Sie sind auf Seite 1von 8

IET Science, Measurement & Technology

Research Article

High-impedance fault detection in electrical ISSN 1751-8822


Received on 26th May 2017
Accepted on 26th July 2017
power distribution systems using moving E-First on 11th October 2017
doi: 10.1049/iet-smt.2017.0231
sum approach www.ietdl.org

Kumari Sarwagya1, Sourav De1, Paresh Kumar Nayak1


1Department of Electrical Engineering, Indian Institute of Technology (Indian School of Mines), Dhanbad, Dhanbad 826 004, India
E-mail: nayak.pk.ee@ismdhanbad.ac.in

Abstract: High-impedance faults (HIFs) in electrical power distribution systems produce a very random, non-linear and low-
magnitude fault current. The conventional overcurrent (OC) relaying-based distribution system protection schemes find difficulty
in detecting such low-current HIFs. In this study, a simple two criteria-based protection scheme is proposed for detection and
isolation of HIFs in multi-feeder radial distribution systems. It utilises one-cycle sum of superimposed components of residual
voltage for HIF detection and the maximum value of one-cycle sum of superimposed components of negative-sequence current
for faulted feeder identification. The performance of the proposed scheme is evaluated for a wide variety of possible test cases
by generating data through power systems computer-aided design/electro-magnetic transient design and control software.
Results clearly show that the proposed scheme can assist conventional OC relay for detection and isolation of HIFs in
distribution systems with any grounding connections in a more reliable and faster way.

1 Introduction multiconductor medium-voltage distribution systems. In those


schemes, the fault detection task is accomplished by monitoring the
The overhead conductors in electrical power distribution systems deviations in input impedance values at specific frequencies used
often come in contact with poorly grounded objects such as trees, by narrowband PLC systems and the fault location estimation task
wood fences, vehicles etc. Sometimes the energised conductor is performed by utilising the differences that occur at the responses
breaks and touches the high-impedance ground surfaces such as to impulse injections as measured by the installed PLC devices
asphalt, concrete, grass, sand etc. These contacts restrict the fault along the line. The methods based on frequency-domain analysis
current from few mA to 75 A only [1]. The conventional are capable of extracting some characteristics of the HIF. However,
distribution network protection schemes based on overcurrent their inability to localise time–frequency information
relays, reclosers and fuses find difficulty in detecting such low- simultaneously decreases their detection efficiency.
current high-impedance faults (HIFs). Although, the undetected Time-scale analysis approach known as wavelet transform
low-current HIFs do not cause any damage to distribution network (WT) gives both frequency information and the instant, where
components, the energised conductors on the ground surface can these frequency components occur in signals with time-varying
pose a threat to human life. Also, the arcing caused by such faults spectrum such as HIF currents. Several methods based on WT are
may result fire hazards. The reports state that only few percentages proposed for HIF detection. An HIF detection scheme based on the
(5–20%) of all distribution network faults are HIFs [2]. However, discrete WT of residual voltage and current is proposed in [19]. A
in reality this percentage is higher than the reported value [3]. combined method based on dual tree complex WT and
HIFs are associated with electric arc, and hence generate low- probabilistic neural network method is employed in [20] for HIF
and high-frequency components in the current signal [4]. The arc detection. Although, the methods based on WT give good
non-linearity results low-order harmonics. Several HIF detection simulation results, their practical implementation is still difficult
techniques have been proposed in the literature using different [21]. The training-based methods such as artificial neural network
harmonic components of current and voltage signals. Third [22–25], decision tree [26], adaptive neural fuzzy inference system
harmonic components of current and voltage are widely used for [27] and support vector machine [15, 28] have been used less
HIF detection [5, 6]. Along with third harmonic components, frequently for HIF detection. However, for correct discrimination
combination of other harmonics such as second and fifth of HIFs from other similar non-fault events, generation of large
harmonics, interharmonic current in electric arc during HIF, phase number of training and test cases are required and also
angle difference between third harmonic current and fundamental performances of these methods are system specific. Recently, new
voltage are also used to increase the reliability of third harmonic- algorithms are proposed in [29, 30] based on phasor measurement
based techniques [7–10]. In [11], the sum of even and odd unit for HIF detection. However, these schemes require
harmonics is compared with third harmonic components of current communication medium for data transmission, and hence are
for HIF detection. The energy variance of the low-order even economically less attractive. The state-of-the-art review on HIF
harmonics of the zero-sequence current is utilised in [12] for HIF modelling and detection available up to 2016 is provided in [31].
detection. The superposition of voltage signals with a frequency The aforementioned methods have capability to detect some
higher than the fundamental frequency is utilised in [13] for HIF HIFs in distribution systems, but not all. Apart from few, most of
detection. In [14], the random and sharp variation of the high- the reported methods are computationally complex. In this paper, a
frequency components of the current signal is utilised to detect simple two criteria-based protection scheme is proposed for
HIF. In that scheme, fast Fourier transform is utilised to extract the detection and isolation of HIFs in multi-feeder radial distribution
harmonic components. However, as the HIF current is non- systems. In the first step, the scheme utilises one-cycle sum of
stationary signal, the frequency components of the current are time superimposed components of residual voltage for discriminating
dependent. Therefore, more complex methods such as Kalman HIFs from any other power system disturbances. In the second
filtering are used in [15] to estimate the high-frequency step, the magnitude of one-cycle sum of superimposed components
components of the HIF current. Methods using power line of negative-sequence currents flowing in all the feeders are
communication (PLC) systems are proposed in [16–18] for compared and the maximum of them are utilised for faulted feeder
detection and location estimation of HIFs occurring in single and
IET Sci. Meas. Technol., 2018, Vol. 12 Iss. 1, pp. 1-8 1
© The Institution of Engineering and Technology 2017
Fig. 1  Schematics of the test system along with the circuit used for HIF simulation

