Beruflich Dokumente
Kultur Dokumente
Qualitative Detailed Damage Assessment, Seismic Vulnerability Assessment & Retrofit Design of “Shree
Karfok Vidhya Mandir, Karfok, Illam” has been assessed by DIGICON-IDEAL JV in January 2018. This
assessment of the building is done based on the best engineering judgment arrived from the site visit. The
Damage Assessment has been carried out by visualization and identification of damages to different
components of the building due to Gorkha earthquake 2015. Seismic Vulnerability assessment to future
earthquakes involves the use of set of checklists and identification of potential weakness in the buildings.
The assessed building is single story rubble stone masonry building. The detailed damage assessment
shows that the building has suffered a damage of Grade-1, as per EMS-98 scale. Furthermore, seismic
vulnerability assessment shows that the building is likely to suffer damage grade five (DG5) at MMI IX
intensity of earthquake which indicates total collapse of the building.
Both side RC jacketing with 4.75mm diameter TMT bar of diameter 150mm c/c is designed to address the
seismic vulnerabilities of the present stone in mud masonry building. The cost of retrofitting the building
is estimated to be Rs. 22,95,195.
1
Table of Contents
EXECUTIVE SUMMARY ......................................................................................................................... 1
1 INTRODUCTION ............................................................................................................................... 3
1.1 Background of Building ............................................................................................................... 3
1.2 Background of Project ................................................................................................................. 5
2 METHODOLOGY .............................................................................................................................. 6
2.1 Desk Study & Rapid Visual Screening (RVS) ............................................................................. 7
2.2 Field Visit for detail data acquisition ........................................................................................... 7
2.3 Preliminary Evaluation ................................................................................................................ 7
2.4 Detailed Evaluation ...................................................................................................................... 7
2.4.1 Determination of Shear Strength of Masonry ...................................................................... 7
2.4.2 Determination of Compression Strength and Modulus of Elasticity of Masonry ................ 8
2.5 Retrofitting Design....................................................................................................................... 8
3 DAMAGE ASSESSMENT.................................................................................................................. 9
3.1 Findings of the Assessment.......................................................................................................... 9
3.2 Expected Damage in the Building due to 25th April, 2015, Gorkha Earthquake ...................... 11
3.2.1 Vulnerability Class of the Building.................................................................................... 11
3.2.2 Intensity of 2015 Earthquake at the Site ............................................................................ 11
3.2.3 Expected Damage due to the Earthquake at the site .......................................................... 12
4 VULNERABILITY ASSESSMENT ................................................................................................. 13
4.1 Vulnerability of the Building against Design Earthquake ......................................................... 13
4.2 Qualitative Detailed Vulnerability Assessment ......................................................................... 13
4.3 Detailed Vulnerability Assessment ............................................................................................ 13
4.3.1 Numerical Model of the Building ...................................................................................... 13
4.3.2 Shear Strength Check ......................................................................................................... 15
5 CONCLUSION AND RECOMMENDATIONS OF VULNERABILITY ASSESSMENT ............. 17
6 RETROFIT OF THE BUILDING ..................................................................................................... 17
6.1 Methodology Adopted ............................................................................................................... 17
6.2 Calculation of Base Shear .......................................................................................................... 17
6.3 Retrofit Design against In-plane Tensile Forces ........................................................................ 18
6.4 Retrofit design against out of plane bending forces ................................................................... 21
6.5 Design against Shear .................................................................................................................. 23
7 DESIGN SUMMARY ....................................................................................................................... 24
8 DESIGN CONCLUSION AND RECOMMENDATION ................................................................. 25
References .................................................................................................................................................. 25
2
1 INTRODUCTION
3
Salient Features of the Building
Building Typology: Field Stone Masonry with mud mortar joint
Shape of the Building: Rectangular
Plinth Area of the Building: 149.55 m2
No. of Stories: 1
Roof Type: Flexible Diaphragm
Age of the Building: 34 years
Use Type: Classroom
Vulnerability Class of the Building (EMS 98): CLASS A
4
1
2
3
19200
13000 5768
587 507
530 900 900 1163 900 697 900 933 900 900 953 900 2611 900 1452
3252 900
X
W1
7400
7800
1203
7800
7400
ROOM ROOM
7000x12600 5372x7000
500 900 900 900
W1
W1
W1 W1 W1 W1 W1
D1 D1 D1 D1
B B
1000 900 940 900 903 900 950 900 960 900 953 900 770 900 900 1522 900
13000 5769
19172
X 685
1
2
3
5
The basic principle of the reconstruction in recovery process after disaster is to build better and also as
possible to make community and infrastructures disaster resilient to create resilient societies. For this, the
existing building need to be assessed whether it can be retrofitted or not. The objective of the assignment
is to assess in detail the damage and earthquake vulnerability of existing school building and to prepare
detailed design and drawings for retrofitting of the buildings in order to make them disaster resilient.
