Beruflich Dokumente
Kultur Dokumente
OMICRON PTL
XRIO Converter
AREVA KBCH120
User Manual
V1.000
Contents
1 General Information
The AREVA KBCH 120 XRIO converter is designed for testing AREVA KBCH differential protection relays
by using the OMICRON Test Universe 2.22 software but you can also use this converter with version
above 2.20. The converter provides all necessary data for testing the differential protection. The converter
is tested with the following relay:
5 Functional Range
The AREVA KBCH 120 XRIO converter implements the following functions:
•
th
87 differential protection for two and three windings transformer with transient over flux (5
harmonic blocking)
Some of the functions listed above use the RIO interface of the Test Universe software. Consequently, the
test modules are configured automatically without using LinkToXRIO.
The following functions are using the RIO interface:
•
th
87 Differential protection and 5 harmonic blocking
8 Converter Structure
The converter is divided into two sections: the KBCH120 and the RIO section. Both sections consist of
several function blocks. The converter comes up in the standard view; the RIOplus section and the
template controller section can only be seen in the advanced view.
Note 1: The parameter “Trip Contact Condition” is used in case the tripping contact on the relay is
defined as Single Phase Trip.
Note 2: The parameter “Transformer Model” can be used to define the transformer data. This parameter
can be found under Additional Information – Test Parameters. If the parameter Transformer Model is
selected as “TR model with additional Transformer Information”, the information of transformer needs
to fill in under Additional Information – Transformer Information. In another way, if this parameter is
selected as “TR model calculated with the relay settings” then the transformer model is calculated
according to the setting of “Vector Correction” and “Ratio Correction”, assumed rated of transformer 20
MVA and the setting of the vector group according the instruction manual, as table below.
Note: The setting of the interposing CT should be in the line with the recommend from instruction manual.
8.1.3.1 NamePlate
The NamePlate block contains all necessary information to identify the protection device to be tested. This
block contains the relay vendor, serial number, model, the relay location, hardware revision, software
revision and a description.
8.1.3.2 ProtectedObject
This block contains all necessary information about the protected object (here the transformer). The
ProtectedObjectElements – Transformer1 contains 3 sub blocks with the winding information for two- or
three winding transformers. Each sub block consists of the nominal values Vnom, Inom and Snom, the
WindingType, the StarpointGrounding and the WindingPhaseShift.
8.1.3.1 PowerSystemParameters
The number of phases, phase rotation and the nominal frequency are stored in this block.
8.1.3.2 TransformerDifferentialProtection
This block contains the information needed for differential protection tests. This includes the differential
characteristic and the harmonic restraint elements. As the differential characteristic is identical for all
protected transformer windings, the special test values for each transformer winding are collected in this
block, too.
8.2 RIO
The RIO section of the converter contains all specialized RIO functions which are needed to use the more
specialized test modules (like Advanced Distance or Differential) provided by the OMICRON Test
Universe software.
Warning: Do not change any values in this section. The values have been set using the relay settings of
the Customer Input section.
Note: Do not activate the former test object view in the advanced mode of the XRIO test object. Changing
parameters in this view will disable formulas in the RIO section.
8.2.1 Differential
This RIO Differential function provides the necessary values for testing the differential protection functions
of the AREVA KBCH120/130/140 relay. The RIO differential function contains all values needed for using
the following OMICRON Test Universe modules:
• Diff Configuration
• Diff Characteristic
• Diff Trip Time
• Diff Harmonic Restrain