s) ........................................................................................ 4-23
Configuring MCA I/O Circuit Card Analog Output(s) ..................................................................................... 4-25
Configuring MCA I/O Circuit Card Binary Input(s) ......................................................................................... 4-26
MCA Audible Alarm Cutoff Reset Time Period .............................................................................................. 4-27
MCA Rectifier Sequencing Feature ............................................................................................................... 4-27
Manually Initiated Timed Test/Equalize Feature ............................................................................................ 4-27
Automatic Test/Equalize Feature ................................................................................................................... 4-27
MCA Power Share Feature ............................................................................................................................ 4-27
Alarm Relay Test Feature .............................................................................................................................. 4-27
MCA “Alternate Current Limit” Feature .......................................................................................................... 4-27
CHAPTER 5 SYSTEM MAINTENANCE ................................................................................ 5-1
Admonishments ............................................................................................................................................... 5-2
General Safety ........................................................................................................................................... 5-2
Voltages ..................................................................................................................................................... 5-2
LMS Maintenance Procedures ......................................................................................................................... 5-2
System Maintenance Procedures .................................................................................................................... 5-3
Adding a Rectifier ............................................................................................................................................. 5-8
CHAPTER 1
SYSTEM OVERVIEW
TABLE OF CONTENTS
Preface ............................................................................................................................ 1-2
System Description .......................................................................................................... 1-3
System Overview Illustrations ......................................................................................... 1-6
Power/Distribution Bay .............................................................................................. 1-6
Power Only Bay ........................................................................................................ 1-7
Distribution Only Bay ................................................................................................ 1-8
Detail A - Distribution Bus Monitoring Circuit Card ................................................... 1-9
Detail B - System Monitoring and Control Section .................................................. 1-10
Detail C - Monitoring and Control Section (Distribution Only Bays) ....................... 1-11
Detail D - Front Door (Primary Power/Distribution and Power Only Bays)
MCA Control Panel and Display ............................................................................. 1-12
Detail E - MCA Circuit Card (Primary Power/Distribution and Power Only
Bays) and Router Circuit Card (Secondary Power/Distribution and Power
Only Bays and Distribution Only Bays) ................................................................... 1-13
Detail F .................................................................................................................... 1-14
Details G - MCA I/O Circuit Cards .......................................................................... 1-15
Detail H - LMS I/O Circuit Cards ............................................................................. 1-16
Detail J - Rectifier .................................................................................................... 1-24
PREFACE
This document (Section 5877) provides User Instructions for NetSure™ Power System
Model 802NLDB (208V Input Power/Distribution and Power Only Bays), 802NLEB (480V
Input Power/Distribution and Power Only Bays) and 802NL-B (Distribution Only Bay);
Spec. No. 582140000.
For an Installation Guide, refer to Section 5957 located in the separate INSTALLATION
MANUAL. This is a condensed version of the Installation Instructions (Section 5876).
Section 5876 can be accessed via the CD (Electronic Documentation Package) furnished
with your system.
Refer to SAG582140000 (System Application Guide) for additional information. The SAG
can be accessed via the CD (Electronic Documentation Package) furnished with your
system.
For a color MCA Menu Tree, refer to Section 5886. Section 5886 is provided in the
separate INSTALLATION MANUAL and the CD CARRIER MANUAL (it is also provided
on the CD).
Your power system may contain an optional LMS Monitoring System, refer to Section
5879 (LMS1000 Installation Instructions) and Section 5847 (LMS1000 User Instructions)
provided on the CD (Electronic Documentation Package) furnished with your system.
SYSTEM DESCRIPTION
-48V DC @ up to 10,000 amperes power system.
This power system is designed to power a load while charging a positive grounded
battery. This power system is capable of operating in a batteryless installation or off
battery for maintenance purposes. This power system is designed for operation with the
positive output grounded.
The NetSure™ 802NLDB (208V Input Power/Distribution and Power Only Bays), 802NLEB
(480V Input Power/Distribution and Power Only Bays), and 802NL-B (Distribution Only
Bay) DC Power System is a complete integrated power system containing rectifiers,
intelligent control, metering, monitoring, and distribution. This power system consists of
the following components.
Power/Distribution Bays
The system consists of one (1) Primary Power/Distribution Bay and up to nine (9)
Secondary Power/Distribution Bays.
Each Power/Distribution Bay can be equipped with up to ten (10) rectifiers and
provides distribution. Distribution is divided into two buses which accept a choice of
fuse and circuit breaker types and sizes.
Each Power/Distribution Bay contains a Monitor and Control Panel. In the Primary
Power/Distribution Bay, this panel houses the Meter-Control-Alarm (MCA) assembly.
This panel in the Primary Power/Distribution Bay also houses the optional LMS Main
CPU circuit card of the integrated LMS Monitoring System. In a Secondary
Power/Distribution Bay, this panel can be equipped with an optional LMS Expansion
CPU circuit card. (The optional LMS Monitoring System provides a higher level of
monitoring and controlling capabilities to the power system.)
The Monitor and Control Panel in both Primary and Secondary Power/Distribution
Bays contain a seven-slot card cage to house MCA alarm relay circuit cards, MCA
input/output (I/O) circuit cards, and optional LMS I/O circuit cards. (If a Secondary
Power/Distribution Bay is to be equipped with optional LMS I/O circuit cards, it must
also be equipped with an LMS Expansion CPU circuit card.)
Power Only Bays
The system can consist of one (1) Primary Power Only Bay and up to nine (9)
Secondary Power Only Bays.
Each Power Only Bay can be equipped with up to ten (10) Rectifiers.
Each Power Only Bay contains a Monitor and Control Panel. In the Primary Power
Only Bay, this panel houses the Meter-Control-Alarm (MCA) assembly. This panel in
the Primary Power Only Bay also houses the optional LMS Main CPU circuit card of
the integrated LMS Monitoring System. In a Secondary Power Only Bay, this panel
can be equipped with an optional LMS Expansion CPU circuit card. (The optional
LMS Monitoring System provides a higher level of monitoring and controlling
capabilities to the power system.)
The Monitor and Control Panel in both Primary and Secondary Power Only Bays
contain a seven-slot card cage to house MCA alarm relay circuit cards, MCA
input/output (I/O) circuit cards, and optional LMS I/O circuit cards. (If a Secondary
Power Only Bay is to be equipped with optional LMS I/O circuit cards, it must also be
equipped with an LMS Expansion CPU circuit card.)
Distribution Only Bays
The system consists of one (1) to eight (8) Distribution Only Bays.
Each Distribution Only Bay provides four (4) distribution buses.
Each distribution bus accepts a choice of 218-type circuit breakers and TPL-type
fuses.
A Distribution Only Bay may also be equipped with an optional distribution panel
which accepts a choice of TPS/TLS-type fuseholders or Bullet Nose-type circuit
breakers.
Rectifiers
The rectifiers provide load power, battery float current, and battery recharge current
during normal operating conditions.
MCA (Meter-Control-Alarm)
The MCA controls the operation of the rectifiers and provides power system control,
metering, monitoring, and alarm functions.
MCA Local Control Panel: This panel is located on the front of the Primary
Power/Distribution Bay or Power Only Bay and contains a keypad, display, and
indicators for local MCA User interface.
MCA Relay Circuit Card: Each MCA relay circuit card provides six (6) sets of
Form-C relay contacts for customer external alarms. These relays are User
programmable for various power system alarms. Up to sixteen (16) MCA relay circuit
cards can be installed in the Primary and Secondary Power/Distribution and Power
Only Bays. The Primary Power/Distribution and Power Only Bays are factory
equipped with two (2) MCA relay circuit cards.
MCA I/O Circuit Cards: The MCA I/O circuit cards provide analog inputs/outputs
and binary inputs. Up to sixteen (16) MCA I/O circuit cards can be installed in the
Primary and Secondary Power/Distribution and Power Only Bays.
Optional Integrated LMS Monitoring System
The LMS Monitoring System consists of an LMS Main CPU circuit card, optional LMS
Expansion CPU circuit cards, optional LMS I/O circuit cards, optional LMS Expansion
Cabinet, and optional LMS Expansion Assemblies.
The LMS Main CPU circuit card is mounted in the Primary Power/Distribution and
Power Only Bays. Each Secondary Power/Distribution and Power Only Bay that is to
be equipped with optional LMS I/O circuit cards must contain an LMS Expansion
CPU circuit card. LMS Expansion Cabinets and LMS Expansion Assemblies are
available that mount into customer equipment.
The LMS Monitoring System is factory integrated within each Power/Distribution,
Power Only, and Distribution Only Bay and requires no additional customer
interconnections within the bays. Simple cable connections between the
Power/Distribution, Power Only, and Distribution Only Bays complete the interbay
connections required. Separate analog, binary, and relay circuit cards do not have to
be supplied for power system monitoring. Analog, binary, relay, and temperature
circuit cards can be provided to monitor equipment external to the power system.
The LMS input circuit cards monitor a variety of analog, binary, and temperature
points external to the system. An LMS relay output circuit card is also available
which provides programmable relays. These relays may be used for external alarms,
or to control other equipment.
The LMS Monitoring System can be accessed via a local port, a modem port (when
optional modem is ordered), an optional TL1 port, and an Ethernet port (for Telnet
access, optional Web access, optional SNMP access, optional TL1 access, and
Email alarm reporting).
The LMS Monitoring System collects data from the power system and the input circuit
cards monitoring external points. The data collected is used for alarm processing
and reporting, and to provide statistics.
Distribution
Bus #1
Spare
Fuseholders Monitoring
(behind hinged Bus #1 Monitoring Circuit Card (See Detail A)
panel) (behind hinged panel)
Distribution
Bus #2
Spare
Monitoring
Fuseholders
(behind hinged Bus #2 Monitoring Circuit Card (See Detail A)
panel) (behind hinged panel)
Power
PCUs
(See Detail J)
Note
Each MCA component (i.e. PCU, Bus Monitoring
Circuit Card, Bay Router Circuit Card, MCA Relay
Circuit Card) can be programmed with a custom
text message for identification purposes.
Power
PCUs
(See Detail J)
Note
Each MCA component (i.e. PCU, Bus Monitoring
Circuit Card, Bay Router Circuit Card, MCA Relay
Circuit Card) can be programmed with a custom
text message for identification purposes.
Bay LED
Green = OK
Red = Bay Failure
Yellow (Flashing) = Communicating
with MCA
Distribution Di stribution
Bus #1 Bus #2
Monitoring Monitoring
Bus #1 Monitoring Bus #2 Monitoring
Circuit Card Circuit Card
(See Detail A)* (See Detail A)*
(behind hinged panel) (behind hinged panel)
Monitoring and Control Section
See Detail C
Distribution Distribution
Bus #3 Bus #4
Monitoring Monitoring
Bus #3 Monitoring Bus #4 Monitoring
Circui t Card Circuit Card
(See Detail A)* (See Detail A)*
(behind hinged panel) (behi nd hinged panel)
* Spare Fuseholders
are located behind
hinged panel Front Door Removed in
Illustration for Clarity
Front View
Distribution Bay
Identification
Indicator
Green = OK
Red = Failure
Yellow (Flashing) = Communicating with MCA
External MCA*
CAN BUS (Primary Bay) Seven-Slot Card Cage for MCA Customer Alarm
Port or Relay circuit cards, optional MCA I/O circuit cards,
Router and/or optional LMS Input/Output I/O circuit cards.
LMS Ethernet (Secondary Note: MCA circuit cards can be installed in any
Port (Primary Bay) position. LMS I/O circuit cards MUST be
Bay Only) Power Circuit Card populated left to right.
and FA (See Detail E) (See Detail H and I)
Indicators
AC
MAJOR MINOR
Alarm Indicator TESTEQ
Indicator Indicator
Cutoff (Green - OK Indicator
(Flashes (Red)
Indicator Audible Red - Fail) (Yellow)
Red)
(Yellow) Alarm
FUNCTION SET
YES / + / i
Pushbutton Switch
ENTER / /
Pushbutton Switch
NO / -
Pushbutton Switch
FUNCTION
SELECT
ALARM
Up / Down
CUTOFF
LMS LOCAL PORT Pushbutton
Pushbutton
(USB) Switches
Switch
(active only if
optional LMS installed)
5 1
9 6
Mating Connector
in Power System Wire Harness
(9-Pin Female D-Type Jack)
RJ-45 RJ-45
Jack Jack
1 10
Identification
Indicator***
MCA
(PRIMARY POWER/DISTRIBUTION AND
POWER ONLY BAYS) (P/N 509478)
RJ-45 RJ-45
Jack Jack
Identification
Indicator***
ROUTER
(SECONDARY POWER/DISTRIBUTION AND
POWER ONLY BAYS AND DISTRIBUTION
ONLY BAYS) (P/N 509509)
Detail F
Piggy-Back Modem
Circuit Card
(P/N 508951)
Identification Green = OK
Indicator Red = Failure
Yellow (Flashing) = Communicating with MCA
NC 18 9 NC
K3 COM COM K6
NO NO
NC NC
K2 COM COM K5
NO NO
NC NC
K1 COM COM K4 MCA RELAY CIRCUIT CARD
NO 10 1 NO (P/N 514348)
TB1
Identification Green = OK
Indicator Red = Failure
Yellow (Flashing) = Communicating with MCA
_
12
A1 OUT**
+
_
* 0-50 mv DC Shunt Input
A1 IN* ** 0-50 mv DC Output for Remote Plant Output Current Monitoring
+
*** Dry Contacts, Circuit Closure to Activate Alarm
B4***
B3***
B2***
MCA I/O CIRCUIT CARDS
(P/N 524550, 1 analog input, 1 analog output, 4 binary inputs)
B1***
1
TB1
16 LARGE SIGNAL
A4 (0-60 volts DC)
15
14 SMALL SIGNAL
A4 (50 mv shunts, 100 mv shunts,
13 20 ma current loops)
12 LARGE SIGNAL
A3 (0-60 volts DC)
11
10 SMALL SIGNAL
A3 (50 mv shunts, 100 mv shunts,
9 20 ma current loops) Analog input
wiring connection
8 LARGE SIGNAL terminals
A2 (0-60 volts DC)
7
6 SMALL SIGNAL
A2 (50 mv shunts, 100 mv shunts,
5 20 ma current loops)
4 LARGE SIGNAL
TB1 A1 (0-60 volts DC)
3
506336 2 SMALL SIGNAL
A1
(50 mv shunts, 100 mv shunts,
1 20 ma current loops)
Note:
Analog input designations A1 through A4 as shown are for
the circuit card only. The actual analog channel number
depends upon the quantity of analog and temperature
circuit cards installed and location of this analog circuit
card in the system network.
16
A8 50 mv Shunts Only
15
14
A7 50 mv Shunts Only
13
12
A6 50 mv Shunts Only
11
10
A5 50 mv Shunts Only
9 Analog input
wiring connection
8
A4 50 mv Shunts Only terminals
7
6
A3 50 mv Shunts Only
5
4
TB1 A2 50 mv Shunts Only
3
514528 2
A1 50 mv Shunts Only
1
Note:
Analog input designations A1 through A8 as shown are for
the circuit card only. The actual analog channel number
depends upon the quantity of analog and temperature
circuit cards installed and location of this analog circuit
card in the system network.
16
A8
15
14
A7
13
12
A6
11
10
A5
9 Temperature input
wiring connection
8 terminals
A4
7
6
A3
5
TB1 4
A2
506333 3
2
A1
1
Note:
Analog input designations A1 through A8 as shown are for
the circuit card only. The actual analog channel number
depends upon the quantity of analog and temperature
circuit cards installed and location of this temperature circuit
card in the system network.
16
15
14
B4
13
12
11
10
B3
9
8 Binary input
wiring connection
7 terminals
6
B2
5
4
TB1
3
506332 2
B1
1
Note:
Binary input designations B1 through B4 as shown are for
the circuit card only. The actual binary channel number
depends upon the quantity of binary circuit cards installed
and the location of this binary circuit card in the
system network.
+BAT
16
Connections to Battery, as required
15 -BAT
Note:
14 Needed only to complete binary input
path as determined by placement of
13 appropriate jumper. If all binary
inputs require the same battery
12 potential, only that potential needs to
11 be connected.
10
9
B8
8
B7
7
B6
6
B5 Binary input
5
wiring connection
B4 terminals
4
TB1
B3
3
506334 2 B2
B1
1
Note:
Binary input designations B1 through B8 as shown are for
the circuit card only. The actual binary channel number
depends upon the quantity of binary circuit cards installed
and the location of this binary circuit card in the
system network.
16
NC
15
C K4
14
13 NO
12
11 NC
10 C K3
7 NC
6 C K2
5 NO
4
TB1
3 NC
506335 2 C K1
1 NO
Note:
Relay designations K1 through K4 as shown are for the
circuit card only. The actual relay channel number depends
upon the number of relay circuit cards installed and the
location of this relay circuit card in the system network.
unused
16
15 unused
14 unused
Note:
Analog input designations A1 through A12 as shown are for
the circuit card only. The actual analog channel number
depends upon the quantity of analog and temperature
circuit cards installed and location of this analog circuit card
in the system network.
Detail J - Rectifier
208V and 480V Rectifier
Output
Operate / Standby Switch Current
Bargraph
CHAPTER 2
NAVIGATING THE MCA
0B
Located on the Primary Power/Distribution and Power Only Bays’ front door.
AC
MAJOR MINOR
Alarm Indicator TESTEQ
Indicator Indicator
Cutoff (Green - OK Indicator
(Flashes (Red)
Indicator Audible Red - Fail) (Yellow)
Red)
(Yellow) Alarm
FUNCTION SET
YES / + / i
Pushbutton Switch
ENTER / /
Pushbutton Switch
NO / -
Pushbutton Switch
FUNCTION
SELECT
ALARM
Up / Down
CUTOFF
LMS LOCAL PORT Pushbutton
Pushbutton
(USB) Switches
Switch
(active only if
optional LMS installed)
5 1
9 6
Mating Connector
in Power System Wire Harness
(9-Pin Female D-Type Jack)
Navigating the MCA is an easy process. You just have to remember a few key
combinations (as shown in the following chart). The symbols that appear at the end of
the fourth line of the display indicate which keypad buttons can be pressed at any given
time.
YES / + / i and NO / -
U
ENTER
U
You can travel left to right from one
menu to another by pressing ENTER.
Moving from One Menu
You can also go back to a specified
to Another Menu ENTER / /
menu by pressing ENTER while the
menu's name is being displayed.
NO / -
MCA MESSAGES
3B
The following chart provides an explanation of each MCA message appearing on the
MCA Menu Tree (Section 5886). The MCA Menu Tree is located in the separate
INSTALLATION MANUAL and the CD CARRIER MANUAL (it is also provided on the
CD). Note that each line in the MCA Menu Tree contains a number. This number is
referenced in the following chart.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Rectifier Module (PCU) emergency shutdown
EMERGENCY STOP Main
1 or fire alarm disconnect signal applied to the
INPUT ACTIVE Alarm Menu
system.
HI VOLTAGE SHUTDOWN Main High voltage shutdown signal applied to the
2
INPUT ACTIVE Alarm Menu system.
Indicates that all rectifier modules (PCUs) are
operating in the “Alternate Current Limit” mode.
ALTERNATE CURRENT Main
2A Rectifier output current will be limited to the
LIMIT ACTIVE Alarm Menu
percent of capacity specified by the “Alternate
Current Limit Capacity” parameter setting.
System voltage below a preset adjustable
value, indicating that the battery has been
continuously supplying the load and has
SYSTEM VOLTAGE IS Main discharged to approximately half its reserve
3
VERY LOW Alarm Menu time.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT vv.vvV Displays the alarm limit setpoint and the actual
3A --
NOW AT vv.vvV value of the monitored input.
System voltage below a preset adjustable
value, indicating that the battery is supplying
SYSTEM BATTERY IS ON Main the load and is discharging.
4
DISCHARGE Alarm Menu
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT vv.vvV Displays the alarm limit setpoint and the actual
4A --
NOW AT vv.vvV value of the monitored input.
System voltage above a preset adjustable
SYSTEM HIGH VOLTAGE Main value.
5
#1 ALARM Alarm Menu Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT vv.vvV Displays the alarm limit setpoint and the actual
5A --
NOW AT vv.vvV value of the monitored input.
System voltage above a preset adjustable
SYSTEM HIGH VOLTAGE Main value.