identification. The performance of the algorithm is tested for branch voltage source V n, a diode Dn and a variable resistor Rn are
numerous HIF and non-HIF cases. Analysis on the results clearly connected in series. The dc voltage sources are of unequal
shows that using the proposed method detection and isolation of magnitudes and their values are set according to the phase voltage
HIFs in multi-feeder radial distribution systems with any of the study system. When vph > V p, the fault current flows toward
grounding method can be performed in a more faster and reliable ground and the current reverses when vph < V n. No current flows
manner. The rest of this paper is organised as follows. The physical during V n < vph < V p. In the present paper, the values of V p and V n
characteristics, the mathematical modelling and the corresponding
are set approximately at half and one fourth of the phase voltage of
power systems computer-aided design (PSCAD)/electro-magnetic
the distribution system, respectively. During HIF, the values of the
transient design and control (EMTDC) simulation results for a
resistors Rp and Rn are varied randomly between 300 and 1000 Ω in
typical HIF case is provided in Section 2. The detail description of
the proposed method is provided in Section 3. The results of such a manner that the fault current contribution from the
numerous test cases are discussed in Section 4. The comparative substation remains always <1% of the pre-fault current. Random
assessment of the proposed method with two existing techniques is variation in resistor value introduces asymmetry in the fault
provided in Section 5. Finally, this paper is concluded in Section 6. current.
To validate the HIF model, at 1.0 s, a line-to-ground fault
(phase-a-to-ground type) is created through the HIF model on
2 System modelling feeder F1 at a distance of 1 km from the substation (Fig. 1). The
2.1 Modelling of multi-feeder radial distribution system fault continues till 1.2 s. The voltage and current of the faulted
phase at the fault point are shown in Figs. 2a and b, respectively.
The schematic diagram of the distribution system studied in the From Fig. 2a, it is evident that as the fault is of high-impedance
present work is shown in Fig. 1. It consists of a 30 MVA, 33 kV type the change in the voltage magnitude from pre-fault to fault is
substation and five numbers of 11 kV radial distribution feeders negligible. Also, a little distortion in the voltage waveform is
named as F1, F2, F3, F4 and F5. The positive-sequence impedance observed during HIF. On the other hand, the current through the
of the distribution line is 0.3 + j0.25 Ω/km. The per-phase linear HIF model is random in nature and also have unequal positive and
load of each 1.874 MVA at 0.95 lagging power factor are negative half cycles. The interruption near zero crossing in the
connected to feeders F1, F3 and F5 through 11/0.4 kV step-down current waveform shows temporary arc extinction.
transformers. The per-phase load connected to feeders F2 and F4 The v − i characteristic of the HIF model is shown in Fig. 2c.
through 11/0.4 kV step-down transformers are of each 2.811 MVA The current waveform and the v − i characteristic obtained during
at 0.95 lagging power factor. For performance evaluation of the HIF using the model matches well with those obtained from
proposed method in the presence of non-linear load, one of the laboratory experiments, on actual distribution system and from the
linear loads is replaced with a 6-pulse converter load. different high-impedance arc models reported in the literature [33].
This shows that the HIF model chosen for the present paper can
2.2 HIF modelling faithfully represent the randomness, asymmetry, non-linearity and
intermediate arc extinctions in the fault current.
HIFs are mostly associated with electric arc which introduces some
peculiarities to fault currents such as asymmetry, non-linearity,
buildup, shoulder and intermittence [32]. HIFs are also 3 Proposed method
characterised by the presence of harmonics and high-frequency HIFs are mostly single-line-to-ground type. Occurrences of such
components [27]. Several methods are available in the literature to faults in distribution systems introduce unbalance into the system.
model HIF [33–36]. In this paper, the HIF model chosen for study In this paper, a two criteria-based protection scheme is proposed
is similar to [33]. The circuit diagram of the HIF model is shown in for detection and isolation of HIFs in multi-feeder radial
Fig. 1. The HIF model is connected between one phase and ground distribution systems. The residual voltage at the substation bus is
of the distribution feeder. The model consists of two parallel utilised as first criterion for discriminating HIFs from any other
branches. A dc voltage source V p, a diode Dp and a variable possible power system disturbances. The second criterion utilises
resistor Rp are connected in series in one branch and in the other the negative-sequence currents flowing through the feeders

