Beruflich Dokumente
Kultur Dokumente
PRO 2017
CHAPTER 1
INTRODUCTION TO STRUCTURE
1.1 GENERAL
As the cities are growing rapidly with fast economy, thus resulting in expansion of the
city. As the population increasing every day, demand for shelter is exorbitantly increasing. It
becomes the responsibility of civil engineers to build structures, ensuring all safety measures
causing no damage to the structure.
An attempt has been made to learn the steps which are involved in the construction
activity. The project mainly deals with analysis and design of Residential building in
Mangalore.
Analysis and design has been done for five storied Residential building. The structure
is analyzed using STAAD PRO V8i version software for gravity loads and the results thus
obtained were used for design, which was done manually by incorporating the limits state
method using IS 456:2000 and SP-16 codes.
1.1.1 MULTI-STORY
A multi-storied building is a building that supports two or more floor above ground.
There is no formal restriction on the height of such a building or the number of floors a multi
–story building may contain, though taller building does face more practical difficulties’
multi -story building may be designed as a place of business, such as a hospital, law firm , a
casino, a mall or a government building. Other types of multi-story apartment buildings to
provide adequate housing within the local area, or to meet the housing needs of a growing
community.
A commercial building is a building that is used for commercial use. Types can include office
building, warehouses, or retail (i.e. convenience stores, “big box” stores, shopping mall, etc.)
1. The structure must be safe, for society demands, security in structures it inhabitants.
2. The structure must fulfill its intended purpose during its intended life span.
3 The structure must be economical with first cost and to maintenance costs; indeed, the
most design decisions are, implicitly, economic decisions.
A structural project is initiated by client, who states his requirements of the f
structure. His requirements are usually vague because he is not aware of the possibilities and
limitations of the structural engineering. In fact his most important requirements are often not
explicitly stated. For example, he will assume that the structure will be safe and it will remain
serviceable during its intended life.
State I: Planning
It involves analysis of structure for the determination of external design forces in the
members and behavior of the structure under the action of these forces, bending moment,
shear force etc, and structural analysis is done using STAAD PRO software
This stage involves determination of sizes of the members, amount and detailing
reinforcement for resisting the design forces calculated.
I. Planning
After getting an architectural plan of the building, structural planning of the building
frame is done. This involves determination of the following
a) Position and orientation of the columns
b) Positioning of the beams
c) Spanning of the slabs
d) Layouts of the stairs
e) Selecting proper type of loading
II. Loading
III. Analysis
Structural analysis is the determination of internal forces like bending moment and
shear force developed in the members of the structure and to study the behaviors of the
structure as whole. In the proposed project the analysis has been done using the software
STAAD PRO.
a) Flexural
b) Compression
c) Shear
d) Torsion
This state corresponds to development of excessive deformation and is used for checking
member in which magnitude of deformations may limit the rise of the structure of its
components.
a) Deflection
b) Cracking
c) Vibration
4. Kani’s method
5. Cantilever method
6. Portal method
Iterative methods: These methods involve distributing the known fixed and moments of the
structural member to adjacent members at the joints in order satisfy the conditions of
compatibility.
Limitations:
Horizontal cases: The behavior of a structure subjected to horizontal forces depends upon its
heights to width ratio among their factor. It is necessary ti differentiate between low rise and
high rise frames in this case.
Low rise structures: If height is less than width -It is characterized predominately by shear
deformation.
High rise buildings: If height is greater than Width-It is dominated by bending action.
Modern method of analysis and design lead us to the level at which various forces,
moments act in the member of a frame are known, and appropriate cross sections are
chosen.
The building is proposed to construct at Kannur, Kerala and it is planned in keeping
view of the people to provide better opportunity in their area. The design of building is so
planned that is financially viable. The limit state design is more realistic than other
methods and it is safer to use, since it is a more scientific approach for the design of steel
structures.
When an earthquake struck any residential area, Hundreds of people get killed and
many get injured when an earthquake struck any residential area. Tremors can be felt from at
hundreds of kilometers from the epicenter of the earthquake. An earthquake is a phenomenon
in which Earth’s surface shakes due to the release of seismic energy from large blocks of the
crust along a fault. Faults are cracks in the crust. The point under the earth crust on the fault
surface where the process of earthquakes begins, it is the source of earthquake and it is
termed as the focus. Focus is the center from where Seismic waves radiates outward.
Earthquake Epicenters: The point which is directly above the focus on earth surface is
called the epicenter. If we join the entire earthquake epicenter on map it shows a well-defined
regions of the Earth which is long and narrow and sometimes referred to as earthquake belts.
Tectonic plates: Movement of tectonic plates is one of the major reasons of earthquakes.