2 METHODOLOGY
Evaluation Process
Detail Evaluation;
Linear Static /Linear Dynamic Analysis
Make Report
For the detail retrofitting design of building, series of tasks are needed to be done in a sequential order. The
methodology to be adopted is given below.
6
2.1 Desk Study & Rapid Visual Screening (RVS)
In this phase the literatures shall be reviewed for identifying the importance of building and its background.
The historical use pattern and structural makeup of the building and other data (if available) is extracted
from the literatures. Site visit for Rapid Visual survey is done. This is to identify the basic structural system
of the building, basic condition and damages in the building.
After detailed evaluation, the recommendation shall be made for preservation and retrofitting of the
building.
The nondestructive test measures the in situ shear strength between a clay masonry unit and the mortar bed
joints above and below the unit. A small hydraulic jack is placed in a void left by removal of a masonry
unit immediately adjacent to the test unit. The head joint on the opposite face of the test unit is removed to
isolate the test unit so that it may be displaced horizontally when pushed.
A horizontal force is applied to the test unit until it starts to slide. Shear strength is then inferred as the
measured force divided by the area of the bed joints above and below the masonry unit. The estimated
vertical compressive stress at the test location is subtracted from this value to give the bed joint shear stress,
7
vto, assuming a coefficient of friction equal to 1.0. Because expected values of wall shear strength are to
be used, the 50th percentile value, vt, is used as the index value. (Reference FEMA 274)
Individual bed-joint shear strength test values, vto, shall be determined in accordance with undermentioned
equation,
Where:
D = In-plane width dimension of masonry,
t = Thickness of wall,
vme = expected masonry shear strength given by Equation below,
Where:
vte = Average bed-joint shear strength and not to exceed 0.68 MPa;
PCE = Expected gravity compressive force applied to a wall or pier component stress;
An = Area of net mortared/grouted section.
The shear strength of the building for which in-situ shear test could not be carried out, shear strength lower
bond value, as recommended by FEMA 356, is adopted for design calculation and retrofitting purpose.
2.4.2 Determination of Compression Strength and Modulus of Elasticity of Masonry
The compressive strength of the building masonry system is adopted as per the recommendation of FEMA
356. The design values are adopted on the basis of visual inspection of the building masonry system.
8
weakness shall be performed. Drawings and detailing shall be prepared. The cost estimation of the retrofit
shall be prepared and submitted with the retrofit design report.
3 DAMAGE ASSESSMENT
The crack pattern found in the building was compared with the crack pattern of the EMS-98 scales. This
resulted in the designation of the Damage Grade 1 of the building.
The quantity describing the damage is defined by following scale guidelines for grading is given in next
figure.
9
Figure 9: EMS-98 Damage Grading
Few important photographs depicting the damages in the building are given below.
10
3.2 Expected Damage in the Building due to 25th April, 2015, Gorkha Earthquake
3.2.1 Vulnerability Class of the Building
According to EMS-98, the building falls under Vulnerability Class A.