2 IET Sci. Meas. Technol., 2018, Vol. 12 Iss. 1, pp. 1-8


© The Institution of Engineering and Technology 2017
Fig. 2  HIF simulation study
(a) Voltage across HIF model, (b) Current through HIF model, (c) v − i characteristics of the HIF model

connected to the secondary side of the substation transformer for value of σth in this paper is set at 0.1 pu which corresponding to
faulted feeder identification. The detail computational steps of the 100 V. With this value of σth, the proposed scheme can discriminate
proposed scheme are provided below. HIFs from any other disturbances reliably.

3.1 Criterion-1: HIF detection using superimposed 3.2 Criterion-2: faulted feeder identification using
components of the residual voltage superimposed components of the negative-sequence current
The phase voltages measured at the primary substation are sampled It should be noted that the aforementioned index σ proposed in this
at 1 kHz (for a 50 Hz power system). The residual voltage vrk paper has ability to discriminate HIFs from any other possible non-
computed at the kth instant is given as fault disturbances occur in distribution systems. However, the
index σ alone cannot discriminate the faulted feeder from the
vrk = vak + vbk + vck (1) healthy feeders in a multi-feeder radial distribution system as the
index is derived by using the phase voltages of the substation bus
where vak, vbk and vck are the measured voltages at the kth instant of to which all the feeders are connected. For identifying the faulted
phase-a, phase-b and phase-c, respectively. The superimposed feeder in a multi-feeder distribution system, a second criterion
components of the residual voltage are computed for measuring the based on negative-sequence current is utilised in this paper. As it is
randomness, non-periodicity and the non-harmonic components already mentioned that HIFs are mainly of line-to-ground type,
present during HIFs. The one-cycle superimposed components of occurrences of HIFs in a feeder produce both negative- and zero-
the residual voltage are computed as sequence currents. However, zero-sequence current may not be
present in isolated grounding type distribution system. Owing to
vrk_sup = vrk − vrk − N (2) the above reason, in the present work, negative-sequence current is
used for faulted feeder identification. The calculation steps of the
where N is the number of samples per cycle. Furthermore, to obtain proposed faulted feeder identification method are provided below.
a purposeful index, the absolute sum of vrk_sup is computed for one The negative-sequence current flowing in feeder F1 (Fig. 1) at the
cycle in (3) as kth instant is expressed as

k I¯2F1k = I¯aF1k + α2I¯bF1k + αI¯cF1k /3 (5)


σk = ∑ vrk_sup n (3)
n=k−N−1 where I¯aF1k, I¯bF1k and I¯cF1k are the phasor values of currents flowing
at the kth instant in phase-a, phase-b and phase-c of feeder F1,
where n is used for carrying out a sliding window covering 20 ms.
From simulation study, it is observed that the transients caused at respectively and α = e j2π /3. In the similar manner, the negative-
the inception of non-fault events (load switching, line switching or sequence currents flowing in all other four feeders (Fig. 1) can be
capacitor switching) can also introduce significant value of index computed. Let I¯2F2k, I¯2F3k, I¯2F4k and I¯2F5k are the negative-sequence
σ . However, the value of σ in such non-fault events persists only currents flowing at the kth instant in feeders F2, F3, F4 and F5,
for two cycles and afterwards it dies out to almost zero. Therefore, respectively. Full-cycle discrete Fourier transform is used in this
for correct discrimination of HIFs from non-fault events, in the work for phasor extraction.
proposed scheme a wait time twait is introduced. In this paper, twait Ideally, the feeder on which HIF occurs has maximum value of
is fixed at 0.1 s. The proposed algorithm detects an HIF only if negative-sequence current magnitude compared with other feeders.
So, the feeder through which maximum magnitude of negative-
σk + twait > σth (4) sequence current flows can be considered as faulted feeder.
However, from simulation study it is found that a feeder may draw
where σth is a threshold used for discriminating HIF from any other more value of negative-sequence current if unbalance loading/
single-phasing operation occurs in that feeder compared with the
power system disturbances producing one or more characteristics
feeder having HIF. So, negative-sequence current magnitude in
similar to HIF. The value of σth is zero during normal operating
such situation may not be a good indicator for faulted feeder
condition as well as 0.1 s after the inception of any power system identification. However, it is observed that the rate of the change of
disturbances other than HIF. However, to ensure a perfect balance negative-sequence current magnitude is always greater in the
between dependability and security of the proposed algorithm the feeder having HIF compared with the feeder having single-phasing