6
#2 ALARM Alarm Menu Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT vv.vvV Displays the alarm limit setpoint and the actual
6A --
NOW AT vv.vvV value of the monitored input.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
One or more system fuses or circuit breakers
open. (### = number of open system fuses or
circuit breakers.)
1 SYSTEM BREAKER OR
Press ENTER to view which fuse(s) or circuit
FUSE ALARM
Main breaker(s) is open.
7 or
Alarm Menu Note that the individual fuses and circuit
### SYSTEM BREAKER &
FUSE ALARMS breakers in the bullet nose-type device holders
(plug-in) are not counted. If any number within
a bullet nose-type device holder (plug-in) are
open, only one will be counted.
Identification of open system fuse or circuit
breaker. (F/CB/PI B#-P#A/B = Fuse or Circuit
Breaker or PlugIn, Bay Number-Distribution
F/CB/PI B#-P#A/B Fuse Device Position Number [Group A or B
8
IS OPEN Alarm Menu
Designation if applicable.])
Press UP and DOWN ARROWS to scroll if
multiple distribution devices are open.
GO TO MAIN ALARM Fuse
9 Press ENTER to go to this menu.
MENU Alarm Menu
GO BACK TO MENU TREE Fuse Press ENTER to go to the beginning of the
10
BEGINNING Alarm Menu MCA Menu Tree.
AC POWER IS OFF TO Main AC input voltage to all Rectifier Modules
11
ALL PCUs Alarm Menu (PCUs) below a preset non-adjustable value.
One or more Rectifier Modules (PCUs) failed.
1 PCU (### = number of failed Rectifier Modules
HAS FAILED [PCUs].)
or Press ENTER to view which Rectifier Module
### PCUs Main (PCU) failed.
12
HAVE FAILED Alarm Menu
or or
NO PCUs ARE If the MCA does not recognize any Rectifier
IN INVENTORY Module (PCU), NO PCUs ARE IN INVENTORY
is displayed.
Identification of failed Rectifier Module (PCU).
(B#-ID#/N# = Bay Number-Rectifier Module
MCA ID# w/in Bay/Number of Rectifier
PCU B#-ID#/N# PCU Modules in System.)
13
FAILURE Alarm Menu Press UP and DOWN ARROWS to scroll if
multiple Rectifier Modules failed.
Press ENTER to view why Rectifier Module
failed.
More than one Remote Rectifier (PCU) failed.
### REMOTE PCUS PCU
14 (### = number of failed Remote Rectifiers
HAVE FAILED Alarm Menu
[PCUs].)
1 REMOTE PCU PCU
15 One Remote Rectifier (PCU) failed.
HAS FAILED Alarm Menu
GO TO MAIN ALARM PCU
16 Press ENTER to go to this menu.
MENU Alarm Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
GO BACK TO MENU TREE PCU Press ENTER to go to the beginning of the
17
BEGINNING Alarm Menu MCA Menu Tree.
Rectifier Module (PCU) is in Emergency Stop
PCU B#-ID#/N# PCU Alarm Mode. (B#-ID#/N# = Bay Number-Rectifier
18
EMERG. STOP Detail Menu Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
Rectifier Module (PCU) is in High Voltage
PCU B#-ID#/N# PCU Alarm Shutdown. (B#-ID#/N# = Bay Number-Rectifier
19
H.V. SHUTDOWN Detail Menu Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
No AC Input to Rectifier Module (PCU) or
Rectifier Module's (PCU’s) processor failed.
PCU B#-ID#/N# PCU Alarm
20 (B#-ID#/N# = Bay Number-Rectifier Module
AC LINE OFF Detail Menu
MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
Rectifier Module's (PCU’s) Low AC Line Alarm
PCU B#-ID#/N# PCU Alarm active. (B#-ID#/N# = Bay Number-Rectifier
21
AC LINE LOW Detail Menu Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
Rectifier Module's (PCU’s) High AC Line Alarm
PCU B#-ID#/N# PCU Alarm active. (B#-ID#/N# = Bay Number-Rectifier
22
AC LINE HIGH Detail Menu Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
Rectifier Module's (PCU’s) AC Line Phase Lost
PCU B#-ID#/N# PCU Alarm Alarm active. (B#-ID#/N# = Bay Number-
23
AC PHASE LOST Detail Menu Rectifier Module MCA ID# w/in Bay/Number of
Rectifier Modules in System.)
Rectifier Module's (PCU’s) internal power
PCU B#-ID#/N# PCU Alarm factor circuit failed. (B#-ID#/N# = Bay Number-
24
POWER FACTOR Detail Menu Rectifier Module MCA ID# w/in Bay/Number of
Rectifier Modules in System.)
Rectifier Module's (PCU’s) internal DC/DC
PCU B#-ID#/N# PCU Alarm converter circuit failed. (B#-ID#/N# = Bay
25
DC/DC CONV. Detail Menu Number-Rectifier Module MCA ID# w/in
Bay/Number of Rectifier Modules in System.)
Rectifier Module's (PCU’s) DC output fuse
PCU B#-ID#/N# PCU Alarm open. (B#-ID#/N# = Bay Number-Rectifier
26
FUSE/BREAKER Detail Menu Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
Rectifier Module's (PCU’s) output inhibited.
PCU B#-ID#/N# PCU Alarm (B#-ID#/N# = Bay Number-Rectifier Module
27
INHIBITED Detail Menu MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
Rectifier Module's (PCU’s) Standby/Operate
PCU B#-ID#/N# PCU Alarm switch is in the "standby" position. (B#-ID#/N#
28
ON STANDBY Detail Menu = Bay Number-Rectifier Module MCA ID# w/in
Bay/Number of Rectifier Modules in System.)
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Rectifier Module (PCU) in Thermal Current
PCU B#-ID#/N# PCU Alarm Limit. (B#-ID#/N# = Bay Number-Rectifier
29
THERMAL LIMIT Detail Menu Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
Rectifier Module (PCU) in Thermal Shutdown.
PCU B#-ID#/N# PCU Alarm (B#-ID#/N# = Bay Number-Rectifier Module
30
THERMAL STOP Detail Menu MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
Rectifier Module's (PCU’s) High Temperature
PCU B#-ID#/N# PCU Alarm Alarm active. (B#-ID#/N# = Bay Number-
31
HIGH AMBIENT Detail Menu Rectifier Module MCA ID# w/in Bay/Number of
Rectifier Modules in System.)
Load is not balanced with the other Rectifier
PCU B#-ID#/N# PCU Alarm Modules (PCUs). (B#-ID#/N# = Bay Number-
32
LOAD SHARE Detail Menu Rectifier Module MCA ID# w/in Bay/Number of
Rectifier Modules in System.)
1 Rectifier Module (PCU) Fan Fail Alarm
PCU B#-ID#/N# PCU Alarm active. (B#-ID#/N# = Bay Number-Rectifier
33
1 FAN SPEED Detail Menu Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
2 or more Rectifier Module (PCU) Fan Fail
PCU B#-ID#/N# PCU Alarm Alarms active. (B#-ID#/N# = Bay Number-
34
2+ FANS SPEED Detail Menu Rectifier Module MCA ID# w/in Bay/Number of
Rectifier Modules in System.)
PCU B#-ID#/N# PCU Alarm
35 Not used at this time.
NO VOLT SENSE Detail Menu
PCU B#-ID#/N# PCU Alarm
36 Duplicated Reference Designations.
DUPLICATED Detail Menu
MCA communications with Rectifier Module
PCU B#-ID#/N# PCU Alarm (PCU) lost. (B#-ID#/N# = Bay Number-Rectifier
37
NO RESPONSE Detail Menu Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
PCU Alarm
38 GO TO PCU ALARM MENU Press ENTER to go to this menu.
Detail Menu
GO BACK TO MENU TREE PCU Alarm Press ENTER to go to the beginning of the
39
BEGINNING Detail Menu MCA Menu Tree.
One or more Distribution Bus Monitoring Circuit
1 DIST. PANEL Cards failed. (## = number of failed
HAS FAILED Distribution Bus Monitoring Circuit Cards.)
or
Press ENTER to view which Distribution Bus
## DIST. PANELS Main Monitoring Circuit Card(s) failed.
40
HAVE FAILED Alarm Menu
or or
NO DIST. PANELS ARE If the MCA does not recognize any Distribution
IN INVENTORY Bus Monitoring Circuit Card, NO DIST.
PANELS ARE IN INVENTORY is displayed.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Identification of failed Distribution Bus
Monitoring Circuit Card. (B#-P# A/B = Bay
Number-Distribution Bus Monitoring Circuit
Card Position Number [Group A or B
DIST. PANEL B#-P#A/B Distribution Designation if applicable.])
41
FAILURE Alarm Menu Press UP and DOWN ARROWS to scroll if
multiple Distribution Bus Monitoring Circuit
Cards failed.
Press ENTER to view why Distribution Bus
Monitoring Circuit Card failed.
GO TO MAIN ALARM Distribution
42 Press ENTER to go to this menu.
MENU Alarm Menu
GO BACK TO MENU TREE Distribution Press ENTER to go to the beginning of the
43
BEGINNING Alarm Menu MCA Menu Tree.
DIST. PANEL B#-P#A/B
DISCONNECTED Distribution
44 or Alarm Not utilized at this time.
DIST. PANEL B#-P#A/B Detail Menu
RECONNECT?
MCA cannot find a distribution device.
(B#-P#A/B = Bay Number-Distribution Device
POSITION B#-P#A/B Position Number [Group A or B Designation if
NOT FOUND Distribution applicable.])
45 or Alarm (B#-P#A/B = Bay Number-Distribution Bus
POSITION NOT FOUND Detail Menu Monitoring Circuit Card Position Number
PANEL B#-P#A/B [Group A or B Designation if applicable.])
Press UP and DOWN ARROWS to scroll if
multiple distribution devices not found.
MCA cannot identify the distribution device.
(B#-P#A/B = Bay Number-Distribution Device
Distribution Position Number [Group A or B Designation if
POSITION B#-P#A/B
46 Alarm
TYPE UNKNOWN applicable.])
Detail Menu
Press UP and DOWN ARROWS to scroll if
multiple distribution devices not identified.
Distribution device current is above the shunt's
rating. (F/CB/PI B#-P#A/B = Fuse or Circuit
Distribution Breaker or PlugIn, Bay Number-Distribution
F/CB/PI B#-P#A/B Device Position Number [Group A or B
47 Alarm
OVER CURRENT Designation if applicable.])
Detail Menu
Press UP and DOWN ARROWS to scroll if
multiple shunts are over-ranged.
Distribution
DIST. PANEL B#-P#A/B
48 Alarm Not utilized at this time.
LVD FAILURE
Detail Menu
Group A / Group B jumper setting on
Distribution
DIST. PANEL B#-P#A/B Distribution Bus Monitoring Circuit Card
49 Alarm
A/B CHANGED changed. (B#-P# = Bay Number-Distribution
Detail Menu
Bus Monitoring Circuit Card Position Number)
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Distribution Bus Monitoring Circuit Card's
Distribution processor failed. (B#-P#A/B = Bay Number-
DIST. PANEL B#-P#A/B
50 Alarm Distribution Bus Monitoring Circuit Card
PROCESSOR
Detail Menu Position Number [Group A or B Designation if
applicable.])
Distribution
DIST. PANEL B#-P#A/B IS
51 Alarm Duplicated Reference Designations.
DUPLICATED
Detail Menu
MCA communications with Distribution Bus
Distribution
DIST. PANEL B#-P#A/B Monitoring Circuit Card lost. (B#-P# = Bay
52 Alarm
NO RESPONSE Number-Distribution Bus Monitoring Circuit
Detail Menu
Card Position Number)
Distribution
GO TO DISTRIBUTION
53 Alarm Press ENTER to go to this menu.
ALARM MENU
Detail Menu
Distribution
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
54 Alarm
BEGINNING MCA Menu Tree.
Detail Menu
1 I/O BOARD One or more MCA I/O Circuit Cards failed. (##
HAS FAILED = number of failed MCA I/O Circuit Cards.)
or Press ENTER to view which MCA I/O Circuit
## I/O BOARDS Main Card(s) failed.
55
HAVE FAILED Alarm Menu or
or If the MCA does not recognize any MCA I/O
NO I/O BOARD S ARE Circuit Card, NO I/O BOARDS ARE IN
IN INVENTORY INVENTORY is displayed.
Identification of failed MCA I/O Circuit Card.
(B#-P# = Bay Number-MCA I/O Circuit Card
Position Number.)
I/O BOARD B#-P# I/O Board
56 Press UP and DOWN ARROWS to scroll if
FAILURE Alarm Menu
multiple MCA I/O Circuit Cards failed.
Press ENTER to view why MCA I/O Circuit
Card failed.
GO TO MAIN ALARM I/O Board
57 Press ENTER to go to this menu.
MENU Alarm Menu
GO BACK TO MENU TREE I/O Board Press ENTER to go to the beginning of the
58
BEGINNING Alarm Menu MCA Menu Tree.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Custom test message stored in MCA for binary
input that is in alarm state. If multiple inputs in
alarm state, scroll through each.
Note: Refer to System Operating Procedures
I/O Board chapter in Section 5877 for procedure how to
Binary Input Customer
59 Alarm Detail enter custom test messages. Refer to
Text Message
Menu Installing the Rectifier Modules and Initially
Starting the Power System chapter in Section
5876 for procedure how to program binary
input alarm state (either open or close contact
state).
If the current reflected by the analog inputs or
I/O Board outputs gets up to 95% of the shunt rating, the
I/O BOARD B#-P#
60 Alarm Detail I/O board activates an over current alarm.
OVER CURRENT
Menu (B#-P# = Bay Number-MCA I/O Circuit Card
Position Number.)
I/O Board MCA I/O Circuit Card's processor failed.
I/O BOARD B#-P#
61 Alarm Detail (B#-P# = Bay Number-MCA I/O Circuit Card
PROCESSOR
Menu Position Number.)
I/O Board
I/O BOARD B#-P# IS
62 Alarm Detail Duplicated Reference Designations.
DUPLICATED
Menu
I/O Board MCA communications with MCA I/O Circuit
I/O BOARD B#-P#
63 Alarm Detail Card lost. (B#-P# = Bay Number-MCA I/O
NO RESPONSE
Menu Circuit Card Position Number.)
I/O Board
GO TO I/O BOARD
64 Alarm Detail Press ENTER to go to this menu.
ALARM MENU
Menu
I/O Board
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
65 Alarm Detail
BEGINNING MCA Menu Tree.
Menu
1 ROUTER One or more Router Circuit Cards failed. (## =
HAS FAILED number of failed Router Circuit Cards.)
or Press ENTER to view which Router Circuit
## ROUTERS Main Card(s) failed.
66
HAVE FAILED Alarm Menu or
or If the MCA does not recognize any Router
NO ROUTERS ARE Circuit Card, NO ROUTERS ARE IN
IN INVENTORY INVENTORY is displayed.
Identification of failed Router Circuit Card. (B#
= Bay Number.)
ROUTER B# Router Press UP and DOWN ARROWS to scroll if
67
FAILURE Alarm Menu multiple Router Circuit Cards failed.
Press ENTER to view why Router Circuit Card
failed.
GO TO MAIN ALARM Router
68 Press ENTER to go to this menu.
MENU Alarm Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
GO BACK TO MENU TREE Router Press ENTER to go to the beginning of the
69
BEGINNING Alarm Menu MCA Menu Tree.
ROUTER B# REMOTE Router Alarm Router Circuit Card External A/D Voltage Alarm
70
SENSE OPEN Detail Menu active. (B# = Bay Number.)
ROUTER B# INTERNAL Router Alarm Router Circuit Card Internal A/D Voltage Alarm
71
SENSE OPEN Detail Menu active. (B# = Bay Number.)
Router Alarm Router Circuit Card's processor failed. (B# =
72 ROUTER B# PROCESSOR
Detail Menu Bay Number.)
ROUTER B# REPORTS AN Router Alarm MCA dose not recognize a node's type or
73
ILLEGAL NODE Detail Menu identification number. (B# = Bay Number.)
ROUTER B# IS Router Alarm
74 Duplicated Reference Designations.
DUPLICATED Detail Menu
ROUTER B# Router Alarm MCA communications with Router Circuit Card
75
NO RESPONSE Detail Menu lost. (B# = Bay Number.)
GO TO ROUTER ALARM Router Alarm
76 Press ENTER to go to this menu.
MENU Detail Menu
GO BACK TO MENU TREE Router Alarm Press ENTER to go to the beginning of the
77
BEGINNING Detail Menu MCA Menu Tree.
One or more MCA Customer Alarm Relay
1 RELAY BOARD Circuit Cards failed. (## = number of failed
HAS FAILED MCA Customer Alarm Relay Circuit Cards.)
or Press ENTER to view which MCA Customer
## RELAY BOARDS Main Alarm Relay Circuit Card(s) failed.
78
HAVE FAILED Alarm Menu or
or If the MCA does not recognize any MCA
NO RELAY BOARDS ARE Customer Alarm Relay Circuit Card, NO
IN INVENTORY RELAY BOARDS ARE IN INVENTORY is
displayed.
Identification of failed MCA Customer Alarm
Relay Circuit Card. (B#-P# = Bay Number-
Relay Circuit Card Position Number.)
RELAY BOARD B#-P# Relay Press UP and DOWN ARROWS to scroll if
79
FAILURE Alarm Menu multiple MCA Customer Alarm Relay Circuit
Cards failed.
Press ENTER to view why MCA Customer
Alarm Relay Circuit Card failed.
GO TO MAIN ALARM Relay
80 Press ENTER to go to this menu.
MENU Alarm Menu
GO BACK TO MENU TREE Relay Press ENTER to go to the beginning of the
81
BEGINNING Alarm Menu MCA Menu Tree.
Relay does not change state. (B#-P#-R# =
RELAY B#-P#-R# IS Relay Alarm
82 Bay Number-Relay Circuit Card Position
STUCK Detail Menu
Number-Relay Number on Card.)
MCA Customer Alarm Relay Circuit Card's
RELAY BOARD B#-P# Relay Alarm
83 processor failed. (B#-P# = Bay Number-Relay
PROCESSOR Detail Menu
Circuit Card Position Number.)
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
RELAY BOARD B#-P# IS Relay Alarm
84 Duplicated Reference Designations.
DUPLICATED Detail Menu
MCA communications with MCA Customer
RELAY BOARD B#-P# Relay Alarm
85 Alarm Relay Circuit Card lost. (B#-P# = Bay
NO RESPONSE Detail Menu
Number-Relay Circuit Card Position Number.)
GO TO RELAY ALARM Relay Alarm
86 Press ENTER to go to this menu.
MENU Detail Menu
GO BACK TO MENU TREE Relay Alarm Press ENTER to go to the beginning of the
87
BEGINNING Detail Menu MCA Menu Tree.
Battery ambient temperature above preset
HIGH TEMPERATURE #1 Main adjustable value.
88
ALARM Alarm Menu Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT ttt°C/F Displays the alarm limit setpoint and the actual
88A --
NOW AT ttt°C/F value of the monitored input.
Battery ambient temperature above preset
HIGH TEMPERATURE #2 Main adjustable value.
89
ALARM Alarm Menu Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT ttt°C/F Displays the alarm limit setpoint and the actual
89A --
NOW AT ttt°C/F value of the monitored input.
Battery ambient temperature below preset
LOW TEMPERATURE #1 Main adjustable value.
90
ALARM Alarm Menu Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT ttt°C/F Displays the alarm limit setpoint and the actual
90A --
NOW AT ttt°C/F value of the monitored input.
Battery ambient temperature below preset
LOW TEMPERATURE #2 Main adjustable value.
91
ALARM Alarm Menu Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT ttt°C/F Displays the alarm limit setpoint and the actual
91A --
NOW AT ttt°C/F value of the monitored input.
TEMPERATURE SENSOR Main MCA Temperature Sensor signal lost, if
92
NO SIGNAL Alarm Menu Temperature Sensor installed.
MAJOR MONITORING
ALARM(S) Major Alarm conditions detected by LMS1000.
Main
93 or Alarm Messages derived from LMS1000 are
Alarm Menu
Monitoring Major displayed by the MCA.
LED Messages
MINOR MONITORING
ALARM(S) Minor Alarm conditions detected by LMS1000.
Main
94 or Alarm Messages derived from LMS1000 are
Alarm Menu
Monitoring Minor displayed by the MCA.
LED Messages
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
MONITORING
INFORMATION Status Messages detected by LMS1000.
