Sie sind auf Seite 1von 9

TYPE OF

NO. SIGNAL DESCRIPTION


SIGNAL

FEEDER MCU POWER FEEDER- TYPE M1/M2


IED TESYS T LTMR
PROTOCOL MODBUS RTU
1 STATUS MOTOR RUNNING
2 TRIP/ALARM STARTER TRIP / FAULT STATUS
3 STATUS MOTOR AVAILABLE
4 STATUS MCCB ON
5 TRIP/ALARM MOTOR PROTECTION RELAY OPERATED (37)
6 TRIP/ALARM MOTOR PROTECTION RELAY OPERATED (46)
7 TRIP/ALARM MOTOR PROTECTION RELAY OPERATED (49)
8 TRIP/ALARM MOTOR PROTECTION RELAY OPERATED (51LR)
9 ALARM MCU COMMUNICATION FAILURE
10 TRIP/ALARM UNDER VOLTAGE (27) OPERATED
11 TRIP/ALARM OVER CURRENT (51P/50P) OPERATED
12 STATUS LOCAL STATUS
13 STATUS REMOTE STATUS
14 MEASUREMENTS CURRENT LINE (Ia)
CURRENT LINE (Ib)
CURRENT LINE (Ic)
15 MEASUREMENTS REAL POWER (kW)
16 MEASUREMENTS POWER FACTOR
17 MEASUREMENTS MOTOR OPERATING TIME
TOTAL
TO PMS TO HCP Register Address
SDI SDO SAI SAO HDI HDO HAI HAO
logic Bit
Address Address

1 455 7
1 455 4
1 455 0,1
1 459 4
1 452 7
1 453 5
1 452 3
1 452 5
1 PMS will detect this as
comm fail
1 453 10
1 453 3
1 459 2
1 459 3
1 502-503
1 504-505
1 506-507
1 482
1 481
1 119-120
13 0 6 0 0 0 0 0
OK

OK

OK
OK
OK
OK

OK
OK
OK
OK
TO
NO. TYPE OF SIGNAL SIGNAL DESCRIPTION SDI

FEEDER VFD FEEDER- TYPE M6


IED MICROLOGIC 6.2E / VFD ALTIVAR 630
PROTOCOL MODBUS TCP / IP (VFD) / MODBUS RTU (MICROLOGIC)
1 STATUS VFD/MOTOR RUNNING 1
2 STATUS VFD/MOTOR STOPPED 1
3 ALARM VFD TRIP 1
4 STATUS MCCB ON 1
5 TRIP/ALARM PROTECTION RELAY OPERATED (37) 1
6 TRIP/ALARM PROTECTION RELAY OPERATED (49) 1
7 TRIP/ALARM PROTECTION RELAY OPERATED (46) 1
8 TRIP/ALARM PROTECTION RELAY OPERATED- motor stall error 1
9 ALARM VFD COMMUNICATION FAILURE 1

10 TRIP/ALARM UNDER VOLTAGE (27) OPERATED 1


11 TRIP/ALARM OVER CURRENT (51P/50P) OPERATED 1
12 MEASUREMENTS LINE CURRENT La
LINE CURRENT Lb
LINE CURRENT Lc
13 MEASUREMENTS Active Load (kW)
14 MEASUREMENTS POWER FACTOR
15 MEASUREMENTS MOTOR run time
TOTAL 11
TO PMS TO HCP Register Address
SDO SAI SAO HDI HDO HAI HAO logic Bit Value Test
Address Address

3201 2 ok
3201 5 ok
3201 3 ok
5202 2 ok
7121 100
7121 16
7121 33 ok
7121 148 ok
PMS will detect this as
comm fail
16113 6 ok
12004 1
1 12015
1 12016
1 12017
1 3294 OK
1 13787 OK
1 3246 OK
0 6 0 0 0 0 0

from micrologic
ST15 , 16115 Bit4
ST16, 16116 Bit1
[Output Phase Loss] (OPF2)
[Motor Stall Error] (STF)

7121-22 [Supply Mains UnderV] (USF)


7121-17 (motor overload) ST15 , 16115 Bit5
TO
NO. TYPE OF SIGNAL SIGNAL DESCRIPTION SDI

FEEDER VFD FEEDER- TYPE M6


IED MICROLOGIC 6.2E / VFD ALTIVAR 630
PROTOCOL MODBUS TCP / IP (VFD) / MODBUS RTU (MICROLOGIC)
1 STATUS VFD/MOTOR RUNNING 1
2 STATUS VFD/MOTOR STOPPED 1
3 ALARM VFD TRIP 1
4 STATUS MCCB ON 1
5 TRIP/ALARM PROTECTION RELAY OPERATED (37) 1
6 TRIP/ALARM PROTECTION RELAY OPERATED (49) 1
7 TRIP/ALARM PROTECTION RELAY OPERATED (46) 1
8 TRIP/ALARM PROTECTION RELAY OPERATED- motor stall error 1
9 ALARM VFD COMMUNICATION FAILURE 1

10 TRIP/ALARM UNDER VOLTAGE (27) OPERATED 1


11 TRIP/ALARM OVER CURRENT (51P/50P) OPERATED 1
12 MEASUREMENTS LINE CURRENT La
LINE CURRENT Lb
LINE CURRENT Lc
13 MEASUREMENTS Active Load (kW)
14 MEASUREMENTS POWER FACTOR
15 MEASUREMENTS MOTOR run time
TOTAL 11
TO PMS TO HCP Register Address
SDO SAI SAO HDI HDO HAI HAO logic Bit Value Test
Address Address

3202 2 ok
3202 5 ok
3202 3 ok
5203 2 ok
7122 100
7122 16
7122 33 ok
7122 148 ok
PMS will detect this as
comm fail
16114 6 ok
12004 1
1 12015
1 12016
1 12017
1 3294 OK
1 13787 OK
1 3246 OK
0 6 0 0 0 0 0

from micrologic
ST15 , 16115 Bit4
ST16, 16116 Bit1
[Output Phase Loss] (OPF2)
[Motor Stall Error] (STF)

7121-22 [Supply Mains UnderV] (USF)


7121-17 (motor overload) ST15 , 16115 Bit5

Das könnte Ihnen auch gefallen