IET Sci. Meas. Technol., 2018, Vol. 12 Iss. 1, pp. 1-8 3


© The Institution of Engineering and Technology 2017
4 Results and discussion
The reliability of the proposed method is tested by creating HIFs at
different locations, fault inception time and pre-fault loading of the
five-feeder radial distribution system (Fig. 1). Tests are conducted
in the presence of balanced, unbalanced and harmonic loads.
PSCAD/EMTDC simulation software is used for data generation.
The data sampling rate is maintained at 1 kHz. Performance of the
proposed method is also tested for various power system
disturbances such as balanced and unbalanced load switching,
capacitors switching etc., which sometimes exhibit one or more
characteristics similar to HIFs. The characteristics of HIFs depend
very much on the method of grounding connections of the
distribution system [11]. In the present paper, four methods of
grounding connections, namely (i) solidly grounding, (ii)
impedance grounding, (iii) resonant grounding and (iv) isolated
grounding are considered in the distribution system for
performance evaluation of the proposed method. A resistor of 4 Ω
and an inductor of 12.73 mH are connected between substation
transformer star neutral and ground for simulating impedance and
resonant grounding connections, respectively. The performances of
the proposed scheme for few typical test cases are presented below.

4.1 Performance for HIF (phase-a-to-ground type) on feeder


F1 of the five-feeder radial distribution system
For performance evaluation, an HIF of AG-type is created at 1.0 s
on feeder F1 at a distance of 1 km from the substation (Fig. 1). The
results for solidly grounding, impedance grounding, resonant
grounding and isolated grounding are shown in Figs. 4(i)–(iv),
respectively. The observation on Fig. 4ia clearly shows that a
Fig. 3  Flowchart of the proposed method distorted value of residual voltage is present during HIF. The
residual voltage and hence the fault detector index σ remains zero
operation. In this work, the absolute sum of the superimposed during normal operating condition (Fig. 4ib). On the other hand,
components of negative-sequence current over one cycle is used the presence of irregularities in the residual voltage during HIF
for faulted feeder identification. helps to obtain a distinguishable index σ which exceeds σth just
The one-cycle superimposed component of negative-sequence after the inception of the HIF and continues till HIF persists. It
current magnitude at the kth instant in feeders F1 is expressed as shows that by using the proposed index σ , HIF can be detected in
distribution system. Then, for faulted feeder identification, the
I¯2F1_sup k = I¯2F1 k − I¯2F1 k − N (6) magnitude of negative-sequence currents flowing in all the feeders
are computed and are shown in Fig. 4ic. From this figure, it is
observed that feeder F1 has highest value of negative-sequence
Similarly, let I¯2F2_sup k, I¯2F3_sup k, I¯2F4_sup k and I¯2F5_sup k are the current and is variable in nature due to randomness present in the
one-cycle superimposed component of negative-sequence current HIF. Then, the feeder identification index β is computed for each
magnitudes at the kth instant in feeders F2, F3, F4 and F5, of the feeders and are shown in Fig. 4id. From this figure, it is seen
respectively. Furthermore, to obtain a better index, the absolute that feeder F1 has highest value of index β confirming the faulted
sum of the superimposed components of negative-sequence current feeder. The observation on Figs. 4(ii)–(iv) clearly shows that the
over one-cycle β is computed for all five feeders (Fig. 1) and are performance of the proposed scheme is independent of the type of
compared for faulted feeder identification. The calculation steps grounding connections.
are as follows:
k
4.2 Performance for HIF (phase-b-to-ground type) on feeder
F4 of the five-feeder radial distribution system
βF1k = ∑ I¯ 2F1_sup n
n=k−N+1 To test the performance of the proposed scheme for detecting HIFs
k on distribution feeder with different pre-fault loading, fault
βF2k = ∑ I¯2F2_sup n location, fault inception time and fault type, an HIF of BG-type is
n=k−N+1 created at 3.0 s on feeder F4 at a distance of 5 km from the
k substation (Fig. 1). In this case also simulation is carried out for
βF3k = ∑ I¯2F3_sup n (7) four types of grounding connections. Results for solidly grounding,
n=k−N+1 impedance grounding, resonant grounding and isolated grounding
k are provided in Figs. 5(i)–(iv), respectively. First, the observation
βF4k = ∑ I¯2F4_sup n for solidly grounding system is discussed. Like the previous case,
n=k−N+1 in this case also a distorted residual voltage is observed during HIF
k (Fig. 5ia). From Fig. 5ib, it is clearly observed that the fault
βF5k = ∑ I¯2F5_sup n detector index σ remains zero during normal operating condition.
n=k−N+1 The presence of irregularities in the residual voltage during HIF
helps to obtain a distinguishable index σ which remains higher than
where βF1k, βF2k, βF3k, βF4k and βF5k are the absolute sum of the the threshold till the fault persists. Thus, the HIF is detected
superimposed components of negative-sequence current over one reliably. Then, for faulted feeder identification, the magnitude of
cycle at the kth instant in feeders F1, F2, F3, F4 and F5, negative-sequence currents flowing in all the feeders are computed
respectively. The feeder having the maximum value of β is and shown in Fig. 5ic. From this figure, it is observed that feeder
declared as faulted feeder. The flowchart of the proposed scheme is F4 has highest value of negative-sequence current magnitude. The
provided in Fig. 3. shape of the current is irregular during the period HIF persists. This
helps in obtaining the highest value of index β in feeder F4
4 IET Sci. Meas. Technol., 2018, Vol. 12 Iss. 1, pp. 1-8
© The Institution of Engineering and Technology 2017
Fig. 4  Performance for an HIF on feeder F1 with different grounding connections: (i) solidly grounding, (ii) impedance grounding, (iii) resonant grounding
and (iv) isolated grounding
(a) Residual voltage, (b) Fault detector index σ , (c) Negative-sequence currents, (d) Faulted feeder identification index β