Main
95 or Status Messages derived from LMS1000 are
Alarm Menu
Monitoring Info displayed by the MCA.
LED Messages
MONITORING DOES NOT Main
96 MCA communications with LMS1000 lost.
RESPOND Alarm Menu
CONTROLLER FAILURE Main
97 MCA failed (#### = type of memory failure)
#### Alarm Menu
THE CONTROLLER IS Main
98 The MCA is initializing.
INITIALIZING Alarm Menu
System load current above preset adjustable
value (includes distribution loads monitored by
the Distribution Bus Monitoring Circuit Cards
TOTAL LOAD CURRENT Main and any MCA I/O Circuit Card set as
99
ALARM Alarm Menu "Distribution" [other setting choice is
"Auxiliary"]).
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT aaaaaA Displays the alarm limit setpoint and the actual
99A --
NOW AT aaaaaA value of the monitored input.
Sum of load currents monitored by all
Distribution Bus Monitoring Circuit Cards set as
DISTRIBUTION GROUP A Main Group A designation above preset adjustable
100
LOAD ALARM Alarm Menu value.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT aaaaaA Displays the alarm limit setpoint and the actual
100A --
NOW AT aaaaaA value of the monitored input.
Sum of load currents monitored by all
Distribution Bus Monitoring Circuit Cards set as
DISTRIBUTION GROUP B Main Group B designation above preset adjustable
101
LOAD ALARM Alarm Menu value.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
ALARM LIMIT aaaaaA Displays the alarm limit setpoint and the actual
101A --
NOW AT aaaaaA value of the monitored input.
THE DISPLAY DOES NOT Main
102 MCA communications with MCA Display lost.
RESPOND Alarm Menu
Main
103 GO TO FUNCTION MENU Press ENTER to go to this menu.
Alarm Menu
GO BACK TO MENU TREE Main Press ENTER to go to the beginning of the
104
BEGINNING Alarm Menu MCA Menu Tree.
VIEW THE SYSTEM Function
105 Press ENTER to go to this menu.
MEASUREMENTS Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
The voltage of the external (remote) source
connected to the MCA / Router circuit card (for
SYSTEM OUTPUT SENSE MCA alarms and meter reading), if connected.
vv.vvV (REM)
Measurement or
106 or
Menu System output sense voltage (average of all
SYSTEM OUTPUT SENSE
bay's internal sense voltages).
vv.vvV (AVG)
Press ENTER to view individual bay sense
voltages.
External (remote) sense voltage applied to the
Router MCA / Router Circuit Card, if connected. (B# =
ROUTER B# REMOTE Bay Number).
107 Voltage
SENSE vv.vvV
Menu Press UP and DOWN ARROWS to view other
Router Circuit Cards' sense voltages.
Internal sense voltage applied to the Router
Router Circuit Card. (B# = Bay Number).
ROUTER B# INTERNAL
108 Voltage
SENSE vv.vvV Press UP and DOWN ARROWS to view other
Menu
Router Circuit Cards' sense voltages.
Router
GO TO MEASUREMENT
109 Voltage Press ENTER to go to this menu.
MENU
Menu
Router
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
110 Voltage
BEGINNING MCA Menu Tree.
Menu
TOTAL SYSTEM Measurement
111 Total system load current.
LOAD aaaaaA Menu
Total distribution load current (includes
distribution loads monitored by the Distribution
Bus Monitoring Circuit Cards and any MCA I/O
Circuit Card set as "Distribution" [other setting
TOTAL DISTRIBUTION choice is "Auxiliary"]).
LOAD aaaaaA Press ENTER to view individual bay
System
112 or distribution load currents.
Load Menu
TOTAL AUXILIARY
or
LOAD aaaaaA
Total (sum) load current monitored by MCA I/O
Circuit Cards set as "Auxiliary".
Press ENTER to view individual MCA I/O
circuit card load currents.
Total load current monitored by Distribution
DISTRIBUTION GROUP A System
113 Bus Monitoring Circuit Cards set as Group A
LOAD aaaaaA Load Menu
designation.
Total load current monitored by Distribution
DISTRIBUTION GROUP B System
114 Bus Monitoring Circuit Cards set as Group B
LOAD aaaaaA Load Menu
designation.
Total Remote Distribution load current reported
REMOTE SYSTEM System
115 by the LMS when LMS Function Channel 63
LOAD aaaaaA Load Menu
value is greater than zero.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
GO TO MEASUREMENT System
116 Press ENTER to go to this menu.
MENU Load Menu
GO BACK TO MENU TREE System Press ENTER to go to the beginning of the
117
BEGINNING Load Menu MCA Menu Tree.
Sum of load currents monitored by the
Distribution Bus Monitoring Circuit Card.
(B#-P#A/B = Bay Number-Distribution Bus
Monitoring Circuit Card Position Number
DIST. PANEL B#-P#A/B Distribution [Group A or B Designation if applicable.])
118
LOAD aaaaaA Load Menu Press UP and DOWN ARROWS to view other
Distribution Bus Monitoring Circuit Cards' load
currents.
Press ENTER to view individual distribution
device load currents.
Load current monitored by the first MCA I/O
Circuit Card (set as "Distribution" or "Auxiliary"
as determined by what is being displayed on
I/O BOARD B#-P# Distribution
119 line #112). (B#-P# = Bay Number-MCA I/O
LOAD aaaaaA Load Menu Circuit Card Position Number.)
Press UP and DOWN ARROWS to view other
MCA I/O Circuit Cards' load currents.
GO TO SYSTEM LOAD Distribution
120 Press ENTER to go to this menu.
MENU Load Menu
GO BACK TO MENU TREE Distribution Press ENTER to go to the beginning of the
121
BEGINNING Load Menu MCA Menu Tree.
Distribution device identification number and
load current. (F/CB/MISC 50-73 B#-P#A/B =
Distribution Fuse or Circuit Breaker or Bullet Device, Bay
F/CB/MISC 50-73 B#-P#A/B Number-Distribution Device Position Number
122 Load Detail
LOAD aaaaaA
Menu [Group A or B Designation if applicable.])
Press UP and DOWN ARROWS to view other
Distribution Devices' load currents.
Distribution
GO TO DISTRIBUTION
123 Load Detail Press ENTER to go to this menu.
LOAD MENU
Menu
Distribution
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
124 Load Detail
BEGINNING MCA Menu Tree.
Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Total Rectifier Module (PCU) output current.
Press ENTER to view individual Rectifier
Module load currents.
TOTAL PCU OUTPUT or
aaaaaA Total Rectifier Module and legacy rectifier
Measurement
125 or output current when LMS1000 Function
Menu
TOTAL PCU/RECTIFIER Channel #64 reported value is greater than
aaaaaA zero.
Press ENTER to view individual Rectifier
Module load currents and legacy system
current.
Rectifier Module (PCU) output current. (B#-
ID#/N# = Bay Number-Rectifier Module MCA
PCU B#-ID#/N# PCU ID# w/in Bay/Number of Rectifier Modules in
126
aaaaaA Load Menu System).
Press UP and DOWN ARROWS to view other
Rectifier Modules' load currents.
Legacy Rectifier System output current as
RECTIFIER OUTPUT PCU
127 reported by the LMS1000 Function Channel
aaaaaA Load Menu
#64.
GO TO MEASUREMENT PCU
128 Press ENTER to go to this menu.
MENU Load Menu
GO BACK TO MENU TREE PCU Press ENTER to go to the beginning of the
129
BEGINNING Load Menu MCA Menu Tree.
TEMPERATURE SENSOR Measurement Temperature detected by Temperature Sensor,
130
ttt C/F Menu if installed.
Measurement
131 GO TO FUNCTION MENU Press ENTER to go to this menu.
Menu
GO BACK TO MENU TREE Measurement Press ENTER to go to the beginning of the
132
BEGINNING Menu MCA Menu Tree.
Allows you to change the Rectifier Module
FLOAT MODE IS ACTIVE (PCU) output voltage mode.
SET TEST/EQ? 1. Refer to "Changing a Value or Setting"
or in the table at the beginning of this
TEST/EQ MODE ACTIVE chapter.
SET FLOAT? or
or The user tried to set Float Mode while an
Function
133 TEST/EQUALIZE INPUT external test/equalize input signal was being
Menu
IS ACTIVE supplied to the system.
or Note: Test/Equalize Mode requires Power
TURN OFF POWER SHARE Share and Alternate Current Limit to be turned
or off. A message is displayed if Power Share or
TURN OFF ALTERNATE Alternate Current Limit is on. Turn Power
CURRENT LIMIT Share or Alternate Current Limit off first then
return to this menu.
VIEW THE SYSTEM Function
134 Press ENTER to go to this menu.
INVENTORY Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
1 PCU IS
REPORTING Number of Rectifier Modules (PCUs) in MCA
or inventory.
### PCUs ARE Inventory Press ENTER to view individual Rectifier
135
REPORTING Menu Module inventory information.
or or
NO PCUs ARE No Rectifier Modules installed.
INSTALLED
Rectifier Module (PCU) identification number
and output current rating. (B#-ID#/N# = Bay
PCU
PCU B#-ID#/N# Number-Rectifier Module MCA ID# w/in
136 Inventory
RATED aaaaaA Bay/Number of Rectifier Modules in System).
Menu
Press UP and DOWN ARROWS to view other
Rectifier Modules.
PCU
137 GO TO INVENTORY MENU Inventory Press ENTER to go to this menu.
Menu
PCU
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
138 Inventory
BEGINNING MCA Menu Tree.
Menu
Rectifier Module (PCU) Assembly Number.
PCU
B#-ID#/N# ASSY. (B#-ID#/N# = Bay Number-Rectifier Module
139 Inventory
#################### MCA ID# w/in Bay/Number of Rectifier
Detail Menu
Modules in System).
Rectifier Module (PCU) Serial Number. (B#-
PCU
B#-ID#/N# SERIAL ID#/N# = Bay Number-Rectifier Module MCA
140 Inventory
#################### ID# w/in Bay/Number of Rectifier Modules in
Detail Menu
System).
Rectifier Module (PCU) Bootcode Number.
PCU
B#-ID#/N# BOOT (B#-ID#/N# = Bay Number-Rectifier Module
141 Inventory
#################### MCA ID# w/in Bay/Number of Rectifier
Detail Menu
Modules in System).
Rectifier Module (PCU) Software Number.
PCU
B#-ID#/N# SW VER (B#-ID#/N# = Bay Number-Rectifier Module
142 Inventory
#################### MCA ID# w/in Bay/Number of Rectifier
Detail Menu
Modules in System).
PCU PSC (Primary Side Controller) Assembly
PSC B#-ID# ASSEMBLY
143 Inventory Number. (B#-ID# = Bay Number-PSC Position
####################
Detail Menu Number).
PCU
PSC B#-ID# SERIAL # PSC (Primary Side Controller) Serial Number.
144 Inventory
#################### (B#-ID# = Bay Number-PSC Position Number).
Detail Menu
PCU PSC (Primary Side Controller) Bootcode
PSC B#-ID# BOOTCODE
145 Inventory Number. (B#-ID# = Bay Number-PSC Position
####################
Detail Menu Number).
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
PCU PSC (Primary Side Controller) Software
PSC B#-ID# SOFTWARE
146 Inventory Number. (B#-ID# = Bay Number-PSC Position
####################
Detail Menu Number).
PCU
GO TO PCU
147 Inventory Press ENTER to go to this menu.
INVENTORY
Detail Menu
PCU
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
148 Inventory
BEGINNING MCA Menu Tree.
Detail Menu
1 PCU POSITION
IS EMPTY
or
### PCU POSITIONS Inventory Number of empty Rectifier Module (PCU)
149
ARE EMPTY Menu mounting positions in the system.
or
NO PCU POSITIONS
ARE EMPTY
1 DIST. PANEL IS Number of Distribution Bus Monitoring Circuit
REPORTING Cards in MCA inventory.
or Press ENTER to view individual Distribution
## DIST. PANELS ARE Inventory Bus Monitoring Circuit Card inventory
150
REPORTING Menu information.
or or
NO DIST. PANELS ARE No Distribution Bus Monitoring Circuit Cards
INSTALLED installed.
Number of distribution devices this Distribution
Bus Monitoring Circuit Card is monitoring. (B#-
P#A/B = Bay Number-Distribution Bus
PANEL B#-P#A/B INCLUDES Monitoring Circuit Card Position Number
1 POINT Distribution [Group A or B Designation if applicable.])
151 or Inventory
Press UP and DOWN ARROWS to view other
PANEL B#-P#A/B INCLUDES Menu
Distribution Bus Monitoring Circuit Cards'
## POINTS
distribution devices.
Press ENTER to view individual distribution
devices' inventory information.
Distribution
152 GO TO INVENTORY MENU Inventory Press ENTER to go to this menu.
Menu
Distribution
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
153 Inventory
BEGINNING MCA Menu Tree.
Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Distribution device identification number and
type.
(B#-P#A/B = Bay Number-Distribution Device
Distribution Position Number [Group A or B Designation if
POINT B#-P#A/B IS A
154 Inventory
F/CB/PI applicable.])
Detail Menu
(F/CB/PI = Fuse or Circuit Breaker or PlugIn)
Press UP and DOWN ARROWS to view other
Distribution Devices' inventory information.
Distribution Panel Assembly Number.
Distribution
PANEL B#-P#A/B ASSEMBLY (B#-P#A/B = Bay Number-Distribution Bus
155 Inventory
#################### Monitoring Circuit Card Position Number
Detail Menu
[Group A or B Designation if applicable.])
Distribution Panel Serial Number. (B#-P#A/B =
Distribution
PANEL B#-P#A/B SERIAL # Bay Number-Distribution Bus Monitoring Circuit
156 Inventory
#################### Card Position Number [Group A or B
Detail Menu
Designation if applicable.])
Distribution Panel Bootcode Number.
Distribution
PANEL B#-P#A/B BOOTCODE (B#-P#A/B = Bay Number-Distribution Bus
157 Inventory
#################### Monitoring Circuit Card Position Number
Detail Menu
[Group A or B Designation if applicable.])
Distribution Panel Software Number.
Distribution
PANEL B#-P#A/B SOFTWARE (B#-P#A/B = Bay Number-Distribution Bus
158 Inventory
#################### Monitoring Circuit Card Position Number
Detail Menu
[Group A or B Designation if applicable.])
Distribution
GO TO DISTRIBUTION
159 Inventory Press ENTER to go to this menu.
INVENTORY
Detail Menu
Distribution
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
160 Inventory
BEGINNING MCA Menu Tree.
Detail Menu
1 I/O BOARD IS
REPORTING Number of MCA I/O Circuit Cards in MCA
or inventory.
## I/O BOARDS ARE Inventory Press ENTER to view individual MCA I/O
161
REPORTING Menu Circuit Card inventory information.
or or
NO I/O BOARDS ARE No MCA I/O Circuit Cards installed.
INSTALLED
MCA I/O Circuit Card identification number.
I/O Board (B#-P# = Bay Number-I/O Circuit Card Position
I/O BOARD B#-P# IS Number).
162 Inventory
INSTALLED
Menu Press UP and DOWN ARROWS to view other
MCA I/O Circuit Cards' identification numbers.
I/O Board
163 GO TO INVENTORY MENU Inventory Press ENTER to go to this menu.
Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
I/O Board
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
164 Inventory
BEGINNING MCA Menu Tree.
Menu
I/O Board MCA I/O Circuit Card Assembly Number.
BOARD B#-P# ASSEMBLY
165 Inventory (B#-P# = Bay Number-MCA I/O Circuit Card
####################
Detail Menu Position Number).
I/O Board MCA I/O Circuit Card Serial Number.
BOARD B#-P# SERIAL #
166 Inventory (B#-P# = Bay Number-MCA I/O Circuit Card
####################
Detail Menu Position Number).
I/O Board MCA I/O Circuit Card Bootcode Number.
BOARD B#-P# BOOTCODE
167 Inventory (B#-P# = Bay Number-MCA I/O Circuit Card
####################
Detail Menu Position Number).
I/O Board MCA I/O Circuit Card Software Number.
BOARD B#-P# SOFTWARE
168 Inventory (B#-P# = Bay Number-MCA I/O Circuit Card
####################
Detail Menu Position Number).
I/O Board
GO TO I/O BOARD
169 Inventory Press ENTER to go to this menu.
INVENTORY
Detail Menu
I/O Board
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
170 Inventory
BEGINNING MCA Menu Tree.
Detail Menu
1 ROUTER IS
REPORTING Number of Router Circuit Cards in MCA
or inventory.
## ROUTERS ARE Inventory Press ENTER to view individual Router Circuit
171
REPORTING Menu Card inventory information.
or or
NO ROUTERS ARE No Router Circuit Cards installed.
INSTALLED
Router Circuit Card identification number. (B#
Router = Bay Number).
ROUTER B# IS
172 Inventory
INSTALLED Press UP and DOWN ARROWS to view other
Menu
Router Circuit Cards' identification numbers.
Router
173 GO TO INVENTORY MENU Inventory Press ENTER to go to this menu.
Menu
Router
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
174 Inventory
BEGINNING MCA Menu Tree.
Menu
Router
ROUTER B# ASSEMBLY Router Assembly Number.
175 Inventory
#################### (B# = Bay Number).
Detail Menu
Router
ROUTER B# SERIAL # Router Serial Number.
176 Inventory
#################### (B# = Bay Number).
Detail Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Router
ROUTER B# BOOTCODE Router Bootcode Number.
177 Inventory
#################### (B# = Bay Number).
Detail Menu
Router
ROUTER B# SOFTWARE Router Software Number.
178 Inventory
#################### (B# = Bay Number).
Detail Menu
Router
GO TO ROUTER
179 Inventory Press ENTER to go to this menu.
INVENTORY
Detail Menu
Router
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
180 Inventory
BEGINNING MCA Menu Tree.
Detail Menu
1 RELAY BOARD IS Number of MCA Customer Alarm Relay Circuit
REPORTING Cards in MCA inventory.
or Press ENTER to view individual MCA
## RELAY BOARDS ARE Inventory Customer Alarm Relay Circuit Card inventory
181
REPORTING Menu information.
or or
NO RELAY BOARDS ARE No MCA Customer Alarm Relay Circuit Cards
INSTALLED installed.
MCA Customer Alarm Relay Circuit Card
identification number. (B#-P# = Bay Number-
Relay
RELAY BOARD B#-P# IS Relay Circuit Card Position Number).
182 Inventory
INSTALLED Press UP and DOWN ARROWS to view other
Menu
MCA Customer Alarm Relay Circuit Cards'
identification numbers.
Relay
183 GO TO INVENTORY MENU Inventory Press ENTER to go to this menu.
Menu
Relay
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
184 Inventory
BEGINNING MCA Menu Tree.
Menu
MCA Customer Alarm Relay Circuit Card
Relay
BOARD B#-P# ASSEMBLY Assembly Number. (B#-P# = Bay
185 Inventory
#################### Number-MCA Customer Alarm Relay Circuit
Detail Menu
Card Position Number).
MCA Customer Alarm Relay Circuit Card Serial
Relay
BOARD B#-P# SERIAL # Number. (B#-P# = Bay Number-MCA
186 Inventory
#################### Customer Alarm Relay Circuit Card Position
Detail Menu
Number).
MCA Customer Alarm Relay Circuit Card
Relay
BOARD B#-P# BOOTCODE Bootcode Number. (B#-P# = Bay
187 Inventory
#################### Number-MCA Customer Alarm Relay Circuit
Detail Menu
Card Position Number).
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
MCA Customer Alarm Relay Circuit Card
Relay
BOARD B#-P# SOFTWARE Software Number. (B#-P# = Bay Number-MCA
188 Inventory
#################### Customer Alarm Relay Circuit Card Position
Detail Menu
Number).
Relay
GO TO RELAY BOARD
189 Inventory Press ENTER to go to this menu.
INVENTORY
Detail Menu
Relay
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
190 Inventory
BEGINNING MCA Menu Tree.
Detail Menu
TEMPERATURE SENSOR
REPORTING Temperature Sensor is in MCA inventory.
Inventory
191 or or
Menu
NO TEMPERATURE No Temperature Sensor installed.
SENSOR
MONITORING IS
REPORTING LMS1000 is communicating with the MCA.
Inventory
192 or or
Menu
NO MONITORING IS No LMS1000 installed in the MCA's inventory.
INSTALLED
Monitoring
MONITORING ASSEMBLY Specification number (Spec. No.) of the
193 Inventory
#################### LMS1000 Main CPU circuit card.