The lithosphere is divided into many tectonic plates which are moving slowly with respect to
each other. There are 7-8 major plates and many minor plates. Movement of plates varies
between 0 to 100mm per year, these plates float on the underlying hot and viscous mantle.
The Richter scale: Charles F. Richter developed the Richter magnitude scale in 1935 in
California. The magnitude of an earthquake is determined by analyzing the waves recorded
by seismographs. On the Richter scale, the magnitude of earthquake is expressed as whole
numbers in decimal fractions. Because of the logarithmic basis of the scale, each increase in
magnitude represents a tenfold increase in measured amplitude. Earlier, the Richter scale
could be applied only to those records which are from instruments manufactured by same
company. Now, instruments are carefully calibrated with respect to each other. Thus, Richter
scale can be applied to record of any calibrated seismograph.
Impact of Earthquake: Earthquake has a huge impact on our day-to-day life. The
following things are affected due to earthquake:
E Density α
Mat Name (kN/mm2) v (kg/m2) o
(/ C)
CHAPTER 2
LITERATURE REVIEW
Ho Jung Lee.et.al.
The Burj Dubai Tower, when completed, will be the world's tallest structure. Whereas
the final height of this multi-use skyscraper is a “well-guarded secret," it will comfortably
exceed the current record holder of 509 meter (1671 ft) tall Taipei 101. The 280.000 m2
(3.000.000 ft2) reinforced concrete tower will be used for retail, an Armani hotel, residences,
and offices. The goal of the Burj Dubai Tower is not simply to be the world's highest
building—it is to embody the world's highest aspirations. Designers purposefully shaped the
structural concrete for the Burj Dubai to be Y-shaped in plan to reduce the wind forces as
well as to keep the structure simple and foster constructability. The structural system can be
described as a buttressed core, as shown in Fig. I and 2. Each wing, with its own high-
performance concrete core and perimeter columns, buttresses the others via a six-sided
central core, or hexagonal hub. The result is a tower that is extremely stiff torsion ally. The
design team purposely aligned all the common central core and column elements to form a
building with no structural transfers.
Each tier of the building steps back in a spiral pattern that causes the tower’s width to
change at each setback. The advantage of this stepping and shaping is to “confuse the wind.”
The wind vortexes never become organized because at each new tier the wind encounters a
different building shape that reduces the overall wind loads on the structure. Due to the
tapering of the tower, the primary demand on the link beams is from gravity load
redistribution, flow from the taller core to the perimeter of the structure. The 280,000 m2
(3,000,000 ft2) tower and 185,000 m2 (2,000,000 ft2) podium structures are currently under
construction. The project is scheduled for completion in 2009.
A of the ACI 318-02 Building Code (Cagley 2001).which is intended to replace the
procedure given in Section 11.8 of the ACI 318-99 Code. The behaviour of the deep beams is
described in terms of cracking pattern. Joad-versus-deflection response, reinforcement,
concrete strains, failure load and failure mode. The experimental failure load of each
specimen is compared with the load capacities calculated using the procedures given in the
ACI 318-99 Code, and Appendix A of the ACI 318-02 Building code
ManickaSelvam.V. K, et.al.
In this paper, a new approach is put forward for the determination of shear in
columns, which eliminates the flow of the improved portal method and at the same time
yields results close to that of the improved portal method. The proposed method is scientific
as it is founded on a principle depending on the principal flexibility influence co-efficient. It
is a valid and useful addition to the improved portal method.
Prashanth.et.al.
STAAD PRO and ETABS are the present day leading design software’s in the
market. Many design companies use these software’s for their project design purposes. So,
this project mainly deals with the comparative analysis of the results obtained from the design
of a regular and a plan irregular (as per IS 1893) multi storey building structure when
designed using STAAD PRO and ETABS software’s separately. These results will also be
compared with manual calculations of a sample beam and column of the same structure
designed as per IS 456.
A large number of multi-storey reinforced concrete (R/C) framed building structures in urban
India are constructed with masonry in fills for architectural, aesthetic or economic reasons.