confirming the faulted feeder. Similar observations are also soon as an HIF has occurred on feeder F2 at 2.0 s, the negative-
obtained for other three types of grounding connections. This sequence current in feeder F2 increases from zero to a higher
shows that the performance of the proposed HIF detection value. During HIF, the negative-sequence current flowing through
technique is independent of types of grounding, pre-fault loading, feeder F2 is irregular and random in nature. However, there is
fault location, fault type and fault inception time. almost no change in negative-current magnitude through feeder F4
from normal condition to the occurrences of HIF on feeder F2. As
4.3 Performance for HIF during unbalanced loading a result, the highest value of the faulted feeder identification index
β is obtained in feeder F2 and continues till HIF persists (Fig. 6d).
The typical distribution systems supplying electricity to urban and Thus, as per the proposed method feeder F2 is declared as faulted
rural parts of India are three-phase, 4-wire with multiple-grounded feeder. This shows that the performance of the proposed scheme is
neutral. Distribution transformers are mostly three-phase independent of unbalanced loading. Similar results are also
transformers connected in delta–star. However, few single-phase obtained for other three types of grounding connections.
transformers are also installed in rural areas. The connections of
single-phase loads introduce unbalance into the system. The 4.4 Performance during unbalanced load switching
present HIF detection and isolation scheme are being based on
residual voltage and negative-sequence currents need to be To test the performance of the proposed method during single-
evaluated under single-/two-phase loading condition. For phase load switching, one phase of the three-phase loads connected
performance evaluation of the proposed method for detection and to feeder F2 (Fig. 1) is disconnected at 1.5 s. The result for the
isolation of HIF during unbalanced loading, an HIF (phase-a-to- solidly grounding distribution system is provided in Fig. 7(i). From
ground type) is created at 2 s on feeder F2 at a distance of 3 km Fig. 7ia it is evident that as soon as the single-phase load is
from the substation (Fig. 1) while power is fed to a two-phase switched off at 1.5 s, a significant magnitude of residual voltage is
unbalanced load connected to feeder F4. The study is made for all produced. However, as the residual voltage is sinusoidal in nature
the four grounding connections. However, due to page limitation, the fault detector index σ appears only for a period of two-cycle
only the result of solidly grounding system is provided in Fig. 6. and afterwards it vanishes. In this case, as the index σ is zero after
From Fig. 6a, it is evident that two-phase loading on feeder F4 0.1 s such single-phase load switching is treated by the proposed
produces certain magnitude of residual voltage even during normal method as a non-fault event. This shows that the proposed method
operating condition. However, the residual voltage is sinusoidal in is secured enough to unbalanced load switching. Similar results are
nature, and hence the fault detector index σ remains zero during also observed for other three grounding connections.
two-phase loading. As soon as an HIF is initiated at 2.0 s, a
significant distortion appears in the residual voltage and the index 4.5 Performance during capacitor switching
σ exceeds σth and continues till the HIF persists (Fig. 6b). This
helps in the detection of HIF even during unbalanced loading. On To test the performance of the proposed method during capacitor
the other hand, as the unbalanced load is connected to feeder F4, a switching, a three-phase capacitor bank of 1000 kVAR is switched
constant magnitude of negative-sequence current is flowing on at the substation at 2.0 s. The result for the switching case is
through feeder F4 during normal operating condition (Fig. 6c). As provided in Fig. 7(ii). From Fig. 7iia, it is clearly seen that
capacitor switching at 2.0 s does not affect the current waveform
IET Sci. Meas. Technol., 2018, Vol. 12 Iss. 1, pp. 1-8 5
© The Institution of Engineering and Technology 2017
Fig. 5  Performance for an HIF on feeder F4 with different grounding connections: (i) solidly grounding, (ii) impedance grounding, (iii) resonant grounding
and (iv) isolated grounding
(a) Residual voltage, (b) Fault detector index σ , (c) Negative-sequence current, (d) Faulted feeder identification index β