Detail Menu
Router
MONITORING SERIAL # Serial number of the LMS1000 Main CPU
194 Inventory
#################### circuit card.
Detail Menu
Monitoring
MONITORING BOOTCODE Software bootcode revision number of the
195 Inventory
#################### LMS1000 Main CPU circuit card.
Detail Menu
Monitoring
MONITORING SOFTWARE Software version number of the LMS1000 Main
196 Inventory
#################### CPU circuit card.
Detail Menu
Monitoring
197 GO TO INVENTORY MENU Inventory Press ENTER to go to this menu.
Detail Menu
Monitoring
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
198 Inventory
BEGINNING MCA Menu Tree.
Detail Menu
Indicates if an external (remote) voltage input
SENSE VOLTAGE IS (for MCA alarms and meter reading) is applied
REMOTE INPUT to the MCA / Router circuit card,
Inventory
199 or or
Menu
SENSE VOLTAGE IS if the voltage input for MCA alarms and meter
AVERAGED reading is the average of each bay's sense
voltages (no external input applied).
CONTROLLER ASSEMBLY Inventory Specification number (Spec. No.) of the
200
#################### Menu MCA/Router circuit card.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
CONTROLLER SERIAL # Controller
201 Serial number of the MCA/Router circuit card.
#################### Detail Menu
CONTROLLER BOOTCODE Controller Software bootcode version number of the
202
#################### Detail Menu MCA/Router circuit card.
CONTROLLER SOFTWARE Controller Software version number of the MCA/Router
203
#################### Detail Menu circuit card.
DISPLAY ASSEMBLY Controller Specification number (Spec. No.) of the Display
204
#################### Detail Menu circuit card.
DISPLAY SERIAL # Controller
205 Serial number of the Display circuit card.
#################### Detail Menu
DISPLAY BOOTCODE Controller Software bootcode version number of the
206
#################### Detail Menu Display circuit card.
DISPLAY SOFTWARE Controller Software version number of the Display circuit
207
#################### Detail Menu card.
Controller
208 GO TO INVENTORY MENU Press ENTER to go to this menu.
Detail Menu
GO BACK TO MENU TREE Controller Press ENTER to go to the beginning of the
209
BEGINNING Detail Menu MCA Menu Tree.
Allows resetting the inventory count when an
inventory item is removed from the system by
the user.
When an inventory item is removed from
the system, an alarm will be reported until
"UPDATE THE INVENTORY" is entered.
Inventory Example, if a Rectifier Module (PCU) is
210 UPDATE THE INVENTORY
Menu removed from the system, the Rectifier
Module will not be removed from the
MCA's inventory until "UPDATE THE
INVENTORY" operation is completed.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
Inventory
211 GO TO FUNCTION MENU Press ENTER to go to this menu.
Menu
GO BACK TO MENU TREE Inventory Press ENTER to go to the beginning of the
212
BEGINNING Menu MCA Menu Tree.
ADJUST THE SYSTEM Function Press ENTER to go to the System Adjustment
213
VOLTS & AMPS Menu Menu.
Allows you to change the Float Output Voltage
System set point.
FLOAT SETPOINT
214 Adjustment 1. Refer to "Changing a Value or Setting"
= vv.vvV
Menu in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Allows you to change the Test/Equalize Output
System Voltage set point.
TEST/EQUALIZE
215 Adjustment 1. Refer to "Changing a Value or Setting"
= vv.vvV
Menu in the table at the beginning of this
chapter.
POWER SHARE IS OFF
TURN IT ON? Allows you to enable or disable the Power
or Share or Alternate Current Limit feature.
POWER SHARE IS ON
1. Refer to "Changing a Value or Setting"
TURN IT OFF?
in the table at the beginning of this
or
chapter.
ALT. LIMIT IS OFF
or
TURN IT ON?
or System The Power Share feature requires
216 ALT. LIMIT IS ON Adjustment Temperature Compensation and Alternate
TURN IT OFF? Menu Current Limit to be turned off. The Alternate
or Current Limit feature requires Temperature
TURN OFF POWER SHARE Compensation and Power Share to be turned
or off. A message is displayed if Temperature
TURN OFF ALTERNATE Compensation, Power Share, or Alternate
CURRENT LIMIT Current Limit is on. Turn the feature off first,
or then return to this menu to enable Power Share
TURN OFF TEMPERATURE or Alternate Current Limit.
COMPENSATION
Enter the percentage value of the total capacity
of THIS Power System that will initially feed the
load. This value must be set to ensure that the
System current delivered by THIS Power System is
PS INITIAL CAPACITY lower than the total load current from the two
217 Adjustment
LIMIT = ##%
Menu DC power systems.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
Enter the value that will be added to the float
voltage to ensure THIS Power System will
initially carry the load. This value must be
higher than the sum of the voltage drop in the
cables connecting the two systems in parallel
and the output voltage regulation specific to the
System rectifiers of the existing DC power system. If
PS VOLTAGE OFFSET
218 Adjustment the sense leads are connected to the same
= v.vV sensing points as the existing DC power
Menu
system, the Voltage Offset should take into
consideration the output voltage regulation
only.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Enter the percentage value of the rated rectifier
output capacity to which the rectifier output
System current should be limited.
ALTERNATE CURRENT LIMIT
218A Adjustment
= ##% 1. Refer to "Changing a Value or Setting"
Menu
in the table at the beginning of this
chapter.
Allows you to change the High Voltage
System Shutdown set point.
HI VOLTAGE SHUTDOWN
219 Adjustment 1. Refer to "Changing a Value or Setting"
= vv.vvV
Menu in the table at the beginning of this
chapter.
Allows you to temporarily change the High
Voltage Shutdown set point to another value
(such as system voltage) to test the high
voltage shutdown circuits.
1. Press ENTER and ALARM CUTOFF
(at the same time).
TEST H.V. SHUTDOWN 2. Press YES / + / i or NO / - to increment
= vv.vvV System or decrement, respectively, the High
220 Adjustment Voltage Shutdown value displayed.
LOSS IS POSSIBLE. GO Menu 3. A WARNING appears. Press ENTER
AHEAD ANYWAY? and ALARM CUTOFF (at the same
time) if you wish to proceed. This
immediately changes the HVS setting.
U U
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
System
223 GO TO FUNCTION MENU Adjustment Press ENTER to go to this menu.
Menu
System
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
224 Adjustment
BEGINNING MCA Menu Tree.
Menu
ADJUST THE ALARM Function Press ENTER to go to the Alarm Adjustment
225
SETPOINTS Menu Menu.
Allows you to change the System High Voltage
Alarm #1 Alarm set point.
SYSTEM HI VOLTAGE #1
226 Adjustment 1. Refer to "Changing a Value or Setting"
= vv.vvV
Menu in the table at the beginning of this
chapter.
Allows you to change the System High Voltage
Alarm #2 Alarm set point.
SYSTEM HI VOLTAGE #2
227 Adjustment 1. Refer to "Changing a Value or Setting"
= vv.vvV
Menu in the table at the beginning of this
chapter.
Allows you to change the Battery on Discharge
Alarm Alarm set point.
BATTERY ON DISCHARGE
228 Adjustment 1. Refer to "Changing a Value or Setting"
= vv.vvV
Menu in the table at the beginning of this
chapter.
Allows you to change the Very Low Voltage
Alarm Alarm set point.
VERY LOW VOLTAGE
229 Adjustment 1. Refer to "Changing a Value or Setting"
= vv.vvV
Menu in the table at the beginning of this
chapter.
Allows you to change the Total Load Current
Alarm Alarm set point.
TOTAL LOAD CURRENT
230 Adjustment 1. Refer to "Changing a Value or Setting"
= aaaaaA
Menu in the table at the beginning of this
chapter.
Allows you to change the Distribution Group A
Alarm Load Current Alarm set point.
DISTRIBUTION GROUP A
231 Adjustment 1. Refer to "Changing a Value or Setting"
= aaaaaA
Menu in the table at the beginning of this
chapter.
Allows you to change the Distribution Group B
Alarm Load Current Alarm set point.
DISTRIBUTION GROUP B
232 Adjustment 1. Refer to "Changing a Value or Setting"
= aaaaaA
Menu in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Allows you to change the High Temperature #1
Alarm set point, or disable the alarm.
1. Refer to "Changing a Value or Setting"
HIGH TEMPERATURE #1 in the table at the beginning of this
= ttt C/F Alarm chapter.
233 or Adjustment Note: To disable the feature, press
NO HIGH TEMPERATURE Menu YES / + / i when in the change setting
#1 ALARM mode to scroll to NO HIGH
TEMPERATURE #1 ALARM
(displayed when you scroll up to
"100 C").
Allows you to change the High Temperature #2
Alarm set point, or disable the alarm.
1. Refer to "Changing a Value or Setting"
HIGH TEMPERATURE #2 in the table at the beginning of this
= ttt C/F Alarm chapter.
234 or Adjustment Note: To disable the feature, press
NO HIGH TEMPERATURE Menu YES / + / i when in the change setting
#2 ALARM mode to scroll to NO HIGH
TEMPERATURE #2 ALARM
(displayed when you scroll up to
"100 C").
Allows you to change the Low Temperature #1
Alarm set point, or disable the alarm.
1. Refer to "Changing a Value or
LOW TEMPERATURE #1 Setting" in the table at the
= ttt C/F Alarm beginning of this chapter.
235 or Adjustment Note: To disable the feature, press
NO LOW TEMPERATURE Menu NO / - when in the change setting
#1 ALARM mode to scroll to NO LOW
TEMPERATURE #1 ALARM
(displayed when you scroll down to
"-50 C").
Allows you to change the Low Temperature #2
Alarm set point, or disable the alarm.
1. Refer to "Changing a Value or Setting"
LOW TEMPERATURE #2 in the table at the beginning of this
= ttt C/F Alarm chapter.
236 or Adjustment Note: To disable the feature, press
NO LOW TEMPERATURE Menu NO / - when in the change setting
#2 ALARM mode to scroll to NO LOW
TEMPERATURE #2 ALARM
(displayed when you scroll down to
"-50 C").
Alarm
237 GO TO FUNCTION MENU Adjustment Press ENTER to go to this menu.
Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Alarm
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
238 Adjustment
BEGINNING MCA Menu Tree.
Menu
TURN PCUs ON OR OFF
or Function Press ENTER to go to the Rectifier Module
239
ENERGY MANAGEMENT IS Menu (PCU) Enable Menu.
IN CONTROL
Allows you to turn a Rectifier Module (PCU)
ON or OFF (Local TR inhibit feature).
1. Press the UP and DOWN ARROWS to
navigate to the Rectifier Module to turn
ON or OFF (B#-ID#/N# = Bay Number-
PCU B#-ID#/N# ON Rectifier Module MCA ID# w/in
TURN IT OFF? Bay/Number of Rectifier Modules in
or System).
PCU B#-ID#/N# OFF PCU 2. Press ENTER and ALARM CUTOFF
240
TURN IT ON? Enable Menu (at the same time) to change the TR
or setting for this Rectifier Module.
ENERGY MANAGEMENT 3. At the "ARE YOU SURE?" prompt,
IN CONTROL press either YES / + / i to accept the
new setting, or NO / - to cancel this
operation without changing the existing
setting.
Note: Rectifier Modules cannot be turned on
or off if energy management is active.
PCU
241 GO TO FUNCTION MENU Press ENTER to go to this menu.
Enable Menu
GO BACK TO MENU TREE PCU Press ENTER to go to the beginning of the
242
BEGINNING Enable Menu MCA Menu Tree.
CHANGE CONFIGURATION Function
243 Press ENTER to go to the Configure Menu.
PARAMETERS Menu
Allows you to change the MCA I/O circuit
CHANGE I/O BOARD Configure card(s) configurable parameters.
244
PARAMETERS Menu Press ENTER to configure the MCA I/O circuit
cards.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Select the MCA I/O circuit card to be
configured, and designate the analog input for
this MCA I/O circuit card as "Distribution" or
"Auxiliary". The MCA displays the AUXILIARY
load currents in a separate menu, the
DISTRIBUTION load currents are added to the
Distribution Menus.
ANALOG INPUT B#-P# IS 1. Press the UP and DOWN ARROWS to
DISTRIBUTION I/O Board navigate to the MCA I/O circuit card to
245 or Configuration configure (B#-P# = Bay Number-MCA
ANALOG INPUT B#-P# IS Menu I/O Circuit Card Position Number).
AUXILIARY 2. Press ENTER and ALARM CUTOFF
(at the same time) to change the
setting for this MCA I/O circuit card.
3. At the "ARE YOU SURE?" prompt,
press either YES / + / i to accept the
new setting, or NO / - to cancel this
operation without changing the existing
setting.
Select the MCA I/O circuit card to be
configured, and set the scale factor for the
analog input on this MCA I/O circuit card.
1. Press the UP and DOWN ARROWS to
I/O Board
ANALOG INPUT B#-P# navigate to the MCA I/O circuit card to
246 Configuration
50mV = aaaaaA configure (B#-P# = Bay Number-MCA
Menu
I/O Circuit Card Position Number).
2. Refer to "Changing a Value or Setting"
in the table at the beginning of this
document to complete the operation.
Select the MCA I/O circuit card to be
configured, and set the scale factor for the
analog output on this MCA I/O circuit card.
1. Press the UP and DOWN ARROWS to
I/O Board
ANALOG OUTPUT B#-P# navigate to the MCA I/O circuit card to
247 Configuration
50mV = aaaaaA configure (B#-P# = Bay Number-MCA
Menu
I/O Circuit Card Position Number).
2. Refer to "Changing a Value or Setting"
in the table at the beginning of this
document to complete the operation.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Select the MCA I/O circuit card to be
configured, and set the alarm state for each
binary input on this MCA I/O circuit card.
1. Press the UP and DOWN ARROWS to
navigate to the MCA I/O circuit card
and binary input to configure (B#-P#-I#
BINARY INPUT B#-P#-I# = Bay Number-MCA I/O Circuit Card
ALARM = CLOSED I/O Board Position Number-Binary Input
248 or Configuration Number).
BINARY INPUT B#-P#-I# Menu 2. Press ENTER and ALARM CUTOFF
ALARM = OPEN (at the same time) to change the
setting for this MCA I/O circuit card.
3. At the "ARE YOU SURE?" prompt,
press either YES / + / i to accept the
new setting, or NO / - to cancel this
operation without changing the existing
setting.
I/O Board
249 GO TO CONFIGURE MENU Configuration Press ENTER to go to this menu.
Menu
I/O Board
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
250 Configuration
BEGINNING MCA Menu Tree.
Menu
Allows you to enable the MCA Audible Alarm
feature and set the Audible Alarm Cutoff Reset
Time Period set point, or disable the feature.
AUDIBLE SILENT TIME 1. Refer to "Changing a Value or Setting"
= mm MINUTES in the table at the beginning of this
Configure
251 or chapter.
Menu
AUDIBLE ALARMS STAY Note: To disable the feature, press
SILENCED NO / - when in the change setting
mode to scroll to AUDIBLE ALARMS
STAY SILENCED (displayed when you
scroll down to "zero minutes").
Allows you to enable the Rectifier Module
(PCU) Sequencing feature and set the Rectifier
Module (PCU) Sequencing Delay set point, or
disable the feature.
PCU SEQUENCING IS 1. Refer to "Changing a Value or Setting"
DISABLED in the table at the beginning of this
Configure
252 or chapter.
Menu
PCU SEQUENCING DELAY Note: To disable the feature, press
= ss SECONDS NO / - when in the change setting
mode to scroll to Rectifier
SEQUENCING IS DISABLED
(displayed when you scroll down to
"zero seconds").
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Allows you to enable the Manual Timed
Test/Equalize feature and set the Timed
Test/Equalize set point, or disable the feature.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
Note: To disable the feature, press
NO / - when in the change setting
mode to scroll to TEST/EQUALIZE
STOP IS MANUAL (displayed when
you scroll down to "zero hours"). This
TEST EQUALIZE IS DISABLED indicates the manually initiated timed
or test/equalize feature is disabled and
MANUAL TEST/EQUALIZE the system must be manually returned
= hh HOURS to the float mode if placed in the
or test/equalize mode.
TEST/EQUALIZE STOP or
IS MANUAL If manually initiated timed test/equalize feature
Configure
253 or is enabled and the system is placed in the
Menu
END TEST/EQUALIZE IN test/equalize mode (via the MCA interface),
hh.hh HOURS remaining test/equalize time is displayed.
or Note: When TEST/EQUALIZE STOP IS
TURN OFF POWER SHARE MANUAL or END TEST/EQUALIZE IN hhh.hh
or HOURS is being displayed, press and release
TURN OFF ALTERNATE ENTER and ALARM CUTOFF simultaneously
CURRENT LIMIT to change the MANUAL TEST/EQUALIZE = hh
HOURS setting.
or
When the Power Share or Alternate Current
Limit feature is enabled, the system cannot be
placed in the Test/Equalize mode.
Note: Test/Equalize Mode requires Power
Share and Alternate Current Limit to be turned
off. A message is displayed if Power Share or
Alternate Current Limit is on. Turn Power
Share or Alternate Current Limit off first then
return to this menu.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Allows you to enable the Auto Test/Equalize
feature and set the Auto Test/Equalize
Multiplier set point, or disable the feature.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
AUTO EQUALIZE IS Note: To disable the feature, press
DISABLED NO / - when in the change setting
or mode to scroll to AUTO EQUALIZE IS
AUTO EQUALIZE FOR ## DISABLED (displayed when you scroll
x DISCHARGE down to "zero x discharge").
or
Configure or
254 END AUTO EQUALIZE IN
Menu Displays remaining auto test/equalize time if an
hhh.hh HOURS
auto test/equalize is in process.
or
TURN OFF POWER SHARE or
or When the Power Share or Alternate Current
TURN OFF ALTERNATE Limit feature is enabled, the system cannot be
CURRENT LIMIT placed in the Test/Equalize mode.
Note: Test/Equalize Mode requires Power
Share and Alternate Current Limit to be turned
off. A message is displayed if Power Share or
Alternate Current Limit is on. Turn Power
Share or Alternate Current Limit off first then
return to this menu.
Allows you to define a Relay Function Channel
DEFINE RELAY Configure by assigning alarm conditions to a specific
255
FUNCTIONS Menu Relay Function Channel.
Press ENTER to define relay functions.
Select the Relay Function Channel to be
defined.
1. Press the UP and DOWN ARROWS to
navigate to the desired Relay Function
Relay Channel. (A# = Relay Function
DEFINE RELAY Channel Number.)
256 Function
FUNCTION A#
Menu 2. Press ENTER to define the selected
Relay Function Channel.
Note: See the table in Section 5876
(Installation Instructions) for the MCA default
configuration.
Relay
257 GO TO CONFIGURE MENU Function Press ENTER to go to this menu.
Menu
Relay
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
258 Function
BEGINNING MCA Menu Tree.
Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Select whether the relay(s) assigned to this
CHECKED CONDITIONS Relay Function Channel will energize or
DE-ENERGIZE Relay deenergize for any condition checked
Function
259 or (selected) below.
Definition
CHECKED CONDITIONS 1. Refer to "Changing a Value or Setting"
Menu
ENERGIZE in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
EMERGENCY STOP
INPUT ACTIVE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
260 or
Definition symbol.
EMERGENCY STOP Menu 1. Refer to "Changing a Value or Setting"
INPUT ACTIVE
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
HI VOLTAGE SHUTDOWN
INPUT ACTIVE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
261 or
Definition symbol.
HI VOLTAGE SHUTDOWN Menu 1. Refer to "Changing a Value or Setting"
INPUT ACTIVE
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
ALTERNATE CURRENT
LIMIT ACTIVE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
261A or
Definition symbol.
ALTERNATE CURRENT Menu 1. Refer to "Changing a Value or Setting"
LIMIT ACTIVE
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
SYSTEM VOLTAGE IS
VERY LOW Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
262 or
Definition symbol.
SYSTEM VOLTAGE IS Menu 1. Refer to "Changing a Value or Setting"
VERY LOW
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
SYSTEM BATTERY ON
DISCHARGE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
263 or
Definition symbol.
SYSTEM BATTERY ON Menu 1. Refer to "Changing a Value or Setting"
DISCHARGE
in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
This condition is selected when the
(checkmark) symbol is displayed.
SYSTEM HIGH VOLTAGE
#1 ALARM Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
264 or
Definition symbol.
