Beruflich Dokumente
Kultur Dokumente
ZTL for the low-voltage winding and ZTH for the high-voltage winding. An infinite
impedance between the junction point of these impedances to the fictitious bus R is
connected. In computer calculations this infinite impedance will be simulated by a
large value, i.e., 999 þ j9999, on a per unit basis.
The zero sequence network is treated in a similar manner, i.e., the zero
sequence impedance is split between the windings and the equivalent grounding
resistor 3RN is connected between the junction point and the fictitious bus R.
Figure 1-15( c) shows another approach to the creation a fictitious bus R to
preserve the integrity of nodes in the sequence networks. For the positive sequence
network, a large impedance is connected between bus 2 and bus R, while for the zero
sequence network an impedance equal to Z0TH þ 3RN is connected between bus 2
and bus R.
This chapter provides the basic concepts. The discussions of symmetrical com-
ponents, construction of sequence networks, and fault current calculations are car-
ried over to Chapter 2.
Problems
1. A short transmission line of inductance 0.05 H and resistance 1 ohm is
suddenly
pffiffiffi short-circuited at the receiving end, while the source voltage is
480 ð 2Þ sin ð2ft þ 30 Þ. At what instant of the short-circuit will the dc
offset be zero? At what instant will the dc offset be a maximum?
2. Figure 1-1 shows a nondecaying ac component of the fault current.
Explain why this is not correct for a fault close to a generator.
3. Explain similarity transformation. How is it related to the diagonaliza-
tion of a matrix?
4. Find the eigenvalues of the matrix:
2 3
6 2 2
6 7
4 2 3 1 5
2 1 3
5. A power system is shown in Fig. 1-P1. Assume that loads do not con-
tribute to the short-circuit currents. Convert to a common 100 MVA
base, and form sequence impedance networks. Redraw zero sequence
network to eliminate discontinuities.
6. Three unequal load resistances of 10, 20, and 20 ohms are connected in
delta 10 ohms between lines a and b, 20 ohms between lines b and c and
200 ohms between lines c and a. The power supply is a balanced three-
phase system of 480 V rms between the lines. Find symmetrical compo-
nents of line currents and delta currents.
7. In Fig. 1-10, the zigzag transformer is replaced with a wye–delta con-
nected transformer. Show the distribution of the fault current for a phase-
to-ground fault on one of the phases.
8. Resistances of 6, 6, and 5 ohms are connected in a wye configuration
across a balanced three-phase supply system of line-to-line voltage of
480 V rms (Fig. 1-P2). The wye point of the load (neutral) is not
grounded. Calculate the neutral voltage with respect to ground using
symmetrical components and Clarke’s components’ transformation.
Figure 1-10 (a) Current distribution in a delta–delta system with zigzag grounding trans-
former for a single line-to-ground fault; (b) zigzag transformer winding connections.
The impedance to the zero sequence currents is that due to leakage flux of the
windings. For positive or negative sequence currents, neglecting magnetizing current,
the connection has infinite impedance. Figure 1-10(a) shows the distribution of zero
sequence current and its return path for a single line to ground fault on one of the
phases. The ground current divides equally through the zigzag transformer; one-
third of the current returns directly to the fault point and the remaining two-thirds
must pass through two phases of the delta connected windings to return to the fault
point. Two phases and windings on the primary delta must carry current to balance
we can say that, in a core type, the windings surround the core, and in the shell type,
the core surrounds the windings.
Figure 1-9 (a) Derivations of equivalent zero sequence circuit for a delta–wye transformer,
wye neutral solidly grounded; (b) zero sequence circuit of a delta–wye transformer, wye
neutral isolated.
Example 1.2
Figure 1-13(a) shows a single line diagram, with three generators, three transmission
lines, six transformers, and three buses. It is required to construct positive, negative,
and zero sequence networks looking from the fault point marked F. Ignore the load
currents.
The positive sequence network is shown in Fig. 1-13(b). There are three gen-
erators in the system, and their positive sequence impedances are clearly marked in