5 Comparative assessment
Several HIF detection techniques based on harmonic components
of current and voltage signals have already been discussed in
Section 1. Among the existing approaches two important
approaches, i.e. (i) magnitude comparison of third and fifth
harmonic currents, phase angle difference between third harmonic
current and fundamental voltage and the negative-sequence current
magnitude-based approach [9] and (ii) the comparison of sum of
the odd and even harmonic components with third harmonic
components of current and the comparison of total harmonic
distortion (THD) of faulted phase with the average THD of the
three-phase currents based approach [11] are considered for
comparison with the proposed method.
The inclusion of power electronic interfaced non-linear loads
has been increased in the recent years by both residential and
industrial consumers. Such loads introduce time-varying harmonics
into distribution systems similar to HIFs. In such situation, the
performances of the HIF detectors based on harmonic components
of voltage and/or current signals may be affected. For comparative
Fig. 6  Performance for an HIF on feeder F2 while power is fed to a two- assessment in the presence of non-linear loads, a dc load of 650 
phase load connected to Feeder F4 of the solidly grounding distribution kW, at 3.6 kV is connected through a 6-pulse converter bridge to
system feeder F2 (Fig. 1). In the presence of converter load, an HIF is
(a) Residual voltage, (b) Fault detector index σ , (c) Negative-sequence currents created at 3.0 s on feeder F2 at a distance of 6 km from the
flowing through different feeders, (d) Faulted feeder identification index β substation. The result for the solidly grounding system is shown in
Fig. 8. The currents flowing through feeder F2 and the HIF model
(Fig. 7iia). However, introduces transient to voltage waveforms are shown in Figs. 8ia and ib, respectively. From Fig. 8ia, it is
(Fig. 7iib).The presence of transient in the voltage waveform does clearly observed that due to converter load connected to feeder F2,
not produce any residual voltage as evident from Fig. 7iic. As a the current flowing through feeder F2 contains harmonics. Also,
result, the fault detector index σ remains zero during such the change in the current magnitude from pre-fault to fault is
switching event (Fig. 7iid). Thus, capacitor switching is treated as a almost negligible as the fault current in this case is restricted to
non-fault event by the proposed method. Parameters associated below 1% of normal rated current.
with faulted feeder identification are not shown in this case as the The performance of [9] for the HIF case is shown in Fig. 8(ii).
scheme has already declared it as a non-fault event. Similar results According to the method, the magnitude of third harmonic current
are also observed for other three grounding connections. should always be greater than the fifth harmonic current. However,
in the present case the above condition is not satisfied due to the

6 IET Sci. Meas. Technol., 2018, Vol. 12 Iss. 1, pp. 1-8


© The Institution of Engineering and Technology 2017
Fig. 7  Performance during non-fault switching events, (i) unbalanced load switching and (ii) capacitor switching
i(a) Residual voltage, i(b) Fault detector index σ , i(c) Negative-sequence currents through different feeders, i(d) Faulted feeder identification index β, ii(a) Three-phase current at the
substation, ii(b) Three-phase voltage at the substation, ii(c) Residual voltage, ii(d) Fault detector index σ

Fig. 8  Comparative assessment for the case of HIF in the presence of converter load, (i) current through feeder F2 and HIF model, (ii) performance of [9],
(iii) performance of [11] and (iv) performance of proposed method
i(a) Feeder F2 current, i(b) HIF current, (ii) Method [9], (iii) Method [11], (iv) Proposed method

presence of converter loads (Fig. 8iia). The other two criteria, i.e. remains zero during normal loading condition (Fig. 8iva). As soon
phase angle difference between third harmonic current and as an HIF is initiated at 3.0 s, a significant irregularity appears in
fundamental voltage, magnitude of third harmonic and negative- the residual voltage and a significant magnitude of fault detector
sequence currents are satisfying. According to Torres et al. [11], index σ is obtained after the inception of the HIF and is continued
the sum of odd harmonics should always be greater than third till the fault persists. Thus, the proposed method is able to
harmonic current and the third harmonic current should always be discriminate HIF from non-linear converter loads. From Fig. 8ivc,
greater than the sum of even harmonics current during the period it is observed that the inception of HIF on feeder F2 results a
HIF persists. However, in the presence of converter load the third significant value of negative-sequence current flowing in feeder
harmonic current is not always greater than the sum of the even F2. The magnitude of negative-sequence current during HIF is
harmonic which is clearly observed in Fig. 8iiic. The other irregular in nature. As a result, the faulted feeder identification
criterion, i.e. the THD of faulted phase should always be greater index β of feeder F2 is found to be maximum. Thus, feeder F2 is
than the average THD of the three-phase currents is also not declared as faulted feeder. Therefore, the performance of the
satisfied (Fig. 8iiid). proposed method for detecting HIF in the presence of converter
The performance of the proposed method is shown in Fig. 8(iv). load outperforms over the existing two important harmonic
Converter loads do not affect the substation phase voltages. As a component-based methods.
result, the residual voltage and hence the fault detector index σ