SYSTEM HIGH VOLTAGE Menu 1. Refer to "Changing a Value or Setting"
#1 ALARM
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
SYSTEM HIGH VOLTAGE
#2 ALARM Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
265 or
Definition symbol.
SYSTEM HIGH VOLTAGE Menu 1. Refer to "Changing a Value or Setting"
#2 ALARM
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
1 SYSTEM BREAKER OR
FUSE ALARM Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
266 or
Definition symbol.
1 SYSTEM BREAKER OR Menu 1. Refer to "Changing a Value or Setting"
FUSE ALARM
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
2+ SYSTEM BREAKER &
FUSE ALARMS Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
267 or
Definition symbol.
2+ SYSTEM BREAKER & Menu 1. Refer to "Changing a Value or Setting"
FUSE ALARMS
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
AC POWER IS OFF TO
1 PCU Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
268 or
Definition symbol.
AC POWER IS OFF TO Menu 1. Refer to "Changing a Value or Setting"
1 PCU
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
AC POWER IS OFF TO
2+ PCUs Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
269 or
Definition symbol.
AC POWER IS OFF TO Menu 1. Refer to "Changing a Value or Setting"
2+ PCUs
in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
This condition is selected when the
(checkmark) symbol is displayed.
AC POWER IS OFF TO
ALL PCUs Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
270 or
Definition symbol.
AC POWER IS OFF TO Menu 1. Refer to "Changing a Value or Setting"
ALL PCUs
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
1 PCU FAILURE
ANY TYPE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
271 or
Definition symbol.
1 PCU FAILURE Menu 1. Refer to "Changing a Value or Setting"
ANY TYPE
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
2+ PCU FAILURES
ANY TYPE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
272 or
Definition symbol.
2+ PCU FAILURES Menu 1. Refer to "Changing a Value or Setting"
ANY TYPE
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
This condition is deselected when a space is
displayed instead of the (checkmark)
1 PCU FAILURE
Relay symbol.
'MAJOR' TYPE
Function 1. Refer to "Changing a Value or Setting"
273 or
Definition in the table at the beginning of this
1 PCU FAILURE Menu chapter.
'MAJOR' TYPE
Note: Thermal Current Limit, 1 Fan Failure,
High Ambient Temperature, and Sense Loss
are 'Minor' alarm conditions. All other Rectifier
Module alarms are 'Major' alarm conditions.
This condition is selected when the
(checkmark) symbol is displayed.
This condition is deselected when a space is
displayed instead of the (checkmark)
2+ PCU FAILURES
'MAJOR' TYPE Relay symbol.
Function 1. Refer to "Changing a Value or Setting"
274 or
Definition in the table at the beginning of this
2+ PCU FAILURES Menu chapter.
'MAJOR' TYPE
Note: Thermal Current Limit, 1 Fan Failure,
High Ambient Temperature, and Sense Loss
are 'Minor' alarm conditions. All other Rectifier
Module alarms are 'Major' alarm conditions.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
This condition is selected when the
(checkmark) symbol is displayed.
This condition is deselected when a space is
displayed instead of the (checkmark)
1 PCU FAILURE
Relay symbol.
'MINOR' TYPE
Function 1. Refer to "Changing a Value or Setting"
275 or
Definition in the table at the beginning of this
1 PCU FAILURE Menu chapter.
'MINOR' TYPE
Note: Thermal Current Limit, 1 Fan Failure,
High Ambient Temperature, and Sense Loss
are 'Minor' alarm conditions. All other Rectifier
Module alarms are 'Major' alarm conditions.
This condition is selected when the
(checkmark) symbol is displayed.
This condition is deselected when a space is
displayed instead of the (checkmark)
2+ PCU FAILURES
'MINOR' TYPE Relay symbol.
Function 1. Refer to "Changing a Value or Setting"
276 or
Definition in the table at the beginning of this
2+ PCU FAILURES Menu chapter.
'MINOR' TYPE
Note: Thermal Current Limit, 1 Fan Failure,
High Ambient Temperature, and Sense Loss
are 'Minor' alarm conditions. All other Rectifier
Module alarms are 'Major' alarm conditions.
This condition is selected when the
(checkmark) symbol is displayed.
NO PCUs ARE
IN INVENTORY Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
277 or
Definition symbol.
NO PCUs ARE Menu 1. Refer to "Changing a Value or Setting"
IN INVENTORY
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
1 DIST. PANEL
FAILURE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
278 or
Definition symbol.
1 DIST. PANEL Menu 1. Refer to "Changing a Value or Setting"
FAILURE
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
2+ DIST. PANEL
FAILURES Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
279 or
Definition symbol.
2+ DIST. PANEL Menu 1. Refer to "Changing a Value or Setting"
FAILURES
in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
This condition is selected when the
(checkmark) symbol is displayed.
NO DIST. PANELS
IN INVENTORY Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
280 or
Definition symbol.
NO DIST. PANELS Menu 1. Refer to "Changing a Value or Setting"
IN INVENTORY
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
1 I/O BOARD
FAILURE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
281 or
Definition symbol.
1 I/O BOARD Menu 1. Refer to "Changing a Value or Setting"
FAILURE
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
2+ I/O BOARD
FAILURES Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
282 or
Definition symbol.
2+ I/O BOARD Menu 1. Refer to "Changing a Value or Setting"
FAILURES
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
NO I/O BOARDS ARE
IN INVENTORY Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
283 or
Definition symbol.
NO I/O BOARDS ARE Menu 1. Refer to "Changing a Value or Setting"
IN INVENTORY
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
1 ROUTER FAILURE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
284 or
Definition symbol.
1 ROUTER FAILURE Menu 1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
2+ ROUTER FAILURES Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
285 or
Definition symbol.
2+ ROUTER FAILURES Menu 1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
This condition is selected when the
(checkmark) symbol is displayed.
NO ROUTERS ARE
IN INVENTORY Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
286 or
Definition symbol.
NO ROUTERS ARE Menu 1. Refer to "Changing a Value or Setting"
IN INVENTORY
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
1 RELAY BOARD
FAILURE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
287 or
Definition symbol.
1 RELAY BOARD Menu 1. Refer to "Changing a Value or Setting"
FAILURE
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
2+ RELAY BOARD
FAILURES Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
288 or
Definition symbol.
2+ RELAY BOARD Menu 1. Refer to "Changing a Value or Setting"
FAILURES
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
NO RELAY BOARDS ARE
IN INVENTORY Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
289 or
Definition symbol.
NO RELAY BOARDS ARE Menu 1. Refer to "Changing a Value or Setting"
IN INVENTORY
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
HIGH TEMPERATURE #1
ALARM Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
290 or
Definition symbol.
HIGH TEMPERATURE #1 Menu 1. Refer to "Changing a Value or Setting"
ALARM
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
HIGH TEMPERATURE #2
ALARM Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
291 or
Definition symbol.
HIGH TEMPERATURE #2 Menu 1. Refer to "Changing a Value or Setting"
ALARM
in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
This condition is selected when the
(checkmark) symbol is displayed.
LOW TEMPERATURE #1
ALARM Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
292 or
Definition symbol.
LOW TEMPERATURE #1 Menu 1. Refer to "Changing a Value or Setting"
ALARM
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
LOW TEMPERATURE #2
ALARM Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
293 or
Definition symbol.
LOW TEMPERATURE #2 Menu 1. Refer to "Changing a Value or Setting"
ALARM
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
TEMPERATURE SENSOR
NO SIGNAL Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
294 or
Definition symbol.
TEMPERATURE SENSOR Menu 1. Refer to "Changing a Value or Setting"
NO SIGNAL
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
This condition is deselected when a space is
displayed instead of the (checkmark)
MAJOR MONITORING symbol.
ALARM(S) Relay
Function 1. Refer to "Changing a Value or Setting"
295 or in the table at the beginning of this
Definition
MAJOR MONITORING chapter.
Menu
ALARM(S) Note: If any of these LMS1000 conditions are
selected to contribute to an MCA alarm, the
User must ensure that the LMS1000 is
programmed so that the MCA does not
contribute to the LMS1000 condition.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
This condition is selected when the
(checkmark) symbol is displayed.
This condition is deselected when a space is
displayed instead of the (checkmark)
MINOR MONITORING symbol.
ALARM(S) Relay
1. Refer to "Changing a Value or Setting"
Function
296 or in the table at the beginning of this
Definition
MINOR MONITORING chapter.
Menu
ALARM(S) Note: If any of these LMS1000 conditions are
selected to contribute to an MCA alarm, the
User must ensure that the LMS1000 is
programmed so that the MCA does not
contribute to the LMS1000 condition.
This condition is selected when the
(checkmark) symbol is displayed.
This condition is deselected when a space is
displayed instead of the (checkmark)
All Monitoring LED symbol.
Messages Relay
Function 1. Refer to "Changing a Value or Setting"
297 or in the table at the beginning of this
Definition
All Monitoring LED chapter.
Menu
Messages Note: If any of these LMS1000 conditions are
selected to contribute to an MCA alarm, the
User must ensure that the LMS1000 is
programmed so that the MCA does not
contribute to the LMS1000 condition.
This condition is selected when the
(checkmark) symbol is displayed.
MONITORING DOES NOT
RESPOND Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
298 or
Definition symbol.
MONITORING DOES NOT Menu 1. Refer to "Changing a Value or Setting"
RESPOND
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
CONTROLLER FAILURE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
299 or
Definition symbol.
CONTROLLER FAILURE Menu 1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
This condition is selected when the
THE CONTROLLER IS (checkmark) symbol is displayed.
INITIALIZING Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
300 or
Definition symbol.
THE CONTROLLER IS Menu 1. Refer to "Changing a Value or Setting"
INITIALIZING in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
TOTAL LOAD CURRENT
ALARM Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
301 or
Definition symbol.
TOTAL LOAD CURRENT Menu 1. Refer to "Changing a Value or Setting"
ALARM
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
DIST. GROUP A
LOAD ALARM Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
302 or
Definition symbol.
DIST. GROUP A Menu 1. Refer to "Changing a Value or Setting"
LOAD ALARM
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
DIST. GROUP B
LOAD ALARM Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
303 or
Definition symbol.
DIST. GROUP B Menu 1. Refer to "Changing a Value or Setting"
LOAD ALARM
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
THE DISPLAY DOES
NOT RESPOND Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
304 or
Definition symbol.
THE DISPLAY DOES Menu 1. Refer to "Changing a Value or Setting"
NOT RESPOND
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
TEST/EQUALIZE MODE
IS ACTIVE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
305 or
Definition symbol.
TEST/EQUALIZE MODE Menu 1. Refer to "Changing a Value or Setting"
IS ACTIVE
in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
This condition is selected when the
(checkmark) symbol is displayed.
THE AUDIBLE ALARM
IS ACTIVE Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
306 or
Definition symbol.
THE AUDIBLE ALARM Menu 1. Refer to "Changing a Value or Setting"
IS ACTIVE
in the table at the beginning of this
chapter.
This condition is selected when the
(checkmark) symbol is displayed.
AUDIBLE ALARMS ARE
SILENCED Relay This condition is deselected when a space is
Function displayed instead of the (checkmark)
307 or
Definition symbol.
AUDIBLE ALARMS ARE Menu 1. Refer to "Changing a Value or Setting"
SILENCED
in the table at the beginning of this
chapter.
Relay
GO TO RELAY FUNCTION Function
308 Press ENTER to go to this menu.
MENU Definition
Menu
Relay
GO BACK TO MENU TREE Function Press ENTER to go to the beginning of the
309
BEGINNING Definition MCA Menu Tree.
Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Set, activate, monitor, or stop the progress of
the MCA Customer Alarm Relay Test Feature.
1. With START RELAY FUNCTION TEST
being displayed, press ENTER and
ALARM CUTOFF (at the same time).
START RELAY FUNCTION
TEST 2. Press the UP and DOWN ARROWS to
or select a time period for each Relay
TIME PER FUNCTION Function Channel test or select NO
= hh:mm:ss TIMEOUT.
or 3. Press ENTER.
TIME PER FUNCTION 4. Press the UP and DOWN ARROWS to
NO TIMEOUT select either AUTOMATICALY TEST
or ALL FUNCTIONS (to test all relay
AUTOMATICALLY TEST function channels), or TEST RELAY
ALL FUNCTIONS FUNCTION A# (to test an individual
Configure relay function channel).
310 or
Menu
TEST RELAY FUNCTION 5. Press ENTER.
A# 6. To start the Relay Function Test; press
or the UP ARROW, to cancel press the
STOP RELAY FUNCTION DOWN ARROW.
TEST 7. The Relay Function being tested and
or the remaining time are displayed.
TESTING FUNCTION A# 8. To terminate the test, press ENTER
= hh:mm:ss and ALARM CUTOFF (at the same
or time) until STOP RELAY FUNCTION
TESTING FUNCTION A# TEST is displayed.
NO TIMEOUT
9. To stop the test, press UP ARROW.
To keep the test running, press DOWN
ARROW.
10. At the "ARE YOU SURE?" prompt,
press YES / + / i.
Allows you to configure a relay by assigning a
ASSIGN RELAYS TO Configure Relay Function Channel to a specific relay.
311
FUNCTIONS Menu
Press ENTER to assign relays to functions.
Select the MCA Customer Alarm Relay to be
configured, and assign a relay function channel
to this relay.
1. Press the UP and DOWN ARROWS to
navigate to the desired relay.
(B#-P#-R# = Bay Number-MCA
Relay Customer Alarm Relay Circuit Card
ASSIGN RELAY B#-P#-R#
312 Assignment
FUNCTION A# Position Number-Relay Number).
Menu
2. Refer to "Changing a Value or Setting"
in the table at the beginning of this
document to complete the operation.
Note: See the table in Section 5876
(Installation Instructions) for the MCA default
configuration.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Relay
313 GO TO CONFIGURE MENU Assignment Press ENTER to go to this menu.
Menu
Relay
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
314 Assignment
BEGINNING MCA Menu Tree.
Menu
Allows you to enable the Battery Charge
Temperature Compensation feature and set
the Battery Charge Temperature
Compensation Slope set point, or disable the
feature.
1. Refer to "Changing a Value or Setting"
NO TEMPERATURE in the table at the beginning of this
COMPENSATION chapter.
or Note: To disable the feature, press
TEMPERATURE SLOPE NO / - when in the change setting
= 0.vvvV/ C/F Configure mode to scroll to NO TEMPERATURE
315
or Menu COMPENSATION (displayed when
TURN OFF POWER SHARE you scroll down to "0V/ C").
or Note: This is the voltage slope of the entire
TURN OFF ALTERNATE battery string, not individual cells.
CURRENT LIMIT Note: The Temperature Compensation feature
requires Power Share and Alternate Current
Limit to be turned off. A message is displayed
if Power Share or Alternate Current Limit is on.
Turn Power Share or Alternate Current Limit off
first then return to this menu to enable
Temperature Compensation.
Allows you to change the Maximum Voltage
with Temperature Compensation set point.
MAXIMUM COMPENSATION Configure
316 1. Refer to "Changing a Value or Setting"
= vv.vvV Menu
in the table at the beginning of this
chapter.
Allows you to change the Minimum Voltage
with Temperature Compensation set point.
MINIMUM COMPENSATION Configure
317 1. Refer to "Changing a Value or Setting"
= vv.vvV Menu
in the table at the beginning of this
chapter.
Allows you to change the temperature unit
(degrees F or degrees C).
NOW DISPLAYING C/F Configure
318 1. Refer to "Changing a Value or Setting"
SET TO C/F? Menu
in the table at the beginning of this
chapter.
Allows you to change the time and time.
IT IS NOW hh:mm:ss Configure 1. Refer to "Changing a Value or Setting"
319
dd-mon-yy Menu in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Deletes all MCA Alarm Log entries.
Configure 1. Refer to "Changing a Control Function"
320 ERASE THE ALARM LOG
Menu in the table at the beginning of this
chapter.
Allows you to view and change the network IP,
CHANGE NETWORK Configure
320A gateway, and netmask addresses used by the
ADDRESSES Menu
LMS1000 when connecting to the network.
Displays the Ethernet (MAC) address used by
Network
##.##.##.##.##.## the LMS1000 when connecting to the network.
320B Address
MAC ADDRESS Note: This address cannot be changed, only
Menu
viewed.
Network Allows you to change the IP address used by
###.###.###.###
320C Address the LMS1000 when connecting to the network.
IP ADDRESS
Menu
Network Allows you to change the netmask address
###.###.###.###
320D Address used by the LMS1000 when connecting to the
NET MASK ADDRESS
Menu network.
Network Allows you to change the gateway address
###.###.###.###
320E Address used by the LMS1000 when connecting to the
GATEWAY ADDRESS
Menu network.
This allows you to save the address changes
that were made. The system must first verify
that the new IP, netmask, and gateway
VALIDATE THE ADDRESS addresses are compatible with each other.
CHANGES? or
or
Network This allows you to pass the saved addresses to
UPDATE/RESTART LMS
320F Address the LMS1000.
WITH CHANGES?
Menu Note: The LMS1000 will need to be restarted
or
THE CHANGES WERE for the address changes to take effect.
REJECTED or
The new IP, netmask, and gateway addresses
are not compatible with each other. The
changes are not accepted.
Network
320G GO TO CONFIGURE MENU Address Press ENTER to go to this menu.
Menu
Network
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
320H Address
BEGINNING MCA Menu Tree.
Menu
321 NO FUNCTION IN THIS SYSTEM
321A NO FUNCTION IN THIS SYSTEM
321B NO FUNCTION IN THIS SYSTEM
321C NO FUNCTION IN THIS SYSTEM
321D NO FUNCTION IN THIS SYSTEM
321E NO FUNCTION IN THIS SYSTEM
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
321F NO FUNCTION IN THIS SYSTEM
321G NO FUNCTION IN THIS SYSTEM
Configure
322 GO TO FUNCTION MENU Press ENTER to go to this menu.
Menu
GO BACK TO MENU TREE Configure Press ENTER to go to the beginning of the
322A
BEGINNING Menu MCA Menu Tree.
Allows you to verify the test, emergency stop,
and high voltage shutdown inputs.
1. Navigate to this menu item.
VERIFY TEST, ESTOP, 2. Apply the Test input. Verify MCA
& HVS INPUTS displays TEST SHUTDOWN INPUT IS
or ON.
TEST SHUTDOWN INPUT 3. With the Test input still applied, apply
IS ON the Emergency Stop input. Verify MCA
Function
323 or displays EMERGENCY STOP INPUT
Menu
EMERGENCY STOP INPUT IS ON. Release the Emergency Stop
IS ON input.
or 4. With the Test input still applied, apply
HI VOLTAGE SHUTDOWN the High Voltage Shutdown input.
INPUT IS ON Verify MCA displays HI VOLTAGE
SHUTDOWN INPUT IS ON. Release
the High Voltage Shutdown input.
5. Release the Test input.
Function
324 VIEW THE ALARM LOG Press ENTER to view the MCA Alarm Log.
Menu
Displays the alarms (with date and time stamp)
recorded for the Controller element of the
system. Note that the recordable alarm
dd-mon-yy hh:mm:ss♪ conditions are set by configuring MCA
CONTROLLER Relay Function Channel #24. The factory
Alarm Log defaults are shown in this chart.
325 or
Menu
dd-mon-yy hh:mm:ss Press UP and DOWN ARROWS to scroll if
CONTROLLER multiple alarms are recorded.
A 'music note' (♪) after the date/time stamp
indicates the alarm went active. A 'checkmark'
() indicates the alarm retired.
MCA
SYSTEM CONTROLLER
326 Alarm Log Recordable MCA (Controller) event.
NO ALARMS
Detail Menu
MCA
EMERGENCY STOP
327 Alarm Log Recordable MCA (Controller) event.
INPUT ACTIVE
Detail Menu
MCA
HI VOLTAGE SHUTDOWN
328 Alarm Log Recordable MCA (Controller) event.
INPUT ACTIVE
Detail Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
MCA
ALTERNATE CURRENT
328A Alarm Log Recordable MCA (Controller) event.