11
Figure 12: Intensity Map of April 25, 2015 Earthquake (Source: USGS)
12
4 VULNERABILITY ASSESSMENT
13
Unit weight of roof = 12.3 KN/m3
Modulus of Elasticity of wall = 700 MPa
Modulus of Elasticity of floor = 12000 MPa
Modulus of Elasticity of roof = 12000 MPa
The compressive strength of the building masonry system is adopted as per the recommendation of FEMA
356. The design values are adopted on the basis of visual inspection of the building masonry system.
Loads
The loads are taken from Indian Standards and the load factors recommended by FEMA 310 are adopted.
Floor Live = 3 KN/m2 at rooms
Floor Live = 4 KN/m2 at corridors and balconies
Roof Live = 1.5 KN/m2
Floor finish = 1 KN/m2
Seismic Load = as per IS 1893-2016 draft code
i.e. Z=0.36, R= 1.5, I=1.5, Sa/g =2.5
Time Period Calculation
h= 3.7 m
d= 7.35 m along short span
Ta =0.09*h/ d 0.5
= 0.20 sec.
The guideline also recommends to increase the value by 1.3 times to get expected strength from lower
bound value. However, adopting a bit conservative approach, the designer has not increased the value by
this amount. The shear capacity of a masonry wall increases with compressive force on the wall. So the
shear strength values are increased by PCE /1.5An .
Shear strength adopted for the building is shown in table below.
Story Dead load at the top of wall of a story Wall area vme
ID KN sq. m Mpa
I 1577.05 17.94 0.050
Then shear capacities of various stories of the building as per FEMA 310 cl. 4.2.6, are given below.
Story vme An along X An along Y Va along X Va along Y
Mpa m2 m2 KN KN
15
I 0.050 9.60 8.30 318.89 275.71
Story Story Shear Vj Va along X Va along Y DCR along X DCR along Y Remark
No. KN KN KN
I 687.45 318.89 275.71 2.160 2.490 Not OK
16
5 CONCLUSION AND RECOMMENDATIONS OF VULNERABILITY
ASSESSMENT
The building has suffered Damage Grade-1: Negligible to slight damage as per (EMS-98) in the
Gorkha, 2015, Earthquake. (Reference: Section 3.1)
The CGI sheet of the building is corroded.
The floor of the building is rough.
The building is likely to suffer Grade-5 damage (Destruction) at design level earthquake.
(Reference: Section 4.1)
The building is unsafe in shear and weak in tension and out of plane forces. (Reference: Section
4.3.2)
Floor and roof stiffeners should be added.
Treatment for wood used should be done by painting weather coat paint/enamel paint.
The building needs retrofitting.
The approximate fundamental natural period of vibration (Ta) in seconds, may be estimated by the
empirical expression:
Ta = 0.09h/d0.5
Where,
17
h = Height of the building in meter and
d = Base dimension of building at plinth level in meter, along the considered direction of lateral force.
Now,
h= 3.7 m
d= 7.35 m along short span
Ta =0.09*h/ d 0.5
= 0.20 sec.