IET Sci. Meas. Technol., 2018, Vol. 12 Iss. 1, pp. 1-8 7


© The Institution of Engineering and Technology 2017
6 Conclusions [16] Milioudis, A.N., Andreou, G.T., Labridis, D.P.: ‘Enhanced protection scheme
for smart grids using power line communications techniques – part I:
In this paper, a simple two criteria-based protection scheme is detection of high impedance fault occurrence’, IEEE Trans. Smart Grid, 2012,
3, (4), pp. 1621–1630
proposed for detection and isolation of HIFs occurring in multi- [17] Milioudis, A.N., Andreou, G.T., Labridis, D.P.: ‘Enhanced protection scheme
feeder radial distribution systems. The first criterion is derived for smart grids using power line communications techniques – part II:
from one-cycle sum of superimposed components of residual location of high impedance fault position’, IEEE Trans. Smart Grid, 2012, 3,
voltage and is used for discriminating HIFs from any other possible (4), pp. 1631–1640
[18] Milioudis, A.N., Andreou, G.T., Labridis, D.P.: ‘Detection and location of
power system disturbances which often exhibit one or more high impedance faults in multiconductor overhead distribution lines using
characteristics similar to HIFs. The maximum value of the one- power line communication devices’, IEEE Trans. Smart Grid, 2015, 6, (2),
cycle sum of superimposed components of negative-sequence pp. 894–902
currents flowing in different feeders is employed as second [19] Elkalashy, N.I., Lehtonen, M., Darwish, H.A.,, et al.: ‘DWT-based detection
and transient power direction-based location of high-impedance faults due to
criterion for faulted feeder identification. Performance of the leaning trees in unearthed MV networks’, IEEE Trans. Power Deliv., 2008,
proposed method is tested by simulating numerous HIFs in the 23, (1), pp. 94–101
presence of balanced, unbalanced and harmonic loads. [20] Moravej, Z., Mortazavi, S.H., Shahrtash, S.M.: ‘DT-CWT based event feature
Performance of the proposed scheme is also tested in the presence extraction for high impedance faults detection in distribution system’, Int.
Trans. Electr. Energy Syst., 2015, 25, pp. 3288–3303
of non-faults events such as line switching, capacitor switching, [21] Li, K.K., Chan, W.L.: ‘Novel methods for high impedance grounding fault
load switching etc. The observations on the results clearly show protection in low voltage supply systems’, Electr. Power Compon. Syst., 2003,
that using the proposed scheme HIFs can be detected and isolated 31, (12), pp. 1133–1150
in a more faster and reliable manner in the distribution systems [22] Eissa, M.M., Sowilam, G.M., Sharaf, A.M.: ‘A new protection detection
technique for high impedance fault using neural network’. IEEE Large
with any grounding connections. The comparative result also Engineering Systems Conf. Power Engineering, Halifax, NS, Canada, 2006
demonstrates the merits of the proposed method over the existing [23] Zadeh, H.K.: ‘ANN-based high impedance fault detection scheme: design and
methods. implementation’, Int. J. Emerging Electr. Power Syst., 2005, 4, (2), pp. 1–14
[24] Samantaray, S.R., Panigrahi, B.K., Dash, P.K.: ‘High impedance fault
detection in power distribution networks using time–frequency transform and
7 References probabilistic neural network’, IET Gener. Transm. Distrib., 2008, 2, (2), pp.
261–270
[1] Tengdin, J., Westfall, R., Stephan, K.: ‘High impedance fault detection [25] Michalik, M., Lukowicz, M., Rebizant, W.,, et al.: ‘New ANN-based
technology’. Power System Relaying Committee, Piscataway, NJ, USA, 1996, algorithms for detecting HIFs in multigrounded MV networks’, IEEE Trans.
Rep. PSRC Working Group D15 Power Deliv., 2008, 23, (1), pp. 58–66
[2] Wester, C.G.: ‘High impedance fault detection on distribution feeders’. GE [26] Sheng, Y., Rovnyak, S.: ‘Decision tree-based methodology for high
Power Management, GER-3993 impedance fault detection’, IEEE Trans. Power Deliv., 2004, 19, (2), pp. 533–
[3] Ghaderi, A., Mohammadpour, H., Ginn, H.,, et al.: ‘High-impedance fault 536
detection in the distribution network using the time-frequency-based [27] Etemadi, A.H., Sanaye-Pasand, M.: ‘High-impedance fault detection using