LIMIT ACTIVE
Detail Menu
MCA
SYSTEM VOLTAGE IS
329 Alarm Log Recordable MCA (Controller) event.
VERY LOW
Detail Menu
MCA
SYSTEM BATTERY IS ON
330 Alarm Log Recordable MCA (Controller) event.
DISCHARGE
Detail Menu
MCA
SYSTEM HIGH VOLTAGE
331 Alarm Log Recordable MCA (Controller) event.
#1 ALARM
Detail Menu
MCA
SYSTEM HIGH VOLTAGE
332 Alarm Log Recordable MCA (Controller) event.
#2 ALARM
Detail Menu
MCA
NO PCUs ARE
333 Alarm Log Recordable MCA (Controller) event.
IN INVENTORY
Detail Menu
MCA
NO DIST. PANELS ARE
334 Alarm Log Recordable MCA (Controller) event.
IN INVENTORY
Detail Menu
MCA
NO ROUTERS ARE
335 Alarm Log Recordable MCA (Controller) event.
IN INVENTORY
Detail Menu
MCA
NO RELAY BOARDS ARE
336 Alarm Log Recordable MCA (Controller) event.
IN INVENTORY
Detail Menu
MCA
HIGH TEMPERATURE #1
337 Alarm Log Recordable MCA (Controller) event.
ALARM
Detail Menu
MCA
HIGH TEMPERATURE #2
338 Alarm Log Recordable MCA (Controller) event.
ALARM
Detail Menu
MCA
LOW TEMPERATURE #1
339 Alarm Log Recordable MCA (Controller) event.
ALARM
Detail Menu
MCA
LOW TEMPERATURE #2
340 Alarm Log Recordable MCA (Controller) event.
ALARM
Detail Menu
MCA
TEMPERATURE SENSOR
341 Alarm Log Recordable MCA (Controller) event.
NO SIGNAL
Detail Menu
MCA
MAJOR MONITORING
342 Alarm Log Recordable MCA (Controller) event.
ALARM(S)
Detail Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
MCA
MINOR MONITORING
343 Alarm Log Recordable MCA (Controller) event.
ALARM(S)
Detail Menu
MCA
Monitoring LED
344 Alarm Log Recordable MCA (Controller) event.
Messages
Detail Menu
MCA
MONITORING DOES NOT
345 Alarm Log Recordable MCA (Controller) event.
RESPOND
Detail Menu
MCA
CONTROLLER FAILURE
346 Alarm Log Recordable MCA (Controller) event.
####
Detail Menu
MCA
THE CONTROLLER IS
347 Alarm Log Recordable MCA (Controller) event.
INITIALIZING
Detail Menu
MCA
TOTAL LOAD CURRENT
348 Alarm Log Recordable MCA (Controller) event.
ALARM
Detail Menu
MCA
GROUP A LOAD CURRENT
349 Alarm Log Recordable MCA (Controller) event.
ALARM
Detail Menu
MCA
GROUP B LOAD CURRENT
350 Alarm Log Recordable MCA (Controller) event.
ALARM
Detail Menu
MCA
THE DISPLAY DOES NOT
351 Alarm Log Recordable MCA (Controller) event.
RESPOND
Detail Menu
MCA
SYSTEM OUTPUT SENSE
352 Alarm Log Recordable System Data.
vv.vvV
Detail Menu
MCA
TOTAL LOAD CURRENT
353 Alarm Log Recordable System Data.
aaaaaA
Detail Menu
MCA
354 GO TO ALARM LOG MENU Alarm Log Press ENTER to go to this menu.
Detail Menu
MCA
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
355 Alarm Log
BEGINNING MCA Menu Tree.
Detail Menu
Displays the alarms (with date and time stamp)
recorded for the Rectifier element of the
dd-mon-yy hh:mm:ss♪
system.
B#-SN#
Alarm Log Press UP and DOWN ARROWS to scroll if
356 or
Menu multiple alarms are recorded.
dd-mon-yy hh:mm:ss
A 'music note' (♪) after the date/time stamp
B#-SN#
indicates the alarm went active. A 'checkmark'
() indicates the alarm retired.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
PCU
PCU B#-SN#
357 Alarm Log Recordable Rectifier Module (PCU) event.
NO ALARMS
Detail Menu
PCU
PCU B#-SN#
358 Alarm Log Recordable Rectifier Module (PCU) event.
EMERG. STOP
Detail Menu
PCU
PCU B#-SN#
359 Alarm Log Recordable Rectifier Module (PCU) event.
H.V. SHUTDOWN
Detail Menu
PCU
PCU B#-SN#
360 Alarm Log Recordable Rectifier Module (PCU) event.
AC LINE OFF
Detail Menu
PCU
PCU B#-SN#
361 Alarm Log Recordable Rectifier Module (PCU) event.
AC LINE LOW
Detail Menu
PCU
PCU B#-SN#
362 Alarm Log Recordable Rectifier Module (PCU) event.
AC LINE HIGH
Detail Menu
PCU
PCU B#-SN#
363 Alarm Log Recordable Rectifier Module (PCU) event.
AC PHASE LOST
Detail Menu
PCU
PCU B#-SN#
364 Alarm Log Recordable Rectifier Module (PCU) event.
POWER FACTOR
Detail Menu
PCU
PCU B#-SN#
365 Alarm Log Recordable Rectifier Module (PCU) event.
DC/DC CONV.
Detail Menu
PCU
PCU B#-SN#
366 Alarm Log Recordable Rectifier Module (PCU) event.
FUSE/BREAKER
Detail Menu
PCU
PCU B#-SN#
367 Alarm Log Recordable Rectifier Module (PCU) event.
INHIBITED
Detail Menu
PCU
PCU B#-SN#
368 Alarm Log Recordable Rectifier Module (PCU) event.
ON STANDBY
Detail Menu
PCU
PCU B#-SN#
369 Alarm Log Recordable Rectifier Module (PCU) event.
THERMAL LIMIT
Detail Menu
PCU
PCU B#-SN#
370 Alarm Log Recordable Rectifier Module (PCU) event.
THERMAL STOP
Detail Menu
PCU
PCU B#-SN#
371 Alarm Log Recordable Rectifier Module (PCU) event.
HIGH AMBIENT
Detail Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
PCU
PCU B#-SN#
372 Alarm Log Recordable Rectifier Module (PCU) event.
LOAD SHARE
Detail Menu
PCU
PCU B#-SN#
373 Alarm Log Recordable Rectifier Module (PCU) event.
1 FAN SPEED
Detail Menu
PCU
PCU B#-SN#
374 Alarm Log Recordable Rectifier Module (PCU) event.
2+ FANS SPEED
Detail Menu
PCU
PCU B#-SN#
375 Alarm Log Recordable Rectifier Module (PCU) event.
NO VOLT SENSE
Detail Menu
PCU
PCU B#-SN#
376 Alarm Log Recordable Rectifier Module (PCU) event.
DUPLICATED
Detail Menu
PCU
PCU B#-SN#
377 Alarm Log Recordable Rectifier Module (PCU) event.
NO RESPONSE
Detail Menu
PCU B#-SN#
TURNED ON PCU
378 or Alarm Log Recordable Rectifier Module (PCU) Data.
PCU B#-SN# Detail Menu
TURNED OFF
PCU
PCU B#-SN#
379 Alarm Log Recordable Rectifier Module (PCU) Data.
aaaaaA
Detail Menu
PCU
SYSTEM OUTPUT SENSE
380 Alarm Log Recordable System Data.
vv.vvV
Detail Menu
PCU
TOTAL LOAD CURRENT
381 Alarm Log Recordable System Data.
aaaaaA
Detail Menu
PCU
382 GO TO ALARM LOG MENU Alarm Log Press ENTER to go to this menu.
Detail Menu
PCU
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
383 Alarm Log
BEGINNING MCA Menu Tree.
Detail Menu
Displays the alarms (with date and time stamp)
recorded for the Distribution Panel element of
dd-mon-yy hh:mm:ss♪
the system.
PANEL B#-P#A/B
Alarm Log Press UP and DOWN ARROWS to scroll if
384 or
Menu multiple alarms are recorded.
dd-mon-yy hh:mm:ss
A 'music note' (♪) after the date/time stamp
PANEL B#-P#A/B
indicates the alarm went active. A 'checkmark'
() indicates the alarm retired.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Distribution
DIST. PANEL B#-P#A/B
385 Alarm Log Recordable Distribution Panel event.
NO ALARMS
Detail Menu
Distribution
DIST. PANEL B#-P#A/B
386 Alarm Log Recordable Distribution Panel event.
DISCONNECTED
Detail Menu
Distribution
POSITION B#-P#A/B
387 Alarm Log Recordable Distribution Panel event.
IS OPEN
Detail Menu
POSITION B#-P#A/B
NOT FOUND Distribution
388 or Alarm Log Recordable Distribution Panel event.
POSITION NOT FOUND Detail Menu
PANEL B#-P#A/B
Distribution
POSITION B#-P#A/B
389 Alarm Log Recordable Distribution Panel event.
TYPE UNKNOWN
Detail Menu
Distribution
POSITION B#-P#A/B
390 Alarm Log Recordable Distribution Panel event.
OVER CURRENT
Detail Menu
Distribution
DIST. PANEL B#-P#A/B
391 Alarm Log Recordable Distribution Panel event.
LVD FAILURE
Detail Menu
Distribution
DIST. PANEL B#-P#A/B
392 Alarm Log Recordable Distribution Panel event.
A/B CHANGED
Detail Menu
Distribution
DIST. PANEL B#-P#A/B
393 Alarm Log Recordable Distribution Panel event.
PROCESSOR
Detail Menu
Distribution
DIST. PANEL B#-P#A/B IS
394 Alarm Log Recordable Distribution Panel event.
DUPLICATED
Detail Menu
Distribution
DIST. PANEL B#-P#A/B
395 Alarm Log Recordable Distribution Panel event.
NO RESPONSE
Detail Menu
Distribution
SYSTEM OUTPUT SENSE
396 Alarm Log Recordable System Data.
vv.vvV
Detail Menu
Distribution
TOTAL LOAD CURRENT
397 Alarm Log Recordable System Data.
aaaaaA
Detail Menu
Distribution
398 GO TO ALARM LOG MENU Alarm Log Press ENTER to go to this menu.
Detail Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Distribution
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
399 Alarm Log
BEGINNING MCA Menu Tree.
Detail Menu
Displays the alarms (with date and time stamp)
recorded for the MCA I/O element of the
dd-mon-yy hh:mm:ss♪
system.
I/O B#-P#
Alarm Log Press UP and DOWN ARROWS to scroll if
400 or
Menu multiple alarms are recorded.
dd-mon-yy hh:mm:ss
A 'music note' (♪) after the date/time stamp
I/O B#-P#
indicates the alarm went active. A 'checkmark'
() indicates the alarm retired.
I/O Board
I/O BOARD B#-P#
401 Alarm Log Recordable Relay event.
NO ALARMS
Detail Menu
I/O Board
I/O BOARD B#-P#
402 Alarm Log Recordable Relay event.
BINARY I#
Detail Menu
I/O Board
I/O BOARD B#-P#
403 Alarm Log Recordable Relay event.
OVER CURRENT
Detail Menu
I/O Board
I/O BOARD B#-P#
404 Alarm Log Recordable Relay event.
PROCESSOR
Detail Menu
I/O Board
I/O BOARD B#-P#
405 Alarm Log Recordable Relay event.
IS DUPLICATED
Detail Menu
I/O Board
I/O BOARD B#-P#
406 Alarm Log Recordable Relay event.
NO RESPONSE
Detail Menu
I/O Board
SYSTEM OUTPUT SENSE
407 Alarm Log Recordable System Data.
vv.vvV
Detail Menu
I/O Board
TOTAL LOAD CURRENT
408 Alarm Log Recordable System Data.
aaaaaA
Detail Menu
I/O Board
409 GO TO ALARM LOG MENU Alarm Log Press ENTER to go to this menu.
Detail Menu
I/O Board
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
410 Alarm Log
BEGINNING MCA Menu Tree.
Detail Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Displays the alarms (with date and time stamp)
dd-mon-yy hh:mm:ss♪ recorded for the Router element of the system.
ROUTER B# Press UP and DOWN ARROWS to scroll if
Alarm Log
411 or multiple alarms are recorded.
Menu
dd-mon-yy hh:mm:ss A 'music note' (♪) after the date/time stamp
ROUTER B# indicates the alarm went active. A 'checkmark'
() indicates the alarm retired.
Router
ROUTER B#
412 Alarm Log Recordable Router event.
NO ALARMS
Detail Menu
Router
ROUTER B# REMOTE
413 Alarm Log Recordable Router event.
SENSE OPEN
Detail Menu
Router
ROUTER B# INTERNAL
414 Alarm Log Recordable Router event.
SENSE OPEN
Detail Menu
Router
ROUTER B# PROCESSOR
415 Alarm Log Recordable Router event.
FAILURE
Detail Menu
Router
ROUTER B# REPORTS AN
416 Alarm Log Recordable Router event.
ILLEGAL NODE
Detail Menu
Router
ROUTER B# IS
417 Alarm Log Recordable Router event.
DUPLICATED
Detail Menu
Router
ROUTER B# DOES NOT
418 Alarm Log Recordable Router event.
RESPOND
Detail Menu
Router
ROUTER B# REMOTE
419 Alarm Log Recordable Router Data.
SENSE vv.vvV
Detail Menu
Router
ROUTER B# INTERNAL
420 Alarm Log Recordable Router Data.
SENSE vv.vvV
Detail Menu
Router
SYSTEM OUTPUT SENSE
421 Alarm Log Recordable System Data.
vv.vvV
Detail Menu
Router
TOTAL LOAD CURRENT
422 Alarm Log Recordable System Data.
aaaaaA
Detail Menu
Router
423 GO TO ALARM LOG MENU Alarm Log Press ENTER to go to this menu.
Detail Menu
Router
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
424 Alarm Log
BEGINNING MCA Menu Tree.
Detail Menu
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Displays the alarms (with date and time stamp)
dd-mon-yy hh:mm:ss♪ recorded for the Relay element of the system.
RELAY B#-P# Press UP and DOWN ARROWS to scroll if
Alarm Log
425 or multiple alarms are recorded.
Menu
dd-mon-yy hh:mm:ss A 'music note' (♪) after the date/time stamp
RELAY B#-P# indicates the alarm went active. A 'checkmark'
() indicates the alarm retired.
Relay
RELAY BOARD B#-P#
426 Alarm Log Recordable Relay event.
NO ALARMS
Detail Menu
Relay
RELAY B#-P#-R# IS
427 Alarm Log Recordable Relay event.
STUCK
Detail Menu
Relay
RELAY BOARD B#-P#
428 Alarm Log Recordable Relay event.
PROCESSOR
Detail Menu
Relay
RELAY BOARD B#-P# IS
429 Alarm Log Recordable Relay event.
DUPLICATED
Detail Menu
Relay
RELAY BOARD B#-P#
430 Alarm Log Recordable Relay event.
NO RESPONSE
Detail Menu
Relay
SYSTEM OUTPUT SENSE
431 Alarm Log Recordable System Data.
vv.vvV
Detail Menu
Relay
TOTAL LOAD CURRENT
432 Alarm Log Recordable System Data.
aaaaaA
Detail Menu
Relay
433 GO TO ALARM LOG MENU Alarm Log Press ENTER to go to this menu.
Detail Menu
Relay
GO BACK TO MENU TREE Press ENTER to go to the beginning of the
434 Alarm Log
BEGINNING MCA Menu Tree.
Detail Menu
Alarm Log
435 GO TO FUNCTION MENU Press ENTER to go to this menu.
Menu
GO BACK TO MENU TREE Alarm Log Press ENTER to go to the beginning of the
436
BEGINNING Menu MCA Menu Tree.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
PCU B#-ID#/N#
RECOGNIZED
or
DSM B#-P#A/B
RECOGNIZED
or
I/O B#-P# Function Lists the last item in the system that was
437
RECOGNIZED Menu recognized by the MCA.
or
CRM B#
RECOGNIZED
or
RCB B#-P#
RECOGNIZED
GO BACK TO MENU TREE Function Press ENTER to go to the beginning of the
438
BEGINNING Menu MCA Menu Tree.
439 NO FUNCTION IN THIS SYSTEM
440 NO FUNCTION IN THIS SYSTEM
441 NO FUNCTION IN THIS SYSTEM
442 NO FUNCTION IN THIS SYSTEM
443 NO FUNCTION IN THIS SYSTEM
444 NO FUNCTION IN THIS SYSTEM
############ WAIT ## When the system is initially started, an
Initialization
A initialization time and MCA software version
Menu
V########### number are displayed.
Allows you to view (and change) the MCA
settings stored in memory before starting the
CHECK VALUES BEFORE Initialization system.
B
STARTING Menu 1. Press the UP and DOWN ARROWS to
view (change) the following MCA
settings.
Allows you to change the Float Output Voltage
set point.
FLOAT SETPOINT Initialization
C 1. Refer to "Changing a Value or Setting"
= vv.vvV Menu
in the table at the beginning of this
chapter.
Allows you to change the Test/Equalize Output
Voltage set point.
TEST/EQUALIZE Initialization
D 1. Refer to "Changing a Value or Setting"
= vv.vvV Menu
in the table at the beginning of this
chapter.
Allows you to change the High Voltage
Shutdown set point.
HI VOLTAGE SHUTDOWN Initialization
E 1. Refer to "Changing a Value or Setting"
= vv.vvV Menu
in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Allows you to change the Current Limit set
point. aaaaaA = System current limit setting,
current limit circuit on all Rectifier Modules are
PCU CURRENT LIMIT
automatically adjusted to ensure system
= aaaaaA
Initialization current does not exceed this value.
F or
Menu 1. Refer to "Changing a Value or Setting"
PCU CURRENT LIMIT in the table at the beginning of this
POWER SHARE chapter.
Note: When Power Share is enabled, current
limit is controlled by the Power Share feature.
Allows you to change the System High Voltage
#1 Alarm set point.
SYSTEM HI VOLTAGE #1 Initialization
G 1. Refer to "Changing a Value or Setting"
= vv.vvV Menu
in the table at the beginning of this
chapter.
Allows you to change the System High Voltage
#2 Alarm set point.
SYSTEM HI VOLTAGE #2 Initialization
H 1. Refer to "Changing a Value or Setting"
= vv.vvV Menu
in the table at the beginning of this
chapter.
Allows you to change the Battery on Discharge
Alarm set point.
BATTERY ON DISCHARGE Initialization
I 1. Refer to "Changing a Value or Setting"
= vv.vvV Menu
in the table at the beginning of this
chapter.
Allows you to change the Very Low Voltage
Alarm set point.
VERY LOW VOLTAGE Initialization
J 1. Refer to "Changing a Value or Setting"
= vv.vvV Menu
in the table at the beginning of this
chapter.
Allows you to change the Total Distribution
Load Current Alarm set point.
TOTAL LOAD CURRENT Initialization
K 1. Refer to "Changing a Value or Setting"
= aaaaaA Menu
in the table at the beginning of this
chapter.
Allows you to change the Distribution Group A
Load Current Alarm set point.
DISTRIBUTION GROUP A Initialization
L 1. Refer to "Changing a Value or Setting"
= aaaaaA Menu
in the table at the beginning of this
chapter.
Allows you to change the Distribution Group B
Load Current Alarm set point.
DISTRIBUTION GROUP B Initialization
M 1. Refer to "Changing a Value or Setting"
= aaaaaA Menu
in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Allows you to change the High Temperature #1
Alarm set point, or disable the alarm.
1. Refer to "Changing a Value or Setting"
HIGH TEMPERATURE #1 in the table at the beginning of this
= ttt C/F chapter.
Initialization
N or Note: To disable the feature, press
Menu
NO HIGH TEMPERATURE YES / + / i when in the change setting
#1 ALARM mode to scroll to NO HIGH
TEMPERATURE #1 ALARM
(displayed when you scroll up to
"100 C").
Allows you to change the High Temperature #2
Alarm set point, or disable the alarm.
1. Refer to "Changing a Value or Setting"
HIGH TEMPERATURE #2 in the table at the beginning of this
= ttt C/F chapter.
Initialization
O or Note: To disable the feature, press
Menu
NO HIGH TEMPERATURE YES / + / i when in the change setting
#2 ALARM mode to scroll to NO HIGH
TEMPERATURE #2 ALARM
(displayed when you scroll up to
"100 C").
Allows you to change the Low Temperature #1
Alarm set point, or disable the alarm.
1. Refer to "Changing a Value or Setting"
LOW TEMPERATURE #1 in the table at the beginning of this
= ttt C/F chapter.
Initialization
P or Note: To disable the feature, press
Menu
NO LOW TEMPERATURE NO / - when in the change setting
#1 ALARM mode to scroll to NO LOW
TEMPERATURE #1 ALARM
(displayed when you scroll down to
"-50 C").
Allows you to change the Low Temperature #2
Alarm set point, or disable the alarm.