We have investigated the effect of the layout of masonry infill panels over the elevation of
masonry in filled R/C frames on the seismic performance and potential seismic damage of the
frame under strong ground motions using nonlinear static push-over analysis based on
realistic and efficient computational models. From output non-linear analysis, we compare
Base shear and Displacement in bare frame, in fill wall frame and ground, it seen that at roof
level, displacement in bare frame is more than other two frames and displacement at ground
floor in weak story is more than other two frames. Mostly hinges are formed in beam than in
column
A study has been carried out to determine the optimum configuration of a multi-storey
building by changing shear walls location. Four different cases of shear wall position for a 25
storey building have been analyzed as a space frame system using a standard package ETAB
subjected to lateral and gravity loading in accordance with UBC provisions. It is found that
columns and beams forces are found to increase on grids opposite to the changing position of
shear wall away from the centroid of the building. Twisting moments in members are
observed to be having increasing trend with enhancement in the eccentricity between
geometrical centroid of the building and shear wall position. Stresses in shear wall elements
have more pronounced effect in elements parallel to displaced direction of shear wall as
compared to those in perpendicular direction. The lateral displacement of the building is
uniform for a zero eccentricity case. On the contrary, the drift is more on grids on one side
than that of the others in case of eccentric shear wall position. It is concluded that the shear
wall should be placed at a point by coinciding centre of gravity and centroid of the building.
4. Accuracy of solution
CHAPTER 3
STAAD PRO AND AUTO CAD
3.1 STAAD PRO
Staad is powerful design software licensed by Bentley. Staad stands for structural
analysis and design Any object which is stable under a given loading can be considered as
structure. So first find the outline of the structure, whereas analysis is the estimation of what
are the type of loads that acts on the beam and calculation of shear force and bending moment
comes under analysis stage. Design phase is designing the type of materials and its
dimensions to resist the load. this we do after the analysis.
To calculate S.F.D and B.M.D of a complex loading beam it takes about an hour. So
when it comes into the building with several members it will take a week. Staad pro is a very
powerful tool which does this job in just an hour’s staad is a best alternative for high rise
buildings. Now a day’s most of the high rise buildings are designed by staad which makes a
compulsion for a civil engineer to know about this software. This software can be used to
carry rcc, steel, bridge, truss etc. according to various country codes.
AutoCAD is powerful software licensed by auto desk. The word auto came from auto
Desk Company and cad stands for computer aided design. AutoCAD is used for drawing
different layouts, details, plans, elevations, sections and different sections can be shown in
auto cad. It is very useful software for civil, mechanical and also electrical engineer. The
importance of this software makes every engineer a compulsion to learn this software’s. We
used AutoCAD for drawing the plan, elevation of a residential building. We also used
AutoCAD to show the reinforcement details and design details of a stair case. AutoCAD is a
very easy software to learn and much user friendly for anyone to handle and can be learn
quickly Learning of certain commands is required to draw in AutoCAD.
The GUI (or user) communicates with the STAAD analysis engine through the STD
input file. That input file is a text file consisting of a series of commands which are executed
sequentially. The commands contain either instructions or data pertaining to analysis and/or
design. The STAAD input file can be created through a text editor or the GUI Modeling
facility. In general, any text editor may be utilized to edit/create the STD input file. The GUI
Modeling facility creates the input file through an interactive menu-driven graphics oriented
procedure.
The floor framing (in global X-Z plane) of a building is an ideal example of a FLOOR
structure. Columns can also be modeled with the floor in a FLOOR structure as long as the
structure has no horizontal loading. If there is any horizontal load, it must be analyzed as a
SPACE structure.
Fig.3.3 3D of structure
G = 0.5 x E/ (1 + POISS)
If Poisson's ratio is not provided, STAAD will assume a value for this quantity based
on the value of E. Coefficient of thermal expansion (ALPHA) is used to calculate the
expansion of the members if temperature loads are applied. The temperature unit for
temperature load and ALPHA has to be the same.
3.7 SUPPORTS
Supports are specified as PINNED, FIXED, or FIXED with different releases (known
as FIXED BUT). A pinned support has restraints against all translational movement and none
against rotational movement. In other words, a pinned support will have reactions for all
forces but will resist no moments. A fixed support has restraints against all directions of
movement. Translational and rotational springs can also be specified. The springs are
represented in terms of their spring constants. A translational spring constant is defined as the
force to displace a support joint one length unit in the specified global direction. Similarly, a
rotational spring constant is defined as the force to rotate the support joint one degree around
the specified global direction.
3.8 LOADS
Loads in a structure can be specified as joint load, member load, temperature load
and fixed-end member load. STAAD can also generate the self-weight of the structure and
use it as uniformly distributed member loads in analysis. Any fraction of this self-weight can
also be applied in any desired direction.
Trapezoidal loads are converted into a uniform load and several concentrated loads.
Any number of loads may be specified to act upon a member in any independent loading
condition. Member loads can be specified in the member coordinate system or the global
coordinate system. Uniformly distributed member loads provided in the global coordinate
system may be specified to act along the full or projected member length.
performed as per IS: 13920 the width of the member shall not be less than 200mm. Also the
member shall preferably have a width-to depth ratio of more than 0.3.