(Sa/g) = 2.5
Z= 0.36 (Zone V)
I= 1.5 (Public building)
R= 2.25 for Reinforced with horizontal RC bands and vertical bars at
corners of rooms and jams of openings
Hence, Ah = 0.3
Therefore, the base shear coefficient is taken as 0.3
Pier 2
Pier 1
Pier 1 Pier 2
Maximum tensile stress due to pier action (N/mm2) : 0.21 0.15
Length of tensile stress zone in pier (mm) : 940 330
Therefore, average tensile stress (N/mm2) : 0.11 0.08
Thickness of wall (mm) : 400 400
Total Tensile force (N) : 41360 10560
For tensile load, adopted bar diameter (mm) : 4.75 4.75
For Fe 500, allowable stress (N/mm2) : 275 275
Nos of bar required, F/(As*Sall) : 8.487323104 2.166976112
Applying band on both faces of pier, Adopt : 5 - 4.75 mm bars 2 - 4.75 mm bars
@ 150 mm @ 150 mm spacing
spacing
Pier 1 Pier 2
Pier 1 Pier 2
2
Maximum tensile stress due to pier action (N/mm ) : 0.16 0.19
Length of tensile stress zone in pier (mm) : 430 530
Therefore, average tensile stress (N/mm2) : 0.08 0.1
Thickness of wall (mm) : 400 400
Total Tensile force (N) : 13760 21200
For tensile load, adopted bar diameter (mm) : 4.75 4.75
For Fe 500, allowable stress (N/mm2) : 275 275
Nos of bar required, F/(As*Sall) : 2.823635539 4.350368709
Applying band on both faces of pier, Adopt : 2 - 4.75 mm bars 3 - 4.75 mm bars @
@ 150 mm 150 mm spacing
spacing
19
Vertical Tensile or Compressive Stress, S22, 0.7D+EQY Loading
Wall along 1-1
Pier 2
Pier 1
Pier 1 Pier 2
2
Maximum tensile stress due to pier action (N/mm ) : 0.21 0.12
Length of tensile stress zone in pier (mm) : 900 2150
Therefore, average tensile stress (N/mm2) : 0.11 0.06
Thickness of wall (mm) : 400 400
Total Tensile force (N) : 39600 51600
For tensile load, adopted bar diameter (mm) : 4.75 4.75
For Fe 500, allowable stress (N/mm2) : 275 275
Nos of bar required, F/(As*Sall) : 8.126160418 10.58863327
Applying band on both faces of pier, Adopt : 5 - 4.75 mm bars 6 - 4.75 mm bars
@ 150 mm @ 150 mm spacing
spacing
Pier 1
Pier 1
2
Maximum tensile stress due to pier action (N/mm ) : 0.03
Length of tensile stress zone in pier (mm) : 7350
Therefore, average tensile stress (N/mm2) : 0.02
Thickness of wall (mm) : 400
20
Total Tensile force (N) : 58800
For tensile load, adopted bar diameter (mm) : 4.75
For Fe 500, allowable stress (N/mm2) : 275
Nos of bar required, F/(As*Sall) : 12.06611699
Applying band on both faces of pier, Adopt : 7 - 4.75 mm bars @
150 mm spacing
21
Maximum bending moment intensity in wall = 23.05 KN-m/m
Distance between maximum and minimum moment intensity = 1.6 m
Average bending moment = 0.5*23.05*1.6 = 18.44 KN-m
Off plane Bending Moment distribution due to 0.7DL+EQx Loading, Horizontal strip
Wall along 1-1
7 DESIGN SUMMARY
The summary of the retrofit design of the building is shown in table below.
24
8 DESIGN CONCLUSION AND RECOMMENDATION
1. Both side RC jacketing with TMT bar of diameter 150mm c/c is designed to address the seismic
vulnerabilities of the present stone in mud masonry building.
2. Individual components are also strengthening as well as braced against local failures under design
level earthquake.
3. Replacement of CGI sheet is required in this building.
4. Roof and floor bracing, anchorage between diaphragm and wall, floor finish, replacement of rusted
roof covering etc., should be performed.
5. Connections for rafter and wall, rafter and beam are required.
6. Chipping, re-plastering and finishing should be done.
7. Treatment for seepage should be done.
8. Painting of truss should be done with enamel.
9. Treatment for woods used is required and can be done by painting with weather coat paint or
enamel paint.
10. Replace the windows with wall and add buttress. (Refer drawing for details)
11. The estimated cost of retrofitting the building is Rs. 22,95,195 which is 31% of reconstruction cost
for the building.
References
[1] EMS-98, European Macroseismic Scale 1998
[2] IS 1893 part 1, Criteria for Earthquake Resistant Design of Structures 2016
[3] IS 875, Code of Practice for Design Loads for Buildings and Structures 1987
[4] FEMA 310, Handbook for Seismic Evaluation of Buildings
25