1. Refer to "Changing a Value or Setting"
LOW TEMPERATURE #2 in the table at the beginning of this
= ttt C/F chapter.
Initialization
Q or Note: To disable the feature, press
Menu
NO LOW TEMPERATURE NO / - when in the change setting
#2 ALARM mode to scroll to NO LOW
TEMPERATURE #2 ALARM
(displayed when you scroll down to
"-50 C").
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Allows you to enable the MCA Audible Alarm
feature and set the Audible Alarm Cutoff Reset
Time Period set point, or disable the feature.
AUDIBLE SILENT TIME 1. Refer to "Changing a Value or Setting"
= mm MINUTES in the table at the beginning of this
Initialization
R or chapter.
Menu
AUDIBLE ALARMS STAY Note: To disable the feature, press
SILENCED NO / - when in the change setting
mode to scroll to AUDIBLE ALARMS
STAY SILENCED (displayed when you
scroll down to "zero minutes").
Allows you to enable the Rectifier Sequencing
feature and set the Rectifier Sequencing Delay
set point, or disable the feature.
PCU SEQUENCING IS 1. Refer to "Changing a Value or Setting"
DISABLED in the table at the beginning of this
Initialization chapter.
S or
Menu Note: To disable the feature, press
PCU SEQUENCING DELAY
NO / - when in the change setting
= ss SECONDS
mode to scroll to Rectifier
SEQUENCING IS DISABLED
(displayed when you scroll down to
"zero seconds").
Allows you to enable the Manual Timed
Test/Equalize feature and set the Timed
Test/Equalize set point, or disable the feature.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
Note: To disable the feature, press
TEST EQUALIZE IS DISABLED NO / - when in the change setting
TURN OFF POWER SHARE mode to scroll to TEST/EQUALIZE
or STOP IS MANUAL (displayed when
you scroll down to "zero hours"). This
MANUAL TEST/EQUALIZE Initialization
T indicates the manually initiated timed
= hh HOURS Menu
test/equalize feature is disabled and
or the system must be manually returned
TEST/EQUALIZE STOP to the float mode if placed in the
IS MANUAL test/equalize mode.
When the Power Share feature is enabled, the
system cannot be placed in the Test/Equalize
mode.
Note: Test/Equalize Mode requires Power
Share to be turned off. A message is displayed
if Power Share is on. Turn Power Share off
first then return to this menu.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Allows you to enable the Auto Test/Equalize
feature and set the Auto Test/Equalize
Multiplier set point, or disable the feature.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
AUTO EQUALIZE IS chapter.
DISABLED Note: To disable the feature, press
or NO / - when in the change setting
Initialization mode to scroll to AUTO EQUALIZE IS
U TURN OFF POWER SHARE
Menu DISABLED (displayed when you scroll
or down to "zero x discharge").
AUTO EQUALIZE FOR ## When the Power Share feature is enabled, the
x DISCHARGE system cannot be placed in the Test/Equalize
mode.
Note: Test/Equalize Mode requires Power
Share to be turned off. A message is displayed
if Power Share is on. Turn Power Share off
first then return to this menu.
Allows you to enable the Battery Charge
Temperature Compensation feature and set
the Battery Charge Temperature
Compensation Slope set point, or disable the
feature.
1. Refer to "Changing a Value or Setting"
NO TEMPERATURE in the table at the beginning of this
COMPENSATION chapter.
or Note: To disable the feature, press
Initialization NO / - when in the change setting
V TURN OFF POWER SHARE
Menu mode to scroll to NO TEMPERATURE
or COMPENSATION (displayed when
TEMPERATURE SLOPE you scroll down to "0V / ~").
= 0.vvvV/ C/F Note: This is the voltage slope of the entire
battery string, not individual cells.
Note: The Temperature Compensation feature
requires Power Share to be turned off. A
message is displayed if Power Share is on.
Turn Power Share off first then return to this
menu to enable Temperature Compensation.
Allows you to change the Maximum Voltage
with Temperature Compensation set point.
MAXIMUM COMPENSATION Initialization
W 1. Refer to "Changing a Value or Setting"
= vv.vvV Menu
in the table at the beginning of this
chapter.
Allows you to change the Minimum Voltage
with Temperature Compensation set point.
MINIMUM COMPENSATION Initialization
X 1. Refer to "Changing a Value or Setting"
= vv.vvV Menu
in the table at the beginning of this
chapter.
MCA Menu
Tree Line No. Associated
Message Displayed Definition
(Section with ...
5886)
Allows you to change the time and date.
IT IS NOW hh:mm:ss Initialization 1. Refer to "Changing a Value or Setting"
Y
dd-mon-yy Menu in the table at the beginning of this
chapter.
Allows you to start the system with the selected
settings.
READY TO START THE Initialization 1. Press ENTER and ALARM CUTOFF
Z
SYSTEM NOW? Menu (at the same time).
2. At the "ARE YOU SURE?" prompt,
press YES / + / i.
CHAPTER 3
SYSTEM OPERATING PROCEDURES
TABLE OF CONTENTS
LMS Operating Procedures ............................................................................................. 3-2
LMS Local Port ................................................................................................................ 3-2
Installing the USB Device Driver from the Furnished CD ......................................... 3-2
Downloading the USB Driver from the Web ............................................................. 3-3
Setting up your Computer to Access the Power System .......................................... 3-3
Local Controls and Indicators .......................................................................................... 3-3
Location and Identification ........................................................................................ 3-3
LMS Main/Expansion CPU Circuit Card (if furnished) Controls and Indicators ........ 3-3
Bay LED Indicator ..................................................................................................... 3-4
Distribution Bus LED Indicator .................................................................................. 3-4
MCA Component LED Indicator................................................................................ 3-4
Bay Monitoring and Control Section Indicators ......................................................... 3-4
MCA Controls and Indicators .................................................................................... 3-5
MCA Display ............................................................................................................. 3-6
Surge Suppression Alarms (available only if a Surge Suppression Option is
furnished) .................................................................................................................. 3-6
Rectifier Controls and Indicators ............................................................................... 3-7
208V and 480V Input Rectifiers .......................................................................... 3-7
External Alarms ............................................................................................................... 3-8
Starting and Stopping System Operation ........................................................................ 3-8
Rectifier Normal Starting Procedure ......................................................................... 3-8
Rectifier Stopping Procedure (Local) ........................................................................ 3-8
Complete Shutdown ........................................................................................... 3-8
Local TR Shutdown ............................................................................................ 3-8
Rectifier Stopping Procedure (Remote) (if optional LMS installed) .......................... 3-8
Restarting Procedures when Rectifier is Automatically or Manually Inhibited, Shut
Down, or Locked Out ....................................................................................................... 3-9
Rectifier High Voltage Shutdown Lockout ................................................................ 3-9
Rectifier Emergency Shutdown and Fire Alarm Disconnect ..................................... 3-9
Remote On/Off (TR) .................................................................................................. 3-9
Output Voltage Mode of Operation Selection .................................................................. 3-9
Placing the System into the Float Mode of Operation .............................................. 3-9
Placing the System into the Test/Equalize Mode of Operation .............................. 3-10
Method 1 (Manual Test/Equalize) Procedure ................................................... 3-10
Method 2 (Manually Initiated Timed Test/Equalize) Procedure ....................... 3-12
Method 3 (Automatic Test/Equalize) Procedure .............................................. 3-14
Method 4 (External Test/Equalize) Procedure ................................................. 3-16
Setting MCA Audible Alarm Cutoff Reset Time Period ................................................. 3-17
Procedure ......................................................................................................... 3-17
Setting Rectifier Sequencing Delay Time Period .......................................................... 3-18
FUNCTION SELECT UP
Moves up and down, respectively, through the list of available entries in the
FUNCTION SELECT DOWN
currently displayed menu.
(Arrow Pushbuttons)
Used to increase or decrease the value of the currently selected menu entry
when in the adjustment or change setting mode.
Note: Pressing the FUNCTION SET YES (+) and NO (-) pushbuttons
simultaneously moves the user to the "Initial Message" display
(beginning).
FUNCTION SET YES (+) (i)
Note: When in the adjustment or change setting mode, depressing the
FUNCTION SET NO (-)
FUNCTION SET YES (+) pushbutton after the "ARE YOU SURE?"
(Pushbuttons)
prompt accepts the new value or setting, depressing the FUNCTION
SET NO (-) pushbutton after the "ARE YOU SURE?" prompt cancels
the adjustment or change setting mode without making any changes.
Note: You can view additional information when the MCA displays the "i"
symbol by pressing this key.
Silences the audible alarm. Any new alarms will reactivate the audible alarm.
Note: Pressing the ALARM CUTOFF pushbutton and the FUNCTION SET
ALARM CUTOFF
ENTER pushbutton simultaneously, allows the user to enter the
(Pushbutton)
adjustment or change setting mode, to change the value or setting of
the currently selected menu entry, if available.
ALARM CUTOFF Illuminates yellow when the MCA audible alarm has been silenced using the
(Indicator) ALARM CUTOFF Pushbutton.
Illuminates green if AC input voltage to all Rectifiers is greater than the preset
non-adjustable low AC input voltage inhibit, less than the preset non-
adjustable high AC input voltage inhibit, and the Standby/Operate switch on
AC
each Rectifier is in the I "operate" position. Illuminates red if AC input voltage
(Indicator) to any Rectifier decreases below or increases above the respective inhibit
value.
Danger: In standby mode, AC input power IS connected to the Rectifier.
TEST/EQ Illuminates yellow when the system is placed in the test/equalize mode, locally
(Indicator) or remotely.
MCA Display
Refer to Chapter 2. Navigating the MCA for MCA Display descriptions.
Surge Suppression Alarms
(available only if a Surge Suppression Option is furnished)
If a surge suppression assembly operates, the MCA displays a "Binary Input Customer
Text Message" in the I/O Board Alarm Detail Message. If you wish to change the default
message, refer to the " SETTING MCA CUSTOM TEXT MESSAGES " in this chapter.
"MCA Customer Alarm Relays" may also be programmed to provide an external alarm.
Note that a Surge Suppression Alarm is active when there is NO AC power, and
resets when AC power is supplied.
EXTERNAL ALARMS
MCA Customer Alarm Relay circuit cards may be installed. These alarm relays are
mapped to the MCA alarms per the MCA configuration. See the table in Section 5876
(Installation Instructions) for the MCA default configuration. Another table is provided in
Section 5876 (Installation Instructions) to document a custom configuration.
8) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
Placing the System into Test/Equalize Mode: Manually place the system into
test/equalize mode by navigating to and activating the "FLOAT MODE IS ACTIVE. SET
TEST/EQ?" menu item in the MCA function menu. The system is placed in the
test/equalize mode and must be manually placed back to the float mode. A step-by-step
procedure is provided next.
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
Note: In the following step, if "TEST/EQ MODE ACTIVE. SET FLOAT?" is
displayed, the system is already operating in the test/equalize mode. In this
case, DO NOT perform steps 2) through 4), proceed with step 5).
2) Press and release the FUNCTION SELECT DOWN arrow key to display "FLOAT
MODE IS ACTIVE. SET TEST/EQ?".
3) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
4) "ARE YOU SURE?" is displayed. Press and release the FUNCTION SET YES
(+) key.
5) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
Returning to Float Mode: To return to float mode, navigate to and activate the
"TEST/EQ MODE ACTIVE. SET FLOAT?" menu item in the MCA function menu, as
previously described in this chapter.
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
Note: In the following step, if "TEST/EQ MODE ACTIVE. SET FLOAT?" is
displayed, the system is already operating in the test/equalize mode. In this
case, DO NOT perform steps 2) through 4), proceed with step 5).
2) Press and release the FUNCTION SELECT DOWN arrow key to display "FLOAT
MODE IS ACTIVE. SET TEST/EQ?".
3) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
4) "ARE YOU SURE?" is displayed. Press and release the FUNCTION SET YES
(+) key.
5) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
Returning to Float Mode: The system automatically returns to float mode when the
"timed test/equalize period" expires.
Note: Navigating to "END TEST/EQUALIZE IN hhh.hh HOURS" of the MCA configure
menu displays the hours remaining in the timed test/equalize period.
Note: Timed test/equalize is canceled and the system is placed in the float mode if any
of the following occurs.
1) Manually placing the system in the float mode by navigating to and activating
"TEST/EQ MODE ACTIVE. SET FLOAT?" menu item in the MCA function
menu, as previously described in this chapter.
2) Resetting the "MANUAL TEST/EQUALIZE = hh HOURS" value in the MCA
configure menu when "END TEST/EQUALIZE IN hhh.hh HOURS" is being
displayed, as described in the previous procedure
3) Applying an external test/equalize signal as described in the next procedure.
In this method, a user enables the Automatic Equalize feature via the MCA Control
Panel. The system is automatically placed in the equalize mode and automatically
returns to float mode for the conditions as described above. Follow the procedures
described below.
Note: The automatic equalize feature is intended for use only with wet cell batteries.
Using this feature with valve regulated batteries is not recommended.
Description
This feature can be enabled or disabled by a user via the MCA. The default state is
disabled.
The Automatic Equalize feature is a time based function which is controlled by a
customer selectable multiplier and by the "System Battery is on Discharge" alarm
setpoint. The MCA’s default setting is for a multiplier of zero, which disables the
Automatic Equalize feature.
When the Automatic Equalize feature is enabled, if system voltage drops to less than the
"System Battery is on Discharge" alarm setpoint, the MCA initiates a timing cycle to
measure the discharge time period. The MCA requires at least 15 minutes of continuous
"System Battery is on Discharge" alarm in order to prevent nuisance equalization cycles.
When system voltage rises to above the "System Battery is on Discharge" alarm setpoint,
the MCA ends the discharge timing cycle and (assuming a minimum of 15 minutes has
elapsed) places the Rectifiers into the equalize mode for a customer selectable multiple
of the discharge time period (the discharge time period includes the initial 15 minutes).
The equalize time period can be set for 0 to 15 times the discharge time period, up to a
maximum of 300 hours. A zero (0) setting disables the feature.
When the Automatic Equalize feature is enabled, the MCA prevents a user from setting
the equalize value lower than the float setpoint. If the equalize value is set first, the MCA
automatically sets the Automatic Equalize Multiplier to zero (0), disabling the feature.
Manually setting the system to float or equalize mode cancels the automatic function, if
active.
Note: Equalization is only effective if the correct multiplier is entered to allow the battery
to charge to capacity. It makes no sense to end the equalize cycle before battery
capacity has been restored. To determine the multiplier, load current and system
capacity must be known. For example, consider a system with 200 amps of
Rectifier capacity and 150 amps of load. If there is a 2-hour outage of AC power,
300 amp-hours (150 x 2) will be drained from the battery. When AC power is
restored, the battery charge current will be 50 amps (200-150), and it will take at
least 6 hours (300/50) to replace the battery capacity. In this scenario, the
multiplier must be set greater than 3 for the Automatic Equalize feature to have
any effect.
Enabling and Disabling the Automatic Equalize Feature: To enable, set the "AUTO
EQUALIZE FOR ## x DISCHARGE" menu item in the MCA Configure Menu to a value
between 0 and 15. To disable, set the "AUTO EQUALIZE FOR ## x DISCHARGE" menu
item in the MCA Configure Menu to 0. A step-by-step procedure is provided next.
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
2) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"CHANGE CONFIGURATION PARAMETERS" is displayed. Press and release
the FUNCTION SET ENTER key.
3) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"AUTO EQUALIZE FOR ## x DISCHARGE" or "AUTO EQUALIZE IS
DISABLED" is displayed.
Note: If "AUTO EQUALIZE FOR ## x DISCHARGE" is displayed, the system is
already set for Automatic Equalize. In this case, you can proceed with steps
4) through 7) to change the current setting, or proceed with step 8) if no
changes are required.
Note: If "END AUTO EQUALIZE IN hhh.hh HOURS" is displayed, the system is
already set for Automatic Equalize, and an Automatic Equalize is in progress.
In this case, you can proceed with steps 4) through 7) to cancel the Automatic
Equalize in progress and change the current setting, or proceed with step 8)
to proceed with the Automatic Equalize in progress and make no changes.
4) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
5) Press the FUNCTION SET YES (+) or FUNCTION SET NO (-) key until the
desired value is displayed, then release the key. Note that as you scroll below 1,
"AUTO EQUALIZE IS DISABLED" is displayed. Scroll back up to redisplay
"AUTO EQUALIZE FOR ##".
6) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
7) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
8) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
Placing the System into Test/Equalize Mode: The MCA automatically does this for the
conditions as previously described.
Returning to Float Mode: The MCA automatically does this for the conditions as
previously described.
Note: Navigating to "END AUTO EQUALIZE IN hhh.hh HOURS" of the MCA Configure
Menu displays the hours remaining in an automatic equalize period, if active.
Note: Auto Equalize is canceled and the system is placed in the float mode if any of the
following occurs.
1) Manually placing the system in the float mode by navigating to and activating
"TEST/EQUALIZE MODE ACTIVE. SET FLOAT?" menu item in the MCA
Function Menu.
2) Resetting the "AUTO EQUALIZE FOR ## x DISCHARGE" value in the MCA
Configure Menu when "END AUTO hhh.hh HR" is being displayed, as
described in the previous procedure
3) Applying an external test/equalize signal.
Programming the MCA Power Share Feature in the New Power System
After a New Power System has been connected to an Existing Power System and both
systems set for the same float voltage, you will have to configure the Power Share
parameters in the MCA of the New Power System.
Note: The “Power Share” feature is not compatible with the temperature compensation
feature. If temperature compensation is programmed ON, then “Turn Off
Temperature Compensation” is displayed in the Power Share menu. If Power
Share is programmed ON, then “Turn Off Power Share” is displayed in the
temperature compensation menu.
Note: The Rectifier current limit menu item setting is ignored when Power Share is
enabled. When Power Share is enabled, the message “PCU Current Limit Power
Share” is displayed in the PCU Current Limit menu.
Enabling Power Share
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
2) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"ADJUST THE SYSTEM VOLTS & AMPS" is displayed.
3) Press and release the FUNCTION SET ENTER key.
4) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"POWER SHARE IS OFF, TURN IT ON?" is displayed.
Note: If “TURN OFF TEMPERATURE COMPENSATION” is displayed, the MCA
is set for temperature compensation. Disable temperature compensation
and then return to this procedure.
5) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously. "ARE YOU SURE?" is displayed. Press and release the
FUNCTION SET YES (+) key.
6) Continue with the next procedure.
Setting the Power Share Initial Capacity Limit
1) From the previous procedure, press and release the FUNCTION SELECT
DOWN arrow key to display "PS INITIAL CAPACITY LIMIT = ##%".
2) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
3) Press and hold the FUNCTION SET YES (+) or NO (-) key to change this setting
as required. Release the key when the desired value is displayed.
Note: Enter the percentage value of the total capacity of the New Power System
that will initially feed the load. This value must be set to ensure that the
current delivered by the New Power System is lower than the total load
current from the existing and New Power Systems.
4) With the desired value being displayed, press and release the FUNCTION SET
ENTER key.
5) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
6) Continue with the next procedure.
Setting the Power Share Voltage Offset
1) From the previous procedure, press and release the FUNCTION SELECT
DOWN arrow key to display "PS VOLTAGE OFFSET = v.vV".
2) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
3) Press and hold the FUNCTION SET YES (+) or NO (-) key to change this setting
as required. Release the key when the desired value is displayed.
Note: Enter the value that will be added to the float voltage to ensure the New
Power System will initially carry the load. This value must be higher than
the sum of the voltage drop in the cables connecting the two systems in
parallel and the output voltage regulation specific to the rectifiers of the
Existing Power System. If the sense leads are connected to the same
sensing points as the Existing Power System, the Voltage Offset should
take into consideration the output voltage regulation only.
b) In a Power Share application where the New Power System is taking only part of
the load (operating continuously at the current level equivalent to the
programmed “PS Initial Capacity Limit” percentage) and the rectifiers in the
Existing Power System are taking the rest of the load, use an external dry load
bank of sufficient capacity to increase the load in order to exceed the total
capacity of the rectifiers in the Existing Power System (or shut down some of the
rectifiers in the Existing Power System if the capacity of the external dry load
bank is not sufficient).
1) Verify that the New Power System starts taking the additional load as soon
as the total capacity of the rectifiers in the Existing Power System is
exceeded.