3. The minimum tension steel ratio on any face, at any section, is given by:
ρmin = 0.24√fck/fy
The maximum steel ratio on any face, at any section, is given by ρma0.025
4. The positive steel ratio at a joint face must be at least equal to half the negative steel at that
face.
5. The steel provided at each of the top and bottom face, at any section, shall at least be equal
to one-fourth of the maximum negative moment steel provided at the face of either joint.
3. The minimum dimension of column member shall not be less than 200 mm. For columns
having unsupported length exceeding 4m, the shortest dimension of column shall not be less
than 300 mm.
4. The ratio of the shortest cross-sectional dimension to the perpendicular dimension shall
preferably be not less than 0.
5. The` spacing of hoops shall not exceed half the least lateral dimension of the column,
except where special confining reinforcement is provided.
6. Special confining reinforcement shall be provided over a length lo from each joint face,
towards mid span, and on either side of any section, where flexural yielding may occur. The
length lo shall not be less than a) larger lateral dimension of the member at the section where
yielding occurs, b) 1/6 of clear span of the member, and c) 450 mm.
7. The spacing of hoops used as special confining reinforcement shall not exceed ¼ of
minimum member dimension but need not be less than 75 mm nor more than 100 mm.
The basic principle in deciding the layout of component members is that the loads should be
transferred to the foundation along the shortest path.
1. Columns should preferably be located at or near the corners of the building and at the
intersections of the beams/walls.
2. Since the basic function of the columns is to support beams which are normally placed
under the walls to support them, their position automatically gets fixed. The commercial
buildings have normally rectangular pattern of grid type but especially for residential
buildings. The said type of pattern for columns does not become possible.
3. Select the position of column so as to reduce the bending moments in beams, when the
location of two columns are very near then one column should be provided instead of
two at such a position so as to reduce beam moment.
4. Under certain rare circumstances to satisfy the functional requirements, it may not be
possible to provide upper storey columns above the columns at the parking level. Then
the column at parking level is required to support the eccentric columns at the upper
stories. In such a case the column S at parking level is splayed or provided with a bracket
to support the columns at the upper stored. However, the column at parking level will be
subjected to heavy concentrated loads transferred from the columns of the upper stories.
Avoid larger spans of beams. 3D Analysis and Design of a multi storey building
5. When the center to center distance between intersections of walls is large or where there
are no cross walls, the spacing between two columns is governed by limitations on spans
of supported beams, because spacing of columns decides the span of the beam. As the
span of the beam increases, the required depth of the beam, and its self-weight, and total
load on beam increases. It is well known that the moment governing with the increase in
span, there is considerable increase in the size of the beam.
6. On the other hand, in the case of column, the increase in total load due to increase in
length is negligible as long as the column is short. Therefore, the cost of the beam per
unit length increases rapidly with the span as compared to that of column. Columns are,
therefore in general, always cheaper compared to beams on the basis of unit cost.
Therefore, large spans of beams should preferably be avoided for economy reasons. In
general, the maximum spans of beams carrying live loads up to 4 KN/m2 may be limited
to following values. Avoid large center to center distance between columns.
7. Larger spacing of columns not only increases the span and the cost of beams but it
increases the load on the column at each floor posing problem of stocky columns in
lower stored of a multi-stored building. Heavy sections of column lead to offsets from
walls and obstruct the floor area.
The columns on property line need special treatment. Since column footing requires
certain area beyond the column, difficulties are encountered in providing footing for such
columns. In such cases, the column may be shifted inside along a cross wall to make room for
accommodating the footing within the property line. Brackets may be taken out from the
column in continuation of cross beams to support walls along the boundary line.
Alternatively, a combined footing or a strap footing may be provided.
1. Beams, shall, normally be provided under the walls to avoid the loads directly coming
on slabs.
2. Since beams are primarily provided to support slabs, its spacing shall be decided by
the maximum spans of slabs. Slab requires the maximum volume of concrete to carry
a given load. Therefore, the thickness of the slab is required to be kept minimum. The
3DAnalysis and Design of a multi storey building maximum practical thickness for
residential/office/public buildings is 200 mm and minimum is 100 mm.
3. Avoid maximum spacing of beams from deflection and cracking criteria.
4. It is well known that the deflection varies directly with the cube of the span and
inversely proportional with the cube of depth i.e. L3/D3. Hence larger span may be
avoided
5. However for larger spans, normally higher L/D ratio is taken to restrict the depth from
considerations of headroom, aesthetics and psychological effect. Therefore, spans of
beams which require the depth of beam greater than one meter should as far as
possible be avoided.
1. When the rectangular slab is supported at its four edges, it acts as one-way slab when
(ly/lx)>2 and two-way slab for (ly/lx) <2. However, the two-way action of slab not
only depends on the aspect ratio (ly/lx) but also on ratio of reinforcement in the two
directions.