algorithm’, IEEE Trans. Power Deliv., 2015, 30, (3), pp. 1260–1268 multi-resolution signal decomposition and adaptive neural fuzzy inference
[4] Russell, B., Chichali, R., Kim, C.: ‘Behaviour of low frequency spectra system’, IET Gener. Transm. Distrib., 2008, 2, (1), pp. 110–118
during arcing fault and switching events’, IEEE Trans. Power Deliv., 1988, 3, [28] Sarlak, M., Shahrtash, S.M.: ‘High-impedance fault branch identification
(4), pp. 1485–1492 using magnetic field signature analysis’, IEEE Trans. Power Deliv., 2013, 28,
[5] Jeerings, D.I., Linders, J.R.: ‘Unique aspects of distribution system harmonics (1), pp. 67–74
due to high impedance ground faults’, IEEE Trans. Power Deliv., 1990, 5, (2), [29] Zanjani, M.G.M., Kargar, H.K.: ‘High impedance fault detection of
pp. 1086–1094 distribution network by phasor measurement units’. IEEE Conf. Electr. Power
[6] Jeerings, D.I., Linders, J.R.: ‘A practical protective relay for down-conductor Distribution Networks (EPDC), Tehran, Iran, 2012
faults’, IEEE Trans. Power Deliv., 1991, 6, (2), pp. 565–574 [30] Zanjani, M.G.M., Karegar, H.K., Niaki, H.A.: ‘Application of PMUs for high
[7] Jeeringes, D., Linders, J.: ‘Unique aspects of distribution system harmonics impedance fault detection of distribution network by considering effect of
due to high impedance ground faults’, IEEE Trans. Power Deliv., 1990, 5, (2), transformer vector group’. IEEE Conf. Electrical Power Distribution
pp. 1086–1094 Networks (EPDC), Kermanshah, 2013
[8] Russell, B., Benner, C.: ‘Arcing fault detection for distribution feeders: [31] Ghaderi, A., Ginn, H.L.III, Mohammadpour, H.A.: ‘High impedance fault
security assessment in long term field trials’, IEEE Trans. Power Deliv., 1995, detection: a review’, Electr. Power Syst. Res., 2017, 143, pp. 376–388
10, (2), pp. 676–683 [32] Jenkins, N., Allen, R., Crossley, P.,, et al.: ‘Embedded generation’, Series 31
[9] Yu, D.C., Khan, S.H.: ‘An adaptive high and low impedance fault detection (IEE Power & Energy, London, 2000, 2nd edn.)
method’, IEEE Trans. Power Deliv., 1994, 9, (4), pp. 1812–1821 [33] Gautam, S., Brahma, S.: ‘Detection of high impedance faults in power
[10] Macedo, J.R., Resende, J.W., Bissochi, C.A.,, et al.: ‘Proposition of an distribution systems using mathematical morphology’, IEEE Trans. Power
interharmonic-based methodology for high-impedance fault detection in Syst., 2013, 28, (2), pp. 1226–1234
distribution systems’, IET Gener. Trans. Distrib., 2015, 9, (16), pp. 2293– [34] Costa, F.B., Souza, B.A., Brito, N.S.D.,, et al.: ‘Real-time detection of
2601 transients induced by high-impedance faults based on the boundary wavelet
[11] Torres, V., Guardado, J.L., Ruiz, H.F.,, et al.: ‘Modeling and detection of high transform’, IEEE Trans. Ind. Appl., 2015, 51, (6), pp. 5312–5323
impedance faults’, Electr. Power Syst. Res., 2014, 61, pp. 163–172 [35] Elkalashy, N., Lehtonen, M., Darwish, H.A.,, et al.: ‘Modeling and
[12] Lien, K., Chen, S., Liao, C.,, et al.: ‘Energy variance criterion and threshold experimental verification of high impedance arcing fault in medium voltage
tuning scheme for high impedance fault detection’, IEEE Trans. Power Deliv., networks’, IEEE Trans. Dielectr. Electr. Insul., 2007, 14, (2), pp. 375–383
1999, 14, (3), pp. 810–817 [36] Nam, S.R., Park, J.K., Kang, Y.C.,, et al.: ‘A modelling method of a high
[13] Zamora, I., Majon, A.J., Sagastabeitia, K.J.,, et al.: ‘New method for detecting impedance fault in a distribution system using two series time-varying
low current faults in electrical distribution systems’, IEEE Trans. Power resistances in EMTP’. IEEE Conf. Power Engineering Society Summer
Deliv., 2007, 22, (4), pp. 2072–2079 Meeting, Vancouver, BC, Canada, 2001
[14] Benner, C., Carswell, P., Russell, B.D.: ‘Improved algorithm for detecting
arcing faults using random fault behaviour’, Electr. Power Syst. Res., 1989,
17, (1), pp. 49–56
[15] Samantaray, S.R., Dash, P.K.: ‘High impedance fault detection in distribution
feeders using extended Kalman filter and support vector machine’, Eur. Trans.
Electr. Power, 2010, 20, (3), pp. 382–393

8 IET Sci. Meas. Technol., 2018, Vol. 12 Iss. 1, pp. 1-8


© The Institution of Engineering and Technology 2017

Das könnte Ihnen auch gefallen