CHAPTER 4
MCA SYSTEM ADJUSTMENTS
TABLE OF CONTENTS
Adjustment Location and Identification ............................................................................ 4-2
Adjusting Float Output Voltage ........................................................................................ 4-3
Adjusting Test/Equalize Output Voltage .......................................................................... 4-4
Adjusting High Voltage Shutdown ................................................................................... 4-5
Adjusting Rectifier Current Limit ...................................................................................... 4-6
Adjusting System High Voltage Alarm 1.......................................................................... 4-7
Adjusting System High Voltage Alarm 2.......................................................................... 4-8
Adjusting System Battery On Discharge Alarm ............................................................... 4-9
Adjusting System Very Low Voltage Alarm ................................................................... 4-10
Adjusting Total Distribution Load Alarm ........................................................................ 4-11
Adjusting Distribution Group A Load Alarm ................................................................... 4-12
Adjusting Distribution Group B Load Alarm ................................................................... 4-13
Adjusting Battery Ambient High Temperature #1 Alarm (if Battery Charge Digital
Temperature Compensation Probe is installed) ............................................................ 4-14
Adjusting Battery Ambient High Temperature #2 Alarm (if Battery Charge Digital
Temperature Compensation Probe is installed) ............................................................ 4-15
Adjusting Battery Ambient Low Temperature #1 Alarm (if Battery Charge Digital
Temperature Compensation Probe is installed) ............................................................ 4-16
Adjusting Battery Ambient Low Temperature #2 Alarm (if Battery Charge Digital
Temperature Compensation Probe is installed) ............................................................ 4-17
Configuring Battery Charge Digital Temperature Compensation Slope ....................... 4-18
Configuring Battery Charge Digital Temperature Compensation Maximum
Voltage........................................................................................................................... 4-19
Configuring Battery Charge Digital Temperature Compensation Minimum Voltage ..... 4-20
Configuring Degree Units Displayed ( F or C) ............................................................. 4-21
Configuring the System Date and Time ........................................................................ 4-22
Configuring MCA I/O Circuit Card Analog Input(s) ........................................................ 4-23
Configuring MCA I/O Circuit Card Analog Output(s) ..................................................... 4-25
Configuring MCA I/O Circuit Card Binary Input(s) ......................................................... 4-26
MCA Audible Alarm Cutoff Reset Time Period.............................................................. 4-27
MCA Rectifier Sequencing Feature ............................................................................... 4-27
Manually Initiated Timed Test/Equalize Feature ........................................................... 4-27
Automatic Test/Equalize Feature .................................................................................. 4-27
MCA Power Share Feature ........................................................................................... 4-27
Alarm Relay Test Feature .............................................................................................. 4-27
MCA “Alternate Current Limit” Feature .......................................................................... 4-27
To toggle the setting, press and release the ALARM CUTOFF and FUNCTION
SET ENTER keys simultaneously.
“ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
To select another analog input (if available), press the FUNCTION SELECT
DOWN arrow key.
7) When the last MCA I/O circuit card with an analog input is selected, press the
FUNCTION SELECT DOWN arrow key to display ANALOG INPUT B#-P# 50mV
= aaaaA (B#-P# = Bay Number – MCA I/O Circuit Card Position Number).
Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
Observe the value displayed. To change this value, press and hold the
FUNCTION SET YES (+) or NO (-) key. Release the key when the desired value
is displayed.
With the desired value being displayed, press and release the FUNCTION SET
ENTER key.
“ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
To select another analog input (if available), press the FUNCTION SELECT
DOWN arrow key.
8) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
Observe the value displayed. To change this value, press and hold the
FUNCTION SET YES (+) or NO (-) key. Release the key when the desired value
is displayed.
With the desired value being displayed, press and release the FUNCTION SET
ENTER key.
“ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
To select another analog output (if available), press the FUNCTION SELECT
DOWN arrow key.
7) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
This setting determines the alarm state of the monitored binary input.
To toggle the setting press and release the ALARM CUTOFF and FUNCTION
SET ENTER keys simultaneously.
“ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
To select another binary input located on the card, press the FUNCTION
SELECT DOWN arrow key. When the last binary input is selected, pressing the
FUNCTION SELECT DOWN arrow key displays the next MCA I/O circuit card
with binary inputs (if available).
7) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
Note: If a binary input alarms, the MCA displays a "Binary Input Customer Text
Message" in the I/O Board Alarm Detail Message. If you wish to change
the default message, refer to 'Chapter 3. System Operating Procedures'
for an adjustment procedure.
CHAPTER 5
SYSTEM MAINTENANCE
TABLE OF CONTENTS
Admonishments ............................................................................................................... 5-2
General Safety .......................................................................................................... 5-2
Voltages .................................................................................................................... 5-2
LMS Maintenance Procedures ........................................................................................ 5-2
System Maintenance Procedures ................................................................................... 5-3
Adding a Rectifier ............................................................................................................ 5-8
ADMONISHMENTS
General Safety
Danger: SERVICE PERSONNEL MUST FOLLOW APPROVED SAFETY
PROCEDURES.
Note: This table may be reproduced as necessary to record and document system
performance.
Table 5-2 (cont’d on next page)
Procedures that MAY be Performed at 12-Month
Intervals to Track System Operation
Bay # (__),
Rectifier 1
Bay # (__),
Rectifier 2
Bay # (__),
Rectifier 3
Bay # (__),
Rectifier 4
Bay # (__),
Section 5877,
Measure and Record Rectifier 5
Chapter 2.
Output Current of Each
Navigating the MCA,
Individual Rectifier Bay # (__),
(Line #126).
Rectifier 6
Bay # (__),
Rectifier 7
Bay # (__),
Rectifier 8
Bay # (__),
Rectifier 9
Bay # (__),
Rectifier 10
Section 5877,
Record Rectifier High Chapter 2.
--
Voltage Shutdown Value Navigating the MCA,
(Line #219).
Section 5877,
Record Rectifier Current Chapter 2.
--
Limit Value Navigating the MCA,
(Line #221).
Note: This table may be reproduced as necessary to record and document system
performance.
Table 5-2 (cont’d from previous page, cont'd on next page)
Procedures that MAY be Performed at 12-Month
Intervals to Track System Operation
ADDING A RECTIFIER
To increase system current capacity, an additional Rectifier can easily be installed in an
existing bay that contains an empty Rectifier mounting position. Follow the procedure
detailed below. A Rectifier may be installed in a live system.
The Rectifier weighs approximately 40 lbs.
Rectifiers can be inserted or removed with power applied (hot swappable).
Procedure
1) Remove the blank panel from the Rectifier mounting position. Save this panel.
The panel must be re-installed if a Rectifier is removed.
2) Ensure that the Standby/Operate switch on the Rectifier to be installed is in the
"standby" position.
Note: In the next step, a safety latch is present on the left-hand (as viewed from the
front) side panel of each Rectifier. The latch is designed to prevent the
Rectifier from inadvertently being removed completely from the Bay once it
has been installed. It should not be necessary to depress the safety latch
release when installing the Rectifier.
3) Install the Rectifier into the bay by sliding it evenly into its mounting position.
Secure the Rectifier to the bay by tightening the captive fasteners on the
Rectifier.
4) Place the Standby/Operate switch on the Rectifier installed to the I "operate"
position.
5) The MCA automatically adds the capacity of the new Rectifier to the current limit
and displays the new current limit setting.
6) If the current limit setting is correct, go to step 10). If the current limit setting is
not correct, press and release the ALARM CUTOFF and FUNCTION SET
ENTER pushbuttons simultaneously.
7) Observe the value displayed. This is the system current limit setting. Reset this
value to the new current limit setting. Each Rectifier’s current limit circuit will be
automatically adjusted to ensure that system current does not exceed this value.
To change this value, press and hold the FUNCTION SET YES (+) or NO (-)
pushbutton. Release the pushbutton when the desired value is displayed.
8) With the desired current limiting value being displayed, press and release the
FUNCTION SET ENTER pushbutton.
9) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) pushbutton.
Note: The system current limit value will not be changed and the adjustment
mode will be exited if the FUNCTION SET YES (+) pushbutton is not
pressed within 10 seconds of the “ARE YOU SURE?” prompt.
10) Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons
simultaneously, to return to the beginning of the MCA menu tree.
11) Ensure that there are no local or remote alarms activated on the system.
CHAPTER 6
SYSTEM TROUBLESHOOTING AND REPAIR
CONTACT INFORMATION
Support contact information is provided on the inside of the back cover of this document.
TABLE OF CONTENTS
Contact Information ......................................................................................................... 6-1
Admonishments ............................................................................................................... 6-2
General Safety .......................................................................................................... 6-2
Voltages .................................................................................................................... 6-2
Circuit Card Handling ................................................................................................ 6-3
LMS Troubleshooting Procedures ................................................................................... 6-3
Troubleshooting Information ............................................................................................ 6-4
General ..................................................................................................................... 6-4
Adjustments .............................................................................................................. 6-4
MCA Messages ......................................................................................................... 6-4
Rectifier Current Sharing Unbalance ........................................................................ 6-5
Rectifier Module Fault Symptoms and Troubleshooting ........................................... 6-6
Updating the Inventory after Changes to the System Have Been Made .................. 6-7
Replacement Information ................................................................................................ 6-8
Replacement Assemblies ......................................................................................... 6-8
Replacement Cables ................................................................................................. 6-8
Replacement Procedures ................................................................................................ 6-9
Rectifier Replacement ............................................................................................... 6-9
MCA Circuit Card Replacement .............................................................................. 6-11
Router Circuit Card Replacement ........................................................................... 6-15
Distribution Bus Monitoring Circuit Card Replacement........................................... 6-18
MCA Customer Alarm Relay Circuit Card Replacement ........................................ 6-21
MCA I/O Circuit Card Replacement ........................................................................ 6-21
Alarm, Reference, and Control Fuse Replacement ................................................ 6-22
Rectifier Fan Replacement ..................................................................................... 6-25
Adding a Battery Charge Digital Temperature Compensation Probe to a
Previously Operated System ......................................................................................... 6-26
Removing a Battery Charge Digital Temperature Compensation Probe from a
Previously Operated System ......................................................................................... 6-27
ADMONISHMENTS
General Safety
Danger: SERVICE PERSONNEL MUST FOLLOW APPROVED SAFETY
PROCEDURES.
TROUBLESHOOTING INFORMATION
General
This system is designed for ease in troubleshooting and repair. The various indicators,
as described in Chapter 3. System Operating Procedures, are designed to isolate a
failure to a specific element. Once the faulty element has been identified, refer to the
next sections, “Replacement Information” and "Replacement Procedures".
The procedures listed in Chapter 5. System Maintenance, can also be used by servicing
personnel in identification and/or prevention of trouble symptoms in the system.
Adjustments
If the suspected cause of a trouble symptom is an out of adjustment condition, that
particular adjustment setting should be checked or reset using the appropriate
adjustment procedure detailed in Chapter 4. MCA System Adjustments. If a failed
Rectifier or circuit card is suspected, the adjustment procedures can also be used to
verify the setpoints as well as the operation of the Rectifier or circuit card.
MCA Messages
An MCA Menu Tree (Section 5886) is provided in the separate INSTALLATION MANUAL
and the CD CARRIER MANUAL (it is also provided on the CD). Each line in the MCA
Menu Tree contains a number. This number is referenced in a chart provided in Chapter
2. Navigating the MCA. This chart provides a description of each line listed on the MCA
Menu Tree.
If the MCA displays an alarm message, find the line in the MCA Menu Tree showing this
message. For an explanation of this alarm, locate the corresponding MCA Menu Tree
Line Number in the chart provided in Chapter 2. Navigating the MCA.
Note: If the MCA is replaced with an MCA previously used in another power system, the
MCA may reflect inventory items not in the current power system and may display
alarms. In this case, update the inventory as detailed in this chapter. Also, if you
remove an inventory item (a component) from the power system, you must update
the inventory to clear alarms.
Note: If you remove a Battery Charge Digital Temperature Compensation Probe, alarms
are displayed. Manually set the Battery Charge Digital Temperature
Compensation feature to off as described in "Chapter 4. MCA System
Adjustments" to clear the alarms.
REPLACEMENT INFORMATION
Replacement Assemblies
When a trouble symptom is localized to a faulty Rectifier or circuit card, that particular
Rectifier or circuit card should be replaced in its entirety. No attempt should be made to
troubleshoot or repair individual components on any Rectifier or circuit card.
Refer to SAG582140000 (System Application Guide) for replacement part numbers. The
SAG can be accessed via the CD (Electronic Documentation Package) furnished with
your system.
Replacement Cables
Refer to SAG582140000 (System Application Guide) for replacement part numbers. The
SAG can be accessed via the CD (Electronic Documentation Package) furnished with
your system.
REPLACEMENT PROCEDURES
Rectifier Replacement
Danger: Observe the instructions on top of the Rectifier as you remove it.
Note: If a Rectifier is removed without being replaced, perform the UPDATE
INVENTORY procedure found in this chapter to clear alarms.
The Rectifier weighs approximately 40 lbs.
Rectifiers can be inserted or removed with power applied (hot swappable).
Procedure
1) Observe the admonishments presented at the beginning of this chapter, and
those encountered in this procedure.
2) Performing this procedure may activate external alarms. Do one of the following.
If possible, disable these alarms. If these alarms cannot be easily disabled,
notify the appropriate personnel to disregard any future alarms associated with
this system.
3) On the Rectifier to be removed, place the Standby/Operate switch to the
"standby" position.
Note: In the next step, a safety latch is present on the left-hand (as viewed from the
front) side panel of each Rectifier. The latch is designed to prevent the
Rectifier from inadvertently being removed completely from the Bay once it
has been installed. It should not be necessary to depress the safety latch
release when installing the Rectifier.
4) Loosen the captive fasteners on the front of the Rectifier to be removed. Use the
handle provided on the front of the Rectifier, and pull the Rectifier out until it is
stopped by a safety latch located on the left-hand side panel of the Rectifier.
Refer to Figure 6-1 for latch and release location. Depress and hold the latch
release, and remove the Rectifier from the shelf. Support the bottom of the
Rectifier as you pull it out. Observe the instructions on top of the Rectifier as
you remove it.
5) Ensure that the Standby/Operate switch on the replacement Rectifier is in the
"standby" position.
6) Slide the replacement Rectifier evenly into its mounting position. It should not be
necessary to depress the safety latch release. Secure the Rectifier to the bay by
tightening the captive fasteners located on the Rectifier.
7) Place the Standby/Operate switch on this Rectifier to the I "operate" position.
8) Enable the external alarms, or notify appropriate personnel that this procedure is
finished.
9) Ensure that there are no local or remote alarms active on the system.
SAFETY LATCH
LATCH RELEASE
INSTRUCTIONS
ON TOP OF PCU AS
PCU IS REMOVED GRASP SIDE IN THIS GRASP SIDE IN THIS
AREA TO CARRY CENTER OF AREA TO CARRY
OR REMOVE PCU. GRAVITY AREA OR REMOVE PCU.
ATTENTION: CAUTION:
SPRING LATCH ON LEFT
SIDE OF PCU MUST BE WEIGHT 40 LBS (18.1kG)
DEPRESSED TO REMOVE
THE PCU FROM THE BAY.
Figure 6-1
208V and 480V Rectifiers
15) Replace fuse F3 which supplies input power to the MCA circuit card. Refer to
Figure 6-7 for location.
16) The MCA goes through an initialization routine (as detailed in Chapter 5.
Installing the Rectifiers and Initially Starting the System of the INSTALLATION
INSTRUCTIONS [Section 5877]). During this initialization routine, check (and if
required change) the MCA settings for your Site. In lieu of manually entering
new MCA settings, if the old MCA configuration was downloaded via the LMS;
upload the configuration. Refer to the LMS User Instructions for a procedure.
17) Remove the grounding wrist strap.
18) Close the bay's front door.
19) Enable the external alarms, or notify appropriate personnel that this procedure is
finished.
20) Ensure that there are no local or remote alarms active on the system.
Factory Required
Setting
Default Setting Site Setting
Float Output Voltage 52.00V
Test/Equalize Output Voltage 52.00V
High Voltage Shutdown 57.50V
100% of Rated
Rectifier Current Limit
Full Load
High Voltage #1 Alarm 55.50V
High Voltage #2 Alarm 56.50V
Battery On Discharge Alarm 51.00V
Very Low Voltage Alarm 47.00V
Total Distribution Load Alarm 2000A
Distribution Group A Load
2000A
Alarm
Distribution Group B Load
2000A
Alarm
High Battery Ambient
Off
Temperature #1 Alarm
High Battery Ambient
Off
Temperature #2 Alarm
Low Battery Ambient
Off
Temperature #1 Alarm
Low Battery Ambient
Off
Temperature #2 Alarm
Digital Temperature Off
Compensation (Slope) (0V/ C)
Digital Temperature
Compensation (Maximum 56.50V
Compensation)
Digital Temperature
Compensation (Minimum 50.00V
Compensation)
Table 6-2
MCA Basic Settings
Factory Required
Setting
Default Setting Site Setting
MCA Audible Alarm
15 Minutes
Silent Time Period
Manually Initiated Timed
1 Hour
Test/Equalize Feature
Automatic
Disabled
Test/Equalize Feature
Alarm Relay
45 Seconds
Test Feature
MCA Customer
-- Program as required.
Alarm Relays
Table 6-3
MCA Advanced Setting
Power/Distribution Bay
(Power Only Bay Similar)
MCA/Router
Circuit Card
Figure 6-2
Power/Distribution Bay
MCA/Router Circuit Card Replacement
(Power Only Bay Similar)
Router
Circuit Card
Distribution Bays
Figure 6-3
Distribution Only Bay
MCA/Router Circuit Card Replacement
Power/Distribution Bays
Distribution Bus
Monitoring
Circuit Card
Figure 6-4
Power/Distribution Bay
Distribution Bus Monitoring Circuit Card Replacement
Distribution Bays
Distribution
Bus Monitoring
Circuit Card
Figure 6-5
Distribution Only Bay
Distribution Bus Monitoring Circuit Card Replacement
Figure 6-6
Installation of Safety Fuse Covers
F1 F2 F3
3A 3A 3A
Figure 6-7
Power/Distribution Bay Fuse Locations
(Power Only Bay Similar)
Distribution Bays
F1 (3A) Router
Figure 6-8
Distribution Only Bay Fuse Locations
REVISION RECORD
Change
Issue Number Description of Change
(ECO)
AA LLP035201 New
LMS 12-Input Analog card added. MCA version 1.1.0 features added. MCA I/O
AB LLP203036
cards added.
Alarm, Reference, and Control Fuse Replacement section in
AC LLP203895
TROUBLESHOOTING chapter updated.
PDSC Surge Suppression Alarms added to "Local Controls and Indicators"
AD LLP205577
section.
AE LLP209720 Distribution Only Bay Added.
Updated for MCA version 2.0.0.19 (relay test feature enhanced, Power Share
AF LLP210933
feature added [legacy rectifier interface]).
AG LLP211532 Model number changed, 480V Rectifier changed.
AH LLP212313 LMS Dual MCA Option Added. Updates for latest MCA version.
AJ LLP213082 Updates for LMS Firmware 9.1 and MCA version 2.2.
AK LLP215440 Implementation of new spiral bound covers.
AL LLP214855 Updated for MCA version 2.3.0.5. Corrected part number of LMS CPU card.
Input redesigned. LMS Local Port on front door now USB (was RS-232).
AM LLP216269
Distribution Only Bay Options deleted.
Update USB to Serial illustration label; add instructions to download and install
AN LLP215965
USB driver to customer computer; added 582140000 distribution only bay.
AP LLP217313 Distribution Only Bay model number changed to 802NL-B.
AQ LLP217720 PCU current limit = aaaaaMAX added. Power Only Bay added.
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
NetPerform™ Optimization Services
At Emerson Network Power, we understand the importance of reliable equipment – it’s critical to both
your business and your bottom line. That is why we offer a wide array of services to meet all of your
network infrastructure needs.
Technical Support
Email DCpower.TAC@Emerson.com Answers technical product and system
OSP.TAC@Emerson.com questions; determines status of warranties and
Phone 1.800.800.5260 contractual agreements for repair.
Spare Parts
Email DCpower.Spares@Emerson.com Pricing and PO processing of spare parts,
OSP.Spares@Emerson.com including but not limited to breakers, cables,
fuses, rectifier fans, misc. breaker and fuse
Phone 1.800.800.1280, option 5
panels, enclosure fans, doors & switches, etc.