2. A slab with (ly/lx)>2 is designed as one way, since in that case one-way action is
predominant. In one-way slab, main steel is provided along the short span only and load
is transferred to two opposite supports only. The steel along the long span just act as
distribution steel and is not designed for transferring the load but to distribute the load.
3. A two-way slab having aspect ratio (ly/lx) <2 is general economical compared to one
way slab because steel long both the spans acts as main steel and transfer the load to all
its four supports.
4. The two-way action is advantageous essentially for large spans and for live loads
greater than 3 KN/m2. For short spans and light loads, steel required for two-way slab
3D Analysis and Design of a multi storey building does not differ appreciably as
compared to steel for one-way slab because of the requirement of the minimum steel.
CHAPTER 4
MODELLING
4.1 INTROUDUCTION
and analyzed for the maximum and minimum bending moments and shear forces by trial and
error methods as per IS 456-2000. The help is taken by software Staad pro and the
computations of loads, moments and shear forces and obtained from this software.
4.2 PLAN
The auto cad plot represents the plan of a G+2 building. The plan clearly shows that it
is a combination of apartments and shops in the ground floor. We can observe there is a
combination between apartments in the first and second floors of the building. The building
located at Kannur city which is surrounded by many apartments.
The plan shows the details of dimensions of each and every room and the type of
room and orientation of the different rooms like bed room, bathroom, kitchen, hall etc... All
the shops and apartments have different room arrangement.
There is some space left around the building for parking of cars. The plan gives
details of arrangement of various furniture like sofa, table etc. The plan also gives the details
of location of stair cases in different blocks. we have stair cases for each block and designing
of stair case is shown in AutoCAD plot in the middle we have a small construction which
consists of lifts and those who want to go through lift can use this facility and we know for a
building with G+2 floors should compulsory have lift and the charges for the facilities is
collected by all the members. At that junction we have a club for our enjoyment and charges
are collected by all the building occupants every month. So these represent the plan of our
building and detailed explanation of remaining parts like elevations and designing is carried
in the next sections.
4.3 ELEVATION
AutoCAD Fi 1.2 represents the elevation of building. It shows the elevation of a G+2
building representing the front view which gives the overview of a building block. Each floor
consists of height 3m which is taken as per GHMC rules for commercial buildings. The
building is not designed for increasing the number of floors in future.so the number of floors
is fixed for future also for this building due to unavailability of the permissions of respective
authorities. Also special materials like fly ash and self-compacted concrete were also used in
order to reduce the dead load and increase life of the structure and also improve economy.
But these materials were not considered while designing in staad to reduce the complexity
and necessary corrections are made for considering the economy and safety of the structure as
it is a very huge building with shops and apartments.
This is regarding the plan and details of the site and next section deals with the
design part of the building under various loads for which the building is designed.
CHAPTER 5
LOADS
As an integrated system, all the structural elements must resist and transmit all the
effects of gravity loads and lateral loads acting on it to the foundation and ground below. The
various loads to which the building is designed are discussed in the following sections.
The dead load in a building shall comprise of the self-weight of all the frames, walls,
partitions, floors and roofs and shall include the weight of all other superimposed loads which
are permanently attached to the structure.
Floor load various type of building have been categorized into different classes and
live load corresponding to them have been specified in the code: IS: 875-1987(Part 2).
1. 1.5(DL+LL)
2. 1.2(DL+LL+EQX)
3. 1.2(DL+LL-EQX)
4. 1.2(DL+LL+EQY)
5. 1.2(DL+LL-EQY)
6. 1.5(DL+EQX)
7. 1.5(DL-EQX)
8. 1.5(DL+EQY)
9. 1.5(DL-EQY)
10. 0.9DL+1.5EQX
11. 0.9DL-1.5EQX
12. 0.9DL+1.5EQY
13. 0.9DL-1.5EQY
14. DL+0.5LL
15. 1.5DL+0.75LL
Where,
DL - Dead load
LL - live load
EQX - earthquake load in X direction
EQ-X – Earthquake load in (-X) direction
EQZ – earthquake load in Z direction
EQ-Z – earthquake load in (-Z) Direction
2 Beam 230x300
230x450
3 Column 230x300
230x450
A multi- storied frame consists of beams and columns whose degree of indeterminacy is
very high. The design of various members such as beams, columns trusses requires
bending moment, shear force and direct thrust at all sections. The bending moment at all
sections of beams or columns are obtained by analysis of frames. Frames are analyzed for vertical
and final moments are obtained by super imposing.
CHAPTER 6
SLAB DESIGN
6.1 INTRODUCTION
Reinforced concrete solids are constricted as one of the followings:
The slab is usually analysed and designed, considering a strip of uniform width.
