Sie sind auf Seite 1von 1

Industry-Electronic Cable

JE-Y(St)Y Bd Si according to DIN VDE 0815

Technical data Cable structure Application


± Special core insulation to ± Solid plain copper conductor wire This cable type is especially suited for
DIN VDE 0815/DIN 57815 0,8 mm 1 transmission of signals and measure-
± Conductor resistance at 208 C ± Special PVC core insulation YI3, to ments in the fields of electronics and for
36,6 Ohm/km DIN VDE 0207 part 4 data transmission in computers. Suitable
± Temperature range ± Simatic colour coded to DIN VDE 0815 for fixed installation in and under plaster,
flexing ± 58 C to +508 C ± Cores stranded in pairs with optimal in dry and moist environments as well as
fixed installation ±308 C to +708 C lay-length in the open. C
± Nominal voltage 225 V ± 4 pairs stranded to a unit This cable with a blue outer jacket is
(not for purposes of high current and ± Units stranded in layer suitable for intrinsic safe installations.
power installation) ± Polyester foil wrap
± Test voltage ± PVC coated aluminium foil screen These cables are not allowed for
core/core 500 V ± Copper drain-wire, bare purposes of high current and power
core/screen 2000 V ± Special PVC outer sheath YM1, to installation.
± Insulation resistance DIN VDE 0207 part 5
min. 100 MOhm x km colour grey (RAL 7032) or blue
± Mutual capacitance (RAL 5015)
max. 100 pF/m (the value can exceed of ± PVC self-extinguishing and flame retar-
20% by cables up to 4 pairs) dant, test method B according to
± Capacitance unbalance DIN VDE 0472, part 804 and IEC 60332-1
max. 200 pF/100 m
± Inductance approx. 0,70 mH/km
± Attenuation at 800 Hz
approx. 1,1 dB/km
± Radiation resistance
up to 80 x 106 cJ/kg (up to 80 Mrad)
± Minimum bending radius
stationary approx. 6 x cable 1
Caloric load values see page T 68
= The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.

jacket colour grey jacket colour grey


Part No. pairs x Outer 1 Cop. Weight Preis Part No. pairs x Outer 1 Cop. Weight Preis
No. diameter ca. mm weight ca. kg / km DM / 100 m No. diameter ca. mm weight ca. kg / km DM / 100 m
mm kg / km Cu 200, ± mm kg / km Cu 200, ±
48500 1 x 2 x 0,8 4,8 20 43 48505 16 x 2 x 0,8 14,5 166 290
48501 2 x 2 x 0,8 6,0 25 60 48506 20 x 2 x 0,8 16,0 206 350
48502 4 x 2 x 0,8 8,5 45 95 48507 32 x 2 x 0,8 20,0 327 545
48503 8 x 2 x 0,8 11,0 85 157 48508 40 x 2 x 0,8 22,0 407 660
48504 12 x 2 x 0,8 13,0 126 224 48509 80 x 2 x 0,8 30,0 809 1160

jacket colour blue jacket colour blue


Part No. pairs x Outer 1 Cop. Weight Preis Part No. pairs x Outer 1 Cop. Weight Preis
No. diameter ca. mm weight ca. kg / km DM / 100 m No. diameter ca. mm weight ca. kg / km DM / 100 m
mm kg / km Cu 200, ± mm kg / km Cu 200, ±
48519 1 x 2 x 0,8 4,8 20 43 48524 16 x 2 x 0,8 14,5 166 290
48520 2 x 2 x 0,8 6,0 25 60 48525 20 x 2 x 0,8 16,0 206 350
48521 4 x 2 x 0,8 8,5 45 95 48526 32 x 2 x 0,8 20,0 327 545
48522 8 x 2 x 0,8 11,0 85 157 48527 40 x 2 x 0,8 22,0 407 660
48523 12 x 2 x 0,8 13,0 126 224 48528 80 x 2 x 0,8 30,0 809 1160

Also available in a halogen-free version.


See group ¹Halogen-free cablesª page G 8.
PVC cables will be changed to lead free PVC successively.