Shear stresses are usually low and shear reinforcement is usually avoided.
Preference is given to increase in depth over the region critical in shear. However
shear becomes a controlling factor in a slab without a beam.
Distribution steel is provided at right angles to main steel in both the directions.
Step 1
Assume a suitable overall thickness for the slab , calculate the factored loads (DL & LL) for
design. This initial guess for thickness of slab may be made from empirical relation between
depth and span. The allowable span/ overall depth ratio of slabs may be taken as given
earlier. The minimum depth for ease of construction is 100mm.the factored load is
(1.5DL+1.5LL).A suitable cover depending on exposure condition should be assumed.
Step 2
Considering the slab as beam of one meter width and using effective span, determining the
maximum bending moments M for the ultimate factored load. For continuous slabs,
coefficient of slab below (is 456:2000 Table 7) may be used for this purpose. Otherwise any
established elastic analysis may be used.in latter case redistribution of moment is also
allowed.
Step 3
Using the formula Mu=Kfck bd2 and b=1000mm, find the effective depth required as in
beams. Add cover and find the total depth of slabs from strength consideration. Check the
depth with the width assumed in step 1 generally. The depth from step 1 will be more the
obtained from the strength formula.
Step 4
Check the depth used for shear. As the actual percentage of steel at support is not known, the
check is only approximate.
Step 5
As the depth is usually greater than the minimum depth d, the tension steel required will be
less than balanced amount for the section. Determine the steel required by a suitable formula
or by use of SP 16 chart and tables.
Design of slab
Length by width ratio ly/lx 2.2108844
Hence it will be designed as one way slab
Depth of slab
(1/25)*span 58.8 mm
Let us select d 125 mm
Design for Mu
Xu lim = 0.48*d 60 mm
Mu lim = 0.36fckbXu lim(d-0.42Xu lim) 43.11 kN-m
Hence Mu < Mu lim
Singly reinforced section can be designed
Mu = 0.87*fy*Ast*d*(1-((Ast/bd)*(fy/fck)))
x = Mu/(0.87*fy*d) 273.86
y = 1/(fy/(b*d*fck)) 6024.10
Ast = (y-√(y2-(4*x*y))/2 287.59 mm2
Main Reinforcement
Using bars of dia φ1 10 mm
Spacing S =(((π/4)*φ2 )/Ast)*b 273.21 mm
Spacing provided S 250 mm
Distribution Steel
As =( 0.12*b*d)/100 150 mm2
use bar dia of φ2 8 mm
Spacing S = (((π/4)*φ2^2)/D)*b 335.24 mm
CHAPTER 7
DESIGN OF BEAM
7.1 BEAMS
The beam is a very commonly used structural element.it may exist independently or
may form an equipment of a structural framework as in “grids” and “rigid frames”. A beam is
normally horizontal member, which provides support to the slab and the vertical walls. A
reinforced concrete beam should be able to resist bending moment, tensile, compressive and
shear stress induced in it by the loads on the beam.
In all such cases, the beam is treated as a one-dimensional (line) element with known
material and geometric properties for the purpose of structural analysis.
Balanced section
A RC section in which maximum compressive strain in concrete reaches its ultimate
value 0.0035 and maximum tensile strain in reinforcement reaches its yield value
simultaneously is known as a balanced or critical section.
The percentage of steel in this section is known as critical percentage of steel.in this
case failure occurs by yielding of steel in tension and crushing of concrete in compression
simultaneously.
The section undergoes large rotational deformation from the initial stage(yielding of
steel),to final stage(crushing) and impending failure. Since the failure is initiated by yielding
of steel in tension, it is known as primary tension failure.
A section having percentage of tensile steel greater than the critical percentage is known
as over reinforced section. Since the concrete in this section is relatively in sufficient to
balance the tension in steel, the maximum compressive strain in concrete reaches the ultimate
crushing value before the tensile strain in steel reaches the yielding value.
This causes sudden failure of the section due to crushing of concrete in compression,
without giving any warning. Since this failure initiated by compression in concrete, it is
known as primary compression failure. No over reinforced sections are preferred in limit state
design.
Reinforced concrete beams provided with steel reinforcement in the tension and
compression zones are called doubly reinforced beams. It is essential to put steel in
compression are also when the area of the concrete in the induced moments. This becomes
necessary under the following states:
1. When the construction depth is restricted and the movement the beam has to carry is
greater than the movement capacity of the beam in concrete failure.
Mu=K fcdbd2
This usually occurs at supports of continuous beams and in beams where the
2. When the bending moment in the section can charge in sign(as many occur in a
section in the span of a continuous beam with moving loads) so that the
compression zone with one sign of the movement become the tension zone with the
opposite sign of the movement, as in continuous bridge girder.
3. When the compression steel can substantially improve the density of the beam and its
use is Therefore advisable in member when large amount of tension steel becomes
necessary for the strength.
4. Compression steel is always used in structure in earthquake regions to increase their
ductility.
5. Compression reinforcement will also aid significantly in reducing the long term
deflection of beams.
Size of beam
B 230 mm
D 500 mm
Fck 20 N/mm2
fy 415 N/mm2
d' 40 mm
Effective depth
d=D-d', d= 460 mm
Ultimate moment, Mu 49 kN-m
Shear force, Vu 47.6 kN
Calculation of Ast
Mu = 0.87*fy*Ast*d*(1-((Ast/bd)*(fy/fck)))
x = Mu/(0.87*fy*d) 295.03
y = 1/(fy/(b*d*fck)) 5098.80
Ast = (y-√(y2-(4*x*y))/2 314.42 mm2
Dia of bar 16 mm
ast=(∏*d2)/4 201.09 mm
No of bars required 2 No's
Hence provide 3 No of bars 2 No's
Ast (pro)=No of bars*ast
Ast(pro) 402.18 mm2
Shear Reinforcement
τc=Vu/(b*d)
Τc 0.450 N/mm2
Percentage of steel,Pt=(Ast(Pro)*100)/(b*d) 0.380
From table 19 of IS 456,
Xu lim = 0.48*d, 0.422 N/mm2
Vc=τc*b*d
Vc 44612.7 N
Vus=Vu-Vc
Vus 2987.31 N
Diameter of bar 8
Provide mm dia of 2LVS
Asv 100.53 mm
Vus=(0.875*fy*Asv*d)/Sv
Sv 307.00 mm
Max Spacing
0.75*d 345 mm
Spacing required 300.00 mm
provide spacing 100.00 mm
Hence provide mm dia 2LVS@ mm
c/c
CHAPTER 8
DESIGN OF COLUMN
8.1 GENERAL
Columns such as external columns of framed buildings or columns carrying crane
loads through corbels of a column are subjected not only to direct loads (P), bur also moment
(M) due to eccentricity in the application of load. In the above column of eccentricity is
respect to one axis only and these columns are said to be under uniaxial bending , on the
other hand , corner column of the building is subjected to eccentric load along X and Y axis.
Such columns are said to be under biaxial bending.
3 .The maximum compressive strain in concrete at failure is a governing criteria for ultimate
failure. The magnitude of this failure strain is given by the equation ɛc=0.0035-0.75ec.
Where ɛc is the maximum strain in compression in the section at failure and ɛc is the
minimum strain in compression in the sectional failure .the minimum compression strain in
beam ec is equal to zero so that ɛc=0.0035.in axially loaded column, ɛc= ɛc.so that ɛc at failure
is equal to 0.002.
It is interesting to note that the above expression is also equivalent to assuming that
the strain distribution diagram rotates around a fulcrum at a distance 3D/7 from the highly
compressed edge. this fulcrum point is the same point where the concrete strain will be
0.002at failure with neutral axis at far edge of the section.
Size of beam
B 230 mm
D 450 mm
Fck 20 N/mm2
d' 50
fy 415 N/mm2
L 3000 mm
Pu 756 kN
Mu 72.644 kN-m
L/D 6.67
L/D=7<12
e=Mu/Pu 96.09 mm
e min=(L/500)+(D/30) 21.00 mm
Pu/fck*b*D 0.365
Mu/fck*b*D^2 0.08
d'/D 0.11
CHAPTER 9
DESIGN OF FOOTING
To transmit the load of the structure safely onto a sufficient area of the soil so that
stresses induced in the soil are within safe limits.
To ensure uniform settlements, the intensity of soil reaction should be the same under
all the footings of a structure.
The foundation area should be designed such that the C.G of loads in plan coincide
with the C.G of the foundation area.
Footings under wall are one way footings and those under columns, two way footings.
The first step in design of footing is to calculate the necessary area from the formula.
Having the determined the size of the footing, its structural design is carried out by
using factored load and principles of limit state design as already discussed in the case of
other RC members. The main items to be designed are the thickness of the footings and its
reinforcements. The thickness should be sufficient to resist the shear force without shear steel
and the BM without compression steel.
Give the structure the required structural rigidity so that the foundation reaction below
can be assumed.
Withstand the corrosion that can be caused from the ground.(This min. cover
required is not less than 75 mm when the concrete is cast against the ground and not less than
40mm when it is cast against the ground , and not less than 40mm when it is cast against a
layer of binding concrete of 75 to 80mm thickness).The min. Cover specified in IS 456:2000
For footings is 50mm.It is also important to remember that the percentage steel provided
should not be less than 0.15 for Fe250 and 0.12 for Fe415 steel as specified for slabs in IS
456:2000,clause 26.5.2.1
Therefore FL on going per meter horizontal width =16.8 KN/m and on landing slab
per meter width total load=13.5 KN/m.
Data
Load on column p 776.66 kN
Column width 230 mm
Column Length 450 mm
Grade of concrete M20 fck 20
Grade of steel Fe 415 415
Safe bearing capacity of soil SBC 180 kN/m2
factor of safety 1.5
Size of footing
Self-weight 10% of column load p/10 77.666 kN
Total load P 854.326 kN
m2
Area of footing (total load/SBC) 4.7463
Size of footing (√area) 2.1786 m
Provide width of footing B 2200 mm
Provide length of footing L 2420 mm
Area provided 5.324 m2
Soil reaction for the factored load
0.219 kN/mm2
Depth of footing
Vu = qu*B((B-b)/2-d) = L(M-d)
qu*B = L 481.40
(B-b)/2 = M 985.00
Assuming 0.2% steel, for M20 concrete τc 0.32 N/mm2
Minimum depth required (τc*B*d) = N*d
τc*B = N 704
Depth required 345 mm
Depth provided d 375 mm
Design of reinforcement
Mu = 0.87*fy*Ast*d(1-(Ast/(B*d))*(fy/b))
x = Mu/(0.87*fy*d) 1724.85
y = 1/(fy/(b*d*fck)) 39759.04
Ast = (y-√(y2-4*x*y)/2 1806.97 mm2
Using 12mm bars 12 mm
Spacing S =(((π/4)*φ^2 )/Ast)*b 137.75 mm
Provide spacing of 125.00 mm
Provide 12 mm bars at 125 mm
pt provided = ((π/4*122)/spacing*d)*100
τc from table 19 of IS 456 pg. no. 73 0.2414
vu = qu*B*(((B-b)/2)-d) 0.749 N/mm2
τv = Vu/(B*d) 293654.5
Development length
τbd for M20 concrete and Fe 415 steel (1.2*1.6) pg. no.
43 IS 456 1.92
Ld = 0.87*fy*φ/(4*τbd ) 564.141 mm
Provide 575 mm
Provide development length of 575 mm
CHAPTER 10
DESIGN OF STAIRCASE
Functionally, staircase is an important component of a building, and often the only
means of access between the various floors in the building. It consists of flights of steps,
usually with one or more intermediate landings provided between the floors levels .The
horizontal top portion of a step is termed tread and the vertical projection of the step is called
riser.
10.1TYPES OF STAIRCASE
Dog-legged staircase
j. Headroom: the vertical distance from a line connecting the nosings of all treads and
thesoffit above
Reinforcement
Mu = 0.87*fy*Ast*d*(1-((Ast/bd)*(fy/fck))) mm
x = Mu/(0.87*fy*d) 373.61
y = 1/(fy/(b*d*fck)) 12048.19 mm
Ast = (y-√(y2-(4*x*y))/2 385.97
Using 12mm bars, spacing
required
Spacing 293.02
provide 12mm dia bars @275mm c/c(main bar)
Distribution steel
Ast=0.12% of gross sectional area 336 mm2
S 233.75 mm
provide 10mm bars @230 mm c/c
CHAPTER 11
CONCLUSION
Among the various branches of civil engineering, Construction Engineering is also one of the
important branches which mainly comprises of a set of procedures which includes site
survey, soil Investigation, planning, analysis, and design.
Analysis and design of the building is not only the main criteria. In addition, the cost of the
construction should be reduced. In order to achieve this, proper method of analysis and
design are very important.
Seismic analysis is done for each members such as slab, beam, footing, column and stair and
design is done for these members
An attempt was made to understand the analysts and design of commercial building. An in-
depth understanding the analysis and design of commercial building can be obtained by tool
called STAAD Pro.
REFFERENCE
[1.] D S Prakash Rao ―Design principles & detailing of concrete structures
[2.] S S. Bhavikatti ―”Design of RCC structural Elements”, New age International
publishers
[3] Bureau of Indian standards ―Code of practice for plain and reinforced concrete‖ IS
456:2000, July 2000 New Delhi.
[4.] Bureau of Indian standards,” SP 16”Design Aids for IS 456
[5] Bureau of Indian standard,” Code of practice for design load (other than earthquake) for
Buildings and structures, “IS 875(Part 1):1987, New Delhi.
[6]Bureau of Indian standards, “Code of practice of design of load (other than Earthquake)
for Building and structures, “IS 875(Part II): 1987, New Delhi